DOE-HDBK-1169-2003, Nuclear Air Cleaning Handbook, Chapter 4, Housing Design and Layout
Functional areas: Housing Design, Air Supply, Exhaust Requirements, HEPA Filters
This handbook draws from many special technical areas, each of which requires years of education and practice to master. The authors do not intend to make the reader an "instant expert" in the overall subject or in any of the disciplines of the contributors. The 4th edition of the Nuclear Air Cleaning Handbook succeeds three previous editions: ERDA 76-21, Nuclear Air Cleaning Handbook (1976); ORNL/NSIC-65, Design, Construction and Testing of High-Efficiency Air Filtration Systems for Nuclear Applications (1970); and NSIC-13, Filters, Sorbents, and Air Cleaning Systems as Engineered Safeguards in Nuclear Installations (1966). It benefits from over 25 years of industry experience since the previous edition was published. This revision updates the information provided in ERDA 76-21 and incorporates current thinking as provided by manufacturers, subject matter experts from the DOE complex and members of the ASME Committee on Nuclear Air and Gas Treatment (ASME AG-1 Committee). Chapters have been added on History, Fire Protection, and Occupational Safety and Health.
Related To:
Version history and related documents
Related documents
- DOE-HDBK-1169-2003Nuclear Air Cleaning Handbook, Chapter 2, System Considerations
- DOE-HDBK-1169-2003Nuclear Air Cleaning Handbook, Chapter 5, External Components
- DOE-HDBK-1169-2003Nuclear Air Cleaning Handbook, Chapter 6, Small Air Cleaning Units
- DOE-HDBK-1169-2003Nuclear Air Cleaning Handbook, Chapter 7, Glovebox Filtration
- DOE-HDBK-1169-2003Nuclear Air Cleaning Handbook, Chapter 8, Testing
- DOE-HDBK-1169-2003Nuclear Air Cleaning Handbook, Chapter 9, Special Application Requirements
- DOE-HDBK-1169-2003Nuclear Air Cleaning Handbook, Chapter 10, Fire Protection
- DOE-HDBK-1169-2003Nuclear Air Cleaning Handbook, Chapter 11, Occupational Safety and Health
- DOE-HDBK-1169-2003Nuclear Air Cleaning Handbook, Appendix A, Care and Handling of HEPA Filters
- DOE-HDBK-1169-2003Nuclear Air Cleaning Handbook, Appendix B, Receiving Inspection Direction and Checklist
- DOE-HDBK-1169-2003Nuclear Air Cleaning Handbook, Appendix C, Determination of HEPA Filter Life
- DOE-HDBK-1169-2003Nuclear Air Cleaning Handbook, Chapter 1, History of the Development of Air Cleaning Technology in the Nuclear Industry
- DOE-HDBK-1169-2003Nuclear Air Cleaning Handbook, Chapter 3, Filters for the Nuclear Industry
- DOE-HDBK-1169-2003Nuclear Air Cleaning Handbook (Introduction) (Part 1 of 15, links to all Parts)
Document text
Text extracted from the attached file. Refer to the original document for the authoritative version.
Section 1
4-1
CHAPTER 4
HOUSING DESIGN AND LAYOUT
4.1 Introduction
This chapter discusses housing design and requirements
for air cleaning units in which filters and/or adsorbers
are installed (see Chapter 6, �Small Air Cleaning Units,�
for single filter housing design information). Two basic
designs are addressed in this section: man-entry and
side-access (see Figures 4.1 and 4.2). In addition, two
side-access housing types are addressed�one utilizing
square filters and the other radial flow/round filters
(Figure 4.3). Both side-access designs are for housings
with two or more filters and for system capacities greater
than 2,000 cubic feet per minute (cfm). Single-filter
inline housings, man-entry housings larger than 30 high-
efficiency particulate air (HEPA) filters, and
masonry/concrete housings are not considered here.
4.2 Housing System Design
Large-volume air supply and exhaust requirements may be met by a number of side-access or man-entry filter
housing installations operating in parallel, or in a single central system. Parallel housings have the advantages
of: (1) greater flexibility for system modification; (2) minimum interference with operations during filter
replacement because individual units can be shut down without affecting the remaining systems; (3) good
overall ventilation control in the event of malfunction, fire, or accident to one or a few individual units; and
(4) easy system testing and balancing.
4.2.1 Man-entry Housing System Design
The man-entry filter housing consists of a fabricated steel confinement room with one or more walls seal-
welded in place. The walls have holes and hardware to mount HEPA filters or absorbers. The room has
access doors providing entry at each side of the walls.
Air is ducted into one end of the room; passed through
the filters/absorbers mounted on the wall; and exits
from the other end of the room. A wall with
filters/absorbers mounted on it is considered a �stage�
or �bank.� The man-entry design is best used for
housings with stages of 15 filters (5 across, 3 high) or
more. As the number of filters/absorbers increases,
consideration must be given to the ability to test the
filters/absorbers and to the distribution of airflow. For
larger systems (over 30 filters per stage), the designer
should consider segmenting the system into two or more
parts of equal airflow capacity, with each part in a
separate, parallel housing. Isolation valves on each
housing are desirable for convenient system control,
Figure 4.1 – Model of a Man-entry Plenum
Figure 4.2 – Side-access Design
(Square Filter)
Nuclear Air Cleaning Handbook U.S. Department of Energy
4-2
isolation of individual units during an emergency, and
maintenance or testing activities.
4.2.2 Arrangement and Location
Maintainability is a major consideration when laying out
filter housings. Although some systems may have only a
single bank of HEPA filters, most will have at least one
additional bank of prefilters, and many will have multiple
banks of HEPA filters. Those systems in which
contaminated gaseous releases must be controlled will also
require one or more banks of adsorbers. Often a bank of
demisters is required, resulting in as many as six or more
banks of components in a single housing. There must be
sufficient clear corridor space adjacent to the housing for
Section 2
handling filters during filter changes, as well as an adequate number of corridors to and from the housing.
Dollies are often used to transport filters to and from the housing area. This practice results in safer
operations that reduce the risk of both injury to personnel and spread of contamination from dropped filters.
When dollies are used, space is required to move the dollies in and out, and for loading and unloading.
Additional space is desirable for stacking new filters adjacent to the work area during the filter change-out
process. Recommended clearances for housings and adjacent aisles or airlocks are given in Figure 4.4.
Proper access to the filter housing is sometimes
overlooked. Too frequently, housings are situated
among machinery, equipment, and ductwork where
workmen are required to climb between, over, or
under obstructions to get to the housing door,
where they still have inadequate workspace. In
some installations, it is necessary to carry filters one
at a time over ductwork and then rely on rope
slings to transfer them up to the floor above where
the air cleaning system is located. It is essential to
preplan the route for getting filters and adsorbers to
and from the housing, and to provide elevators or
cranes where they have to be hoisted to an upper
level. Gallery stairways are also recommended in
lieu of ladders. See Figures 4.5 through 4.10.
High-risk operations often require segmented
systems with two or more housings ducted in
parallel that exhaust from the same area and vent to the same stack. Each housing must have inlet and outlet
isolation dampers to permit one to be held in standby or, when both are normally operated simultaneously, to
allow one housing to be shut down for maintenance, testing, and emergencies.
Another important consideration in housing layout is uniformity of airflow through the installed components.
This is especially important for adsorbers, since flow through those components must achieve the gas
residence time required for efficient adsorption of gaseous contaminants. For large, multiple-filter housings
that must operate in parallel, equalizing screens may be required in each filter unit to ensure uniform flow in
housings. Long transitions are difficult, particularly in large housings. Nevertheless, every effort should be
made to locate and design inlets and outlets to avoid stratification and to enhance the uniformity of airflow
through components.
Figure 4.3 – Side-access Design
Cylindrical (Radial Flow Filters)
Figure 4.4 – Recommended Clearances for
Man-entry HEPA Filter Banks
DOE-HDBK-1169-2003 Chapter 4
4-3
Special care must be taken in designing side-access
housings to ensure uniform flow through all filter
elements. It is recommended that manufacturers
performance-test prototype side-access filter units in
accordance with American Society of Mechanical
Engineers (ASME) AG-1, Section TA,1 to document
uniformity of flow through side-access filter units before
fabrication of production units. When high-activity alpha-
emitters such as plutonium or transuranic elements are
handled, it may also be desirable to compartmentalize the
system, both in series, with separate housings for prefilters
and HEPA filters, and in parallel for extra safety.
4.3 Component Installation
4.3.1 General
Proper installation of HEPA filters, adsorber cells, and
demisters is critical to the reliable operation of a high-efficiency air cleaning system. HEPA filter and
adsorber frames should be designed in accordance with the requirements of ASME AG-1, Section FG.1
Section 3
4.3.2 Considerations
The following factors must be considered in designing HEPA filter and adsorber frames:
• Structural rigidity of mounting frames;
• Rigid and positive clamping of components to
the mounting frame;
• Careful specification of and strict adherence to
close tolerances on alignment, flatness, and the
surface condition of component seating surfaces;
• Welded-frame construction and the welded seal
between the mounting frame and housing;
• Ability to inspect the interface between
components and the mounting frame during
installation (man-entry);
• Adequate spacing between components in the
bank (man-entry); and
• Adequate spacing in the housing for men to
work (man-entry).
Figure 4.5 – Airlock Entry for Man-entry
Plenum (Filters Above Doors are to
Allow Pressure Equalization)
Figure 4.6 – Man-entry Two-Level
Plenum (lower level) (Looking at Mist
Eliminator Upstream Side of First HEPA
Filter Stage)
Nuclear Air Cleaning Handbook U.S. Department of Energy
4-4
4.3.3 Housing Construction
The components and mounting frame should form a
continuous barrier between the contaminated and clean zones
of the system. Any hole, crack, or defect in the mounting frame
or in the seal between components and the frame that permits
bypassing will result in leakage of contaminated air into the
clean zone and reduced system effectiveness. A mounting
frame that is not sufficiently rigid can flex so much during
operation, particularly under abnormal conditions, that leaks
may develop in the HEPA filters clamped to the frame (due to
differential flexing of the filter case relative to the mounting
frame). Cracks may also open between the filters and the
frame, between frame members (due to weld cracking or
fatigue), or between the frame and the housing. Insufficient
attention to maintenance provisions in the original design can
increase operating costs and reduce reliability of the system.
Once the system is installed, defects are difficult to locate, costly
to repair, and may even require rebuilding the system.
Mounting frames for HEPA filters and other critical
components should be all-welded structures of carbon or
stainless steel structural shapes. Carbon steel frames should be
painted or coated for corrosion resistance. Galvanized steel is
not recommended because of welding difficulties and because
the zinc coating does not give adequate protection in the
environments that may be encountered in a contaminated
exhaust system. Aluminum is not recommended because of the
high cost of surface preparation. Stainless steel is often the best
and most economic choice for radiochemical plant applications.
Suitable housing and mounting frame materials include the
following (source references are listed at the end of this chapter
as noted below):
• Stainless steel shapes, American Society for Testing and
Materials (ASTM) A479, alloy UNS S30403, class C,
annealed and pickled2;
• Stainless steel plate, ASTM A240, alloy UNS S30403,
hot-rolled, annealed, and pickled3;
• Stainless steel sheet, ASTM A240, alloy UNS S30403,
annealed and pickled, 2D or 2B finish3;
• Carbon steel shapes and plate, ASTM A36,4 A4995;
• Carbon steel structural tubing, ASTM A5006, and
• Carbon steel sheet, ASTM A1011-03.7
Figure 4.7 – Man-entry Two-Level
Plenum (Upper Level Looking at
Upstream Side of First HEPA
Filter Stage)
Figure 4.8 – Man-entry Plenum
(Looking at a Ship Door Between
HEPA Filter Stages)
DOE-HDBK-1169-2003 Chapter 4
4-5
Section 4
Information relating to fabrication includes:
• �Specification for the Design, Fabrication, and
Erection of Structural Steel for Buildings,� Manual of
Steel Construction Allowable Stress Design, American
Institute of Steel Construction, New York, NY, 1989. 8
• Cold Formed Steel Design Manual and Specification for the
Design of Cold-Formed Steel Structural Members, American
Iron and Steel Institute, 4th Edition, New York, NY,
1996. 9
• AWS Structural Welding Code-Steel, AWS D1.1,
D1.1M-02 American Welding Society, Miami, FL,
2002. 10
• Design of Welded Structures, O. W. Blodgett,
James F. Lincoln Arc Welding Foundation, Cleveland,
OH, 1976.11
4.3.4 Potential Housing Leakage
Contaminated filter housings must be leaktight to prevent
contamination of adjacent service and operating areas.
(Leak-testing of filter housings is covered in Chapter 8). The design of nuclear air cleaning system housings
must consider the potential for leakage. By locating the filter unit in an appropriate plant location and
locating the fan relative to the filter housing, leakage amounts (especially leakage of contaminated air) can be
minimized.
A once-through contaminated exhaust filter housing may be designed with the exhaust fan located after the
filter housing and the housing located in a space that is �cleaner� than the air entering the housing. The
benefit of this system configuration is that the air cleaning system up to the fan is under a negative pressure.
Leakage is into the housing, thereby minimizing the potential impact of contaminated leakage on plant
personnel during system operation. This system
configuration does not mean leakage should not be
considered. It means that the leakage potential can be
reduced by component location and that further
reductions in personnel dose to levels as low as reasonably
achievable (ALARA) are possible via housing
construction.
If the space where an air cleaning system housing is
located is more contaminated than the air entering the
housing, it would be better to locate the fan on the inlet
side of the housing. This arrangement would eliminate in-
leakage of more contaminated air downstream of the
filters.
For a habitability system where the housing is located
within a protected space, the fan should be located downstream of the filter unit to ensure any potential in-
leakage is �cleaner� air. If the housing in a habitability system is located in an area outside the protected
Figure 4.9 – Common Aisle Between Two
Man-entry Plenums
Figure 4.10 – Man-entry Housing Located
Outside Building
Nuclear Air Cleaning Handbook U.S. Department of Energy
4-6
space, then the fan should be located upstream of the filter unit to ensure potentially contaminated air does
not bypass the filter unit.
The first step in determining housing leaktightness is to assess the relative contamination potential between
the air entering the housing and the space where the housing is situated. Locate the fan accordingly, then
determine the allowable leak rate to maintain: (1) the personnel dose within the requirements of 10 CFR 2012
for inplant personnel, (2) the offsite dose per 10 CFR 100,13 and (3) the ability of the system to maintain
performance [e.g., direction of airflow, required pressure differential, air exchange (dilution) rates]. The latter
item depends on the system design and margin. ASME N509-8914 and ASME AG-1,1 Section HA,
�Housings,� provide guidance on determining allowable leakage.
Section 5
The allowable leakage should be considered when determining construction requirements. However, for
filter housings, the structural design requirements for pressure and dynamic forces dictate that the housing
fabricated of heavy platework (10-gauge to 3/16-inch-thick) can be seal-welded to join the transverse and
longitudinal joints, instead of using bolts, without significantly increasing cost. This will result in a low-
leakage installation.
4.3.5 Paints and Protective Coatings
Coatings and paint requirements must be consistent with the corrosion expected in a particular application
and the size of the duct. Corrosion and radiation-resistant paints and coatings should, at a minimum, meet
the requirements of ASTM D514415, Standard Guide for Use of Protective Coatings in Nuclear Power Plants. Unless
special spray heads are used, spray coating the interior of ducts with an effective minimum diameter of
12 inches is often unreliable because it is difficult to obtain a satisfactory coating and inspection for defects
and voids. The interior of ducts 8 inches and smaller cannot be satisfactory brush painted. Dip coating is
recommended instead. Ducts to be brush painted should not exceed a length of 5 or 6 feet to ensure proper
coverage.
Carbon steel housing interiors and mounting frames must be painted to protect against corrosion and to
facilitate cleaning and decontamination. Surfaces must be properly prepared, and primer and topcoats must
be applied in strict accordance with the coating manufacturer�s instructions in order to obtain the necessary
wet-film and dry-film thicknesses. Film thicknesses should be tested during and after application. Surfaces to
be coated should be abrasive blasted to a profile of 1 to 2 mils in accordance with the Society of Protective
Coating (SPC) SSPC-SP-5/NACE No. 1, Near White Metal Blast Cleaning.16 The prime coat must be applied
within 2 to 3 hours, but in no case more than 8 hours, after surface preparation.
For exterior carbon steel surfaces, either hand or power tool cleaning (SSPC-SP-217 or SSPC-SP-318) is usually
sufficient. For certain conditions, such as highly humid atmospheres, exterior carbon steel surfaces should be
prepared in accordance with SSPC-SP-5/NACE No. 1 instead. Both ambient and metal surface temperatures
should be 10 to 20 degrees Fahrenheit (6.6 to 12.2 degrees Celsius) above the dew point before starting to
paint and there must be adequate drying time (recommended by the coating manufacturer) between coats.
Quality assurance for nuclear grade coatings is discussed in ASTM AG-1, Section AA1 and ASTM D384319,
Practice for Quality Assurance for Protective Coatings Applied to Nuclear Facilities. Other standards applicable to
painting of nuclear facilities include ASTM D3911,20 Standard Test Method for Evaluating Coatings Used in Light
Water Nuclear Power Plants at Simulated Design Basis Accident (DBA) Conditions and ASTM D3912-95,21 Standard
Test Method for Chemical Resistance of Coatings Used in Light Water Nuclear Power Plants.
Because the difficulty in applying nuclear grade coatings to carbon steel surfaces often results in
unsatisfactory performance of the coatings in service, designers should seriously consider use of stainless steel
for mounting frames and housings in corrosive environments or where frequent decontamination is required.
While there are some special handling and fabrication rules associated in working with stainless steel,
DOE-HDBK-1169-2003 Chapter 4
Section 6
4-7
(particularly the highly polished surface finishes that must be protected from scratches during fabrication) the
overall costs of painted carbon steel versus stainless are similar.
4.4 Man Entry Housing
4.4.1 General
Steel man-entry housings may be shop built or field fabricated. The trend is increasingly toward shop-built
steel housings. Stainless steel is the most common material of construction; however, carbon steel also may
be used. Aluminum and galvanized steel are not suitable.
4.4.2 Structural
The mounting frame is a statically indeterminate lattice that generally consists of a set of full-length members
spanning the height or width of the bank (whichever is shorter), connected by cross members that are slightly
shorter than the width of individual filter (adsorber) units. For design purposes, the frame may be considered
as an array of simply supported, uniformly loaded beams. Experience has shown that, to obtain adequate
frame rigidity, these beams (frame members) should deflect no more than 0.1 percent of their length under a
loading equivalent to 1.5 times the maximum dirty filter pressure drop across the bank. This loading is
determined from the following equation.
pSW ∆= )5.1(036.0 (4.1)
Where
0.036 = conversion factor, inches water gauge (in.wg) to pounds per square inch (psi)
W = uniform beam loading, lb/in.
∆ p = pressure drop across bank, in.wg.
S = center to center spacing of filters on bank, inches
Assuming a center-to-center spacing of 26 inches for 24- x 24-inches filters, equation (4.1) reduces to:
pW ∆= 404.1 (4.2)
The value determined from equation (4.2) can be used in standard beam equations8 to determine the
minimum moment of inertia required. Knowing the minimum moment of inertia required for the member,
the size and shape can be selected directly from the tables of structural shape properties given in the
American Institute of Steel Construction (AISC) Manual of Steel Construction.8 It can also be determined by
calculating the moment of inertia of a built-up or cold-formed section. For ASTM A36 steel, the standard
beam equation reduces to the following equations. 4
Major frame members,
6
3
1059.1 x
pL
I
∆= (4.3)
Cross members,
149
p
I
∆= (4.4)
Where
I = minimum moment of inertia4 required, inches
∆p = maximum dirty � filter pressure drop across bank, in.wg.
L = length of member, inches (cross members assumed to be 22 inches long)
Nuclear Air Cleaning Handbook U.S. Department of Energy
4-8
In addition to flexural strength, the frame for an exhaust or air cleanup filter system should also be capable of
withstanding a shock loading of at least 3 psi across the bank without exceeding the elastic limit of the frame
material. In most cases, members calculated using equations (4.3) and (4.4) will meet this requirement;
nevertheless, they should be checked. The section moduli (S values) given in Part I of the AISC Manual of
Steel Construction8 then should be compared with the minimum values obtained from the following equations.
Major frame members,
af
L
S
213= (4.5)
Cross
af
S
6290= (4.6)
Where
S = section modulus, in.3
Fa = maximum allowable fiber stress, psi
L = length of member, inches (cross members assumed to be 22 inches long)
For ASTM A36 steel, these equations reduce to
Major frame members, S = 0.00361L2 (4.7)
Cross members, S = 0.175 (4.8)
Section 7
For built-up and cold-formed members, the minimum S value calculated from these expressions is compared
with the value for the member calculated from the formula.
c
I
S = (4.9)
Where
S = section modulus, in.3
I = moment of inertia8 of the section, inches
c = distance from neutral axis of member to extreme fiber, inches
If the S values obtained from the AISC manual or calculated by using equation (4.9) are greater than the
values calculated from equations (4.5) through (4.8) (as applicable), the members selected are satisfactory.
Note: The above equations are for illustrational purposes only. The designer is responsible for verifying this
information.
4.4.3 Structural Design
Structural design of housings for both Engineered Safeguard Feature (ESF) air cleaning units and non-ESF
units must consider the service conditions the housing may experience during normal, abnormal, and accident
plant conditions. The design requirements for determining housing plate thickness, stiffness, spacing, and
size are presented in the ASME ASME AG-1, Section AA.1
Housing design should consider the following load criteria.
• Additional dynamic loads,
• Constraint of free end displacement loads,
• Dead weight,
DOE-HDBK-1169-2003 Chapter 4
4-9
• Design pressure differential,
• Design wind,
• External loads,
• Fluid momentum loads,
• Live load,
• Normal loads,
• Normal operating pressure differential,
• Seismic load, and
• System operational pressure transient.
Stress criteria limits are given in ASME AG-1, Section AA.1 The maximum deflection for panels, flanges, and
stiffeners for the load combination should be the lesser of the two values derived as shown below.14
4.4.3.1 Criterion 1
• Plate or sheet: 1/8 inch per foot of the maximum unsupported panel span in direction of airflow, but not
more than 3/4 inch
• Stiffeners and flange connections: not to exceed 1/8 inch per foot of span, but not more than 3/4 inch
• Flange connection to dampers and fans: 1/360th of the span, but not to exceed 1/8 inch
4.4.3.2 Criterion 2
Deflections shall be limited to values that will not cause:
• Distortion of the airflow path cross-section, resulting in unacceptable increase in system pressure;
• Damage to safety-related items such as instrumentation or other safety-related equipment or accessories;
• Impingement of deflected elements on adjacent services such as equipment, pipe, cables, tubing, etc.;
• Loss of leaktightness (in excess of leakage limit);
• Buckling (refer to ASME AG-1, Section AA-4000)1; or
• Functional failure of components attached to ductwork (e.g., instrument lines, etc.).
Nuclear Air Cleaning Handbook U.S. Department of Energy
4-10
4.4.4 Mounting Frame Configuration
The basic type of mounting frame construction is face-sealed (i.e., the filter seals to the outermost surfaces of
the frame members by means of gaskets glued to the front surface or to the flange around the face of the
filter unit) as shown in Figure 4.11. The face-sealed configuration is generally recommended for
conventional-design HEPA filters and Type I adsorber cells.22
A minimum face width of 4 inches is
recommended for major and cross members of
face-sealed HEPA filter frames. This allows
1-inch-wide filter-seating surfaces to
compensate for any misalignment of the filter
during installation and a 2-inch space between
filters, horizontally and vertically. It also
provides adequate room for handling
(personnel replacing contaminated filters will
probably have to wear double gloves), using
power tools or torque wrenches during filter
change, and manipulating a test probe between
units.
Section 8
Face widths of frame members for installing
Type I (pleated-bed) adsorber cells are the
same as those for HEPA filters. Face widths
of frame members for installing Type II (tray-
type) adsorber cells may be narrower, since
handles are provided on the front of the trays
to facilitate installation. To provide
interchangeability for cells of different
manufacture, Institute of Environmental Sciences and
Technology (IEST) CS-822 recommends the following
mounting frame dimensions for the installation of Type II
cells (see IEST CS-822 for standard cell dimensions):
• Openings: 6.37 by 24.188 inches (+0.063 inches,
-0 inches),
• Space between openings: vertical, 2.5 inches minimum;
horizontal, 2 inches minimum.
Figures 4.12 and 4.13 show a built-up all-welded Type II
adsorber cell mounting frame made from rectangular
structural tubing; note that a structure is required behind
the frame openings to support the weight of the cells
(approximately 100 pounds each). Because the length of
Type II cells may be different for each manufacturer, the
support structure should be deep enough to take a cell up
to 32 inches long to permit interchangeability of cells of
different manufacture.
Figure 4.11 – Adsorber Gasket Seals
Against Mounting Frame Face Plate
Support Angles
Face Plate
Mounting Studs
Adsorber
Tray
Nut
Clamp
Figure 4.12 – Adsorber Tray Mounting
Frame (“X” Cross Units Are for Test
Gas Injection)
DOE-HDBK-1169-2003 Chapter 4
4-11
Satisfactory mounting frames may be made from
rolled structural shapes or rectangular structural
tubing. Figure 4.14 shows a HEPA filter frame
made from 4- × 4-inch structural tubing that
meets all structural requirements. Rolled
structural shapes for building mounting frames
are given in Table 4.1. Square structural tubing
frames for HEPA filters should be made from
rectangular tubing with a face width of at least
4 inches; structural tubing frames for Type II
adsorber cells may have narrower face widths.
4.4.5 Frame Fabrication –
Gasket-Type Filter and
Adsorber
Filter mounting frames should be shop-
fabricated if practicable because it is nearly
impossible to avoid misalignment, warping, and
distortion in field fabrication. Shop fabrication
is less costly than field fabrication and permits
better control over assembly, welding, and
dimensional tolerances. Care must be taken to
avoid twisting or bending the completed frame
during handling, shipping, and field installation.
For proper performance and maintenance of
installed filters, dimensional and surface-finish
tolerances must be tight and rigidly enforced.
Table 4.2 gives minimum tolerances for the
installed frame. Welds on the filter-seating side
of the frame must be ground flat, smooth, and
flush.
Only welders qualified in accordance with the
American Welding Society (AWS) D1.1,
Structural Welding Code-Steel 10 or Section IX of the
ASME Boiler and Pressure Vessel Code 23 should be
permitted to make welds on HEPA filter and
adsorber mounting frames. Both seal and
strength welds should be visually inspected by a
qualified inspector under a light level of at least
100 foot candles on the surface being inspected.
In addition, liquid penetrant (ASTM E165)24 or
magnetic particle inspection (whichever is
applicable for the base material being inspected)
of the seal welds between frame members is
recommended.
2.00 Min.
(51mm)
24.13
(613mm)
22.00
(559mm)
6.38
(162mm)
1.25 (32) Min. Clearance
Area All Around1.00 (25) TCP
& Bottom
Section 9
3.50
(89)
1.00
(25)
1.00
(25)
Shaded Areas to Remain
Clear for Clamping Device
Guide & Support
4.00 Min
(102mm)
Airflow
Direction
(Either Way)
Figure 4.13 – Adsorber Mounting Frame with
Carbon Trays
Figure 4.14 – Filter Mount
Nuclear Air Cleaning Handbook U.S. Department of Energy
4-12
Table 4.1 – Minimum-Cost Structural Members for 24-by-24 HEPA Filter and Type I Adsorber
Mounting Frames (maximum pressure drop to 12 in.wg)
Principal Member a I-beam Cross Member Channel (span = 22 in.) Number of
1,000 cfm Units High Span b Size (in.) lb./ft. Size (in.) lb./ft.
2 4 ft. 8 in. 4 × 4 M 13 4 × 1¾ 5.4
3 6 ft. 10 in. 4 × 4 M 13 4 × 1¾ 5.4
4 9 ft. 0 in. 4 × 4 M 13 4 × 1¾ 5.4
6 13 ft. 4 in. 6 × 4 B 16 4 × 1¾ 5.4
8 17 ft. 8 in. 8 × 4 B 10 4 × 1¾ 5.4
10 22 ft. 0 in. 10 × 4 5/8 25.4 4 × 1¾ 5.4
a Principal members should span the shortest dimension of the bank.
b Span = [(number of filters) (26) = 4] inches
Note: This table is intended to provide information only. The designer is responsible for verifying this information.
Table 4.2 – Recommended Tolerances for HEPA Filter and Adsorber Mounting Frames
Alignment Perpendicularity: maximum offset of adjoining members 1/64 inch/foot or 1/16 inch, which ever is
greater.
Planarity of adjoining members: 1/64 inch maximum offset at any point on the joint.
Flatness Each filter surface shall be plane within 1/16 inch total allowance.
Entire mounting fixture shall be plane within 1/2 inch total allowance in any 8-by 8-foot area.
Dimensions Length and spacing of members shall be true within +0, -1/16 inch.
Surface-finish Filter seating surfaces are 125 microinch (µin.) AA maximum, in accordance with USA Standard B46.1;
pits, roll scratches, weld spatter, and other surface defects shall be ground smooth after welding, and
ground areas shall merge smoothly with the surrounding base metal; waviness not exceeding 1/32 inch in
6 inch is permissible, as long as the overall flatness tolerance is not exceeded.
Note: This table is intended to provide information only. The designer is responsible for verifying this information.
4.4.6 Filter Clamping and Sealing
HEPA filters and adsorber cells must be carefully sealed to the mounting frame (Figures 4.15 and 4.16) to
achieve the required low penetration leakage rates and to allow easy replacement. Except for the fluid-seal
design described at the end of this section, sealants are not a satisfactory substitute for gaskets. Experience in
clean rooms and contaminated exhaust and air cleanup applications has shown that flat, closed-cell, neoprene
gaskets, ASTM D105625 grade 2C3, give the most satisfactory seal for high-efficiency filters, adsorbers, and
demisters. There is no advantage in using shaped (molded) gaskets; not only are they more expensive, but
research has shown that they are prone to leaks.26, 27 Gaskets that are too soft (i.e., are less than grade 2C3)
take an excessive compression set that may permit leakage when there is relaxation of the clamping bolts.
Gaskets that are too hard (i.e., harder than grade 2C4) require such high clamping loads to effect proper
scaling that the filter itself can be distorted or damaged.
Section 10
As little as 20 percent gasket compression is needed to effect a reliable seal when the thickness of the gasket is
uniform to within ±0.01 inches and the seating surface of the mounting frame is plane to within ±0.01
inches16 However, these tolerances are much too restrictive for economical construction, and experience has
shown that it is usually necessary to compress a 2C3 gasket at least 80 percent to effect a reliable seal over
long periods. Eighty-percent compression requires a loading of approximately 20 pounds per square inch of
gasket area, or a total clamping load of about 1,400 pounds for a 24- by 24-inch filter unit. The
recommended procedure for installing filters under nonhazardous conditions is to initially torque the
DOE-HDBK-1169-2003 Chapter 4
4-13
clamping bolts to produce 50 percent gasket
compression and then retorque them 1 or 2
weeks later to a total compression of about
80 percent. In a radioactively contaminated
filter system, replacement can be a hazard to
personnel and to the filters and/or adsorbers
installed in the system. Under such
conditions, one entry is advised. One option
is to manually compress the filter gasket to an
estimated 50 to 80 percent. A spring-loaded
hold-down (Figure 4.17) is another option
used at some U.S. Department of Energy
(DOE) sites. Torsion bar clamps designed to
exert the proper clamping forces are a third
option.
Gaskets that are too thin may not give a
reliable seal using the recommended frame
tolerances given in Table 4.2, whereas those
that are too thick may be unstable and tend to
roll or pull off the flange of the filter case as
they are compressed, perhaps to the extent
that sections may be extruded between the case and mounting frame and produce a serious air leak.
Recommended gasket sizes are 1/4 to 3/8 inch thick by 3/4 inch wide and 1/4 to 3/8 inch thick by 5/8 inch
wide. Gaskets must be glued to the filter element rather than to the mounting frame because they must be
replaced with each filter change. A sealant such as silicone could be applied lightly to the filter gasket.
Residue must be removed before installing new filters as the sealant may be contaminated, making disposal
more difficult. Gaskets should have cut surfaces on both faces because the �natural skin� produced by
molding sometimes tends to bridge discontinuities or defects in the seating surface, and because the silicone
mold-release compounds used in the manufacture of
sheet neoprene prevent proper adhesion of the gasket to
the filter case.
Filter units and adsorber cells must be clamped to the
mounting frame with enough pressure to enable the
gasket to maintain a reliable seal when subjected to
vibration, thermal expansion, frame flexure, shock,
overpressure, and widely varying conditions of
temperature and humidity that can be expected in service.
Clamping devices must function easily and reliably after
long exposure to hostile environments. In addition, they
must be capable of easy operation by personnel dressed
in bulky protective clothing, gloves, and respirators (or
full-face gas masks) while working in close quarters.
Experience has shown that a simple nut-and-bolt system
(Figure 4.17) gives satisfactory service under these
conditions. Nut-and-bolt clamping, however, entails
removal and handling of a large number of nuts, and this
procedure can be a problem during a filter change in a
highly radioactive system. However, clamping systems that provide the required torque and gasket
compression without loose parts are highly recommended. Any system that achieves the desired clamping
torque is acceptable. Examples of Type II adsorbent filter clamping systems are shown in Figure 4.18.
Eccentric, cam-operated, over-center, or spring-loaded latches, and other quick-opening latches, such as the
Section 11
Individual Clamp System
Shared Clamp System
(not recommended)
Figure 4.15 – HEPA Filter Mounting Frame
(Showing Two Clamp Designs)
Figure 4.16 – Absorber Mounting Frame
with Test Section Manifold
Nuclear Air Cleaning Handbook U.S. Department of Energy
4-14
window latch design, are not recommended for clamping
high-integrity components such as HEPA filters and
adsorber cells.
Magnitude and uniformity are major requirements for filter
and adsorber clamping systems. At least four, and
preferably eight, pressure points are required for HEPA
filters and demisters. Individual clamping of each filter unit
is preferred. Shared clamping, in which holding clips (or
bolts) bear on two or more adjacent filters or adsorber
cells, has been widely used because it is less expensive than
individual clamping and requires manipulation of fewer
loose items within the confines of the housing during a
filter change. However, shared clamping limits the ability
to adjust or replace individual filters in the bank without
upsetting the seals of adjacent units. In the improved
system shown in Figure 4.18, no clip bears on more than
two filter units, and the seals of only four surrounding
filters are upset when replacing a filter unit. This common hold-down design is not recommended. The
clamping systems shown in Figures 4.16 and 4.17 have the advantage that clips and nuts do not have to be
removed to replace filters, since the clips can be rotated out of the way after the nuts have been loosened. A
pressure distribution frame is shown in
Figure 4.19. Although this type of clamping
system has been used with good success in nuclear
and nonnuclear applications, many inplace test
personnel object to it because of the extensive leak-
chasing often required before a satisfactory inplace
test can be achieved. Leak-chasing also occurs in
multi-filter common clamping when, on adjusting
or replacing one filter, the seals of surrounding
filters are disturbed, resulting in new leaks that
have to be corrected. This process is time-
consuming, costly, and, when conducted in a
contaminated housing, can result in lengthy
exposure of personnel.
Because of their weight, eight pressure points are
desirable for clamping Type I (pleated-bed)
adsorber cells. For clamping Type II (tray-type)
cells, two pressure points on the top and two on
the bottom edges of the front plate are needed for
proper sealing, with individual clamping, as shown
in Figure 4.15. Clamping on the short sides only is
not adequate. As Figure 4.18 shows, captive nuts reduce the number of loose items that must be manipulated
within the confines of the filter housing during filter or adsorber replacement, but they must be prevented
from rotation when positioned for withdrawal of the filter.
The minimum bolt size recommended for individually clamped filters is 3/8-16-UNC, but 1/2-11-UNC or
5/8-11-UNC bolts are less prone to damage. For Type I adsorbers, 5/8-11-UNC bolts are necessary. The
nuts and bolts of the clamping system must be made of dissimilar materials to prevent galling and seizing.
Bolting materials and clips must be corrosion resistant. Stainless steel (300 series) bolts with brass nuts are
Figure 4.17 – Filter Hold-down-torque
Spring Design
Blank Plate
Shared Clamp System
Figure 4.18 – HEPA Filters Mounting Frame
with Blanking Plate Installed for Filter Change
DOE-HDBK-1169-2003 Chapter 4
4-15
Section 12
frequently used. Springs, if used, should
also be made from a PPH grade of stainless
steel if they are to resist corrosion and
relaxation over a period of service.
The design knife-edge type of framing and
sealing (Figure 4.20),28 employs a special
cross-section-extruded- framing member
which presents a knife-edge-sealing surface
to the filter element. The filters have a
channel filled with a nonflowing,
nonvulcanizing, silicone polymer around the
sealing edge that fits into the knife edge of
the mounting frame to form a positive seal
between filter and frame. Rigidity of the
mounting frame is not a consideration, since
frame flexure cannot affect the seal or the
filter. The clamping pressure needs to be
sufficient only to hold the filter unit in place.
If the filters are installed on the downstream
side of the frame, clamping must be
sufficient to resist displacement of the filter under normal operating filter resistance and the pressures
produced by shock loadings in the system.
4.4.7 Filter Support
A cradle or other support for the filter element as it is
moved into position on the frame is a desirable feature
from a maintenance standpoint. The cradle should not
obscure any more of the filter-to-frame interface than
necessary to avoid interference with inspection as the
filter is installed. The support shown in Figure 4.19 is
better because it obscures less of the gasket-frame
interface. In some installations, filters have been
supported on the bottom clamping bolts, a practice that
risks damage to the threads of the clamping bolts and is
not recommended.
4.4.8 Size and Arrangement of Filter
and Adsorber Banks
The size (nominal airflow capacity) and orientation of
filter banks (vertical or horizontal), the location of filters on the bank (upstream or downstream side), and the
floor plan and height of the bank all affect the reliability, performance, maintainability, and testability of the
air cleaning system. Savings gained by designing for minimum space and materials can be wiped out many
times over by the higher operational, maintenance, and testing costs that will result from higher pressure drop
and cramped working space in the filter housing.
Reinforcing Bars
Filter Mounting
Studs
Filter Support
Pressure
Distribution
Frame
HEPA Filter
Figure 4.19 – HEPA Filter Mounting Using Pressure
Distribution Frame Design Filter Hold Down
Figure 4.20 – Fluid Seal
Filter Media
Knife Edge
Mounting
Frame with
Knife Edge
Filter Case
Fluid Gel In
Filter Case
Channel
Nuclear Air Cleaning Handbook U.S. Department of Energy
4-16
4.4.9 Vertical Filter Banks
Vertical banks with horizontal airflow are preferred in contaminated exhaust systems because the filters are
more favorably oriented with respect to ease of handling, mechanical strength of the filters, and collection of
condensate. On the other hand, the pleats of Type I adsorber cells and the beds of Type II cells must be
installed horizontally to avoid adsorbent settling in the cells. Before designing a horizontal filter bank with
vertical airflow, filter/adsorber components should be validated for performance in this application/design.
In addition, the design should include provisions for filter installation and removal.
4.4.10 Location of Filters on Mounting Frame
No clear-cut preference can be justified for mounting filters on either the upstream or the downstream side
of the mounting frame. Both methods have been used successfully and the advantages and disadvantages of
each are listed below.
Section 13
4.4.10.1 Upstream Mounting of Filters
Advantages:
The filters are withdrawn into and handled within the contaminated side of the system during a filter change.
No contaminated materials are brought into the clean side of the system, so there is more complete
separation of the clean and dirty sides of the system.
Disadvantages:
• Personnel have to work within a potentially contaminated zone during a filter change.
• It is possible that contamination can be tracked or carried out of the contaminated zone by workmen,
unless the filter change is carefully planned and executed.
• The filter clamping devices are located in the dirty side of the system where they are most exposed to
corrosion and dirt.
• Contaminated material may accumulate on the horizontal surfaces of the filter case and may dislodge
during removal.
4.4.10.2 Downstream Mounting of Filters
Advantages:
• Filters are withdrawn into and handled within the clean side of the system, thereby reducing the
likelihood of tracking or carrying contamination into the building during a filter change.
• Filter clamping devices are located on the clean side of the system where they are less subject to
corrosion.
• Leak-scanning of installed filters is more sensitive. If there are gasket or casing leaks, the driving force of
air entering the filter forces the test aerosol through the leak, and they are readily detected. With
upstream mounting, on the other hand, any test aerosol that goes through a leak in a gasket or filter case
mixes with the air and test aerosol passing through the opening in the mounting frame, thus obscuring
DOE-HDBK-1169-2003 Chapter 4
4-17
the leaks. Although the existence of a leak may be disclosed by a test, the location of the leak cannot be
easily determined by probing.
• Only the upstream face of the filter is contaminated during operation. The outer surfaces of the filter
case and the downstream face of the filter pack are not usually contaminated.
Disadvantages:
• The contaminated filters must be withdrawn into the clean side of the system in a filter change. This
disadvantage can be offset by �fixing� (locking down) the contaminated dust by spraying the upstream
side of the filter pack with paint or acrylic spray or by taping cardboard over the upstream face of the
filter. However, this procedure requires personnel to enter the contaminated chamber of the housing,
and the possibility still exists of dislodging contaminated dust into the clean side of the system, either
from the filter itself or from the edges of the frame opening (which is exposed to contaminated air during
operation).
• Filters have been mounted on both sides of a mounting frame in some installations. This is not
recommended. A cardinal rule in contaminated exhaust systems is that no credit is granted for untested
and untestable filters. Such mounting precludes testing of both filters. Therefore, although double
mounting may provide two sets of filters, the operator cannot take credit for two-stage filtration or series
redundancy. This design has been shown to fail in a fire. The upstream filter blows out when plugged
with smoke particles and impacts the filter downstream, causing it to blow out also.
4.4.11 Size of Banks
Section 14
A nominal system capacity of 30,000 cfm has been recommended by DOE and the U.S. Nuclear Regulatory
Commission (NRC) for any filter or adsorber bank. For larger systems, this limit requires the system to be
segmented into two or more smaller subsystems, each contained in an individual housing and having an
installed capacity of 30,000 cfm or less. The purpose of this requirement was to facilitate maintenance and
inplace testing, to improve control in the event of a system upset, and to enhance the reliability of the total
system. A 30,000-cfm bank was considered the largest that can be tested inplace conveniently. By breaking
the system into two or more air cleaning units, testing and filter replacement can be conducted in one unit
while the other unit remains online. NRC Regulatory Guide 1.52 recommends such redundancy for ESF air
cleaning systems in reactors.29 The designer may also choose to segment a system into units of substantially
less than 30,000 cfm when redundancy is desired to achieve advantages of control, maintainability, and
testability. The development of higher-flow aerosol generators and manifold inplace test systems has allowed
larger filter banks than the recommended 30 filters. The use of 1,500-cfm filters allows higher-capacity
systems without increasing the physical size of the bank. Inplace testing and maintenance is the determining
factor.
4.4.12 Arrangement of Banks
Arrangement of filters on a mounting frame influences operating performance and maintenance. Where
possible, banks should be laid out in an array of three filters high or nine Type II adsorber cells high. When
floor space is at a premium, the bank may be arranged with one 3-high array above another, with a service
gallery between, as shown in Figures 4.6 and 4.7. Thus, an 18,000-cfm bank might be arranged in an array
6-wide by 3-high or 3-wide by 6-high, with a service gallery between the third and fourth tiers. The
arrangement of a 24,000-cfm bank in a 6-wide by 4-high array would be undesirable. A better arrangement is
an array 8-wide by 3-high or, if floor space is at a premium, two 4-wide by 3-high arrays, one above the other,
separated by a service gallery. In no case should filter changing require the use of temporary ladders or
scaffolding. To require a workman dressed in bulky protective clothing (with sight obscured by a respirator
or gas mask and sense of feel dulled by double gloves) to manipulate a ladder or scaffold within the confines
Nuclear Air Cleaning Handbook U.S. Department of Energy
4-18
of a filter house is an open invitation to personnel injury and filter damage (see Figure 8.9, which shows
HEPA filters testing). Based on the 95th-percentile man, the maximum height at which a man can operate
hand tools effectively is 78 inches, and the maximum load he can handle at a height of 5 feet or more is
40 pounds, which is the approximate weight of a clean HEPA filter. Therefore, provision for access to the
higher tiers of filters is necessary. In fact, ASME AG-1, Subsection HA,1 requires that a permanent platform
be installed to access filters to access filters above 6 feet.
Filter banks should be rectangular. The use of odd-shaped banks to limit installed filter capacity to calculated
system airflow requirements increases construction costs significantly. By filling out the rectangle,
construction costs will be less. In addition, if all nine spaces are filled with filters, operating costs may also be
reduced because the additional filters permit operation at a lower flow rate per unit resulting in longer filter
life and reduced filter-change frequency, as discussed in Chapter 2. For the purposes of laying out adsorber
banks, three Type II (tray) adsorbers will fit vertically into the space occupied by one 24- by 24-inch
HEPA filter.
Section 15
4.4.13 Floor Plan of Filter Banks
The plenum floor plan of a vertical filter bank varies with the application of the system. The location of
filters and/or adsorbers is shown in Figures 4.21 through 4.28. Judicious configuration of banks can often
reduce pressure losses in the system and bring about more uniform dust loading of filters, thereby equalizing
the utilization of the filters installed in the banks.
The procedures required for construction and operational maintenance must be considered early in the
planning stages. Adequate clearances for access must be maintained at turning points and between the bank
and the nearest obstruction. Passageways both between the banks and between the banks and the housing
wall must be wide enough for welders to operate effectively and for workmen, dressed in bulky clothing, to
get in to change filters (see Figures 4.29 and 4.30). Both welders and workmen will have to kneel or stoop
to get to the bottom tier. A 95th-percentile man in a kneeling position requires a minimum clearance of
36 inches from the face of the filters to the nearest obstruction, excluding withdrawal space for the filter unit
itself. A minimum clearance of 40 inches is therefore recommended between the face of one bank and the
nearest obstruction.
4.4.14 Steel Housings
Design practices used for conventional air conditioning and ventilation system ductwork and equipment
casings are not adequate for high-reliability, high-efficiency contaminated exhaust and air cleanup systems.
Experience has shown that, under system upset and shutdown conditions, housing leaks can result in the
escape of contamination to clean areas. Even with fans operating, reverse leakage of particles from the low-
pressure side of a system (i.e., the interior of the housing or duct) to the high-pressure side (i.e., the occupied
area of the building) can sometimes occur because of dynamic and aspiration effects. Out-leakage may also
occur when the system is shut down. Filter housings for contaminated exhaust service must be able to
withstand negative pressures without damage or permanent deformation at least up to fan cutoff, which may
be equal to 20 in.wg. in many systems. A pressure differential of 2 in.wg. between the inside and outside of a
housing produces a load of more than 1,000 pounds over every 10 square feet of the housing wall. If the
filters are operated to economical pressure drops, the housing may have to withstand 10 or more times this
load without appreciable deflection. Pulsation and vibration may aggravate the condition. In addition, the
housing should be able to withstand design shock loads without damage.
DOE-HDBK-1169-2003 Chapter 4
4-19
AUTOMATIC DELUGE MANUALLY ACTIVATED DELUGE
AIR LOCK (TYP)
AIR LOCK (TYP)
AIR LOCK (TYP)
AIR DEFLECTION PLATE
AIR DEFLECTION PLATE
AIR DEFLECTION PLATE
MANUALLY ACTIVATED DELUGE
MANUALLY ACTIVATED DELUGE
INLET
DUCT
INLET
DUCT
AUTOMATIC DELUGE
AUTOMATIC DELUGE
DRAIN
DRAIN DRAIN
Heal Chamber
One Demister Stage Four Stages HEPA Filters
One Stage Demister Plus Two Stages HEPA Filters
HEPA
HEPAHEPA
M
S
T
E
U
M
IN
A
T
O
R
M
S
T
E
U
M
IN
A
T
O
R
M
S
T
E
U
M
IN
A
T
O
R
M
S
T
E
U
M
IN
A
T
O
R
H
E
P
A
H
E
P
A
H
E
P
A
H
E
P
A
H
E
P
A
H
E
P
A
H
E
P
A
H
E
P
A
H
E
P
A
HEPA
HEPA
HEPA
HEPA
HEPA
HEPA
HEPA
One Stage Demister Plus Four Stages HEPA Filters
Figure 4.21 – Typical Filter and Demister Layouts
Section 16
Nuclear Air Cleaning Handbook U.S. Department of Energy
4-20
AIR FLOW AIR FLOW
OPEN ABOVE AIRLOCK
DOWN STREAM OF FILTER
STAGE ONLY.
SPLIT COMMON INLET AND
OUTLET DUCTS SYMMETRICALLY.
AIR
DEFLECTION
PLATE
DEMISTER
STAGE
HEPA
FILTER
STAGE
Figure 4.22 – Plan Section of
“Double” Plenum
Figure 4.23 – Plan Section of
“Single” Plenum
Figure 4.24 – Common Configurations Requiring Test Manifolds (Plan A)
DOE-HDBK-1169-2003 Chapter 4
4-21
Figure 4.25 – Common Configurations Requiring Test Manifolds (Plan B)
Figure 4.27 – Common Configurations Requiring Test Manifolds (Plan D)
Figure 4.26 – Common Configurations Requiring Test Manifolds (Plan C)
Nuclear Air Cleaning Handbook U.S. Department of Energy
4-22
The references cited in Section 4.4.5 for the design, fabrication, and welding of mounting frames are also
applicable to steel housings. Housings should be of all-welded construction, with bolted flange or welded
inlet and outlet connections to the ducts and fans. Table 4.3 gives minimum sheet metal thicknesses for
sheet steel housings, and Table 4.4 gives minimum moments of inertia for steel reinforcing members. Sheet
metal thicknesses in Table 4.4 are based on a maximum deflection of 1/4 inch per linear foot at a pressure
differential between the interior of the housing and atmosphere equivalent to 1.5 times the maximum
pressure at fan cutoff. The moments of inertia for reinforcing members listed in Table 4.4 were selected to
avoid exceeding the allowable stress of the steel. Members up to 20 inches long were considered to be
uniformly loaded beams with fixed ends, whereas members longer than 20 inches were considered to be
uniformly loaded beams with simply supported ends. The sheet-metal thicknesses in Table 4.3 are given in
U.S. gauge numbers for sheet and fractional inches for plate.
Figure 4.28 – Common Configurations
Figure 4.29 – HEPA Filter Mounted
on Upstream Side of Mounting Frame
Filter Replacement
Figure 4.30 – Blanking Plate Being
Installed On Downstream Side of
Mounting Frame
DOE-HDBK-1169-2003 Chapter 4
4-23
Table 4.3 – Minimum Sheet-Metal Thicknesses a for Welded Steel b Filter Housings
under Negative Pressure
Dimensions of Largest
Unsupported Panel (in.)
Thickness c (U.S. gauge for sheet, fractional in. for plate) for negative pressure
(relative to outside)
Long Side d Short Side 4 in.wg. 8 in.wg. 12 in.wg. 20 in.wg. 1 psi 2 psi
12 18 18 14 16 14 11
24 18 14 11 12 8 1/4
36 16 12 8 11 1/4 3/8
54 (2)
48 14 12 6 8 1/4 3/8
12 18 16 14 16 14 11
24 18 14 11 12 8 1/4
36 16 12 6 11 1/4 3/8
80 (3)
48 14 12 6 8 1/4 3/8
12 18 16 16 14 14 11
24 18 14 12 11 8 1/4
36 16 12 8 6 1/4 3/8
106 (4)
48 16 10 6 1/4 3/8
a Based on flat plate edges held but not fixed (Roark’s Formulas for Stress and Strain),30 and maximum deflection of 0.25 inch per foot
between reinforcements.
b 30,000 to 38,000 psi yield strength.
c Metal thickness less than No. 18 U.S. gauge are not recommended because of welding problems.
d Length based on 2-inch spacing between 24- × 24-inch filter units; the numbers within parentheses denote number of filter units.
The metal thicknesses are adequate for panel lengths within ±10 inches of the length shown.
Note: This table is intended to provide information only. The designer is responsible for verifying this information.
Section 17
Housings installed inside a reactor confinement may experience a pressure lag during rapid pressurization of
the confinement following a major accident. Unless the housings are equipped with pressure-relief dampers,
this lag could result in a pressure differential between the housing and confinement substantial enough to
collapse the housing.
Reinforcing members should be spaced to minimize vibration and audible drumming of the housing walls,
which can be transmitted through the system. Reinforcements should be installed on the outside of the
housing, when possible, to eliminate interior ledges and projections that collect dust and constitute hazards to
personnel working in the housing (Figure 4.31). All sharp corners, welds, weld spatter, and projections
inside the housing should be ground smooth. The housing design must minimize cracks and crevices that are
difficult to clean and that may collect moisture that can cause corrosion.
Mastics and caulking compounds, including silicone-based, room-temperature vulcanizing (RTV) sealants,
deteriorate in service and should not be used for sealing between panels and sections of a contaminated
exhaust housing. Lock seams, rivets, and bolts used in conventional construction for joining panels do not
produce leaktight joints. When bolted flange joints are used between the housing and ducts, 1.5- ×
1.5- × 0.25-inch-angle flanges with ASTM D1056, grade 2C5 or 30-40 Shore-A durometer neoprene gaskets
are minimum requirements.25 A maximum bolt spacing of 4 inches is recommended for flanges.
Shop fabrication of housings is recommended over field fabrication because of the superior workmanship
and control possible under shop conditions. These housings are built in sections and assembled in the field.
Field joints for such housings should be seal welded, since mastic and gasket-sealed joints cannot be
considered reliable for permanent installations.
Nuclear Air Cleaning Handbook U.S. Department of Energy
4-24
Table 4.4 – Recommended Minimum Moments of Inertia for Selecting Reinforcing Members for
Steel Filter Housings under Negative Pressure a, b
Reinforcement Moment of inertia (in.4) c for negative pressure (relative to outside)
Length d
(in.)
Spacing
(in.) 4 in.wg. 8 in.wg. 12 in.wg. 20 in.wg. 1 psi 2 psi
12 0.04 0.04 0.04 0.04 0.04 0.08
24 0.04 0.04 0.04 0.06 0.08 0.16
36 0.04 0.04 0.05 0.09 0.12 0.24
54 (2)
48 0.04 0.05 0.07 0.12 0.16 0.32
12 0.04 0.04 0.05 0.08 0.11 0.21
24 0.04 0.06 0.09 0.16 0.21 0.43
36 0.05 0.10 0.14 0.24 0.32 0.63
80 (3)
48 0.06 0.13 0.19 0.32 0.42 0.86
12 0.04 0.09 0.13 0.22 0.30 0.60
24 0.09 0.18 0.26 0.44 0.60 1.19
36 0.13 0.27 0.39 0.66 0.90 1.79
106 (4)
48 0.18 0.36 0.52 0.88 1.19 2.38
12 0.09 0.17 0.26 0.51 0.69 1.39
24 0.18 0.34 0.52 1.02 1.39 2.78
36 0.27 0.51 0.78 1.53 2.08 4.17
132 (5)
48 0.36 0.68 1.04 2.04 2.76 5.55
12 0.15 0.29 0.44 0.73 1.0 2.0
24 0.29 0.59 0.88 1.46 2.0 4.0
36 0.44 0.87 1.32 2.19 3.0 6.0
158 (6)
48 0.58 1.16 1.76 2.19 4.0 8.0
a Based on permissible deflection of 1/8 inch per foot.
b Uniformly loaded beam, 50 percent simply supported and 50 percent fixed end assumed.
c Structural angles can be chosen from the tables given in the AISC Manual of Steel Construction.8
d Length based on 2-inch spacing between 24- x 24-inch filter units; the numbers within parentheses denote number of filter units.
The metal thicknesses are adequate for panel lengths within ±10 inches of the length shown.
Section 18
Note: This table is intended to provide information only. The designer is responsible for verifying this information.
4.4.15 Masonry and Concrete Housings
Filter housings for low-gamma-activity systems and vaults for high- (or potentially high-) gamma-activity
systems sometimes have been built as an integral part of the building structure utilizing the same concrete
building walls for HEPA housing walls. This construction is not recommended.
4.4.16 Housing Floor
Steel housings should have steel floors welded continuously to the walls of the housing. In no case should
the housing be installed on a wood floor or on a floor having less than a 3-hour fire rating. A steel curb,
welded to the floor, is recommended to raise the filter-mounting frame off the floor. The section of flooring
between two banks of components must be considered a separate floor to be drained independently. Floors
should be free of obstructions or raised items that could be hazardous to workmen.
DOE-HDBK-1169-2003 Chapter 4
4-25
4.4.17 Housing Doors
Easily opened doors are essential on large housings, and more than one door is generally needed. A door
should be provided to each compartment (space between banks) where maintenance, testing, or inspection
may take place. The use of bolted-on removable panels for access to filter compartments should be avoided
for even the smallest filter housings when human entry is required. Sliding doors should never be used for
filter housings, because they cannot be sealed and because they jam after any distortion of the housing.
Sturdy double-pin-hinged doors with rigid, close-fitting casings and positive latches, such as the marine
bulkhead-type shown in Figure 4.32, should be provided on man-entry housings, particularly those for ESF
and other high-hazard service. Doors and gaskets must be designed to maintain a hermetic seal under
positive and negative pressures equal to at least the fan cut-off pressure. Doors of negative pressure systems
must open outward and, since they may have to be opened against the negative pressure, a means for
breaking the vacuum or for mechanically assisted opening is desirable. Doors should have heavy-duty hinges
and positive-latching devices that are operable from inside and outside. Means for locking, preferably a
padlock, should be provided to prevent unauthorized entry. Door stiffness is important because flexible
doors can be sprung when opened against negative pressure or allowed to slam shut under load. An airlock
at the entry to the housing will eliminate problems with opening doors against negative pressure and
slamming, and, if large enough, will provide an intermediate work area for personnel during a filter change.
Housing doors of the type shown in Figure 4.33 require a minimum of two latching dogs on each side.
Lighter-construction doors require additional latches to achieve a satisfactory seal. Latching dogs should be
operable from inside and outside the housing, and shafts must be fitted with O-rings, glands, or stuffing
boxes to prevent leakage. Door hinges should be of the double-pin, loose-pin, or other type that will permit
the full plane of the door to move perpendicular to the plane of the doorframe during the last fraction of an
6'-0"
Airlock Filter
Typical
Reforcing
5’-0”7’-0”7’-0”
(Typ. Each Stage)
4” Pressure
Equalizer
HEPA Filter
Rack
Mist
Eliminator
Plenum
Drain
C
/A
9” 9”
V
a
ri
e
s
C
/A
Section 19
Figure 4.31 – Filter Plenum Floor Plan
Nuclear Air Cleaning Handbook U.S. Department of Energy
4-26
inch of closure. Single-pin hinges, which result in angular
motion throughout the door closing arc, do not permit
the door to seal properly and may cause the gasket to be
rolled out of its groove after a period of use, thus resulting
in the loss of housing leaktightness. If door gaskets are
too hard they will be incompressible, and the door cannot
be sealed properly even with lever-and-wedge latching
dogs. If too soft, the gasket will rapidly take a
compression set and lose its ability to seal. Solid neoprene
or silicone rubber of about 30 to 40 Shore-A durometer is
recommended.
A compromise may have to be made in sizing doors for
man-entry housings. On the one hand, the door must be
large enough for easy access to personnel dressed in bulky
protective clothing, wearing gas masks or respirators, and
perhaps carrying 24- × 24- × 11 1/2-inch filters weighing
up to 40 pounds, or 26- × 6- × 30-inch adsorber cells
weighing up to 130 pounds (dimensions of the door
through which a 95th-percentile man can pass erect
carrying such loads are shown in Figures 4.34 through
4.38). On the
other hand, the
larger the door, the
more difficult it is
to seal and the
more likely that it
or its frame can be
damaged if allowed
to slam under load.
The door should be
as large as possible for easy access, but in no event should it be any less
than 26 inches wide × 48 inches high. A coaming (2-inch-high
minimum to 6-inch-high maximum) should be provided at all doors to
prevent the outflow of contaminated water should the housing
become flooded.
Figure 4.33 – Filter Plenum Entry Door
(No Airlock Type-Test Manifold
with Valves Shown)
Figure 4.34 – Filter Plenum (Inside
Looking at Entry Door)
Figure 4.32 – Marine Bulkhead-Type Door
Gasket Seal
Door Hinge
Plenum Frame
(Inside Plenum)
Plan View
DOE-HDBK-1169-2003 Chapter 4
4-27
Figure 4.35 – Filter Plenum (Looking
from Outside through the Airlock
into the Plenum)
Figure 4.36 – Filter Plenum (Looking
from Outside into the Airlock at the
Final Stage Upstream and
Downstream Doors)
Figure 4.37 – Filter Plenum (Door-
Wheel Style)
Figure 4.38 – Filter Plenum (Door Bar
Style Showing Difficult Access)
Nuclear Air Cleaning Handbook U.S. Department of Energy
4-28
4.4.18 Housing Drains
Floor drains are essential in contaminated-exhaust filter housings, particularly when sprinkler protection is
provided. Even if moisture or condensation is not expected under normal conditions, occasional wash-down
may be required for decontamination and water will be needed in the event of a fire. When the housing is
above grade, the minimum provision for drainage is a Chicago half-coupling that is sealed with a bronze pipe
plug using tetrafluorethylene (Teflon) plastic �ribbon dope� so the plug can be easily removed when
needed. [Note: Use of Teflon in radiation areas needs to be specifically considered for radiolytic
decomposition on a case-by-case basis]. When the filter is at or below grade, drains should be piped to an
underground contaminated waste system during initial construction, since later drainage system installation is
likely to be costly. Drains from contaminated systems should be piped to the radioactive waste system. In
cold climates, water seats, traps, and drain lines must be protected against freezing if they are above the frost
line. In hot climates, water seats/seals may dry out. When fire sprinklers are installed in the filter house, the
drains must be sized to carry away the maximum sprinkler flow without water backup in the housing.
Section 20
If a separate drain is needed for each
chamber of the filter house, then each
drain must have its own water/loop
seal or trap (Figure 4.39). The raised
drain (shown) takes into consideration
criticality concerns while minimizing
wastewater. The spaces between two
banks of components in series are
considered separate chambers. When
piped to a common drain system, drain
lines from the individual chambers of
the housing must have a valve or be
sealed, or otherwise protected to
prevent bypassing of contaminated air
around filters or adsorbers through the
drain system. The drain system must
be tested for leakage as part of the
housing leak test, as well as part of
system bypass testing of the HEPA
and adsorbent filters.
Provision must be made for those seals or traps to ensure they
are filled with water during the plant life (Figure 4.40). Water
seals must be periodically checked to ensure they do not dry out.
A manual or automatic fill system may be utilized to ensure
water seals do not evaporate for systems that do not experience
moisture conditions continuously. Figure 4.41 shows alternate
methods of drain connection. The design of housing drain
systems is often overlooked until the time of filter housing
installation or testing when it is usually very difficult and
expensive to resolve.
Figure 4.40 – Filter Plenum Drain
P-Trap Fill Tube
Figure 4.39 – Plenum Drain Detail
(Note: Maximum 2” for criticality
considerations)
Plenum Floor
1/4” Pl
1 1/2”
Strainer
Existing Concrete Floor
Non-Shrink Grout
P-Trap
DOE-HDBK-1169-2003 Chapter 4
4-29
4.4.19 Demister/Moisture Separator
Mounting Frame
The frame must be fabricated from corrosion-resistant,
non-perforated steel sheet and must be formed and
assembled in a manner that allows no bypassing of the
separator pad (Figures 4.42 through 4.46). Drain holes
must be provided in the bottom of the frame. The design
must include provisions to ensure the pad is maintained
in its operating position and does not settle, pack down,
or pull away from the top or sides of the frame when
installed. Seals must be provided as necessary to prevent
bypass of entrained liquid droplets.
Figure 4.41 – Plenum Drain Designs
Figure 4.42 – Moisture Separator
Mounting Frame
Figure 4.43 – Moisture Separator
and Mounting Frame
Figure 4.44 – Typical Moisture Separator
and Mounting Frame
4.00 MIN.
(102mm)
Water Trough
Clamping Device
Moisture Separator
Hardware
Clamping BarDrain
Frame
Nuclear Air Cleaning Handbook U.S. Department of Energy
4-30
4.4.20 Other Housing Requirements
Figures 4.47 and 4.48 illustrate a number of features that are desirable in an air cleaning housing. The
housing is all-welded construction. This housing consists of the moisture separator, prefilter, HEPA filter,
carbon adsorber, and downstream HEPA filter. The housing is a 9,000-cfm capacity system and includes the
following features.
• Shop fabrication,
• Wired-glass viewports on each side of the
filter bank for visual inspection without
entering the housing (Figure 4.49),
• Permanently installed lights in vapor-tight
globes that are replaceable from outside of
the housing,
• Wiring installed on the outside of the
housing (penetrations for wiring are a
common source of leakage),
• Shock-mounted instruments with a
pressure-drop manometer across each bank
of filters and inlet and outlet temperature
indicators (Figures 4.50 and 4.51),
• A large marine bulkhead door that is
operable from both inside and outside the
housing (Figure 4.52),
Section 21
Figure 4.45 – Moisture Separators with
Heat Sensor (Upstream Side)
Figure 4.46 – Moisture Separator
(Downstream Side)
Figure 4.47 – Desirable Air Cleaning
Housing Features
AIR
FLO
W
ISOLATION
DAMPER
MOISTURE
SEPARATOR
ACCESS
PRE-FILTER ACCESS
LIGHT (TYP.)
3
6
.0
0
M
IN
.
S
E
R
V
IC
E
A
R
E
A
36.00MIN.
SERVICE
AREA
TYPE III CARBON ADSORBER
HEPA FILTER ACCESS
ISOLATION
DAMPER
HEATER ACCESS
DRAIN (TYP.)
HEPA FILTER ACCESS
DOE-HDBK-1169-2003 Chapter 4
4-31
• Ample space (approximately 4 × 7
feet) inside the housing to allow
personnel to work during a filter
change,
• All reinforcements located on the
outside of the housing,
• A housing opening on the aisle that
can be controlled and that serves as
a workspace during filter change-
out,
• All-welded construction to
eliminate leaks to occupied areas,
• All penetrations sealed by either
continuous seal welding or
adjustable compression-gland-type
seals rated and qualified for the
environmental conditions, and
• Housing drains located in each compartment. Permanently installed test aerosol and Freon injection and
sample ports are highly recommended.
MOISTURE SEPARATOR
SECTION
SLIP IN HEATER
HEATER CONTROL PANEL
PREFILTER SECTION
COMBINATION
TEST SECTION
COMBINATION
TEST SECTION
COMBINATION
TEST SECTION
DOWNSTREAM
TEST SECTION
HEPA
FILTER
SECTION
HEPA
FILTER
SECTIONCARBON
FILTER
SECTION
AIR
FLO
W
Figure 4.48 – Desirable Air Cleaning Housing Features
Figure 4.49 – Viewport
D
IA
. =
8"
2"
30
o
TYP.
1
"
A
2" WIDE x 1/4" PL
RING CLAMP
12" O.D.
12-5/16" O STUDS
STRADDLE
1/2" x 3/16" THICK
NEOPRENE
GASKETS
1/4" THICK x 9" O.D.
FIRE RATED
WIRE GLASS
1/8"
1/8"
12-5/16" O STUDS
G
1/4" PL. RING
CLAMP
SEAL WELD
3/16" STL. LINER-TYP.
SECTION A
Nuclear Air Cleaning Handbook U.S. Department of Energy
4-32
4.5 Side-Access Housings
4.5.1 Guidance for Design of Side-Access Housings
The recommended capacity range for side-access housings is 2 filters (24 × 24
× 11 1/2 inches) per stage to 12 filters per stage (4 across × 3 high). Single
filter units are also avaliable. Units may be stacked 3 high or higher if
platforms are provided.
Housings may be provided with or without bag-in/bag-out features
(Figures 4.53 through 4.67). Bag-in/bag-out side-access housings feature a
ribbed bagging ring inside the side-access door. A specially designed
polyvinyl chloride change-out bag is secured around the bagging ring after
initial filter loading. All subsequent filter changes are accomplished through
change-out bags. Contaminants are isolated to the inside of the bag to
protect site personnel and permit safe handling and disposal of spent filters.
A self-adjusting filter seal mechanism prevents filter bypass and maintains a
positive seal during normal system operation. The housing can also be
utilized without the use of change-out bags, which may be specified where
future hazardous contaminants are unknown.
4.5.2 Recommended Design Features
4.5.2.1 Housing Material
The following is a list of recommended housing design features.
• Standard 14-gauge stainless steel.
Figure 4.50 – Manual Control and
Instrument Panel
Figure 4.51 – Air Monitor in Exhaust Duct
from Plenum
Figure 4.52 – Plenum
Door (Wheel-Type
Inside Plenum Access)
DOE-HDBK-1169-2003 Chapter 4
4-33
4.5.2.2 Unit Construction
• All pressure boundary joints and seams seal
welded,
• Surfaces free of burrs and sharp edges, and
• Reinforced to withstand up to 30 in.wg.
Section 22
4.5.2.3 Access Panel
• Completely hand-removable,
• Handles retained in access panel after removal,
and
• Protected panel gasket seal covers entire inner
panel surface.
4.5.2.4 Bagging Ring
• Two continuous ribs for optimum bag seal,
• Ring depth designed to contain bag during operations,
and
• Smooth outer surface and hammed outer edge.
4.5.2.5 Filter Clamping Mechanism
• Spring-loaded pressure bars exert uniform clamping
force on filed frame;
• Spring loading compensated for any loss of filter gasket memory;
• Positive displacement screw-drive clamping
mechanism;
• Leaktight connection for clamping mechanism
on outside of housing;
• Stainless steel clamping mechanism; and
• Over 1/2-inch travel to prevent filter binding.
Figure 4.53 – Bag-In/Bag-Out Filter Housing
Figure 4.54 – Incinerator Exhaust Filter
Figure 4.55 – Side Access Housing with
Combination of Filter and Adsorber Sections
Nuclear Air Cleaning Handbook U.S. Department of Energy
4-34
Figure 4.56 – Two Single Housings with Common
Exhaust Fan (Dual Entry Shown)
Figure 4.57 – Side-Access Housing
Figure 4.58 – Side-Access Housing
with Fan Figure 4.59 – Side-Access Housing
with Single Air Entry
Figure 4.60 – Side-Access Housing Figure 4.61 – Side-Access Housing
DOE-HDBK-1169-2003 Chapter 4
4-35
Figure 4.66 – Side-Access Housing
with Moisture Separator
Figure 4.62 – Side-Access Housing
Figure 4.63 – Side-Access Housing
with Multiple Inlet Valves
Figure 4.64 – Side-Access Housing Figure 4.65 – Side Access-Housing
with Bag-In/Bag-Out Covers
Figure 4.67 – Side-Access Housing
with Test Manifold
Nuclear Air Cleaning Handbook U.S. Department of Energy
4-36
4.5.2.6 Filter-to-Housing Seal
• Standard full perimeter flat mounting frame mates to filter gasket; and
• Full seal weld around filter frame.
4.5.2.7 Filter Removal Rod
• Standard mechanical assist on all multiple wide housings; and
• Operated through bagging ring.
4.5.2.8 Pressure Taps
• Welded in housing, upstream and downstream of filter,
• 1/2-inch National Pipe Thread half-coupling with plug.
Seals and gaskets should be installed on panels, and a �knife-edge� gasket sealing surface should be provided.
The gasket should be installed in as few pieces as possible to minimize the number of joints and designed to
prevent leakage due to miss fitting butt joints. Side-access, bag-out access panels often use gaskets that
accommodate the panel to the housing seals. Latches or bolts must be of sufficient quantity and strength to
compress the gasket and ensure that the housing leakage criteria are met. Panels must allow access for testing
and component inspection. The drawings for each type and size panel should be submitted to the owner for
review before fabrication. Panel drawings should show the location and details concerning the hinges,
latching lugs, and gaskets.
The number of normally open drains should be kept to a minimum. Drain lines must be valved, sealed,
trapped, or otherwise protected to prevent an adverse condition where: (1) air bypass can occur around
filtration components, and (2) cooling/heating coil capacity is negatively impacted.
Traps or loop seals, when used, should be designed for the maximum operating (static) pressure the housing
may experience during system startup, normal operation system transients, or system shutdown. Provision
should be made for manual or automatic fill systems to ensure the water loop seals do not evaporate. If
manual filling is utilized, a periodic inspection or filling procedure should be implemented. Use of a sight
glass should be considered to aid inspection. The same applies if a local sump is included in the design.
Section 23
The drain system should be designed so that liquids do not back up into the housing. Hydraulic calculations
should be prepared by the manufacturer to document this drain system feature to treat maximum coincident
flow rate. Initial testing of the drain system should be performed by the owner onsite after installation to
demonstrate operability. When shutoff valves or check valves are utilized, they should be initially tested for
operability and leakage onsite, after installation, and periodically thereafter.
4.5.2.9 Basic Differences Between Nuclear Filtration Systems and
Commercial/Industrial Filtration Systems
• The standard design pressure for nuclear systems is 10 to 15 in.wg. compared to 3 in.wg. or less for
commercial/industrial systems. In addition, confinement systems can be built to higher pressures, such
as 30 to 40 in.wg. without significant cost increases.
DOE-HDBK-1169-2003 Chapter 4
4-37
• Nuclear systems are designed, manufactured, and tested to a higher level of quality assurance, such as
ASME NQA-1.31 This includes certified welders, in-process inspections, and material traceability.
Several factory tests are standard, such as filter fit, operability of filter locking mechanisms, flatness of
filter sealing surfaces or alignment of knife edges and leak testing of each filter sealing surface and overall
pressure boundary of each housing and/or system. Test reports are available to the customer for their
files.
• Nuclear systems are designed and built with all-weld construction. All pressure-boundary welds are
continuously welded. These systems are built for long life, and RTV sealants are not trusted over long
periods of time.
• Over the last 2 decades, stainless steel has become a standard material of construction for confinement
systems versus galvanized construction for commercial/industrial systems.
• Most nuclear systems incorporate the bag-in/bag-out feature which allows the user to protect their
maintenance personnel and the surrounding environment during filter change-out. Some applications do
not require the bag-in/bag-out feature, but still require all the other features of confinement.
• Nuclear filter housings incorporate filter locking mechanisms that are designed to achieve a filter-to-
frame seal that will last throughout the life of the filter, not just when the filter gasket is new.
• Nuclear systems are designed so that each tier of filters has its own access door. This is absolutely
necessary when the bag-in/bag-out feature is required, but it is a desirable feature even without the bag-
in/bag-out feature.
• Nuclear systems offer optional inplace test sections.
• Nuclear systems offer optional separate access panels for prefilters, which allows the seal of the HEPA
filters to be on the upstream side.
• Most nuclear filter housings have �filter removal rods� to assist in pulling the second or third filter to the
change-out position.
• Nuclear systems now incorporate isolation dampers in many cases. These dampers are now readily
available in both �bubble-tight� and �low-leakage� designs. These dampers are designed, manufactured,
and tested in the same manner as the filter housings.
4.5.2.10 Advantages of Stainless Steel over Heavy Carbon Steel Construction
• Nuclear filtration systems are usually constructed of 14- and 11-gauge stainless steel reinforced externally.
The cost of this design is very nearly the same as manufacturing from heavy steel plates and
priming/painting for corrosion protection.
Section 24
• Stainless steel offers much better corrosion protection during installation and use than painted steel.
• Decontamination and cleaning of systems is much easier with stainless steel.
• Modification of systems in the field is much easier with stainless steel. Changes, including welding, can
be made without ruining the corrosion protection of the system.
• Stainless steel systems typically weigh less than carbon steel systems.
Nuclear Air Cleaning Handbook U.S. Department of Energy
4-38
4.5.3 Side-Access Housings for Radial Flow Cylindrical HEPA Filters
Recently, radial flow cylindrical filters have been applied to DOE nuclear applications. Side-access housings
for radial flow cylindrical filters have been designed for the installation of up to 12 plug-in, 2000-cfm filters,
for a total of 24000 cfm. Larger installations are possible
(Figures 4.68 through 4.70). Operational experience is
still being gathered for these units.
HEPA filters must maintain: (1) their gasket integrity in
both manual and remote handling situations; (2) a reliable
seal after installation; and (3) correct orientation and
fastening must be obtained. Radial flow cylindrical HEPA
filter manufacturers maintain that the use of an internal
seal offers the highest performance with the least force
required. It is integral to the design and is extremely
effective in negating alignment problems because it
eliminates the remote handling restrictions of the square
filters.
Manufacturers claim the following for radial flow
cylindrical HEPA filters.
• Clamping is not required.
• The gasket is less likely to be damaged in normal
handling.
• Positioning and orientation are not required.
• The filter is free of sharp edges and the sealing face
integrity is reliable.
• The filter is normally used in-to-out so that
the collected contaminant is on the inside.
• The outside surfaces are �clean,� thereby
easing handling.
• Radial flow filters permit higher airflow
designs with lower pressure drops compared
with conventional square section filtration
systems.
• Plug-in filters are easy to install; they simply
slide into the canister along guide rails and
locate on a spigot at the rear of the canister.
A ring is provided around the filter access to
facilitate fitting of the change bag
(Figure 4.71). An access cover is positioned
over the filter. A locator fitted in the cover ensures correct positioning of the filter in the module.
Figure 4.68 – Side-Access Housing
(Cylindrical Radial Flow HEPA Design)
Figure 4.69 – Side Access Housing
Cylindrical Radial Flow HEPA Design
DOE-HDBK-1169-2003 Chapter 4
4-39
4.5.4 Inplace Leak Test
This is a test to determine if there is leakage through
the filter frame/filter gasket surface or from damage to
the HEPA filter. Inplace leak testing is performed at
the user facility, not at the DOE FTF, because for this
test, the HEPA filter must be installed in a filter
housing. The FTF performs quality assurance
efficiency testing on each individual filter prior to
installation in a HEPA filter housing. HEPA filter
housings must be supplied with test sections on the
upstream and downstream sides of the filter bank.
Each test section must be isolated from the other to
permit individual leak testing of each HEPA filter and
its supporting framework in parallel and/or in series in
compliance with ASME AG-1.1
Section 25
All leak testing must be conducted from a location
outside the system using apparatus and devices that are
supplied as an integral part of the test sections,
including mixing devices and sample ports. The
upstream and downstream test chambers contain mixing
devices to mix and disperse a uniform challenge
air/aerosol ahead of the filter and the effluent from the
filter being tested. Challenge aerosol inlet ports and
upstream and downstream sample ports must be
provided for each HEPA filter. All mixing devices in the
airstream must be designed to swing aside when testing
has been completed.
The manufacturer must submit evidence that he has
proof-tested his in-place test method according to the
requirements of ASME AG-126 for systems containing
two filters in series and two filters in parallel, with one
leaking filter in each bank.
Figure 4.70 – Side-Access Housing
(Cylindrical Radial Flow HEPA Design)
Figure 4. 71 – Radial Flow Filter
Bag-Out
Nuclear Air Cleaning Handbook U.S. Department of Energy
4-40
4.6 References
1. ASME (American Society of Mechanical Engineers), 2003, Code on Nuclear Air and Gas Treatment, ASME
AG-1, New York, NY.
2. ASTM (American Society for Testing and Materials), 2003, Standard Specification for Stainless and Steel Bars
and Shapes for Use in Boilers and Other Pressure Vessels, ASTM A479/A-2003, West Conshohocken, PA.
3. ASTM (American Society for Testing and Materials), 2003, Standard Specification for Chromium and
Chromium-Nickel Steel Plate, Sheet, and Strip for Pressure Vessels, ASTM A240/A-2003, West Conshohocken,
PA.
4. ASTM (American Society for Testing and Materials), 2003, Standard Specification for Cold-Formed Carbon
Structural Steel, ASTM A36/A-2003a, West Conshohocken, PA.
5. ASTM (American Society for Testing and Materials), 2002, Standard Specification for Steel Bars and Shapes,
Carbon-Rolled from “T” Rails, ASTM A499/2002, West Conshohocken, PA.
6. ASTM (American Society for Testing and Materials), 2003, Standard Specification for Carbon Steel Structural
Tubing in Rounds and Shapes, ASTM A500-03, West Conshohocken, PA.
7. ASTM (American Society for Testing and Materials), 2003, Standard Specification for Steel, Sheet and Strip,
Hot-Rolled, Carbon, Structural, High-Strength Low-Alloy and High-Strength Low-Alloy with Improved Formability,
A1011/A1011M-03, West Conshohocken, PA.
8. AISC (American Institute of Steel Construction), 1998, �Dimensions and Properties,� Manual of Steel
Construction, Section 1, 9th Edition, Chicago, IL.
9. American Iron and Steel Institute, 1996 Edition of the Cold Formed Steel Design Manual and Specification for
the Design of Cold-Formed Steel Structural Members, 4th Edition, Washington, DC.
10. AWS (American Welding Society), 2002, Structural Welding Code-Steel, AWS D1.1/D1.1M-02, Miami, FL.
11. Blodgett, O. W., 1976, Design of Welded Structures, James F. Lincoln Are Welding Foundation,
Cleveland, OH.
12. 10 CFR 20 (Code of Federal Regulations), 2003, Standards for Protection Against Radiation, U.S. Nuclear
Regulatory Commission, Washington, DC or 10 CFR 835, Washington, DC.
13. 10 CFR 100 (Code of Federal Regulations), 2003, Reactor Site Criteria, U.S. Nuclear Regulatory
Commission, Washington, DC.
14. ASME (American Society of Mechanical Engineers), 2002, Nuclear Power Plant Air Cleaning Units and
Components, ASME N509, New York, NY.
15. ASTM (American Society for Testing and Materials), 2000, Standard Guide for Use of Protective Coatings in
Nuclear Power Plants, D5144-00, West Conshohocken, PA.
Section 26
16. SPC (Society of Protective Coating [formerly Steel Structures Painting Council]), 2000, �Near White
Metal Blast Cleaning,� Steel Structures Painting Manual, Surface Preparation Specification 5, SPC-SP-
5/NACE No. 1, vol. 2, Pittsburgh, PA, September.
DOE-HDBK-1169-2003 Chapter 4
4-41
17. SPC (Society of Protective Coating [formerly Steel Structures Painting Council]), 2000, Hand Tool Cleaning,
SSPC-SP2, Pittsburgh, PA, September.
18. SPC (Society of Protective Coating [formerly Steel Structures Painting Council]), 1982 (editorial changes
September 1, 2000), Power Tool Cleaning., SSPC-SP3, Pittsburgh, PA, November 1.
19. ASTM (American Society for Testing and Materials), 2000, Standard Practice for Quality Assurance for
Protective Coatings Applied to Nuclear Facilities, ASTM D3843-00, West Conshohocken, PA.
20. ASTM (American Society for Testing and Materials), 2003, Standard Test Method for Evaluating Coatings Used
in Light-Water Nuclear Power Plants at Simulated Design Basis Accident (DBA) Conditions, ASTM D3911-03,
West Conshohocken, PA.
21. ASTM (American Society for Testing and Materials), Rev. 2001, Standard Test Method for Chemical Resistance
of Coatings Used in Light-Water Nuclear Power Plants, ASTM D3912-95, West Conshohocken, PA.
22. IEST (Institute of Environmental Sciences and Technology), 1984 (reaffirmed 1999), Gas-Phase Adsorber
Cells, IEST-RP-CC008, Mt. Prospect, IL.
23. ASME (American Society of Mechanical Engineers), 2001, Boiler and Pressure Vessel Code, �Welder
Qualification,� New York, NY.
24. ASTM (American Society for Testing and Materials), 2001, Standard Recommended Practice for Liquid
Penetrant Inspection Method, ASTM E165, West Conshohocken, PA.
25. ASTM (American Society for Testing and Materials), 2000, Standard Specification for Flexible Cellular
Materials-Sponge or Expanded Rubber, ASTM D1056, West Conshohocken, PA.
26. Adley, F. E., 1966, �Factors Influencing High- Efficiency Gasket Leakage,� 9th Air Cleaning Conference,
U.S. Atomic Energy Commission Report CONF-660904, National Technical Information Service,
Springfield, VA, September.
27. Sims, L. L., 1969, �Molded HEPA Filter Gasket Leakage,� Hanford Environmental Health Foundation
Report HOHF-11, Richland, WA, September.
28. Sketch provided by Flanders Filters, Inc., Washington, DC.
29. NRC (U.S. Nuclear Regulatory Commission), 2001, Design, Inspection, and Testing Criteria for Air Filtration
and Adsorption Units of Post-Accident Engineered-Safety-Feature Atmospheric Cleanup Systems in Light-Water-Cooled
Nuclear Power Plants, Regulatory Guide 1.52, Revision 3, Washington, DC, June.
30. Young, W. and R. Budynas, 1989, Roark’s Formulas for Stress and Strain, 7th Edition., McGraw-Hill,
New York, NY.
31. ASME (American Society of Mechanical Engineers), 2000, Quality Assurance Requirements for Nuclear Facility
Applications, ASME NQA-1-2000, New York, NY.