DOE-HDBK-1169-2003, Nuclear Air Cleaning Handbook, Chapter 2, System Considerations
Functional areas: Component Design Considerations, Ventilation System, Air Cleaning System
This handbook draws from many special technical areas, each of which requires years of education and practice to master. The authors do not intend to make the reader an "instant expert" in the overall subject or in any of the disciplines of the contributors. The 4th edition of the Nuclear Air Cleaning Handbook succeeds three previous editions: ERDA 76-21, Nuclear Air Cleaning Handbook (1976); ORNL/NSIC-65, Design, Construction and Testing of High-Efficiency Air Filtration Systems for Nuclear Applications (1970); and NSIC-13, Filters, Sorbents, and Air Cleaning Systems as Engineered Safeguards in Nuclear Installations (1966). It benefits from over 25 years of industry experience since the previous edition was published. This revision updates the information provided in ERDA 76-21 and incorporates current thinking as provided by manufacturers, subject matter experts from the DOE complex and members of the ASME Committee on Nuclear Air and Gas Treatment (ASME AG-1 Committee). Chapters have been added on History, Fire Protection, and Occupational Safety and Health.
Related To:
Version history and related documents
Related documents
- DOE-HDBK-1169-2003Nuclear Air Cleaning Handbook, Chapter 1, History of the Development of Air Cleaning Technology in the Nuclear Industry
- DOE-HDBK-1169-2003Nuclear Air Cleaning Handbook, Chapter 5, External Components
- DOE-HDBK-1169-2003Nuclear Air Cleaning Handbook, Chapter 6, Small Air Cleaning Units
- DOE-HDBK-1169-2003Nuclear Air Cleaning Handbook, Chapter 7, Glovebox Filtration
- DOE-HDBK-1169-2003Nuclear Air Cleaning Handbook, Chapter 8, Testing
- DOE-HDBK-1169-2003Nuclear Air Cleaning Handbook, Chapter 9, Special Application Requirements
- DOE-HDBK-1169-2003Nuclear Air Cleaning Handbook, Chapter 10, Fire Protection
- DOE-HDBK-1169-2003Nuclear Air Cleaning Handbook, Chapter 11, Occupational Safety and Health
- DOE-HDBK-1169-2003Nuclear Air Cleaning Handbook, Appendix A, Care and Handling of HEPA Filters
- DOE-HDBK-1169-2003Nuclear Air Cleaning Handbook, Appendix B, Receiving Inspection Direction and Checklist
- DOE-HDBK-1169-2003Nuclear Air Cleaning Handbook, Appendix C, Determination of HEPA Filter Life
- DOE-HDBK-1169-2003Nuclear Air Cleaning Handbook, Chapter 3, Filters for the Nuclear Industry
- DOE-HDBK-1169-2003Nuclear Air Cleaning Handbook, Chapter 4, Housing Design and Layout
- DOE-HDBK-1169-2003Nuclear Air Cleaning Handbook (Introduction) (Part 1 of 15, links to all Parts)
Document text
Text extracted from the attached file. Refer to the original document for the authoritative version.
Section 1
2-1
CHAPTER 2
SYSTEM CONSIDERATIONS
2.1 Introduction
A nuclear air cleaning system is an assembly of interrelated, interactive parts that include the air cleaning
system components, the contained space served by the air cleaning system (e.g., the glovebox, hot cell, room,
or building), and the processes served by that system.
This chapter discusses the design, operational, and codes- and standards-related requirements for nuclear
facility air cleaning systems. Topics will include system, subsystem, and component design considerations, as
well as general descriptions of various systems used in production and fabrication facilities, fuel processing
and reprocessing plants, research facilities, storage facilities, and other applications. This chapter will also
consider operating costs and how the design of an air cleaning system directly affects the ventilation system
performance and costs. Examples of some lessons learned from the operation and maintenance of nuclear
air cleaning systems will be provided.
2.2 Environmental Considerations
The complexity of the air cleaning system needed to provide satisfactory working conditions for personnel
and to prevent the release of radioactive or toxic substances to the atmosphere depends on the following
factors:
• Nature of the contaminants to be removed (e.g., radioactivity, toxicity, corrosivity, particle size and size
distribution, particle shape, and viscidity);
• Heat (e.g., process heat, fire);
• Moisture (e.g., sensible humidity process vapors, water introduced from testing);
• Radiation (e.g., personnel exposure and material suitability considerations);
• Other environmental conditions to be controlled; and
• Upset or accident or accident hazard considerations.
In designing an air cleaning system, development of the environmental operating conditions must be the first
step. Before appropriate individual system components can be environmentally qualified, the designer must
consider all environmental parameters on an integrated basis. This may require additional qualifications.
The facility owner normally identifies the design and environmental parameters that are compatible with the
overall facility design. These parameters must be identified prior to system design because they must be the
basis for the equipment design. If the environmental parameters are carefully considered, a detailed analysis
of cost versus long-term operation will provide an environmental maintenance schedule for replacing
components and parts throughout the intended operational life of the system. This will ensure that the
Nuclear Air Cleaning Handbook U.S. Department of Energy
2-2
system will perform its intended function properly, efficiently, and cost-effectively. Table 2.1 lists some
common system environmental parameters that should be considered for system design.
Table 2.1 – Environmental Parameters for System Design
Parameters Examples
Types of gases treated Air, hydrogen, oxygen, nitrogen, argon, etc.
Flow rate(s) The maximum and minimum operating flow rates for normal and accident
conditions.
Pressure and pressure drop The external pressure and/or vacuum pressure at the inlet and/or outlet of the
system; the maximum system pressure, usually accident or upset mode; the
maximum allowable pressure drop across the air cleaning system components.
Temperatures The maximum and minimum operating temperatures of the airstream and
equipment.
Section 2
Radiation The maximum expected alpha, beta, and gamma radiation dose rates
(rads/hour) and cumulative levels (rads).
Relative humidity, condensation,
and direct introduction of liquids
The maximum and minimum relative humidity of the gas entering the air
cleaning system, condensation with potential for wicking, and direct
introduction of water sprays for fire protection.
Contaminants that may be
removed (or not) from the gas
stream
Removal efficiencies for particulate, gaseous, entrained water, chemical,
radiological, volatile organic chemicals, and other materials, as well as
considerations of other materials’ capabilities for air contaminants.
Seismic requirements Seismic response curves for the expected equipment location.
Pressure-time transients Deflagration (internal), tornado (external)
Design life and operating life Projected facility and equipment operating life [e.g., high-efficiency particulate
air (HEPA) filter service life].
2.2.1 Airborne Particulates and Gases
To properly design an air cleaning system and optimize its performance, the types of contaminants in the gas
stream must be identified. All of the contaminants, both particulate and gaseous, including concentration
levels and particle sizes, must be evaluated to properly design and size the system. The presence of other
particulates, gases, and chemicals must be clearly determined. The presence of volatile organic chemicals
(VOCs), entrained water, and acids will affect the performance of various system components and must be
addressed, if they are present, in the design of the system and its components.
Intake air cleaning systems or supply systems filter the atmospheric dust brought into the facility.
Recirculating systems, if used, clean the air in a building or location and return the air to that location. Other
sources of particulate and gaseous contamination are infiltration and “people-generated” particulates
(e.g., lint, skin, hair) and offgassing of materials such as paint, solvents, carpets, and furniture. All of these
factors must be considered in determining the parameters for proper system design. These contaminants
contribute to degradation and sometimes become radioactive when exposed to certain environments (e.g., by
adsorption of radioactive vapors or gases or by agglomeration with already radioactive particles). Because
particles in the size range of 0.05 to 5 micrometers (µm) tend to be retained by the lungs when inhaled, they
are of primary concern in operations that involve radioactive material.1 They are also recognized as among
the health hazards of nonradioactive air pollution. As shown in Table 2.2, over 99 percent, by count, of
typical urban air samples have a mean particle size of 0.05 µm.
DOE-HDBK-1169-2003 Chapter 2
2-3
Table 2.2 – Distribution of Particles in Typical Urban Air Sample
Mean Particle Size
(µm)
Particle Size Range
(µm)
Approximate Particles Count per
Cubic Foot of Air
Percent by
Weight
Percent by
Count
20.0 50-10 12.5 × 103 28 1 × 10-10
7.5 10-5 10 × 104 63 8 × 10-10
2.5 5-1 12.5 × 106 6 1 × 107
0.75 1-0.5 10 × 107 2 8 × 107
0.25 0.5-0.1 12.5 × 109 1 1 × 104
0.05 0.1-0.001 12.5 × 1015 <1 99.9999
Section 3
Reports of dust concentrations in air are generally based on the masses of the particulate matter present. As
shown in Table 2.2, mass accounts for only a negligible portion of the total number of particles in the air.
This is important in filter selection because it indicates that some filters with a high efficiency based on weight
may be inefficient on a true count basis. That is, the filters are efficient for large particles, but inefficient for
small (less than 0.75 µm) particles. This is true of most common air filters used as prefilters. On the other
hand, the HEPA filter is highly efficient for all particle sizes down to and including the smallest shown in
Table 2.2. The 99.97 percent minimum efficiency claimed for these filters is actually for the most penetrating
size particles, i.e., those ranging in size from 0.07 to 0.3 µm. Dust concentrations vary widely from place to
place and, for the same location, from season to season and from time to time during the same day.
Concentrations in the atmosphere may vary from as low as 20 micrograms per cubic meters (µg/m3) in rural
areas to more than 20 mg/m3 in heavily industrialized areas. Dust-producing operations may generate
concentrations as great as several thousand g/m3 at the workplace. Because the weight percent determinations
on which these concentrations are based account for only a small fraction of the number of particles present,
the true count of particles smaller than 5 µm may number in the billions per 1000 cubic feet (ft3).
Atmospheric dust concentrations can vary significantly through the year.2
Filter selection, particularly prefilter and building supply filter selection, must consider the atmospheric dust
concentrations that can be encountered at a particular site at any time of the year.
Figure 2.1, Distribution of Particles, shows the distribution of particles (by weight percent) in atmospheric air as
a function of particle shape. Variations in particle shape, mean particle size, particle size range, and
concentration affect filter life, maintenance costs, and operational effectiveness. The size range of various
types of particles, the technical nomenclature of various types of aerosols, and the applicability of various
types of air cleaning devices as a function of particle size are shown in Figure 2.2. A major source of the lint
often found on filters is derived from the
abrasion of clothing as people move about. In
addition, a person at rest gives off more than
2.5 million particles (skin, hair, etc.) and
moisture droplets/minute in the size range of
0.3 to 1 µm.3 Process-generated aerosols fall
into two general size ranges. Those produced
by machining, grinding, polishing, and other
mechanical operations are generally large,
(from 1 to several hundred µm), according to
the nature of the process, and can be removed
effectively by common air filters or other
conventional air cleaning techniques. The
other size range includes those produced by
evaporation/condensation and other chemical
operations, which generate droplets and solid Figure 2.1 – Distribution of Particles
Description Appearance Kinds
Percent Present
by Weight
Range Average
Spherical
Irregular
Cubic
Flakes
Fibrous
Condensation
Flocs
Smokes
Pollens
Fly Ash
Minerals
Cinder
Minerals
Epidermis
Lint
Plant Fibers
Carbon
Smokes
Fumes
0-20
10-90
0-10
3-35
0-40
10
40
5
10
15
Nuclear Air Cleaning Handbook U.S. Department of Energy
2-4
Section 4
particles that are often submicrometer-sized. These aerosols are more difficult to separate from air or gases,
requiring collectors such as HEPA filters. Ultra Low Penetration Air (ULPA) filters provide a higher cleaning
efficiency (up to 99.9999 percent for submicrometer particles). [Note: A need for this level of efficiency is
rare for nuclear applications. The media used in ULPA filters is weaker than that used in nuclear-grade
HEPA filters, a factor that must be considered for any application of ULPA filters to a nuclear air cleaning
system or other applications where durability and reliability are concerns.]
2
0.001
Particle Diameter, Micrometers (M)
N2
O2
CO2
CO
He
SO2 n-C H6 10
H O2
C H2 6
Atmospheric Aerosol
Gas
Molecules
3 4 5 6 789 2
0.01
3 4 5 6 789 2
0.1
3 4 5 6 789 2
1
3 4 5 6 789 2
10
3 4 5 6 789 2
100
3 4 5 6 789 2
1,000
3 4 5 6 789 2
10,000
3 4 5 6 789
X-rays Ultraviolet
Visible
Near Infrared Far Infrared Microwave
Solar Radiation
Respirable
Fog Mist Raindrops
Nuclei
Mode
Accumulation
Mode
Coarse
Mode
Particle Size Selective TLV
Thoracic Inhalable
Rickettsia BacteriaVirus
CN CCN
Cloud Condensation Nuclei
Condensation Nuclei
Zinc Oxide Fume
Carbon Black
Oil Smoke
Colloidal
Silica Paint Pigments
Spray Dried Milk
Alkali Fume
Tobacco Smoke
Contact
Sulfuric Mist
Insecticide Dusts
Ground Talc
Sulfuric
Concentrator Mist
Milled Flour
Pulverized Coal
Red Blood Cell
Plant
Spores
Pollens
Flotation Ores
Sneezes
Human Hair
Beach Sand
Visible to Eye
Produced Primarily by
Attrition, Resuspension, or
Coagulation of Previously
Formed Material
Produced Primarily by
Condensation or
Chemical Reactions
from the Gas Phase
TLV = Threshold Limit Value, an occupational
exposure limit for chemicals
Figure 2.2 – Characteristics of Atmospheric and Process-Generated Particulates, Fumes, and
Mists and Effective Range of Air Cleaning Equipment
DOE-HDBK-1169-2003 Chapter 2
2-5
For reactor operations, process-generated contaminants include radioactive noble gases and halogens.
Because of their chemical inertness, limited reactivity with available sorbents, and the great difficulty of
separating them, the noble gases (xenon and krypton) have been treated in the past by simple holdup to allow
time for radioactive decay of the shorter half-life elements, as well as dilution before discharge to the
atmosphere. They can also be separated by cryogenic fractionation, charcoal adsorption, or fluorocarbon
adsorption and stored until a significant degree of radioactive decay takes place. The halogen gases,
essentially elemental iodine and certain volatile organic iodides, are captured by adsorption either on activated
carbon or certain synthetic zeolites.
2.2.2 Pressure
Pressure is one of a number of variables that needs to be evaluated in the course of designing the air cleaning
system because it can significantly affect the fan power requirements and the airflow rate. The pressure of the
airstream can be impacted significantly by the change from the normal operating pressure to the accident or
upset air pressure (e.g., fire may cause pressure increases). See Chapter 5, Section 5.4, entitled “Fans and
Motors,” for fan requirements.
2.2.3 Moisture
Section 5
Moisture is an important consideration in air cleaning system design. Moisture in the air may affect the
performance of the air cleaning system by binding the particulate filters and/or blocking pores and fissures in
the activated charcoal. Where water mist or steam can be expected under either normal or upset conditions,
moisture separators and heaters, if appropriate, must be provided upstream of the filters to prevent plugging,
deterioration, and reduced performance. Condensation from saturated air and gas streams or carryover from
air washers and scrubbers are common sources of moisture. When fire-protection sprinklers are provided in
operating areas, ducts, or plenums, moisture can be drawn into the filters if they are activated. In nuclear
reactors, large volumes of steam and moisture should be expected in the highly unlikely event of a major loss-
of-coolant accident (LOCA) or heat exchanger failure. Moisture on the face of a filter will blind or plug the
filter, creating the potential for filter failure. [Note: HEPA filters exposed to carryover from intentional or
inadvertent fire sprinkler actuation must be replaced.]
Condensation is particularly troublesome when filters are installed in underground pits, in outdoor housings,
or in unheated spaces within buildings. Even when the air entering through the ducts is above the dew point,
duct walls, dampers, or filters may be cold enough to cause condensation on their surfaces. Condensation
can also take place in standby systems. Inspection of standby filters on a monthly or even weekly basis is
recommended to prevent the detrimental effects of condensation.
2.2.4 Temperature
Although some air cleaning system components are prequalified to operate in a given temperature range, the
air cleaning system designer must verify all components of the system will function at the maximum and
minimum temperature conditions for the specified application. If the temperature range of the specific
application exceeds the components’ design qualification temperature, requalification is necessary to meet the
operational and design life requirements of the system.
In general, continuous operation at high temperature (greater than 250 degrees Fahrenheit) is detrimental to
both HEPA filters and activated carbon-filled adsorbers.4 At high temperatures, the shear strength of
adhesives and binders used in the manufacture of HEPA filters and filter media may diminish, thereby
limiting the safe pressure drop to which they can be subjected. The limiting temperature varies with the
specific adhesive and binders used. Filter manufacturers have designed HEPA filters for temperatures above
250 degrees Fahrenheit (a 500-degree Fahrenheit filter is also available). The filter manufacturer should
Nuclear Air Cleaning Handbook U.S. Department of Energy
2-6
provide objective evidence that the filters are qualified for the higher-temperature environments of the
specific application.
For high-temperature applications, particulate filtration can be accomplished with the use of metal filters
constructed of sintered metal or metal mesh. The construction and performance requirements for metal
filters will be found in American Society of Mechanical Engineers (ASME) Code AG-1, Code on Nuclear Air
and Gas Treatment.4 Metal filters are manufactured for medium efficiency and HEPA efficiency ranges. Due
to their relatively high cost, metal filters should be considered only for those applications where standard
glass fiber filters would not meet the environmental or design conditions.
Section 6
The limiting temperature of adsorbents for capturing radioactive iodine and iodine compounds is related to
the desorption temperature of the adsorbed compound and the chemicals with which it has been impregnated
to enhance its adsorption of organic radioiodides. For example, the limiting temperature of adsorbents
impregnated with chemicals (e.g., triethylene-diamine- and iodine-impregnated activated carbon) is
280 degrees Fahrenheit.
When temperatures higher than the operating limits of air cleaning system components must be
accommodated, chilled water coils, heat sinks, dilution with cooler air, or some other means of cooling must
be provided to reduce temperatures to levels that the components can tolerate. Environmental qualification
of an air cleaning system must address thermal expansion and the heat resistance of ducts, dampers, filter
housings, component mounting frames and clamping devices, and fans. Electrical and electronic components
are specifically susceptible to high and low temperatures and must be designed and qualified for Safety Class
and Safety Significant systems in accordance with the ASME AG-1 Code5 and Institute of Electrical and
Electronics Engineers (IEEE) 323, Standard for Qualifying Class 1E Electrical Equipment for Nuclear Generating
Stations5 and IEEE 344, Recommended Practice for Seismic Qualification of Class 1E Equipment in Nuclear Generating
Stations.6 Operational consideration also must be given to the flammability of dust collected in the ducts and
on the filters. All Safety Class and Safety Significant systems must be built to ASME AG-1.
2.2.5 Corrosion
Many radiochemical operations generate acid or caustic fumes that can damage or destroy filters, system
components, and construction materials. Some products of radiochemical operations can produce shock-
sensitive salts (e.g., perchloric acid salts and ammonium nitrate) that must be specifically considered in the
design and operation. The air cleaning system designer must select components and materials of construction
suitable for the corrosive environment to ensure high levels of system performance and reliability.
Acid-resistant prefilters and HEPA filters are available. These filters utilize media constructed with Nomex®
or Kevlar® fibers mixed with glass fibers during manufacturing, epoxy-coated separators to extend the life of
the aluminum separators, and stainless steel frames.
Metal filters with a demonstrated suitability for a corrosive atmosphere, in accordance with the ASME AG-1
Code4, are recommended for hydrogen fluoride or other highly acidic applications. Hydrogen fluoride is a
concern because it will attack the glass media. Wood-case filters are vulnerable to attack by nitric acid that
will form nitrocellulose.
Stainless steel is recommended for ductwork and housings when corrosion can be expected. Even this
material may be insufficient in some cases, and coated (e.g., vinyl, epoxy) stainless steel or fiber-reinforced
plastics may be necessary (corrosion-resistant coatings are covered by American Society for Testing and
Materials (ASTM) D5144, Standard Guide for Use of Protective Coating Standards in Nuclear Power Plants.7 The
system designer can either: (1) use existing databases containing information about the performance of
DOE-HDBK-1169-2003 Chapter 2
2-7
materials (including the filter media) exposed to various concentrations of corrosive contaminants, or
(2) perform actual testing to validate the air cleaning system design.
Section 7
Scrubbers or air washers may be employed to pretreat the air or gas before it enters the air cleaning system or
to scrub the airstream of perchloric and ammonium nitrate salts, but consideration must also be given to
moisture carryover if the scrubbers or air washers are not designed and operated properly. Stainless steel
moisture separators are recommended ahead of the filters. Corrosion is always a danger, but is not always
obvious. In activated carbon-filled adsorbers, for example, even trace amounts of nitrous oxide or sulfur
dioxide will concentrate in the adsorbent over time. In the presence of moisture, these compounds can form
nitric or sulfuric acids that are capable of corroding the stainless steel parts of the adsorber, i.e., the perforated
metal screens. Aluminum and carbon steel are subject to corrosion when in contact with moisture-laden
carbon. For this reason, stainless steel is always specified for adsorber cells and for adsorber-cell mounting
frames.
Electrical and electronic components are particularly susceptible to corrosive atmospheres. Plastics become
brittle over time, contacts corrode, etc. For this reason, all electronic components must be environmentally
qualified for the intended application.
Care must be exercised in selecting and using gaskets, as some gasket material reacts with the moisture in the
airstream and releases chlorides that can corrode steels (including stainless steel). Gasket material selection
should also include consideration of the effects of the material’s use in acidic, radioactive, or other harsh
environments. In addition, care must be exercised for gasket stability when dealing with radiation. Radiation
may also lead to undesirable reactions such as decomposition of Teflon™ into hydrofluoric acid.
2.2.6 Vibration
Vibration and pulsation can be produced in an air or gas cleaning installation by turbulence generated in
poorly designed ducts, transitions, dampers, and fan inlets and by improperly installed or balanced fans and
motors. Excessive vibration or pulsation can result in eventual mechanical damage to system components
when accelerative forces (e.g., from an earthquake or tornado) coincide with the resonant frequencies of
those components. Weld cracks in ducts, housings, and component mounting frames can be produced by
even low-level local vibration if sustained, and vibrations or pulsations that produce no apparent short-term
effects may cause serious damage over longer periods.
Vibration produces noise that can range from the unpleasant to the intolerable. Important factors in the
prevention of excessive vibration and noise include planning at the initial building layout stage and space
allocation to ensure that adequate space is provided for good aerodynamic design of ductwork and fan
connections. Spatial conflicts with the process and with piping, electrical, and architectural requirements
should be resolved during early design to avoid the compromises so often made during construction that
frequently lead to poor duct layout and resulting noise and vibration. Ducts should be sized to avoid
excessive velocities, while maintaining the transport velocities necessary to prevent the settling out of
particulate matter during operation. Fan vibration can be minimized through the use of vibration isolators
and inertial mountings. Some designers require hard mounting of fans where seismic requirements and
continued operation during and after an earthquake must be considered. Flexible connections between the
fan and ductwork are often employed, but must be designed to resist seismic loads and high static pressures,
particularly in parts of the system that are under negative pressure to minimize air-in leakage. Finally, the
ductwork system must be balanced after installation, not only to ensure the desired airflows and resistances,
but also to “tune out” any objectionable noise or vibration that may have been inadvertently introduced
during construction.
Section 8
Nuclear Air Cleaning Handbook U.S. Department of Energy
2-8
2.2.7 Electrical
Emergency electrical power is required when specified by facility safety documentation. Emergency power
has specific requirements and may not be required for all systems. Standby electrical power is used for many
safety air cleaning systems not classified as Safety Class. Standby power is required for safety-significant air
cleaning systems.8, 9, 10 The amount of emergency power required for fans, dampers, valves, controls, and
electrical heaters to control the relative humidity of the effluent airstream (as dictated by the facility design
requirements) must be accounted for during accident or upset conditions. Close coordination between the
system designers of both the air cleaning and electrical systems is required to ensure this is done, as there is a
set amount of emergency power available.
2.2.8 Radiological Considerations
Radiation may affect the air cleaning system in at least three different ways:
• The buildup of radioactive material in and around the air cleaning system may limit personal access
during operations and maintenance, and must be specifically factored into the design.
• The buildup of radioactive material in and around the air cleaning system may lead to special
considerations for construction materials used for the system—particularly those containing Teflon® or
Kel-F®. This buildup can also limit component life.
• The amount of radioactive material that may be released limits the acceptable selection and operating
ranges for the air cleaning system components (e.g., the HEPA and adsorption units).
The design of workroom ventilation systems should be consistent with the requirements of 10 CFR 835,
Occupational Radiation Protection, Subpart K, “Design and Control,” which establishes the U.S. Department of
Energy’s (DOE) design objectives for workplace radiological control.11 Two key components of these
requirements are that: (1) for controlling airborne radioactive material, under normal conditions, the design
objective will be to avoid releases to the workplace atmosphere, and (2) confinement and ventilation will
normally be used to accomplish this objective (i.e., engineered controls should be applied rather than relying
on administrative controls). Furthermore, effluent releases from ventilation systems must be in accordance
with DOE directives and relevant regulatory requirements (e.g., DOE Order 5400.5, Radiation Protection of the
Public and the Environment,12 and 40 CFR Part 61, subpart H, National Emission Standards for Air Pollution.13
All work conducted within areas serviced by these ventilation systems, or work on the systems themselves,
should be performed in accordance with site policies and procedures. The requirements for control of
radiation and radioactive material in the workplace are contained in 10 CFR 835.11 This rule also establishes
the requirements for monitoring of workplaces within and surrounding these areas, and that these activities
should be conducted in accordance with site policies and procedures.
Some systems have actually experienced radiological degradation from excessive radiation exposure (e.g., the
A and B underground filters at the Hanford B-Plant). Radiological degradation, overloading, and faulty
installation and change-out of HEPA filters led to contamination of several parking lots and grounds around
ORNL’s Building 3098.
2.2.9 Confinement Selection Methodology
Section 9
Workroom ventilation rates are based primarily on cooling requirements, the potential combustion hazard,
and the potential inhalation hazard of substances that are present in or could be released to the workroom.
Concentrations of radioactive gases and aerosols in the air of occupied and occasionally occupied areas
DOE-HDBK-1169-2003 Chapter 2
2-9
should not exceed the derived air concentrations (DAC) established for occupationally exposed persons
under normal or abnormal operating conditions, and releases to the atmosphere must not exceed permissible
limits for nonoccupationally exposed persons.11 Because radioactive gases and aerosols might be released
accidentally in the event of an equipment failure, a spill, or a system upset, the ventilation and air cleaning
facilities must be designed to maintain airborne radioactive material within prescribed limits during normal
operations.12, 13 In addition, the ventilation and air cleaning facilities must perform in accordance with
expectations established during the evaluation of potential accident conditions.8, 10
The current DACs for radioactive substances in air are specified in 10 CFR 835, Appendix A.11 These DACs
should be applied to the design of a ventilation system using a hazard categorization process where the level
of ventilation control is commensurate with the radiological risk present in the proposed operation. [Note:
In a similar manner, the same conceptual process can also be applied to nonradiological airborne hazards.]
There are no current DOE directives or technical standards that establish such an approach, but guidance is
contained in the archived DOE Order 6430.1A, General Design Criteria,14 and further expanded in the Heating,
Ventilating, and Air Conditioning Design Guide for the Department of Energy Nuclear Facilities,15 published by the
American Society of Heating, Refrigerating, and Air Conditioning Engineers, Inc., (ASHRAE).
Based on the guidance cited above, one approach would be to group the material in use into the hazard
classes shown in Table 2.3, and then to zone the facility ventilation systems based on the criteria shown in
Table 2.4. [Note: The limits given in the tables are guides and should not be considered absolute.] An
alternative approach would be to classify the risk based on the anticipated airborne and surface contamination
levels, as shown in Table 2.5. The user must note that these criteria are based on the potential for the
activity to generate airborne radioactive materials; they do not consider the direct radiation from the material,
which would require separate shielding considerations. By introducing such indexes of potential hazards and
limitations on the quantities of materials that can be handled, it is possible to establish a basis for ventilation
and air cleaning requirements in various parts of a building or plant. Figure 2.3 illustrates a typical zoning
plan for a nuclear facility. Not all of the confinement zones listed in Table 2.4 would be required in all
buildings, and an entire building could possibly be designated a single zone. Confinement zones are defined
with respect to function and permitted occupancy in the following paragraphs.
Confinement Zones
Section 10
As shown in Figure 2.3, the general approach is to establish ventilation zones in a three-tiered manner.
Multizoned buildings are usually ventilated so that air flows from the less contaminated zone to the more
contaminated zone. Areas from which air is not recirculated include areas that produce or emit dust particles,
heat, odors, fumes, spray, gases, smoke, or other contaminants that cannot be sufficiently treated and could
be potentially injurious to health and safety of personnel or are potentially damaging to equipment. These
areas are 100 percent exhausted. Recirculation within a zone (circulating the air through a high-efficiency air
cleaning system before discharge back to the zone) is permitted, but recirculation from a zone of higher
contamination back to a zone of lesser contamination is prohibited. The interiors of exhaust and
recirculating ductwork are considered to be of the same hazard classification as the zone they serve. Airflow
must be sufficient to provide the necessary degree of contaminant dilution and cooling and to maintain
sufficient pressure differentials between zones where there can be no backflow of air spaces of lower
contamination, even under upset conditions. The pressure differentials should be determined during the
facility’s design, and should be in accordance with the applicable standards. [Note: Substantially higher
differentials are often specified between Primary and Secondary Confinement Zones (see below) than for
other boundaries.]
Nuclear Air Cleaning Handbook U.S. Department of Energy
2-10
Table 2.3 – Hazard Classification of Radioisotopes
Hazard Class Relative Hazard DAC, Air (µCi/ml)
1 Very High <10-10
2 High 10-10 to 10-8
3 Moderate 10-8 to 10-6
4 Negligible 10-6
Table 2.4 – Zoning of Facilities Based on Radiotoxicity of Materials Handled
Quantity of Material Permitted in Zone at any One Time a, b
Radiotoxicity of Isotopes Primary Confinement Secondary Confinement Tertiary Confinement
Very High > 10 mCi 0.1 µCi-10mCi 0-0.1 µCi
High > 100 mCi 1.0 µCi-100mCi 0-1.0 µCi
Moderate >1 Ci 10 µCi-1 Ci 0-10 µCi
Negligible >10 Ci 100 µCi-10 Ci 0-100 µCi
a There are practical upper limits to the quantities of materials in any particular zone, based on the type of material and design
of the confinement systems. For example, criticality safety concerns may restrict the amount of fissile material that can be
handled at one time, fire protection concerns may limit the amount of pyrophoric materials, and shielding considerations may
limit the amount of materials when penetrating radiation is emitted. An activity-specific hazards analysis should always be
conducted to determine the actual limits to be applied in practice.
b These criteria are based on the potential for the activity to generate airborne radioactive materials.
Table 2.5 – Zoning of Facilities Based on Contamination Levels
Anticipated Contamination Levels
Type of Contamination Primary Confinement Secondary Confinement Tertiary Confinement
Airbornea >100 × DAC 1 × DAC to 100 × DAC < 1 × DAC
Removable Surfaceb >>RSCVc >RSCVc <RSCV
a For airborne contamination, the DAC is the derived airborne concentration value listed in 10 CFR 835,11 Appendix A, for the
type and chemical form of the material being handled.
b For removable contamination, the RSCV is the removable surface contamination value listed in 10 CFR 835,11 Appendix D,
for the type of the material being handled.
c Removable surface contamination levels do not always directly lead to an increasing level of airborne contamination. The
Section 11
level of airborne contamination strongly depends on the potential for the particular activity to resuspend the deposited
particles into the atmosphere. For this reason, it is difficult to establish a generic correlation. If the RSCV is the main
consideration for differentiating between a secondary and primary confinement specification, then the approach established
in Tables 2.3 and 2.4 should be applied.
The methodology used above is based on the DACs for radioactive substances in air, as specified in 10 CFR
835.11 For toxics and noxious substances, the DACs must be replaced with Permissible Exposure Limits
(PEL), including irritant and nuisance substances, as specified in 29 CFR 1910.16 However, because the
Federal PELs are obsolete in some cases, the Threshold Limit Values (TLVs) published annually by the
American Conference of Governmental Industrial Hygienists (ACGIH)17 should be consulted. In the case of
a difference between the PEL and TLVs, it is generally recognized and accepted practice among industrial
hygienists to use the more stringent of the two limits. A more convenient (and generally more current)
tabulation of occupational exposure limits is published by the ACGIH in the annual issue of Threshold Limit
Values. The latter reference includes a procedure for determining TLVs for mixed toxicants, as well as limit
values for heat stress, nonionizing radiation, and noise. DOE Order 440.1A, Worker Protection Management for
DOE Federal and Contractor Employees,18 specifies how to select PELs and TLVs.
DOE-HDBK-1169-2003 Chapter 2
2-11
Figure 2.3 – Typical Process Facility Confinement Zones
Confinement
Building
Atmosphere
Primary
Confinement
Secondary
Confinement
Tertiary
Confinement
Building
Structure
Airflow
Admin.
Areas
Clean Normally Clean
Potentially Contaminated
Operations/
Maintenance
Rooms
Gloveboxes
Contaminated
(Zone III)(Zone IV) (Zone II) (Zone I)
Primary Confinement Zone
The primary confinement zone comprises those areas where high levels of airborne contamination are
anticipated during normal operations. Facility personnel do not normally enter primary confinement zones.
When entry is necessary, it is done under tightly controlled conditions. This zone includes the interior of a
hot cell, glovebox, piping, vessels, tanks, exhaust ductwork, primary confinement HEPA filter plenums, or
other confinement for handling highly radiotoxic material.16 Confinement features must prevent the spread
of radioactive material within the building under both normal operating and upset conditions up to and
including the design basis accident (DBA) for the facility. Complete isolation (physical separation) from
neighboring facilities, laboratories, shop areas, and operating areas is necessary. Unavoidable breaches in the
primary confinement barrier must be compensated for by an adequate inflow of air or safe collection of the
spilled material. The exhaust system must be sized to ensure an adequate inflow of air in the event of a
credible confinement breach. An air exhaust system that is independent of those serving surrounding areas is
required. High-efficiency filters, preferably HEPA type, are typically required in air inlets, and two
independently testable stages of HEPA filters are required in the exhaust. The exact number of testable
stages is determined by safety analysis.8, 10
Secondary Confinement Zone
Section 12
The secondary confinement zone comprises those areas where airborne contamination could be generated
during normal operations or as a result of a breach of a primary confinement barrier. This zone consists of
the walls, floors, ceilings and associated ventilation systems that confine any potential release of hazardous
materials from primary confinement. Related areas include glovebox operating areas, hot cell service or
maintenance areas, and the ventilation system servicing the operating areas.15 Pressure differentials must be
available to produce inward airflow into the primary confinement should a breach occur. Penetrations of the
secondary confinement barrier typically require positive seals to prevent migration of contamination out of
Nuclear Air Cleaning Handbook U.S. Department of Energy
2-12
the secondary confinement zone. Air locks or a personnel clothing-change facility are recommended at the
entrance to the zone. Restricted access areas are generally included in the secondary confinement zone.
Tertiary Confinement Zone
The tertiary confinement zone comprises those areas where airborne contamination is not expected during
normal facility operations. This zone consists of the walls, floors, ceilings, and associated exhaust system of
the process facility.15 It is the final barrier against release of hazardous material to the environment. This
level of confinement should never become contaminated under normal operating conditions. The secondary
and tertiary boundaries may exist in common, as in a single-structure envelope.
Example Airflow Criteria
As an example of the zoning approach discussed in this section, the criteria listed in Tables 2.6, 2.7, 2.8, 2.9,
and 2.10 are specified at one of DOE’s national laboratories for the design and operation of radiochemical
and laboratory facilities and for the buildings that contain them.19 [Note: Numerical values can be reduced
or increased depending on the requirements for operating conditions and the DBA for that facility.]
Table 2.11 contains recommendations for the pressure differentials between zones in multizoned buildings.
Table 2.6 – Airflow Criteria for Design and Operation of Hot Cells, Caves, and Canyons
(Primary Confinement)
1. A vacuum equal to or greater than 1 (inches water gauge) in.wg relative to surrounding spaces must be maintained at all times
to ensure a positive flow of air into the confinement.
2. Confinement exhaust must be at least 10 percent of cell volume/min to minimize possible explosion hazards due to the
presence of volatile solvents and to ensure that, in the event of cell pressurization due to an explosion, the confinement will be
returned to normal operating pressure (1 in.wg) in a minimum of time.
3. The maximum permissible leak rate must not exceed 1 percent of cell volume/minute for unlined cells and 0.1 percent of cell
volume/minute for lined and sealed cells at a ∆p of 2 in.wg to ensure minimal escape of radioactive material in the event of cell
pressurization; the maximum permissible leak rate for ductwork is 0.1 percent of duct volume/minute at ∆p equal to 1.5 times
the static pressure of ductwork. Hot cells, caves, and canyons must not be hermetically sealed.
4. Seals and doors must withstand a ∆p of at least 10 in.wg to ensure the integrity of closures and penetrations under all operating
and design basis upset conditions.
5. The confinement structure must withstand the DBA for that facility without structural damage or loss of function.
Section 13
6. Operating procedures must be designed to limit quantities of flammable and smoke-producing materials and solvents within
limits that can be accommodated by the ventilation system without endangering the functionability of the air cleaning facility.
Table 2.7 – Airflow Criteria for Gloveboxes (Primary Confinement)
1. The vacuum must be at least 0.3 in.wg between the glovebox and the surrounding room. Consult the latest edition of the
American Glovebox Society’s Guidelines for Gloveboxes, AGS-G001,20 and the ACGIH’s Industrial Ventilation – A Manual of
Recommended Practice21 for guidance concerning ventilation of gloveboxes.
2. The exhaust rate is not specified, but must be adequate for the heat load and dilution requirements of operations conducted in
the glovebox. For example, operations with flammable materials must maintain concentrations below those specified.
3. Airflow must be sufficient to provide an adequate face velocity at the passthrough port to the glovebox [50 linear feet per
minute (fpm)] and to maintain an inward velocity of at least 125 linear fpm (with higher velocities mandated by some operators
for gaseous effluents) through one open gloveport in every five gloveboxes in the system. This will ensure adequate inflow to
prevent the escape of contamination in the event of glove failure.
4. Individual gloveboxes must be isolated or isolatable (under upset conditions) to prevent fire spreading from one box to
another.
DOE-HDBK-1169-2003 Chapter 2
2-13
Table 2.8 – Airflow Criteria for Chemical Fume Hood (Primary Confinement)
1. A vacuum must be at least 0.1 in.wg between the laboratory in which the fume hood is installed and the corridor from which
the laboratory is entered.
2. The exhaust rate of the fume hood must be sufficient to maintain sufficient airflow face velocity into the hood to prevent the
release of fumes from the hood to the room, even when the operator walks rapidly back and forth in front of and close to the
hood face. A face velocity of 80 to 100 linear fpm is recommended for operations with highly hazardous (including
radioactive) materials. Higher velocities were once recommended, but are not now due to the generation of vortices by faster
airflows which cause air inside the hood to migrate to the outside. Consult the latest edition of the American Industrial
Hygiene Association’s American National Standard for Laboratory Ventilation, Z9.5,22 for guidance.
3. Each hood in the laboratory should be isolatable by means of dampers to prevent backflow through a hood when it is not in
service.
4. Each hood used for handling radioactive materials should have a testable HEPA filter in its exhaust duct, located close to the
duct entrance. All hoods should, where practicable, exhaust to a common stack.
Table 2.9 – Airflow Criteria for Secondary Confinement Structures or Buildings
1. The building (structure) must be designed to prevent the dispersal of airborne contamination to the environment in the event
of an accident in a hot cell, glovebox, fume hood, or building space.
2. Under emergency conditions, the building must be capable of being maintained at a vacuum of 0.1 to 0.3 in.wg relative to the
atmosphere. For increased reliability and simplicity, some buildings are held at this pressure under normal operating
conditions. However, if this is not practicable, the ventilation system must be capable of reducing building static pressure to
0.2 in.wg in 20 seconds or less. All building air must be exhausted through at least one stage of HEPA filters. During an
emergency, the differential pressure between primary confinement spaces (gloveboxes, hot cells) and other building spaces
must also be maintained.
Section 14
3. Airflow within the building must be from areas of less contamination to areas of higher (or potentially higher) contamination.
4. Recirculation of air within the same zone or room is permitted, but recirculation from primary and secondary confinement
zone exhausts to other building volumes is prohibited.
Table 2.10 – Airflow Criteria for Air Handling Systems
1. It is recommended that ventilation (recirculating, supply, or exhaust) and offgas systems must be backed up by redundant air
cleaning systems (including filters and fans) to maintain confinement in the event of fan breakdown, filter failure, power
outage, or other operational upset. Airflow must always be from the less hazardous to the more hazardous area under both
normal and upset conditions.
2. Air exhausted from occupied or occasionally occupied areas must be passed through prefilters and at least one stage of HEPA
filters. Contaminated and potentially contaminated air exhausted from a hot cell, cave, canyon, glovebox, or other primary
confinement structure or vessel should pass through at least two individually testable stages of HEPA filters in series, as well as
prefilters, adsorbers, scrubbers, or other air cleaning components that are required for the particular application. Exact HEPA
filter stages are determined by safety analysis.8, 10 Only one stage of HEPA filters is required for the exhaust of: (1) air that is
normally clean, but has the potential of becoming contaminated in the event of an operational upset (e.g., exhaust from a
Secondary Confinement operating area) or during service operations when the zone is opened to a zone of higher
contamination (e.g., a hot cell service area), and (2) air from a potentially mildly contaminated space (e.g., a Secondary
Confinement area).
3. Moisture or corrosives in the exhaust that are capable of damaging or unduly loading the HEPA filters (or other components
such as adsorbers) must be removed or neutralized before they can reach components that could be affected.
4. HEPA filters and adsorbers (where required) must be tested in place at a prescribed frequency in accordance with ASME Code
AG-1, Section TA4 and ASME N510.23 HEPA filter stages should exhibit a stage leak rate better than 0.05 percent, as long as
the leak rate is supported by documented safety analysis and provides an adequate safety margin, as determined by an in-place
test performed in accordance with ASME Code AG-1.4
Nuclear Air Cleaning Handbook U.S. Department of Energy
2-14
Table 2.11 – Recommended Confinement System Differential Pressure (in.wg)15
Type of Facility Primary/Secondary Secondary/Tertiary Tertiary/Atmosphere
New -0.7 to -1.0b,c -0.1 to -0.15 -0.1 to -0.15
Existinga -0.3 to -1.0c,d -0.03 to -0.15 -0.01 to -0.15
a These guidelines should be used if the existing area/facility differential pressure design basis is unknown or if there are no site-
specific standards.
b Canyons, cells: -1.0 in.wg (minimum).
c Gloveboxes (air) typically operate at -0.3 to -1.0 in.wg with respect to the surrounding room. Gloveboxes (air) typically have
alarms set at -0.5 in.wg. Gloveboxes (inert gas): -0.3 to -1.25 in.wg with respect to surrounding room. For the purposes of
enabling the operator to work at the glovebox (ergonomic considerations), the operating differential pressure should be closer to
-0.3 in.wg
d Canyons, cells: approximately -1.0 in.wg.
NOTES:
1. It may be necessary in some cases to split a single zone into two areas, “a” and “b,” where one area contains a greater hazard than
Section 15
the other. If area “a” were the more hazardous area, it would be at a negative pressure compared with area “b.” Usually, no
differential pressure guidelines exist for areas within the same zone. Therefore, maintaining proper airflow directions is typically
the primary requirement.
2. Pressure cascades may need to be established within the secondary confinement. A 0.05–in.wg pressure differential between
cascade stages is generally adequate.
3. If glovebox relief valves are included, they are typically set at -0.4 in.wg. Relief valves are designed for breach of the glove port.
2.3 Operational Considerations
This section addresses safety and design requirements, safety classification, regulatory requirements, codes
and standards requirements, redundancy and separation, and material restrictions.
2.3.1 Operating Mode
According to operational requirements, an air cleaning system may be operated full-time, part-time, or simply
held in standby for emergency service. If processes in the building are operated only one or two shifts a day,
the designer may have a choice between continuous operation and operation only during those shifts. The
designer must evaluate and compare the effects of daily starts and stops on the performance and life of filters
and other components to the higher power and maintenance costs that may be incurred by continuous
operation. All factors considered, experience has shown that continuous operation of air cleaning facilities,
perhaps at reduced flow during weekends and holidays, is generally the most satisfactory mode of operation
for buildings in which radioactive operations are conducted. Unless ducts, filter housings, damper frames,
and fan housings (i.e., the pressure boundary) are extremely leaktight, outleakage of contaminated dust into
occupied spaces of the building may occur during shutdown periods.
Many facilities require standby exhaust or air cleanup systems that are operated only in the event of an
emergency or redundant air cleaning facilities that are brought into operation when a parallel online facility is
shut down because of failure or for maintenance. When designing standby systems, the engineer must keep
in mind the possibility of component, filter, and adsorber deterioration from environmental conditions
(e.g., condensation, temperature) even when the system is not in use.
2.3.2 Particulate Filter Change Frequency
The principal costs of operating a high-efficiency air cleaning system are power (e.g., for fans), replacement
filters and adsorbers, labor, and waste disposal costs for radioactive contaminated wastes. The principal
factor that affects these costs is the frequency of filter changes. Replacement filters and adsorbers and the
labor costs to install and test the filter system in-place after installation of replacement filters may make up as
much as 70 percent of the total cost of owning a system (including capital costs) over a 20-year period.
DOE-HDBK-1169-2003 Chapter 2
2-15
Power accounted for only 15 percent of total owning costs in a study made by the Harvard Air Cleaning
Laboratory.24 Measures such as use of high-efficiency building supply-air filters, use of prefilters ahead of
HEPA filters, operation of the system below its rated airflow capacity, and operation of HEPA filters until
they have reached high airflow resistance before replacement all tend to decrease filter change frequency and
thereby reduce costs. Caution should be exercised when establishing filter change frequency. Filters can
become loaded with radioactive particles or reach an age when replacement is warranted even though they
may not be dust/dirt-loaded to a point that indicates change-out is necessary due to pressure drop. These
same filters may also have an acceptance in-place field test result.
Section 16
For systems governed by commercial nuclear power plant technical specifications, strict requirements for
operating filters at maximum pressure drops are specified. Therefore, filters should not be operated at
maximum pressure drop; they must always be ready with enough remaining capacity and strength to handle
the loading that can be expected from a design basis event.
Lawrence Livermore National Laboratory recently developed the requirement that HEPA filters be replaced
10 years after the date of manufacture. Exceptions to this requirement include:
• Any filter that becomes wet (e.g., as a result of an in-duct water sprinkler’s activation or water spraying
directly on the filter) must be replaced promptly.
• Any filter that potentially could become wet (e.g., via an in-duct water sprinkler’s activation) must be
replaced within 5 years of the date of manufacture.25
The underlying rationale for this set of requirements is found in Bergman’s Maximum HEPA-Filter Life.25 Part
of the author’s rationale is based on remaining acceptable tensile strength, which cannot be determined by
nondestructive field tests.
2.3.3 Building Supply-Air Filters
Atmospheric dust brought into the building with ventilation air constitutes a substantial fraction of the dirt
load in the building and the dust load in the exhaust air cleaning system. Removing this dust before it gets
inside the building provides the double advantage of protecting the exhaust filters from premature dust
loading and reducing janitorial and building maintenance costs. When operations within a building do not
generate heavy concentrations of smoke, dust, or lint, it may be possible to substantially reduce the dust
loading in the exhaust system by providing medium-efficiency [50 to 65 percent ASHRAE
Efficiency/Minimum Efficiency Reporting Value (MERV) 10-11]26 building supply-air filters, thereby shifting
much of the burden of what would otherwise be a change of “hot” (radioactive) prefilters in the exhaust
system to a more economical change of “cold” supply-air filters. The labor costs involved in replacing “cold”
filters is a small fraction of those for replacing “hot” filters. Noticeable reductions in janitorial costs have
been observed in several DOE installations after changing to higher-efficiency building supply-air filters.
Louvers and/or moisture separators must be provided at the air inlet to protect the supply filters from the
weather. Rain, sleet, snow, and ice can damage or plug building supply-air filters, resulting not only in
increased operating costs, but also upset of pressure conditions within the building and possible impairment
of the more critical exhaust air cleaning system. Heaters are desirable in the building supply system even in
warm climates. Icing has caused severe damage to building supply-air filters at a number of DOE
installations, even in the South. Screens should be provided over supply-air inlets located at ground- or roof-
level to protect inlet filters and demisters from grass clippings, leaves, dirt, and windblown trash. If possible,
inlets should be located well above grade or adjacent roofs so they are not exposed to such materials.
Nuclear Air Cleaning Handbook U.S. Department of Energy
2-16
2.3.4 Prefilters
Section 17
Prefilters are intended to remove large particles upstream of HEPA filters. HEPA filters are intended
primarily for removal of submicrometer particles and should not be used as coarse dust collectors. They have
relatively low dust-holding capacity, particularly for large particles and lint, and may plug rapidly when
exposed to high concentrations of such material or smoke. Lint may tend to bridge the pleats of the filter,
further reducing its capacity. The HEPA filter is also the most critical particulate-removal element in the air
cleaning system from the standpoint of preserving confinement, and its failure will result in failure of system
function.
Prefilters, installed either locally at the entrances to intake ducts, in the central exhaust filter house, or both,
extend the life of HEPA filters and provide at least a measure of protection against damage. Local duct-
entrance filters also minimize dust accumulation in
ducts and reduce an otherwise potential fire hazard. A
typical increase in HEPA filter life through the use of
prefilters is depicted in Figure 2.4. The increase for a
specific application depends, of course, on the quality
of the prefilter selected and the nature and
concentration of dusts and particulate matter in the
system.
Generally, prefilters should be provided when the
potential dust concentration in the air leading to the air
cleaning system exceeds 20 mg/m3 and should be
considered if the dust concentration exceeds 1 grain
per 1000 cubic feet (ft3). The use of prefilters is
recommended in engineered safety feature (ESF)
systems for nuclear reactors.27 The decision to install
prefilters should be based on providing the best
operational balance between HEPA filter change
frequency, and procurement and maintenance costs for
the prefilters.
Duct-entrance prefilters can be changed without
entering or interrupting the central air cleaning facility,
can minimize dust buildup in the ducts, and can
provide a measure of protection against duct
corrosion, accidental high-moisture loadings, and
flaming trash or sparks that may be produced by a fire
in the working space. On the other hand, a system
that has a number of local prefilter installations may
cost from two to three times as much as one in which
the same prefilter capacity is installed in a central
housing.24
Prefilters in a central air cleaning system should not be attached directly to or installed back-to-back to HEPA
filters; they should be installed on a separate mounting frame located at least 4 to 5 feet upstream of the
HEPA filters. This installation requires more building space and higher investment costs (particularly when
building space is at a premium), but it is justified by increased safety and greater system reliability. Adequate
space between prefilters and HEPA filters is needed for access and maintenance and to minimize the
propagation of fire by sparks or direct flame impingement. If the possibility of fire is a serious consideration,
Figure 2.4 – Comparison of HEPA Filter
Life With and Without Prefilter
6
4
2
0
0 6 12 18 24
P
re
s
s
u
re
D
ro
p
(i
n
.w
g
)
Service Life (months)
(a) HEPA Filter Alone
6
4
2
0
0 6 12 18 24
P
re
s
s
u
re
D
ro
p
(i
n
.w
g
)
Service Life (months)
(b) HEPA Filter with Prefilter
DOE-HDBK-1169-2003 Chapter 2
2-17
a removable screen, fine enough to stop sparks (10 to 20 mesh), may be installed on the downstream side of
the prefilters.
2.3.5 Operation to High Pressure Drop
Section 18
Most HEPA filter manufacturers’ literature suggests replacement of HEPA filters when the resistance due to
dust loading has reached 2 in.wg. HEPA filters are qualified according to the requirements of ASME AG-1,
Section FC,4 to be capable of withstanding a pressure drop, when new, of 10 in.wg without structural damage
or reduction of efficiency. [Note: This value is for qualification purposes only, and must not be used for
operation.] When other factors such as radioactivity and fan capacity do not have to be considered,
replacement at a pressure drop of only 2 in.wg is considered under-utilization of the filter. At many DOE
facilities, HEPA filters are operated routinely to pressure drops as high as 4 in.wg. Figure 2.5 shows the
effect of such operation on filter life and maintenance costs.
The advantages of operating to high-
pressure drop must be weighed against
initial costs (higher-static-pressure fans,
larger motors, heavier ductwork), higher
power costs, and less efficient fan
operation. The installed fan and motor
must have sufficient capacity to deliver
the design airflow at the maximum
differential pressure under which the
system will operate, with the filters at
maximum dirty-filter pressure drop prior
to change. Therefore, consideration must
not only be given to the increased
installed capacity required to operate to
the higher pressure drop, but also to the
fact that the fan operates at a penalty
much of the time to provide the required
airflow over the wide span of pressure
drop between installation and
replacement of filters.
The cost of ductwork, on the other hand,
may not be significantly affected by
operation to a high pressure drop because
there is a minimum sheet-metal thickness
for effective welding, regardless of
pressure. The cost of fans and motors is
a function of the maximum total pressure
that must be developed. Fan horsepower can be estimated from the following equations.28
Figure 2.5 – Effect of Operating HEPA Filters to
High-Pressure Drop on Filter Life and Maintenance
Cost (including replacement filters and labor)
0 1 2 3 4 5 6
0.700
0.750
0.800
0.850
0.900
0.950
1.00
1.05
1.10
1.20
1.15
0
20
80
60
40
M
a
in
te
n
a
n
c
e
C
o
s
t
In
d
e
x
(c
o
s
t
o
f
p
=
3
in
.w
g
=
1
)
�
� p = Pressure Drop (in.wg)
F
ilt
e
r
L
if
e
(m
o
n
th
s
)
Nuclear Air Cleaning Handbook U.S. Department of Energy
2-18
hp
Q
Ef
f
=
∆ρ
6356
(2.1)
where:
hp
Q
E
f
f
=
=
=
=
fan hp
system airflow, cfm
maximum pressure drop across air cleaning system, in. wg. , at time of filter replacement
fractional efficiency of fan (0.60 usually assumed for estimating).
∆ρ
Motor horsepower can be estimated from the equation:
hp
hp
Em
f
m
= (2.2)
where:
hp
hp
E
m
f
m
motor horsepower
fan horsepower
fractional motor efficiency (0.90 usually assumed for estimating for 20 hp motors and larger).
=
=
=
Annual power costs can be estimated from the following equation:28
C
Q phr
E Ef m
=
′ ′
∆
8520
(2.3)
where:
C
h
r
E and Ef m
annual power cost, dollars,
hours of operation per year,
cost of power, cents/ k / Whr,
efficiency of fan and motor, respectively, over the period of operation from filter
installation to replacement; these will be less than the design efficiencies.
=
=
=
′ ′ =
Section 19
Although investment and power costs will be lower for systems operated to 2-in.wg pressure drop, the total
annual cost of owning a system, including materials and labor costs for filter replacement, may be less for a
system in which HEPA filters are replaced at pressure drops on the order of 4 in.wg. Total savings for the
facility as a whole may be even greater when the reduced interruption of building operations due to the
reduced frequency of filter change is taken into consideration.
Some prefilters can be operated to higher pressure drops than recommended by their manufacturers (but
such overuse must be supported by operating experience). This results in less frequent prefilter changes than
when prefilters are changed at a pressure drop of only two or three times the clean-filter pressure drop, as
recommended by most manufacturers. Care must be taken in selecting prefilters. Because of the many types,
efficiencies, configurations, and constructions available, the designer must specifically investigate the safe
overpressure allowance for the particular model under consideration. Figure 2.6 clearly shows the results of
overpressuring prefilters. In the case shown, the problem of filter blowout was overcome by working with
the manufacturer to reinforce the filter itself. Some benefit could also have been obtained by installing a
screen or expanded metal grille on the downstream face of the prefilters against which the filter cores could
DOE-HDBK-1169-2003 Chapter 2
2-19
bear; in any event, screens or grilles would have prevented damage to the
HEPA filters when pieces of prefilter struck them.
2.3.6 Sizing and Rating
Underrating. The service of all internal components (except moisture
separators) can be extended, and system pressure drop for a given level
of dust loading can be reduced by underrating, i.e., by oversizing the
system and installing more filter and adsorber capacity to meet system
design airflow needs (based on the nominal airflow rating of the
components). Figure 2.7 shows that the increase in filter life obtainable
by underrating is roughly proportional to the square root of the degree
of underrating. A study by the Harvard Air Cleaning Laboratory
suggests that the economic limit of underrating is about 20 percent (i.e.,
system design airflow capacity).24
Overrating. Operation of a system at airflows greater than the installed
airflow capacity of the system must be avoided, particularly in systems
with radioiodine adsorbers whose performance depends on the residence
time of air within the adsorbent bed. When airflow rates exceed the
rated airflow capacity of HEPA filters, efficiency is reduced and filter life
decreases more rapidly than the equivalent increase in flow rate, as can
be seen from the 120 percent curve in Figure 2.7. As noted above, the
residence time of contaminant-laden air in adsorber units is inversely
related to airflow rate. Overrating of these units decreases their ability to
trap gaseous contaminants, thereby degrading their function.
2.3.7 Uniform Airflow Design
In large air cleaning systems, because of the stratification of airflow due
to poor transitions between ducts and housings or between housings and
Section 20
fans, or because of
poorly designed
housings, filters or
adsorbers at the
center of a bank may receive higher airflow than those
on the periphery of the bank. This not only results in
non-uniform dirt loading of filters but may also result
in excessive penetration of those HEPA filters closer to
the air intake if the degree of airflow non-uniformity is
great. Figures 2.8(a) and 2.8(b) show that
penetration of HEPA filters by very small particles is
directly velocity-dependent and increases significantly at
very high airflow rates. Conversely, penetration of
HEPA filters by particles larger than 1 µm may increase
at very low flow rates due to the reduction in
effectiveness of the impaction mechanism on which
trapping of those particles depends. If some filters are
operating at very high airflow and some at very low
airflow, as could happen in a poorly designed housing
and filter bank, it is possible that significant penetration
Figure 2.7 – Effect of Underrating on
Service Life of Extended-Medium Filters,
Based on Percentage of Manufacturer’s
Rated Filter Airflow Capacity
100%120% 80%
60%
0 2,000 4,000 6,000 8,000 10,000
0
0.25
0.50
0.70
1.00
1.25
Operating Time (hr)
R
e
s
is
ta
n
c
e
In
d
e
x
(1
=
ra
te
d
p
re
s
s
u
re
d
ro
p
)
Figure 2.6 – Result of
Overpressuring Prefilters
(b)
(a)
Nuclear Air Cleaning Handbook U.S. Department of Energy
2-20
could occur even though the filters are in
good condition. Low flow rates improve
the efficiency of radioiodine adsorbers, but
high flow rates decrease efficiency.
Therefore, significant non-uniformity of
airflow through a bank of adsorber cells
can reduce the overall efficiency for
trapping radioactive gases of interest. A
well-designed duct-to-housing transition
will produce satisfactory airflow
distribution through the banks of filters
and adsorbers.25
Filter housings can be obtained with built-
in devices to assist in generating uniform
up- and downstream flow distribution
using Stairmand disks and similar devices.
These make testing faster and more
accurate, and minimize those occasions
when personnel must enter the filter
housing (a confined space) for any reason.
Figure 2.8(a) – HEPA Media Penetration34
0.0001
0.0010
0.0100
0.1000
1.0000
0.0 2.0 4.0 6.0 8.0 10.0 12.0
Air Flow Velocity (ft/minute)
Maximum 0.3 µm Penetration
Maximum MPPS Penetration
Source: Hollingsworth & Vose 2003
P
e
n
e
tr
a
ti
o
n
(%
)
Figure 2.8(b) – Maximum Penetration Versus Airflow Velocity
0.0010
0.0100
0.1000
1.0000
0.01 0.10 1.00
Particle Size (µm)
Maximum @
10.5 feet/minute Air velocity
Maximum @
5.0 feet/minute velocity
Typical @
10.5 feet/minute Air velocity
Typical @
5.0 feet/minute velocity
MPPS = 0.13 µm
MPPS Efficiency 99.9%
0.30 µm
Efficiency
99.97%
MPPS = 0.15 µm
MPPS Efficiency 99.98%
0.30 µm Efficiency 99.99%
P
e
n
e
tr
a
ti
o
n
(%
)
Source: Hollingsworth & Vose 2003
MPPS = Most Penetrating Particle Size
DOE-HDBK-1169-2003 Chapter 2
2-21
2.3.8 Maintainability and Testability
Air cleaning systems designed in accordance with ASME AG-14 should result in optimum systems for
maintainability and testability. There are many previously installed systems that were designed to ASME
N509,29 the predecessor to ASME AG-1.4 Systems designed to ASME AG-1 requirements should be tested
in accordance with ASME AG-1, Section TA. Those systems designed to ASME N509 or still covered by its
2002 maintenance revision, should be tested in accordance with the provisions of ASME N510.23 Other
older systems not designed to either ASME AG-1 or N509 are generally tested by following the guidance in
ASME N510.
Section 21
Maintenance and testing are two operational factors whose cost can be minimized by good initial design and
layout of ventilation and air cleaning systems. Inadequate attention to maintenance and testing requirements
at the initial phase of the project can result in much higher operating costs. New system specifications should
be designed and tested in accordance with ASME AG-1.4 Some existing systems may have been designed to
ASME N509.33 These and other non-ASME AG-1-designed systems may be tested in accordance with the
guidelines provided in ASME N510.23
Design of air cleaning systems in accordance with ASME AG-14 will result in optimum maintainability and
testability. Two elements that largely influence the costs of these functions are the accessibility of
components requiring periodic test and service and the frequency of filter and adsorber replacement. In
systems that involve handling of radioactively contaminated filters and adsorbers, the frequency of changing
these components and the time required to accomplish the change can be especially critical, because the total
integrated radiation dose a workman can be permitted to receive in each calendar period is limited. When all
personnel have received their maximum permissible dose for the year, the supervisor faces the prospect of
having no one available to carry out a needed filter change or a scheduled test. Maintenance and testing of
radioactively contaminated and other highly toxic systems are much more costly than the same operations in
nonradioactive systems because of the time required for personnel to change into and out of protective
clothing; to decontaminate and cleanup the area, tools, and equipment after the operation; to dispose of
contaminated filters (a significant cost itself); and to bathe and be monitored by health physicists.
In addition, extra attention must be given to filter or adsorber cell installation (compared with common air
filters, for example). If the system does not meet the test requirements of ASME AG-1, Section TA,4 after
the change, then rework must be performed until the problems are found and corrected. There is also a need
for health physics monitoring before, during, and after all maintenance operations. The fact that personnel
have to work in protective clothing and respirators also adds to the time required. Regardless of these
inherently high time and money costs, proper maintenance and testing are primary factors in ensuring the
reliability of the air cleaning system, and they cannot be done properly unless the facilities have been properly
designed and built.
Frequency of Maintenance and Testing
Measures that reduce the frequency of filter (HEPA and prefilter) and adsorber replacement also reduce
system costs and downtime. Several of the factors discussed earlier—the use of good building supply-air
filters and prefilters and underrating—serve to extend component life and reduce the frequency and cost of
service. Exhaust system HEPA filter and adsorber installations must be tested to the requirements of ASME
AG-1, Section TA,4 after each component change so that any extension of service life also directly reduces
testing costs. [Note, however, that regulatory bodies often dictate frequency of testing.]
Accessibility
When laying out ventilation and air cleaning facilities, the designer must consider the location of fans,
dampers, instruments, and filter housings, as well as the working space adjacent to them; working space and
Section 22
Nuclear Air Cleaning Handbook U.S. Department of Energy
2-22
spacing of banks within man-entry housings; height and array of filter and adsorber banks; and routes to be
used for moving new and used filters and adsorbers between storage, installation, and disposal areas. Where
it is permissible to fill and drain adsorbers in place, it is imperative to provide space and routing (from the
storage location to the air cleaning unit) for the charging cart and the adsorbent drums. This apparatus is a
large piece of movable equipment. In addition, space for drums of adsorbent must be provided because they
are used in conjunction with operation of the charging cart. Failure to provide adequate space in and around
housings and mechanical equipment (fans, dampers, etc.) results in high maintenance and testing costs,
inhibits proper care and attention, creates hazards, and increases the chance for accidental spread of
contamination during service or testing operations. Recommendations for arrangement and space
requirements for air cleaning components should be in accordance with ASME AG-14 and ASME N50929
(for those system components that have not been incorporated into ASME AG-1). Even greater space
requirements are needed for remotely maintainable systems. For systems not designed to meet ASME AG-1
requirements, guidance can be found in ASME N510.23
Ease of Maintenance and Testing
Simplicity of maintenance and testing is a primary factor in minimizing the time personnel must remain inside
a contaminated housing and restricted areas of a building during a filter or adsorber change or test.
Therefore, it is an important factor in reducing both personnel exposures and costs. The following strategies
will help ensure simplicity of maintenance and testing:
• Filter housings should be laid out and designed in accordance with ASME AG-14 and ASME N50929 to
ensure quantitative tests can be performed and to minimize reaching, stooping, and the use of ladders or
temporary scaffolding for gaining access to filter or adsorber cells. Some reaching and stooping is
unavoidable in man-entry housings, but it should not be necessary for personnel to perform physical
contortions or climb ladders to remove and replace filters in single-filter installations. Similarly, in bank
systems, it should not be necessary for workmen to climb ladders or temporary scaffolding to gain access
to the upper tiers of filters or adsorbers. If this is unavoidable, then permanent ladders and platforms
need to be built into the air cleaning housing. Personnel entries into housings should be minimized.
These are, at best, confined spaces that require permits for access and have contaminated surfaces that
require additional, potentially costly and difficult, precautions.
• Racks (frames) should be designed to the requirements of ASME AG-1, Section FG,4 and ASME N50929
to ensure proper spacing between components for maintainability and testability.
• Electrical, water, and compressed air connections should be available nearby, but in no case should they
be located inside the filter house.
• Materials-handling equipment should be employed, including dollies for moving new and used filters and
adsorbers, hoists or other means of handling the heavy adsorber cells in systems containing these
components, and elevators or ramps for moving loaded dollies up and down within the building.
Section 23
• Filter housings should be located inside the building. It is undesirable for personnel to: (1) conduct a
filter change or test out of doors where wind or rain may cause a spread of contamination, (2) cross a
roof to gain access to a filter housing, or (3) wait for good weather to carry out a scheduled filter or
adsorber change or test. Weather damage and corrosion are always possible, especially with wood-
framed filters.
• Decontamination and clothing-change facilities (including showers) should be located nearby.
DOE-HDBK-1169-2003 Chapter 2
2-23
• Maintenance and testing (per ASME AG-1, Section TA,4 and plant maintenance procedures) should be
well planned and rehearsed. This is particularly important to keep radiation exposure for workers at as
low as reasonably achievable (ALARA) levels.
• Adequate finger space (1 inch minimum is desirable) should be available between filter elements, and
handles should be provided on heavy components such as adsorber cells.
• Cradles or benches should be built into the component mounting frame for aligning and supporting
filters (adsorbers) prior to clamping to face-sealed mounting framers (see Chapter 4, Section 4.4.4).
• For simple filter and adsorber clamping devices, a properly designed bolt-and-nut clamping system has
proven most satisfactory in the past, although numerous methods of minimizing or eliminating loose
parts are currently being investigated. Toggle clamps, over-center latches, and other devices are easily
manipulated and require no tools; however, they often tend to jam, become difficult to operate, or lose
their ability to properly clamp the filter or adsorber cell after extended exposure to the hostile
environment of a contaminated air cleaning system. Such devices should be used only after due
consideration of the difficulties that would be involved in replacing them in a contaminated system (see
Chapter 4, Section 4.4.6).
• Ledges and sharp corners that a worker might stumble over or might snag or tear their protective
clothing on should be eliminated.
• Adequate lighting should be provided in, and adjacent to, the filter house and to other items that require
periodic service, inspection, or testing.
• Means of communication between personnel inside and outside the filter house should be provided.
• Floor drains in housing and adjacent workspaces should be provided to facilitate easy removal of water
spilled or applied during decontamination of the area after a filter or adsorber change. Drains must be
designed so that no air can bypass filters or adsorbers.
• Rigid, double-pin-hinged doors should be available on personnel entry housings and should be large
enough for personnel to pass through without excessive stooping or twisting. It should not be necessary
to remove several dozen nuts from a hatch to gain entry to a personnel entry or single-filter housing.
Not only is this too time consuming, but nuts tend to cross-thread or gall to the extent that it is often
necessary to cut off the bolt to open a hatch; or the nuts get dropped and lost and are often not replaced,
thus compromising the seal of the hatch. Sliding doors are not suitable because they will jam with any
distortion of the housing wall (see Chapter 4, Section 4.4.17) and are difficult to seal.
• Maintenance and testing procedures specific to the system being tested should be well planned and
rehearsed.
• There should be adequate space for materials and test equipment and access (through preplanned doors
or panels) to both sides of filter and adsorber banks.
Section 24
Construction
Designing for maintainability requires careful attention to the details of construction, including tolerances,
surface finishes, and the location of adjacent equipment and service lines. Ducts and housings should have a
minimum number of interior ledges, protrusions, and crevices that can collect dust or moisture, impede
personnel, or create a hazard in the performance of their work. Prefilters at duct inlets will minimize the
Nuclear Air Cleaning Handbook U.S. Department of Energy
2-24
accumulation of dust and contamination in the ducts. If these are not provided and the hazard analysis
permits, easily opened ports and hatches for inspection and cleaning must be provided at strategic and
accessible locations in the duct. [Note: Easily opened ports and hatches are not appropriate for plutonium-
bearing systems.] Duct runs should have enough mechanical joints to permit easy erection and dismantling.
Otherwise, replacement of radioactively contaminated ducts can be an expensive and hazardous job.
Housings, ductwork, and component-mounting frames must be able to withstand anticipated system
pressures and shock loadings without distortion, fatigue, or yielding that permits in-leakage or bypassing of
the filters or adsorbers. These components must meet a pressure test in accordance with the requirements of
ASME N50929 and ASME AG-1.4
Interior surfaces and finishes warrant special attention. Regardless of the formulation when coatings are
used, a primary factor in a long, dependable service life is proper preparation of the surface to be coated.
Manufacturers’ coating or paint instructions and plant procedures must be followed precisely. One
alternative to the coating requirements is to build the housings and housing components from stainless steel
or other harsh-environment-resistant materials. This reduces the need for frequent and costly repair to
coatings that are damaged as a result of routine testing and maintenance.
2.4 Emergency Considerations
The ventilation and air cleaning systems of a building in which radioactive materials are handled or processed
are integral parts of the building's confinement. In some cases, these systems may be shut down in the event
of an operational upset, power outage, accident, fire, or other emergency. In other cases, they must remain
operational to maintain the airflows and pressure differentials between building spaces and between the
building and the atmosphere as required to maintain confinement. In some of these cases, airborne
radioactive material may not be a problem until an emergency occurs. In all cases, however, a particular
danger is damage to or failure of the final HEPA filters (and adsorbers in those facilities where radiolytic
particulates could be released) that constitute the final barrier between the contained space (hot cell,
glovebox, room, or building) and the atmosphere or adjacent building spaces. Even if the system can be shut
down in the event of an emergency, protection of the final filters is essential to prevent the escape of
contaminated air to the atmosphere or to allow personnel to occupy spaces of the building.
Section 25
Consideration must be given to: (1) the possible effects of operational upsets, power outages, accidents, fires,
and other emergencies on the ventilation and air cleaning systems, including damage to the filters and
adsorbers from shock, overpressure, heat, fire, and high sensible-moisture loading; (2) the design and
arrangement of ducts and air cleaning components to alleviate these conditions; (3) the means of switching to
a redundant air cleaning unit, fan, or alternate power supply; and (4) the methods of controlling or isolating
the exhaust system during failure conditions. To provide the necessary protection to the public and plant
personnel, the air cleaning and ventilation system components on which confinement leakage control
depends must remain essentially intact and serviceable under these upset conditions. These components
must be capable of withstanding the differential pressures, heat, moisture, and stress of the most serious
accident predicted for the facility, with minimum damage and loss of integrity, and they must remain operable
long enough to satisfy system objectives.
2.4.1 Shock and Overpressure
Mechanical shock in an air cleaning system can be produced by an explosion in an operating area of the
building, by an earthquake, or by rapid compression or decompression of the air inside a system caused by
sudden opening or closing of a damper or housing doors. When pressure transients last for periods
measurable in seconds, static pressure is primarily responsible for any destructive effect. For shocks that last
only a few milliseconds with a nearly instantaneous pressure rise, as occurs in most chemical explosions, the
DOE-HDBK-1169-2003 Chapter 2
2-25
extent of destruction is primarily a function of the momentum of the shock wave. Shocks produced by an
earthquake or inadvertent opening or closing of a damper usually fall somewhere between these two
extremes. Protection of the final filters and adsorbers against failure from shock can be accomplished by
isolating them to prevent the transmission of destructive forces to them and by increasing the shock
resistance of ducts, housings, mounting frames, and equipment supports.
The shock resistance of HEPA filters can be enhanced by faceguards and similar treatment may sometimes
improve the shock resistance of prefilters. Most prefilters used today, however, probably have low shock and
overpressure resistance, and a screen installed between them and the HEPA filters is recommended to
prevent the condition shown in Figure 2.6. Adsorbers, both unit-tray and permanent single-unit types are
generally of a robust construction that should be relatively unaffected by shock loadings if properly installed.
Filter and adsorber mounting frames and housings
designed in accordance with recommendations in
Chapter 4 will probably have adequate shock resistance
for most applications. The difference in the ability of the
two fan installations, shown in Figure 2.9, to withstand a
substantial degree of shock is readily apparent.
Section 26
Protection of the primary air cleaning components can be
achieved by using fast-acting isolation. Although turning
vanes, dampers, moisture separators, and prefilters may
be damaged by a shock wave, they may also serve to
attenuate its force to some degree and thereby provide a
measure of protection to the HEPA filters downstream.
Damage to dampers, however, can result in inability to
control flows or isolate branch lines. Sand filters are
employed in some DOE facilities for protection of the
final filters and to prevent loss of confinement in the
event of explosion, earthquake, tornado, fire, or shock.
As discussed in Chapters 3 and 9, sand filters are large
deep beds of graded sand and gravel, installed in
underground concrete enclosures. In some cases they are
employed as final filters. Because of their size, a true
efficiency test cannot be performed on a sand filter
installation. Field tests have shown leakages comparable
to HEPA filters. Their large mass bed size will dampen
most conceivable explosions and deflagrations. Airflow
is upward through the bed, and leakage caused by the
explosion should be only momentary because of the great
mass of sand and gravel comprising the filter. The
disturbed sand should fall back to heal the breach. This
large mass of sand and gravel also provides a substantial
heat sink in the event of fire in a ventilated space. The
disadvantages of sand filters are very high initial cost and
high pressure drop.
Explosion in an operating area of a building is probably the most likely type of shock-generating incident that
one can expect in radiochemical, laboratory, and experimental facilities. A chemical explosion is no more
than a rapidly burning fire and therefore, in a confined space, can be arrested if a suppressant can be
introduced quickly enough.
Figure 2.9 – Methods Employed for
Installing Axial-Certrifugal Fans in Different
Nuclear Reactor ESF Air Cleaning
Systems—(a) Shock-Resistant Base-
Mounted Fan; (b) Hanger-Rod Supported
Fan. (Note anchor plates provided by Fan
Manufacturer, but not used.)
(a)
(b)
Nuclear Air Cleaning Handbook U.S. Department of Energy
2-26
2.4.2 Power and Equipment Outage
Emergency plans must account for the probable occurrence of power and equipment (particularly fan)
failures. Such failures, if not property planned for, can result in a contamination hazard to the public or
operating personnel, particularly in buildings with zone ventilation where airflow must be maintained to
preserve pressure gradients between zones and to prevent backflow to contaminated air to occupied spaces.
Possible emergency measures include redundant fans, redundant fan motors (perhaps served from
independent power sources), and alternate power supplies (e.g., steam turbine or emergency diesel-electric
generator). Where continuous airflow must be maintained, facilities for rapid automatic switching to an
alternate fan, power supply, or emergency source, or to a standby air cleaning unit, are essential. However, if
brief interruptions of flow can be tolerated, manual switching may be permissible at less expense. In any
event, visible and audible alarms should be provided, both locally and at a central control station, to signal the
operator when a malfunction has occurred. In addition, indicator lights to show the operational status of fans
and controls in the system should be provided in the central control room.
2.4.3 Air Cleaning System Layout Considerations
Section 27
The layout and location of air cleaning facilities can have a direct bearing on the system’s capability of
effecting control under upset conditions and of limiting the adverse consequences of such an upset.
Compartmentation and Segmentation
A higher degree of control is required in the event of a fire, explosion, equipment outage, or other system
upset if the air cleaning system is segmented or if the individual air cleaning units are compartmented.
Segmentation permits isolation of a damaged unit and minimizes the chance that the entire system will
become inoperable at the same time. Series compartmentation is employed in some potentially high-risk
applications to permit further isolation of
the less critical air-pretreatment facilities
(demister, prefilters) from the more critical
final HEPA filters and adsorbers. Series
parallel arrangement of a central exhaust
filter system that handles high-specific-
activity alpha-emitting materials is shown in
Figure 2.10. In the event of fire or
equipment damage in any one housing of
this system, or in the filters, the housing can
be isolated and the remainder of the system
kept in service. Also, any one of the
housings can be isolated for testing or filter
change (under normal operating conditions)
without interruption of work being
conducted in the building. NRC Regulatory
Guide 1.5227 recommends that the installed
capacity of any one air cleaning unit be no
greater than 30,000 cubic feet per minute
(cfm) to permit more effective control in
the event of an emergency and to permit
more reliable surveillance testing of the
HEPA filter and adsorber stages of the
unit.29
Figure 2.10 – Series-Parallel Arrangement of Central
Exhaust Filter System of a High-Hazard
Radiochemical Laboratory (Note: Dampers that
Permit Isolation of Any Housing Without Stopping
Exhaust Airflow)
Airflow
Damper
Individual
Housing HEPA Filters: 9 in.
3 by 3 Array
Prefilters: 9 in.
3 by 3 Array
DOE-HDBK-1169-2003 Chapter 2
2-27
Redundance
Redundant air cleaning facilities are often required in potentially high-risk operations, such as reactors and
radiochemical plants, to ensure continuous ventilation in the event of failure of an online air cleaning unit. In
the case of reactor post-accident cleanup systems, redundant air cleaning units are required even though the
system is normally in a standby condition. Figure 2.11 shows the segmented, redundant, normal offgas and
building-exhaust air cleaning systems of an experimental water-cooled reactor with vented confinement. Of
the two units of each system, which are normally online, one is capable of meeting exhaust requirements
when the building supply fans are shut down in the event of an emergency. High-quality isolation dampers
are essential in redundant systems, not only to protect the offline units when not in service, but to prevent
bypassing of the air cleaning system through a damaged offline air cleaning unit.
Fans
Isolation Damper
Single-Component
Air Cleaning Unit
Multicomponent
Air Cleaning SystemIsolation Damper
Prefilter Stage
Bank of HEPA Filters in 3 x 4 Array
Two Adsorption Stages
Final Stage HEPA Filters
Isolation Damper
Figure 2.11 – Experimental Reactor
Nuclear Air Cleaning Handbook U.S. Department of Energy
2-28
Location of Air Cleaning Facilities
Section 28
The location of filters, fans, and other air cleaning components can play a major part in minimizing
component damage and spread of contamination in the event of a fire, system upset, or other emergency. A
common but undesirable practice has been to install such items in random locations in attics or unused
building spaces. Figure 2.12 illustrates a type of filter
installation in which a wood-cased filter was simply
clamped between two flanged duct transitions in an open
attic space. There is no floor a catwalk adjacent to the
filter, with the danger that service personnel risk falling
through the ceiling to the room below. Access is limited by
the adjacent hangers and ducts. Furthermore, because the
location is in an open attic space, dropping a used filter
during a filter change, or breach of the wood filter case in
the event of a fire, would result in the spread of
contamination throughout the entire attic, which would be
difficult if not impossible, to cleanup. In-duct installations
of this type, in which the wood filter case is part of the
pressure boundary, do not conform with NFPA 90A.29 For
this reason, the design is not acceptable and a housing must
be used.
Figure 2.13 illustrates another example of poor filter installation and location. The location of the light
troffer indicates that the air cleaning unit (which is provided for control room ventilation in a nuclear reactor)
is located about 20 feet off the floor, and access is seriously impeded by hangers, cable trays, piping, and
other equipment. This unit is a wood-cased chemical, biological, radiological (CBR) filter, which, like the
filter installation shown in Figure 2.12 does not comply with NFPA 90A.29 Again, this unit is located in an
open and normally occupied building space where a serious spread of contamination could result if the filter
were dropped during service or
breached in an accident or fire.
Furthermore, fire external to the filter
could also breach the filter case and
permit contamination to spread from
the room to other portions of the
building. Figure 2.14 illustrates a
better practice by showing an air
cleaning facility installed in a large
room that can be isolated as a radiation
zone in the event of an emergency or
spill without risking contamination of
adjacent facilities.
Another common practice has been to
install ducts and filter housings on the
roof of a building, which are accessible
only over the roof. In the event a used
filter is dropped during maintenance,
there is a potential for contamination
spread not only to a surface (the roof), which would be difficult to decontaminate, but to the atmosphere as
well. For all systems, but especially for potentially high-hazard systems, it is recommended that all air
cleaning components, including ductwork, be located inside a building space to provide a secondary
Figure 2.12 – An Illustration of Poor
Filter Installation Practice
Figure 2.13 – An Illustration of Poor Filter
Installation Practice
DOE-HDBK-1169-2003 Chapter 2
2-29
confinement against breach of the pressure
boundary. Preferably, such building spaces
should be heated to minimize condensation
in the ducts during the winter months, and
they should be easily accessible for
inspection and service. Housings should be
located in rooms that can be isolated during
service or an emergency and that have walls
and floors that can be easily decontaminated
in the event of a spill. As a minimum
precaution, the general areas surrounding
the housing should be one that can be
cordoned off as a contamination zone. Off-
the-shelf bag-out housings of the type,
shown in Figure 2.15, are being used
Section 29
increasingly for single-filter installations. Although the bag-in bag-out provisions of those housings offer a
measure of protection against spills during service operations, the plastic bags employed can be torn by the
sharp corners of steel-cased filter elements and adsorber cells. It is recommended, therefore, that these
caissons be installed in isolable rooms or controlled building spaces, at least in those cases where intermediate
to high-level radioactive material is, or could be, present in the duct. Additional information on caissons and
bag-in bag-out filter installations is given in Chapter 6.
2.5 Multistage Filtration
Although a single stage of HEPA filters is
sufficient to meet most decontamination
requirements, two, three, or even more stages
may be required to meet the stringent
requirements of facilities in which plutonium
and other transuranic materials are handled.
Multistage HEPA filtration is also employed to
increase system reliability through series
redundancy.
2.5.1 Series Redundancy
Installations such as the DOE national
laboratories and production facilities which
have lived with radiation on a day-to-day basis
for many years have found it necessary to
employ series redundancy of HEPA filters in exhaust and air cleanup facilities for Zone I, and often Zone II,
confinements. The purpose is to increase the reliability of the system by providing backup filters in the event
of damage, deterioration, or failure of the first-stage filters. Each stage of filters must be individually testable
if credit for redundancy is to be clamed. That is, if the stages are not individually testable, the combination of
two or more stages must be considered as only a single stage from the standpoint of reliability. On the other
hand, each untestable stage contributes to the overall filtration efficiency of the combination, although not to
an extent equivalent to the nominal stage efficiency of 99.97 percent [decontamination factor (DF)=3333]; a
maximum efficiency of 99.8 percent (DF=500) has been allowed in the past for untestable second- and third-
stage filters, with full credit for the stage. For new systems, no credit should be assumed for non-tested
filters.
Figure 2.14 – Series-Compartmented Air
Cleaning System
Figure 2.15 Exhaust Air Cleaning System of
Radiopharmaceutical Company
Nuclear Air Cleaning Handbook U.S. Department of Energy
2-30
Redundant stages should be well spaced, the first often being a duct-entrance filter in a room, glovebox, or
hot cell, and the second being the final filters of a central exhaust system. In some systems, for example the
ESF air cleaning units of nuclear power plants, the series-redundant filter banks are installed within the same
housing. In any event, redundant stages should be spaced sufficiently far apart to allow for effective in-place
testing and inspection of both faces of the filters; they should not be installed back-to-back or to other
components of the system such as prefilters or adsorber cells.
2.5.2 Increased Decontamination Factor (DF)
Section 30
The particle sizes of plutonium aerosols generated in chemical operations employed in nuclear fuel
fabrication and reprocessing fall within the range of the size of maximum penetration (SMP) for HEPA
filters, 0.07 to 0.3 µm light scattering mean diameter (LMD). Although 0.3 µm LMD is considered the SMP
for dust and other unit-density particles, the SMP for high-density particles, such as plutonium, is
substantially higher. The aerodynamic mean diameter of plutonium particles formed by condensation is
thought to lie between 0.4 and 0.7 µm.28 A HEPA filter, by definition, has a minimum filtration efficiency of
99.97 percent (DF=3333) for 0.3-µm particles (although most of the HEPA filters currently being validated
by the DOE Quality Assurance Stations exhibit DFs on the order of 104). Current NRC Regulatory Guides
recommend a total plant DF of at least 1011 for plutonium in gaseous effluents. Although some
decontamination is effected by plant operations, the greatest portion must come from the HEPA filters,
which means that two, three, or even more stages of filters may be necessary.
Theory predicts that the primary mechanisms in the arrestance of particles by a HEPA filter are diffusion and
inertia; the effectiveness of these mechanisms varies with particle size, airflow velocity through the medium
and, to a lesser extent, particle density as shown in Figure 2.16. Direct interception, or impaction, is a
secondary mechanism that is independent of these parameters. As evident from Figure 2.16, these
mechanisms combine to produce a statistical average DF, not an absolute value for a given particle size. For
this reason, the effect of adding stages of
HEPA filters is multiplicative and does not
produce a screening effect that theoretically
results in an absolute minimum DF for any
given particle size. (In practice, however,
some screening of particles substantially
larger than the SMP can be expected.) In
theory, therefore, the DF of a multistage
HEPA filter installation would be DFnf,
where DFf is the definition DF of the HEPA
filter (DF=3333) and n is the number of
stages. Work at the Los Alamos National
Laboratory suggests that this theory is
essentially true30; DFs of 104 for stages one
and two and of somewhat less than 5 × 103
for the third stage of a three-stage system,
with an average DF of 5 × 103 for each of
the three stages, were determined. These
results were obtained in a small-scale test
system (about 25 cfm) in which conditions
were idealized by eliminating gasket leakage
and employing filter units that exhibited a
test efficiency (according to DOE Quality
Assurance Station testing) of greater than 99.99 percent.
Figure 2.16 – General Effect of Principal
Mechanisms that Affect the Arresting Efficiency
of the HEPA Filter
In
c
re
a
s
in
g
E
ff
ic
ie
n
c
y
In
c
re
a
s
in
g
E
ff
ic
ie
n
c
y
In
c
re
a
s
in
g
E
ff
ic
ie
n
c
y
Increasing Particle Size Increasing Velocity
Increasing Density
Density Constant
Velocity Constant
Particle Size Constant
Density Constant
Particle Size Constant
Velocity Constant
D
iffusion
D
iffusion
D
iffusion
In
er
tia
In
er
tia
In
er
tia
(a) (b)
(c)
DOE-HDBK-1169-2003 Chapter 2
2-31
Section 31
Earlier less definitive tests and experience had indicated substantially lower values of DF in the second and
third stages, and conservatism suggests that values lower than those obtained in the Los Alamos tests should
be used in practice. Conservatism also suggests that a value no higher than DF 3333 be used for the first
stage, and probably somewhat less to allow for filter degradation under service conditions. Although DF
improves with dust lading of the filter, aging and exposure to moisture and corrodents may decrease the
ability of the filter to maintain the higher DF under system upset conditions. For purposes of estimating the
capability of a multistage HEPA filter installation under normal operating conditions, a DF of (3 × 103)n can
be safely used with systems that adhere to the design, construction, testability, and maintainability principles
of this handbook or ASME N509.33
Accident analyses typically assume a first stage credit of 99.9 percent efficiency (DF of 103) for removal of
plutonium aerosols. Second and subsequent stages typically assume an efficiency of 99.8 percent (DF of
5 × 102). These assumed efficiencies are based on the premises that: (1) the HEPA filters have successfully
been through the DOE Filter Test Facility (FTF) at Oak Ridge; (2) they are installed and in-place leak tested
to at least 99.95 percent31; (3) they are installed in a system built to the specifications of AG-1; and (4) are
tested in accordance with national standards.
2.6 Passive Safe Shutdown of Systems
“Passive Safe Shutdown” (PSS) is an expression that describes a confinement concept in use at a hazardous
nuclear facility, whereby potential air exhaust pathways are aligned through filtration components, but
without a motive force pulling the air through. The concept is basically the same as a judicial arrangement of
filtration assets during a facility blackout condition. The potential imminent failure of the exhaust filtration
system may also warrant such an arrangement. The PSS concept can be applied as either a penultimate or a
first response to an accident situation.
As a penultimate response, every hazardous facility manager should have such a prepared plan for what to do
when the lights go out. This should include the arrangement of the facility in such a way that it poses the
least threat possible to the facility workers, the environment, and the public. It may also be useful to enter
this intentional “operational” mode under extenuating circumstances, such as the exhaust filtration system is
in jeopardy of failure (e.g., from internal or external fire threats). However, the plan should also consider
expeditious departure from the PSS mode after entry.
When PSS becomes the first, and sometimes only, response to an accident situation, additional attention must
be given to potential leakage pathways and accident sampling. The reasons for this are simple. The accident
itself could produce some unintended consequences when the PSS mode is entered and the facility is
operating at, or greater than, atmospheric pressure. To understand these two potential challenges
(i.e., potential leakage pathways and accident sampling) each will be examined in the context of a
confinement, versus a containment concept.
Section 32
Hazardous operations at DOE facilities are typically located inside a confinement. The confinement usually
consists of the entire building structure and associated confinement ventilation system(s) (CVS). The building
is maintained at a negative pressure relative to atmosphere by the CVS. The CVS is an assortment of several
subsystems that cascades the building air from areas of lesser contamination to areas of greater
contamination, with some intermediate contaminate removal via filtration. Prior to being exhausted from the
building, the air undergoes filtration, sometimes through multiple stages of filters.
Air is supplied to the confinement building by various air supply systems. Typically, air is supplied at a rate
slightly less than it is exhausted, such that a vacuum can be maintained throughout the facility. Air may also
“leak” into the building through door seals or penetrations and account for the mismatch between supply and
exhaust. Various dampers and valves are usually employed to direct the air to specific locations.
Nuclear Air Cleaning Handbook U.S. Department of Energy
2-32
Theoretically, with the building maintained at a negative relative to atmosphere, all air that enters the building
should exit only after it is filtered.
By contrast, in a containment concept, such as those employed at commercial nuclear power plants, air is
bottled up inside an unfired code pressure vessel (the actual confinement) which is surrounded by a
reinforced concrete structure, which provides the seismic resistance for the facility. Here there is no
unintentional supply or exhaust of air expected during the course of the accident. Also, there is no cascading
of air or vacuums relative to atmosphere. Actually, confinement pressures up to several atmospheres are
expected. This is not to say that confinements are not found in commercial nuclear power applications, for
they are. It’s just that the containment is the primary retention device, and not a confinement.
For actual confinements, several factors may cause the building to either “breath” or “exhale.” “Breathing”
can be caused by the diurnal sun cycle which leads to the heating and cooling of the building and consequent
expansion and contraction of the building air. Since the building seeks to remain at atmospheric pressure, it
will breath, hopefully through a pre-established filtered pathway, to accommodate the expansion and
contractions within the building. This pre-established filtered pathway is the very essence of the PSS concept.
Changes in barometric pressure act in somewhat the same way.
The building can “exhale” by several mechanisms. Fires can cause the air to exhale from the building, as can
the release of compressed gases, which hopefully are not flammable, inside the facility. Strong winds can
create a vacuum on the leeward side of the building and pull air through various penetrations.
The purpose of the last two paragraphs is to demonstrate that there are mechanisms beyond our immediate
control (i.e., diurnal cycling, barometric pressure swings, fires, compressed gas releases and strong winds) that
can lead to undesirable releases from a structure that is in a passive state. Hopefully the releases will be
through filtration devices, but this is dependent upon the integrity of both the structure and the exhaust
pathway established.
Section 33
The greatest threat to confinement, structural integrity, is an earthquake. At nuclear facilities, buildings and
equipment, designated Safety Class or Safety Significant are specifically designed to withstand the effects of a
design basis earthquake (DBE). This means the building should be structurally usable and the equipment able
to perform its intended function after suffering the imparted motions of a DBE or one of lesser magnitude.
Cracks and damaged penetrations may be significant in that they could provide potential unfiltered leakage
pathways.
To gain some insight into the size of cracks that may be of interest, consider the following for diurnal cycling.
A 2 million cubic foot building (200 feet long × 200 feet wide × 50 feet high) and a 25 degree Fahrenheit
temperature increase, will lead to a 5 percent volume change over 10-hour period, leading to a leak rate of
approximately 170 standard cubic feet per minute (scfm). Bypass leak rates of only a few volume percent
have been shown in Documented Safety Analysis (DSA) reports to result in calculations that approach the
exposure guidelines for the general public. The surface area represented by this building is approximately
80,000 square feet. Assuming a 10 square foot leakage pathway (i.e., an average size inlet duct), this
represents a 17-foot-per-minute velocity from the pathway [or roughly 11.5-mile-per-hour (mph) velocity
which is humanly perceptible]. At 100 square feet assumed surface area of cracks, that’s down to 1.15 mph
(not easily perceptible). A 10 square foot leakage pathway represents only 0.0125 percent of the surface area
and could also be represented by a crack 960 feet in length and 1/8 of an inch wide. It is evident that even
small holes and cracks are potentially extremely important to any confinement concept.
When it comes to building penetrations, doors are the most obvious. Under normal conditions, door seals
will leak. Tell-tale air in-leakage marks have been observed at damaged facilities. Since air will follow the
path of least resistance, if there is no impediment to in-flow during normal operations, there will be no
impediment to out-flow during PSS conditions. Also, and most importantly, this may not be a filtered
DOE-HDBK-1169-2003 Chapter 2
2-33
pathway. One facility, in response to establishing Technical Safety Requirements (driven by the importance
of the bypass leakage assumptions to their DSA calculations), has actually measured the air in-leakage during
normal facility operations and set an upper limit of acceptability and periodic surveillance requirements for
operation. Doors, therefore, should be thoroughly analyzed for susceptibility to permanent distortion
resulting from seismic events. This could occur at the door frame to building mounting as well as the door to
the door frame mounting. The amount of expected distortion and resultant leakage pathway, should be taken
into consideration in the safety basis for the facility.
Section 34
The next obvious potential bypass leakage pathways are the inlet and exhaust duct penetrations. As with
doorways, the attachment of the ductwork to the structure represents a potential failure point that should be
analyzed. In addition to the penetration itself, the extension of the ductwork into the facility also offers a
potential bypass leakage pathway, as the skin of the ductwork is actually an inward (or outward) extension of
the confinement boundary. This boundary should end with a testable isolation valve or a seismically designed
filtration system. A few facilities have actually fitted their inlets with HEPA filters, such that the facility can
be alligned to breathe through both the inlet and exhaust HEPAs. Dampers should never be used for
isolation purposes, as they are not designed for this purpose. Obviously, all penetrations through the
ductwork up to the point of isolation represent potential bypass leakage pathways and should be limited and
testable. Potential problem areas include fan shaft seals, boots on fans, valve and damper shafts, instrument
penetrations, electrical penetrations, etc. All these should be considered in estimating potential bypass
leakage. The seismically-designed ductwork supports should not be overlooked. Without them, the
ductwork, that is expected to remain in tact, might not stand during a seismic event.
A not so obvious threat to a PSS confinement (or any confinement for that matter) is the storage of
unsecured waste in large 100-cubic foot boxes or 55-gallon drums throughout the facility. During a seismic
event, such unsecured items could move and possibly endanger the confinement boundary. The same is true
for items stored inside filtration systems (i.e., ladders and tools used for filter testing and change outs). All
these things must be considered.
Besides trash and testing tools, there is also concern for installed equipment that is not seismically designed or
restrained. The potential interaction of nonseismically-designed equipment upon seismically-designed
equipment is referred to commercially as “two over one” considerations. [Note: This is derived from the
seismic level II (nonseismically-designed) and seismic level I (seismically-designed) designations used
commercially.] This has led to cumbersome shield walls and restraints added to commercial designs. The
bottom line is the potential motion of material and nonseismically-designed equipment and its resultant
potentially detrimental impact on the confinement boundary should be taken into consideration.
Internal integrity may also be important if transport assumptions for zone-to-zone communications during
potential accident scenarios effectively reduce the material at risk. All the concerns expressed for
confinement boundary integrity (i.e., cracking, penetration, moving equipment, unsecured trash, etc.) now
should apply to the zones themselves. This could become a calculational quagmire.
Besides bypass leakage considerations, the other significant challenge to the PSS concept involves
post-accident sampling. Such sampling is necessary to adequately inform the facility management so
appropriate and timely actions might be recommended for the protection of the public, workers, and the
environment in the event of an accident. Without sample flow [because there is no power], installed
instrumentation will not work because the electronics will divide the raw counts collected over a period of
time (this is directly proportional to the amount of an assumed isotope released via the fixed pathway) by the
average sample flow rate during the same period of time, which will lead (with division by zero) to
meaningless numbers. It is also assumed that all the leakage is being directed past the monitor, which, as has
already been discussed above, may not be the case.
Section 35
Nuclear Air Cleaning Handbook U.S. Department of Energy
2-34
The use of field sampling results for post-accident decisionmaking suffers from two serious deficiencies:
accuracy and timeliness. With bypass leakage, it is impossible to determine, a priority just where the material
will come from and at what flow rate. So, even though something may be measured, there is no assurance
that it represents the total threat. Also, the time to gather and analyze a sample is too long compared to the
time required for recommending protective actions. There is simply no substitute for directing a known flow
quantity through a known pathway and past a monitor to assess the conditions emanating from inside an
accident stricken confinement.
In conclusion, every hazardous facility should have a plan on how and when to best align for a blackout
condition (i.e., a PSS plan) and on how and when to expeditiously exit a PSS state. That being said, a PSS
concept for a post-accident condition requires both a detailed level of knowledge of the integrity of the
confinement structure itself, all its penetrations, and potential equipment and material movements in the
facility; and, development of reliable and timely sampling techniques. While such knowledge and
development might be useful to pursue, it soon becomes obvious that it is overly burdensome to control all
the potential threats to confinement integrity or to obtain reliable and timely estimates necessary for
protection of the public, workers, and the environment. It is easier, more reliable, and practical to direct flow
by force through a known pathway.
2.7 Air Cleaning System Design Considerations for Commercial
Nuclear Power Plants
The purpose of this section is to introduce the reader to the lexicon and requirements for air cleaning systems
at nuclear power plants. Except for those systems found in confinement, there are many similarities between
the air cleaning systems used at nuclear power plants and those used at DOE facilities. The first difference is
nomenclature (i.e., the names of components). At DOE facilities, the nomenclature used includes “safety
class,” “safety-significant,” and “defense in depth,” or simply production support. Nuclear power plant
systems and equipment are classified as either nuclear-safety-related, ESF, or nonnuclear-safety-related. In
some cases, nonnuclear-safety-related systems and equipment are designated as “Balance Of Plant.” Some
systems and equipment are referred to as “Important to Safety.” This term is not recognized by regulatory
agencies and organizations, but certain situations exist where an air cleaning system must perform a function
that has fewer requirements than those for a system that is fully nuclear-safety-related. One example is the
Technical Support Facility Ventilation Air Cleaning System for commercial nuclear power plants. This area is
used by plant management and technical support staff to support the operating staff in the control room
during unusual events or accidents. The Emergency Operations Centers (EOCs) at DOE facilities are similar
in both function and design to commercial nuclear power plants Technical Support Centers. These systems
are required to: (1) be constructed, operated, and tested in accordance with the requirements of U.S. Nuclear
Regulatory Commission (NRC) Regulatory Guide 1.140,32 (2) be able to provide a positive pressure within the
Technical Support Center when it is operational, and (3) be supplied with Class 1E emergency power. These
systems are nuclear-safety-related, but are not an engineered safety feature.
Section 36
2.7.1 Engineered Safety Feature and Nonnuclear-Safety-Related Systems
Air cleaning systems designed for ESF applications at commercial nuclear power plants must meet the
requirements of Regulatory Guides 1.52,28 and 1.78,33 as well as applicable portions of the facility’s Standard
Review Plan. These documents have been cited routinely by DOE, but generally are not mentioned in
current DOE Orders. In addition, DOE cites numerous of its Orders that have special application to
nonpower-related reactor activities. Many of these documents are site specific, and DOE is currently
reviewing some of them for possible deletion and replacement (by reference) with consensus codes and
standards.
DOE-HDBK-1169-2003 Chapter 2
2-35
Regulatory Guide 1.5227 addresses ESF air cleaning system requirements. Regulatory Guide 1.14032 addresses
nonnuclear-safety-related air cleaning (“normal atmosphere cleanup”) system requirements. Regulatory
Guide 1.7834 addresses climatic affects and requirements for outside air intakes.
For ESF applications, applicable regulations, codes, and standards must be combined with good engineering
practice. Ease of maintenance, operability, testability, cleanability, and decontamination also must be carefully
considered. In addition, air cleaning systems must be integrated into the overall plant or process design,
including monitoring and control requirements. ESF systems are supplied with assured power from the plant
Class IE emergency electrical power system.
Applicable Regulations and Standards for ESF Air Cleaning Systems
Air cleaning systems designed for ESF applications at commercial nuclear power plants must meet the
requirements of ASME Standard N509, Nuclear Power Plant Air Cleaning Units and Components;29 ASME
Standard N510, Testing of Nuclear Air Treatment Systems;23 ASME Standard N511, In-service Testing of Nuclear Air
Treatment Systems (to be published)35; and ASME AG-1, Code on Nuclear Air and Gas Treatment.4 It is good
practice to implement the codes and standards referenced above for all nuclear-related air cleaning systems
and components. All Safety Class and Safety Significant systems must be built to ASME AG-1 requirements.
Specific regulations, regulatory guides, Standard Review Plans (SRPs), and industry guidance and consensus
standards govern the design criteria and operating characteristics for ESF air cleaning systems. Although
these criteria are generated specifically for commercial nuclear generating stations, the principles can be
adapted to other nuclear facilities.
Regulatory guides and SRPs provide more specific guidance and are considered acceptable ways of satisfying
regulatory requirements. Regulatory Guide 1.52, Design, Testing, and Maintenance Criteria for Post Accident
Engineered-Safety-Feature Atmosphere Cleanup System Air Filtration and Adsorption Units of Light-Water Cooled Nuclear
Power Plants,27 details criteria for operating Control Room air cleaning systems in a post-accident environment.
Environmental and system design criteria, component design criteria, qualification testing, maintenance, and
in-place testing are discussed in detail.
The ESF systems designed to contain and mitigate DBAs must be redundant and physically separated so that
damage to one does not cause damage to the other.
Section 37
Redundancy requires two complete trains of equipment and components. There are cases where ductwork
has not been completely redundant. A common space served by the redundant trains, such as control rooms,
may not require 100 percent redundancy of the ductwork, as long as it can be demonstrated that no common
mode failures would render both trains of equipment inoperable.
Separation is required, so that postulated accidents such as internal missiles, fire, and flood cannot render
both trains of the redundant system inoperable from the same event. Separation can be achieved by
physically locating the trains far enough apart that postulated accidents cannot render both trains inoperable,
or by erecting a physical barrier, such as a concrete wall, for protection.
The SRPs are documents prepared by NRC staff to document application review procedures for construction
and operation of nuclear power plants (NUREG-0800).36
The following criteria are applicable to ESF systems for all applications:
• A single active failure cannot result in loss of the system functional performance capability.
• Failure of nonseismic Category I equipment or components will not affect system operation.
Nuclear Air Cleaning Handbook U.S. Department of Energy
2-36
• A suitable ambient temperature can be maintained for personnel and equipment.
• The system can detect and filter airborne contaminants before personnel enter the area.
• The system can detect and isolate portions of the system in the event of a fire.
• The ESF ventilation system will continue to function during all DBAs that require the building or
area of the plant to be habitable and that require the essential equipment served by the ESF
ventilation system to remain in operation.
Most nuclear power plants restrict the amount of zinc and aluminum that can be used inside the confinement
structures. Zinc and aluminum both interact with the spray chemistry of the emergency core cooling systems
to produce hydrogen, which can accumulate in the confinement and become an explosion hazard in the event
of an LOCA. These materials must be tightly controlled, and an accurate inventory must be kept when they
are used inside confinement structures.
Since most HVAC and air cleaning systems use galvanized steel for ductwork and equipment housings,
alternate materials need to be considered for use inside confinement structures. One option is to use stainless
steel for ductwork and equipment housings. Stainless steel is expensive, but its advantage is that it does not
require any coating to prevent the corrosion or scratching that can occur during repair, maintenance, or
testing/surveillance activities. In addition, it is easier to decontaminate than some other materials. Another,
less costly option is to use steel coated with a material that is compatible with the confinement environment.
The disadvantage of using coated steel is that it does not hold up well in environments involving high rates of
ductwork or equipment repair, maintenance, or testing/surveillance activities. The coating also must be
inspected and repaired when damaged, which can cause critical time delays during refueling or other time-
sensitive activities.
Section 38
Galvanized steel ductwork can be used successfully outside confinement, and at a lower cost than stainless
steel. Galvanized steel has many of the same advantages as stainless steel, such as ease of decontamination,
and it holds up well in areas that are subject to frequent repair, maintenance, testing, and surveillance
activities. One caution should be noted, however: if the galvanized coating is severely damaged or removed,
as in cases when welded duct construction is used and when supports are attached by welding, then the
damaged areas must be recoated with a zinc-rich paint to prevent corrosion.
Radiation considerations can also present some material challenges, especially for those units that are
normally in standby but function during and after a DBA and collect large quantities of radioactive materials.
Radiation exposures of ten to hundreds of millions of rads are possible and need to be considered. At these
exposure levels, the decomposition of some organic materials (e.g., gules, gaskets, binders) becomes possible.
[Note: One common sealant, Teflon®, is particularly susceptible to radiolytic decomposition starting at
approximately 1,000 rads of exposure. One decomposition product of note is hydrofluoric acid.]
2.7.2 Design Considerations
A clear definition of the design parameters is probably the most important, but often the least appreciated,
requirement leading to the development of a satisfactory air cleaning system. The design parameters must
consider basic performance requirements; physical limitations; regulatory, code, and standard compliance; and
accident confinement and recovery. All of these parameters must be identified as an initial system design step
because they form the basis for design. This is the responsibility of the facility owner, who is often assisted
by an architectural engineering firm with experience in this type of plant design. See Table 2.1 for system
environmental parameters.
DOE-HDBK-1169-2003 Chapter 2
2-37
Outdoor design conditions can be obtained from the ASHRAE Guide and Data Books,37 from local weather
stations, or from site meteorological data. It is important when selecting outside design conditions to use the
most extreme data, particularly for nuclear-safety-related systems, as they must be capable of operating in these
extremes.
The following examples of design basis accidents should be considered when designing an air cleaning
system:
• Reactor coolant system LOCA (large and small breaks).
• Seismic Loading. [Note: the loads that must be considered when designing the air cleaning system will be
different if the system has to remain operational during and after the event, or if the system only has to
maintain its structural integrity; i.e., the system does not have to function during and after an event.]
• Fire, smoke, and hot air (see Chapter 10).
• Tornado/high winds. [Tornadoes can cause damage due to a significant pressure drop [approximately
3 pounds per square inch in gauge (psig), negative] as the tornado passes over the facility. Openings and
items (e.g., air cleaning equipment, ductwork, etc.) that are exposed to this pressure transient can collapse
if they are not protected by tornado dampers. In addition, tornadoes and high winds can convey missiles
that can enter intakes and other unprotected openings and damage safety-related systems and
equipment.]
• Internal and external missiles. (Internal missiles are usually generated by rotating equipment failure.
External missiles are usually generated by a tornado or high wind.)
Section 39
• Active equipment failure. [This refers to failure of any equipment that provides an “active” function
(e.g., pumps, fans, valves, dampers, switches, etc.) and must be relied on to safely shut down the facility
and/or maintain it in a safe configuration.]
• Loss of onsite and offsite power. (The facility must be designed to be safely shut down and/or be
maintained in a safe configuration in the event of a loss of onsite and offsite power.)
2.7.2.1 System Design
Individual ESF air cleaning systems are limited by Regulatory Guide 1.5227 to approximately 30,000 cfm.
When the system airflow exceeds this limit, multiple systems must be used in parallel. ESF systems contain
the following sequential components: (1) a moisture separator to remove entrained water droplets, (2) a
heater to control relative humidity (RH) when the RH of the air entering the carbon adsorber exceeds
70 percent, (3) prefilters, (4) HEPA filters, (5) a charcoal adsorber, (6) HEPA filters downstream of the
adsorbers, and (7) a fan. Ducts, valves, and dampers are also included for system isolation and flow control,
as well as related instrumentation. When the moisture and dust loads are low for all credible operating
modes, the prefilter and moisture separator may not be required.
As stated previously, ESF systems designed to contain and mitigate accidents must be redundant, and the
redundant systems must be physically separated so that damage to one does not cause damage to the other.
Instruments must make flow rates and pressures available to the Control Room as well as locally, and must
provide visual and auditory alarms as indicated in ASME AG-1, Appendix IA-C, Table IA-C.4 All
instruments, including heater, damper, and fan controls should meet the requirements of IEEE 323, Standard
for Qualifying Class 1E Electrical Equipment for Nuclear Power Generating Stations5 and IEEE 344, Recommended
Practice for Seismic Qualification of Class 1E Equipment in Nuclear Generating Stations.6 Regulatory Guide 1.100,
Nuclear Air Cleaning Handbook U.S. Department of Energy
2-38
Seismic Qualification of Electrical Equipment for Nuclear Power Plants,38 and Regulatory Guide 1.105, Instrument Set
Points,39 are also applicable. Instrument controls and control panels should meet the design, construction,
installation, and testability criteria in Section IA of ASME Code AG-1.4
The design, construction, and test requirements of ASME Code AG-14 apply to the following ESF air cleaning
components and are titled accordingly.
• Section AA, “Common Articles”
• Section BA, “Fans and Blowers” (Motors for fans and blowers must also meet the qualification
requirements of IEEE 334,40 IEEE 323,5 and IEEE 344.6)
• Section DA, “Dampers and Louvers”
• Section SA, “Ductwork”
• Section HA, “Housings”
• Section RA, “Refrigeration Equipment”
• Section CA, “Conditioning Equipment”
• Section FA, “Moisture Separators”
• Section FB, “Medium Efficiency Filters”
• Section FC, “HEPA Filters”
• Section FD, “Type II Adsorber Cells”
• Section FE, “Type III Adsorber Cells”
• Section FF, “Adsorbent Media”
• Section FG, “Frames”
• Section FH, “Other Adsorbers”
• Section FI, “Metal Media Filters”
• Section FJ, “Low-Efficiency Filters”
• Section FK, “Special Round and Duct Connected HEPA Filters”
• Section IA, “Instrumentation and Controls”
• Section TA, “Field Testing of Air Treatment Systems”
DOE-HDBK-1169-2003 Chapter 2
2-39
2.7.2.2 Structural And Seismic Design
Section 40
The structural design of ESF air cleaning systems must consider the service conditions that components and
their housing may experience during normal, abnormal, and the accident conditions contained in Section AA
of ASME AG-1.4 The ESF air cleaning system must remain functional following dynamic loading events
such as an earthquake. The ESF air cleaning systems, including all components, must have their structural
design verified by analysis, testing, or a combination of both. Qualification criteria are contained in Section
AA of ASME AG-1.4 The design requirements for determining housing plate thickness and stiffener spacing
and size are contained in ASME AG-1, Section AA, “Structural Design,” Sections SA, “Ductwork,” and HA,
“Housings.” 4
The maximum allowable deflections for panels, flanges, and stiffeners for the load combinations are
contained in ASME AG-1, Section SA, “Deflection Criteria.”4
2.7.2.3 Equipment Qualification
The fundamental reason for qualifying equipment is to provide adequate levels of safety for the life of the
facility. Equipment qualification assures the ESF system will satisfy two characteristics:
• The equipment will resist common mode failures due to aging degradation.
• Nonmetallic materials will survive anticipated environmental stresses.
Generic or Application-Specific Qualification
Qualification may be generic or application specific. Generic qualification is probably best applied by the
original equipment manufacturer. This type of qualification program requires test parameters that may
exceed the needs of the specified requirements to be able to use the qualified equipment in a variety of
applications and environments. An application-specific qualification limits the use of the component or
system to those with the same or lesser environmental parameters.
Mild or Harsh Environment Qualification
A mild environment qualification can usually be accomplished without determination of a qualified lifetime
(per Section 4 of IEEE 323),5 whereas a harsh environment program usually requires testing to verify
performance under extreme accident conditions. Simulated aging is necessary to arrive at “end of life
conditions” prior to accident condition testing.
Determining Mild or Harsh Environment
When the answer to all of the questions below is “Yes,” the equipment should be assumed to be subjected to
a mild environment and treated accordingly.27 Otherwise, it should be treated under the assumption that it is
subjected to a harsh environment.
• Will the environment where the equipment is located be unaffected during and after a DBA (i.e., will
there be no significant changes in temperature, radiation)?
• Will the equipment perform its safety-related function before the environment becomes harsh?
• Will failure of the equipment in a harsh environment after it has performed its function:
Nuclear Air Cleaning Handbook U.S. Department of Energy
2-40
– Result in misleading information?
– Affect the functioning of other safety-related equipment?
– Cause a breach of pressure boundary integrity?
Safety or Non-Safety-Related Function
It is necessary to determine whether the components are designated as safety-related or nonsafety-related.
Nonsafety-related items can often be excluded from the qualification process when it can be shown that
failure of that component would have no adverse effect on the safety function of the overall equipment.
Equipment Qualification Plan
Section 41
The Qualification Plan must be developed in accordance with IEEE 3235 and must include a determination
of the qualification method, listing of the environmental service conditions, description of any required aging
programs, protocol of the test sequence, and definition of the accident test profiles.
An aging program consists of all stress factors, including thermal aging, mechanical/cyclic aging, radiation
exposure, and mechanical vibration. All are designed to simulate conditions that would be encountered
during the expected life of the test specimen prior to an accident condition or test such as seismic pressure or
LOCA.
Equipment Qualification Methods
Three equipment qualification methods are described below.
• Type Testing:
– Accounts for significant aging mechanisms;
– Subjects the equipment to specified service conditions; and
– Demonstrates subsequent ability to perform safety function.
• Operating Experience:
– Must be compared to equipment with the same generic design; and
– Depends on documentation of past service conditions, equipment performance, maintenance, and
similarity for its validity.
• Analysis:
– Requires logical assessment or mathematical model of the equipment;
– Requires the support of test data, operating experience, or the physical laws of nature; and
– Must be documented to permit verification by a competent third party.
A combination of any of the above qualification methods is recommended.
DOE-HDBK-1169-2003 Chapter 2
2-41
2.7.2.4 Air Cleaning System Integration with the Entire Facility
A critical design consideration that is often overlooked is the question of how the air cleaning system
interrelates with other air handling systems and the entire facility. Often areas of a facility are directly
connected to more than one air handling system. There are an unlimited number of possible combinations,
but some of the most common are:
• An ESF air cleaning unit exhausting an area supplied by a non-safety HVAC system;
• An ESF air cleaning unit in an area normally exhausted by a large fan that may or may not shut down
when the safety system is activated;
• A Control Room ESF air cleaning unit designed to provide a positive pressure in an area served by other
ESF and/or non-ESF systems;
• The maintenance of graduated levels of negative pressure in concentric rings in fuel plants or plutonium
facilities; and
• Gloveboxes, hot cells, and laboratory hoods with independent filtration systems in rooms served by ESF
or non-ESF systems.
These examples illustrate the need to consider the entire facility when designing an ESF system. Two
questions must be addressed: (1) how can the system under design affect other systems and areas, and
(2) how can the remainder of the facility affect this system?
2.7.2.5 Design Areas Requiring Special Attention
There are system characteristics that apply to all air cleaning systems regardless of their specific function or
the nature of the facility. One is that they must be capable of continuing to meet quantifiable test criteria to
provide evidence of maintaining acceptance limits over the life of the installation. Therefore, the ability to
maintain and test systems is as important as the ability of the systems to meet the initial performance criteria.
The following are samples of some of the factors that apply to all systems and must be addressed:
• Airflow distribution in the ducts and housings;
• Airflow balance through the inlet and/or outlet ducts;
Section 42
• Fan balance, leaktightness, and a capacity to provide adequate pressures at all design flows;
• Access for inspection, maintenance, and replacement; and
• Instrumentation that integrates the overall control and monitoring requirements of the facility.
2.7.2.6 Location and Layout
The ducts of ESF air cleaning systems that pass through clean areas should be designed at a higher negative
pressure, and the length of any air cleaning unit positive pressure discharge ducts that must pass through a
clean space should be kept as short as possible. When an ESF air cleaning system is a habitability system,
ducts carrying outside air that are routed through clean space should be designed at a negative pressure.
Housings handling recirculated habitability air should be at a positive pressure when located in a
Nuclear Air Cleaning Handbook U.S. Department of Energy
2-42
contaminated space. Negative pressure ducts located in a contaminated space should be avoided. When this
is not possible, all-welded duct construction should be used. The length of positive pressure ducts outside
the habitability zone should be kept as short as possible.
Generally, the direction of airflow should be from less contaminated spaces toward areas with a higher level
of contamination. All ducts and housings containing a contamination level higher than surrounding areas
should be maintained at a negative pressure. Ducts and housings with lower concentration levels than
surrounding areas should be at a positive pressure. Allowable leakage depends on the difference between
duct/housing concentrations and surrounding area concentrations. For example, a once-through
contaminated exhaust filter housing serving a radioactive waste handling area in a nuclear power plant may
have the exhaust fan located downstream of the filter housing when the housing is located in a space that is
cleaner than the air entering the housing. The benefit of this system configuration is that the air cleaning
system is under a negative pressure up to the fan. Therefore, leakage will be into the housing, and the
potential impact of contaminated leakage on plant personnel during system operation will be minimized.
Such a system configuration does not mean that leakage can be ignored. Where it is crucial to personnel
habitability, acceptable limits should be established and periodically verified by testing and surveillance.
Rather, it means the potential for exposure has been reduced to ALARA levels by system design. When the
space in which an air cleaning system housing is located is more contaminated than the air entering the
housing, it would be better to locate the fan on the inlet side of the housing to eliminate in-leakage of more
contaminated air.
When the housings of habitability systems are located within a protected space, the fan should be located
downstream of the filter unit to ensure that only cleaner air can leak into the housing. When the housing of a
habitability system is located in an area outside a protected space, the fan should be located upstream of the
filter unit to ensure that contaminated air cannot leak in downstream of the filter unit.
Location of fans and housings should be accomplished by assigning a positive designation to the atmosphere
in the cleaner area or duct, and a negative designation to the more contaminated area or duct. When the
pressure difference within an air cleaning housing or duct is positive (+), the fan should be on the
contaminated air-entry side; when the pressure difference is negative (-), the fan should be on the “clean air”
exit side.
Section 43
Serviceability and maintainability are major considerations when designing an ESF air cleaning system.
Access for servicing the inside and outside of the housing for filter replacement, maintenance, and testing
must be provided. Housings should not be situated among machinery, equipment, and ductwork with any
means for ready access. There must also be sufficient space in the access corridors and adjacent to the
housing to allow handling of filters during change-outs, including space for stacking filters adjacent to the
work area. Dollies are often needed to transport filters through the access corridors. When Type III carbon
adsorbers are used, access to the area must be provided for the mobile carbon transfer equipment. Note that
the fill method must be qualified to ensure adequate packing density. Hand filling is not acceptable.
Recommended service clearances are given in ASME N509.29
2.7.2.7 Air Cleaning System Design Considerations for Commercial Nuclear
Power Plant Control Rooms
The operation of a nuclear power plant is complex and must be performed with great care. Although there
are a number of locations where control over operations is exercised at a nuclear power plant, the center of
activity is the Control Room. Broadly described, the Control Room is a dedicated area at any type of nuclear
facility where the plant operations controls are located.
DOE-HDBK-1169-2003 Chapter 2
2-43
Nuclear power plant operators are highly trained licensed individuals. Their primary function is to control
the nuclear reaction to ensure the reactor is operated safely under both normal and abnormal conditions.
Therefore, the Control Room design must ensure that environmental conditions allow achievement of this
goal. Both Control Room operators and equipment (electrical equipment, cables, gauges, instruments,
controls, and computers) must be protected from the radiation and radioactive material present during
normal operation and during abnormal or accident situations, as well as toxic gases, fires, explosions, missiles,
earthquakes, tornadoes, and floods. An environment must be provided where both temperature and RH are
maintained to ensure the continuing performance of Control Room equipment and to provide reasonable
standards of human comfort for the operators. The primary means of achieving these conditions are air
cleaning, ventilation, and air-conditioning systems that are appropriately designed, tested, maintained, and
operated in conformance with the facility design criteria and best engineering practices. In addition, to
enhance operator performance, the Control Room environment must be free from excessive noise, equipped
with adequate lighting, and be designed with easy accessibility to equipment controls.
Control Room System Design Criteria
Section 44
The basic regulation applicable to nuclear station Control Room systems is 10 CFR Part 50, Appendix A,
“General Design Criterion 19.”41 The regulation states, “A Control Room shall be provided from which
actions can be taken to operate the nuclear power unit safely under normal conditions and to maintain it in a
safe condition under accident conditions, including loss-of-coolant accidents. Adequate radiation protection
shall be provided to permit access and occupancy of the Control Room under accident conditions without
personnel receiving radiation exposures in excess of 5 rem whole body, or its equivalent to any part of the
body, for the duration of the accident.” Control Room habitability during a postulated hazardous chemical
release also is the subject of two regulatory guides. Regulatory Guide 1.78, Assumptions for Evaluating the
Habitability of a Nuclear Power Plant Control Room During a Postulated Hazardous Chemical Release,34 identifies
chemicals which, when present in sufficient quantities, could result in the Control Room becoming
uninhabitable. Design considerations to assess the capability of the Control Room to withstand hazardous
chemical releases either onsite or within the surrounding area are covered. SRP 6.4, Control Room Habitability,36
contains guidance for reviewing Control Room ventilation systems and control building layouts, and is
intended to assure that plant operators are protected against the effects of accidental releases of toxic and
radioactive gases. The area served by the Control Room emergency ventilation system must be reviewed to
verify that all critical areas requiring access in the event of an accident are included within the area (Control
Room, kitchen, sanitary facilities, and computer facilities). The ventilation system layout and functional
design must be reviewed to determine whether flow rates and filter efficiencies will be adequate to prevent
buildup of toxic gases or radioactive materials inside the Control Room after an accident. Outside air intake
locations for the Control Room must be reviewed to determine the potential release points of hazardous
airborne materials to assure that such airborne materials cannot enter the Control Room.
The details of the ESF atmosphere cleanup system, including the credit to be assigned to the filtration system
for iodine and particulate removal for use in dose calculations, are covered in SRP 6.5.1.36 This information is
identical to the information specified in Regulatory Guide 1.52.27 The remainder of the Control Room area
ventilation system is reviewed under SRP 8.4.1.336 A functional review of this system must be performed,
including components such as air intakes, ducts, air-conditioning units, filters, blowers, isolation dampers or
valves, and exhaust fans.
Control Room fire protection (for fires occurring either inside or outside the Control Room) is described in
SRP 9.5.1.36 Section 6.4 presents specific details concerning the applicability of fire protection features to
assure Control Room habitability under all required operating conditions.
SRPs 12.3 and 12.436 provide guidance for radiation protection design features. Occupational radiation
exposures are to be kept within ALARA limits by using appropriate shielding and air cleaning. Additional
details on this subject are provided in Chapter 11.
Nuclear Air Cleaning Handbook U.S. Department of Energy
2-44
Section 45
The criteria for the design, installation, operation, testing, and maintenance of Control Room air cleaning
systems have a single objective: to provide a safe environment in which the operator can keep the nuclear
reactor and auxiliary systems under control during normal operation and can safely shut down these systems
during abnormal situations to protect the health and safety of the public and plant workers.
Basic Control Room Layout
The entire Control Room envelope is serviced by the Control Room emergency ventilation system. All areas
that require access in the event of a nuclear accident are included within this envelope. The Control Room
emergency zone includes all of the instruments and controls needed for safe shutdown, the critical reference
files, the computer room (when used as an integral part of the emergency response plan), the shift
supervisor's office, a washroom, and a kitchen. Battery rooms, cable spreading rooms, switchgear rooms,
motor control center rooms, and other spaces that do not require continuous or frequent occupancy after an
accident are generally excluded from the Control Room emergency zone. However, these areas need to be
provided with nuclear-safety-related cooling for essential equipment during and following DBAs. While these
areas usually do not require the same level of protection from radiation and contaminants as the Control
Room, their cooling systems (air handling and water cooling) should meet all of the other requirements.
Control Room General Ventilation Criteria
Control Room ventilation criteria are based on the premise that contaminants must be kept outside the
Control Room. Therefore, Control Rooms are maintained at a positive pressure with respect to their
immediate environs to assure that all air leakage flows out of the Control Room. The ventilation system
should be capable of providing fresh outside air at a rate sufficient to dissipate any internally generated
carbon dioxide or other noxious fumes.42 The system also should be capable of providing sufficient cfm per
occupant to maintain human comfort. There should be no noticeable drafts to disturb operators or
documents. In addition, the ventilation system must take care of the Control Room cooling and heating
loads.
Control Room Temperature and Relative Humidity
The Control Room HVAC system must be capable of maintaining a comfortable temperature and RH range,
generally considered to be 73 degrees Fahrenheit (23 degrees Celsius) to 78 degrees Fahrenheit (26 degrees
Celsius), and 20 to 60 percent RH (ASHRAE Comfort Standard 55-74).42 A secondary criteria is that the air
temperature at floor and head levels should not differ by more than 10 degrees Fahrenheit (5.6 degrees
Celsius).
Effective temperature, which takes into account dry-bulb temperature, RH, and air velocity, is commonly
used as a measure of maximum limit for reliable human performance. The maximum effective temperature
for reliable human performance is believed to be 85 degrees Fahrenheit (29 degrees Celsius). As extremes,
this effective temperature can be achieved with 100 percent humid air at 85 degrees Fahrenheit (29 degrees
Celsius), or with 20 percent humid air at 104 degrees Fahrenheit (40 degrees Celsius). Air velocity under
100 fpm (30.5 m/min.) has a negligible effect on effective temperature. Effective temperature is not intended
to be used as a design criterion, only as a guideline for limiting operating conditions. Because RH is not
normally measured in a Control Room, a worst-case condition should be assumed, implying that a dry-bulb
temperature of 85 degrees Fahrenheit (29 degrees Celsius) should be the maximum temperature for a Control
Room. This temperature should not be exceeded for longer than 1 hour, after which steps should be taken to
reduce the temperature. Previous regulatory requirements in this area were based on equipment qualification
only, and required temperatures were to be kept under 120 degrees Fahrenheit (49 degrees Celsius). This is
too extreme for an operator to function efficiently and has been revised.
Section 46
DOE-HDBK-1169-2003 Chapter 2
2-45
Control Room Air Composition
Clean air breathed by operators can be compromised by radioactive and chemically toxic gases. Chlorine is
used extensively at nuclear power plants, and is the principal toxic gas of concern. With respect to radioactive
materials, the air composition is specified in 10 CFR 20, Appendix B, Table 2.43 The limits specified for every
radionuclide are given as the maximum allowable airborne radioactive material concentrations to occupational
workers during normal operations. During an accident, the HVAC system must be designed to limit the dose
to the Control Room operator to 30 rem thyroid exposure.
Control Room Noise Levels
Verbal communication is necessary for efficient Control Room operation. Background noise, particularly
from HVAC systems, should not impair this communication. Background noise levels should not exceed
65 Decibels A-weighted (dBA), and sound absorption should be sufficient to limit reverberation time.
Control Room Fire Protection Criteria
Fire Events Inside the Control Room. For fire events inside the Control Room, the design must ensure
that plant shutdown capability, independent of the Control Room, is provided. With respect to ventilation,
means should be provided to remove combustion products from the Control Room. Smoke detectors are
necessary to alert Control Room operators of a fire and should be located in Control Room cabinets,
consoles, and air intakes. The location of air supply intakes must be remote from all exhaust air and smoke
vent outlets. The outside Control Room air intakes and all recirculation portions of Control Room
ventilation systems require manual-isolation fire and smoke dampers. Peripheral rooms within the Control
Room emergency ventilation zone should have fire dampers that close when the fire detection or fire
suppression system begins operation.
Fire Events Outside the Control Room. The Control Room complex should be separated from the
remainder of the plant by fire dampers. Important HVAC fire protection features, in addition to detection,
include:
• Fire suppression,
• Qualified penetration seals for all penetrations,
• Portable blowers for smoke removal, and
• Location of all ventilation intakes and exhausts in relation to fire hazard.
2.7.2.8 Control Room Ventilation System Arrangements
The influx to a Control Room of radioactive and other contaminants can be eliminated by a ventilation
system designed to filter the inlet air and by pressurizing the room to ensure that any leakage will be out-
flowing. Design alternatives include one-pass purified outside air, recirculation purified air, stored bottled air,
and a choice of dispersed air inlets.44 Each system has a different application, with advantages and
disadvantages. This section will discuss the four types, present models for calculating doses to the Control
Room operators, and associated air cleaning requirements.
Nuclear Air Cleaning Handbook U.S. Department of Energy
2-46
Control Room Infiltration
Infiltration is defined as unintentional leakage of air into the Control Room caused by pressure differences
across the boundary of the Control Room air space. Typical leak paths are cracks around doorframes; duct,
pipe, and cable penetrations; structural joints; and damper seals. Good Control Room design minimizes
leakage paths by using gaskets, weather stripping, and sealing techniques. However, continuous distributions
of microscopic capillaries and pores in concrete are possible, making complete elimination of infiltration
difficult.
Section 47
Pressure differentials may be due to natural phenomena such as wind and temperature or barometric
differences. Pressure differences can also occur when there are flow imbalances between the Control Room
and adjoining spaces.
Precise evaluation of Control Room infiltration is difficult to predict in the design phase because of the many
variables (e.g., wind direction and speed, building geometry, Control Room leaktightness, and internal
building pressure distribution) that can combine in different ways. In addition, the degree of Control Room
isolation after an accident associated with ingress/egress traffic further compounds the situation. One
approach is to measure infiltration at a number of Control Rooms and analyze the data. An isolated Control
Room can be pressurized to determine the pressurization flow rate required to maintain a constant pressure.
Tracer gases may also be used in a series of concentration decay measurements under various atmospheric
conditions to establish empirical correlation between Control Room configuration, construction quality,
ventilation characteristics, and infiltration characteristics. A study performed at the Zion Generating Station
in Zion, Illinois using sulfur hexafluoride, provided extremely useful results. Sulfur hexafluoride was used
because it is nontoxic, nonreactive, inert, and easily detectable by electron capture gas chromatography. With
a measured makeup flow of 1,700 cfm, total infiltration leakage was experimentally determined to be 150 cfm.
This was reduced by 50 percent when simple corrective measures were taken (new gaskets).
Air Cleaning Criteria
The most important feature of a Control Room air cleaning system is its ability to deliver sufficient quantities
of clean air to the Control Room so that operators can perform their assigned duties in comfort and safety.
During normal operations, the Control Room ventilation system keeps out dust and noxious contaminants
and maintains effective temperature at acceptable levels. It also keeps the Control Room pressurized to
1/4 in.wg to prevent in-leakage. During an accident situation, the Control Room air cleaning system must
continue to function and provide a habitable environment for the operators. The system must be designed to
seismic Category I and must be redundant to satisfy the single failure criterion. Automatic activation is
necessary. Design features and the qualification requirements of an ESF Control Room air cleaning system
are contained in Regulatory Guide 1.5227 and ASME Code AG-1.4 The components included in each of the
redundant filter trains are: (1) demisters to remove entrained moisture, (2) prefilters to remove the bulk of the
particulate matter, (3) HEPA filters, (4) iodine adsorbers (generally, activated carbon), (5) HEPA filters after
the adsorbers for redundancy and collection of carbon fines, (6) ducts and valves, (7) fans, and (8) related
instrumentation. Heaters may be used to reduce the RH entering the carbon beds to maximize performance
and remove radioiodine species. Figure 2.17 is a schematic of a typical ESF air cleaning system.
Subsystems
Cable Spreading Rooms. These rooms contain the cables that are routed to the Control Room. They are
normally cooled by a 100 percent recirculation air conditioning unit that is nuclear-safety-related and has an
assured (nuclear-safety-related) source of cooling to maintain the space temperature for all applicable design
basis events. This unit may be a part of the control complex HVAC system.
Section 48
DOE-HDBK-1169-2003 Chapter 2
2-47
Emergency Electrical Switchgear Rooms. These rooms contain the essential switchgear for the plant.
They are normally cooled by a 100 percent recirculation air conditioning unit that is nuclear-safety-related and
has an assured (nuclear-safety-related) source of cooling to maintain the space temperature for all applicable
design basis events. This unit may be a part of the control complex HVAC system.
Battery Rooms. The essential battery rooms contain the batteries that provide backup power for certain
design basis events. They should be designed for a maximum room temperature of 77 degrees Fahrenheit
(25 degrees Celsius) per IEEE Standard 48443 and should be provided with an assured (nuclear-safety-related)
source of cooling. These batteries also produce hydrogen when they are being charged. Therefore, a nuclear
safety-related exhaust system is required that provides a minimum of five room air changes per hour. Also,
the exhaust pickup points must be located at the ceiling of these rooms because hydrogen is lighter than air
and will pocket at the highest point in the room.
Testability
Qualification testing and quality assurance of individual components by manufacturers in accordance with
ASME N509,29 ASME Code AG-1,4 and ASME NQA-144 are required. After installation, pre-operational
tests on individual components and the complete system are necessary. Deficiencies need to be repaired
prior to accepting the system for operation and subjecting the system to radioactive contamination. An
operating system must undergo periodic surveillance testing to verify that it can continue to perform its
intended function. Technical Specifications, a part of the license for each nuclear power station, define the
limiting conditions for operation (LCO) and the surveillance requirements for satisfying the LCOs. The
LCOs specify which actions must be taken if the system becomes inoperable. The surveillance requirements
are contained in Regulatory Guide 1.52,29 ASME N510,23 and ASME Code AG-1.4
Figure 2.17 – Typical Air Cleaning System for Nuclear Power Plant Applications
36 in. min.
Service Area
Light (typ.)
Pre-Filter Access
Type III Carbon Absorber
HEPA Filter Access
Isolation Damper
Moisture
Separator
Access
Isolation
Damper
36 in. min.
Service Area
Heater Access
Drain (typ.)
HEPA Filter Access
Nuclear Air Cleaning Handbook U.S. Department of Energy
2-48
Inspections of Control Room ventilation and radiation protection provisions for Control Room personnel are
performed during the construction, pre-operational, and operational stages. In the United States, regional
staffs perform this function at nuclear power plants. Inspection guidance is contained in manuals in the form
of inspection modules. Inspections are performed to ensure that all systems will perform their intended
functions, that operating procedures are in place, and that training has been provided.
Licensee Event Reports (LERs) submitted to the NRC by operators of commercial nuclear power plants are a
useful source of information on the performance of habitability systems in Control Rooms, as well as other
air cleaning systems. It is important to evaluate them and factor the lessons-learned into future activities.
Owners of commercial nuclear power plants evaluate LERs through their Operating Experience Program.
DOE-HDBK-1169-2003 Chapter 2
2-49
2.8 References
1. Harrington, R. E., 1974, “Fine ParticulatesThe Misunderstood Air Pollutant,” Journal of Air Pollution
Section 49
Control Association 24(10), pp. 927-929, Pittsburgh, PA.
2. Austin, P. R., 1966, “Personnel Emissions in Laminar-Flow Clean Rooms,” Contamination Control. 5(7).
3. Burchsted, C. A., 1968, “Environmental Properties and Installation Requirements for HEPA Filters,”
Symposium on Treatment of Airborne Radioactive Wastes, International Atomic Energy Agency,
Vienna, Austria.
4. ASME (American Society of Mechanical Engineer), 2003, Code on Nuclear Air and Gas Treatment, ASME
AG-1, New York, NY.
5. IEEE (Institute of Electrical and Electronic Engineers), 1983 (R1996), Standard for Qualifying Class 1E
Electrical Equipment for Nuclear Power Generating Stations, IEEE Standard 323, New York, NY.
6. IEEE (Institute of Electrical and Electronic Engineers), 1987, Recommended Practice for Seismic Qualification of
Class 1E Equipment in Nuclear Generating Stations, IEEE Standard 344, New York, NY.
7. ASTM (American Society for Testing and Materials), 2000, Standard Guide for Use of Protective Coating
Standards in Nuclear Power Plants, Standard D5144-00, West Conshohocken, PA.
8. DOE (U.S. Department of Energy), 2002, Facility Safety, DOE Order 420.1A, Washington, DC.
9. DOE (U.S. Department of Energy), 2000, Nonreactor Nuclear Safety Design Criteria and Explosive Safety
Criteria Guide for Use With DOE O 420.1A, DOE G 420.1, Washington, DC.
10. DOE (U.S. Department of Energy), 1994, Preparation Guide for U.S. DOE Nonreactor Nuclear Facility Safety
Analysis Reports, DOE-STD-3009, Washington, DC.
11. 10 CFR 835 (Code of Federal Regulations), 2003, Occupational Radiation Protection, U.S. Department of
Energy, Washington, DC.
12. DOE (U.S. Department of Energy), 1993, Change 2, Radiation Protection of the Public and the Environment,
DOE O 5400.5, Washington, DC.
13. 40 CFR 61 (Code of Federal Regulations), 2003, National Emission Standards for Air Pollution, Subpart H,
pp. 2-19, Washington, DC.
14. DOE (U.S. Department of Energy), General Design Criteria, DOE O 6430.1A, Washington, DC.
15. ASHRAE (American Society of Heating, Refrigerating and Air Conditioning Engineers), 1993, Heating,
Ventilating and Air Conditioning Design Guide for Department of Energy Nuclear Facilities, Atlanta, GA.
16. 29 CFR 1910 (Code of Federal Regulations), 2003, General Industry Standards, Occupational Safety and
Health Administration, Washington, DC.
17. ACGIH (American Conference of Governmental Industrial Hygienists), Annual Issue, TLVsThreshold
Limit Values for Chemical Substances and Physical Agents in the Workroom Environment, Cincinnati, OH.
Nuclear Air Cleaning Handbook U.S. Department of Energy
2-50
18. DOE (U.S. Department of Energy), 1998, Worker Protection Management for DOE Federal and Contractor
Employees, DOE O 440.1A, Washington, DC.
19. NRC (U.S. Nuclear Regulatory Commission), 1973, General Design Guide for Ventilation Systems of Plutonium
Processing and Fuel Fabrication Plants, Regulatory Guide 3.12, Washington, DC.
20. AGS (American Glovebox Society), 1998, Guidelines for Gloveboxes, AGS-G001, Denver, CO.
21. ACGIH (American Conference of Governmental Industrial Hygienists), 2001, Industrial Ventilation – A
Manual of Recommended Practices, 24th Edition, Cincinnati, OH.
22. AIHA (American Industrial Hygiene Association), 2003, American National Standard Laboratory Ventilation,
ANSI/AIHA Z9.5, May.
23. ASME (American Society of Mechanical Engineers), 1989, Testing of Nuclear Air Treatment Systems, ASME
Standard N510, New York, NY.
Section 50
24. First, M. W., and L. Silverman, 1962, “Cost and Effectiveness of Air Cleaning Systems,” Nuclear Safety.
4(1), pp. 61-66.
25. Bergman, W., 1999, “Maximum HEPA-Filter Life,” UCRL-AR-134141, Lawrence Livermore National
Laboratory, Pleasanton, CA.
26. ASHRAE (American Society of Heating, Refrigerating, and Air Conditioning Engineers), 1999, Method of
Testing Ventilation Air Cleaning Devices for Removal Efficiency by Particle Size, Standard 52.2-99, Atlanta, GA.
27. NRC (U.S. Nuclear Regulatory Commission), 2001, Design, Testing, and Maintenance Criteria for Atmosphere
Cleanup System Air-Filtration and Adsorption Units of Light-Water-Cooled Nuclear Power Plants, Regulatory Guide
1.52, Rev. 3 Washington, DC.
28. American Air Filter Co., Inc., (engineering data) Louisville, KY.
29. ASME (American Society of Mechanical Engineers), (R 2002), Nuclear Power Plant Air Cleaning Units and
Components, ASME N509, New York, NY.
30. Ettinger, H. J., M. Gonzaes, and J. Elder, 1974, Performance of Multiple HEPA Filters Against Plutonium
Aerosols, 13th Atomic Energy Commission Air Cleaning Conference USAEC Report CONF-740807,
pp. 501-525, San Francisco, CA.
31. Miller, G, Fulton, G. and W. Bergman, 1999, Lawrence Livermore National Laboratory HEPA Filter and In-
Place Leak Testing Standard, UCRL-AR-133354, Rev. 1.
32. NRC (U.S. Nuclear Regulatory Commission), Rev. 2, 2001, Design, Testing and Maintenance Criteria for
Normal Ventilation Exhaust System Air Filtration and Adsorption Units of Light-Water-Cooled Nuclear Power
Plants, Regulatory Guide 1.140, Washington, DC.
33. NRC (U.S. Nuclear Regulatory Commission), 2002, Evaluating the Habitability of Nuclear Power Plant Control
Room Operators during a Postulated hazardous Chemical Release, NRC Regulatory Guide 1.78 Rev. 1,
Washington, DC.
34. Hollingsworth and Vose, 2003, Engineering Data.
DOE-HDBK-1169-2003 Chapter 2
2-51
35. ASME (American Society of Mechanical Engineers), In-service Testing of Nuclear Air Treatment Systems,
ASME Standard N511, New York, NY (to be published).
36. NRC (U.S. Nuclear Regulatory Commission), 1987 (Section Revisions 1996 and 2000), Standard Review
Plan for the Review of Safety Analysis Reports for Nuclear Power Plants, NUREG 0800, Washington, DC.
37. ASHRAE (American Society of Heating Refrigerating and Air Conditioning Engineers), 2001,
Fundamentals Handbook, [I-P Edition] Atlanta, GA.
38. NRC (U.S. Nuclear Regulatory Commission), 1988, Seismic Qualification of Electrical Equipment for Nuclear
Power Plants, NRC Regulatory Guide 1.100 Rev. 2, Washington, DC.
39. NRC (U.S. Nuclear Regulatory Commission), 1999, Instrument Set Points, NRC Regulatory Guide 1.105
Rev. 3, Washington, DC.
40. IEEE (Institute of Electrical and Electronic Engineers), 1994, Standard for Qualifying Continuous Duty Class
1E Motors for Nuclear Power Generation Stations, IEEE Standard 334, New York, NY.
41. 10 CFR Part 50 (Code of Federal Regulations), 2003, General Design Criteria, Criterion 19, Appendix A,
Washington, DC.
42. ASHRAE (American Society of Heating Refrigerating and Air Conditioning Engineers), 1992, ASHRAE
Standard 55-74, Thermal Environmental Conditions for Human Occupancy, Atlanta, GA.
43. 10 CFR 20 (Code of Federal Regulations), 2003, Energy: Standards for Protection Against Radiation,
Appendix B, Washington, DC.
44. IEEE (Institute of Electrical and Electronic Engineers), 2002, IEEE Recommended Practice for Installation
Design and Implementation of Vented Lead-Acid Batteries for Stationary Applications, IEEE Standard 484,
New York, NY.
Nuclear Air Cleaning Handbook U.S. Department of Energy