DOE-HDBK-1169-2003, Nuclear Air Cleaning Handbook, Chapter 10, Fire Protection
Functional areas: Fire Prevention, Ventilation, HEPA Filters
This handbook draws from many special technical areas, each of which requires years of education and practice to master. The authors do not intend to make the reader an "instant expert" in the overall subject or in any of the disciplines of the contributors. The 4th edition of the Nuclear Air Cleaning Handbook succeeds three previous editions: ERDA 76-21, Nuclear Air Cleaning Handbook (1976); ORNL/NSIC-65, Design, Construction and Testing of High-Efficiency Air Filtration Systems for Nuclear Applications (1970); and NSIC-13, Filters, Sorbents, and Air Cleaning Systems as Engineered Safeguards in Nuclear Installations (1966). It benefits from over 25 years of industry experience since the previous edition was published. This revision updates the information provided in ERDA 76-21 and incorporates current thinking as provided by manufacturers, subject matter experts from the DOE complex and members of the ASME Committee on Nuclear Air and Gas Treatment (ASME AG-1 Committee). Chapters have been added on History, Fire Protection, and Occupational Safety and Health.
Related To:
Version history and related documents
Related documents
- DOE-HDBK-1169-2003Nuclear Air Cleaning Handbook, Chapter 11, Occupational Safety and Health
- DOE-HDBK-1169-2003Nuclear Air Cleaning Handbook, Appendix A, Care and Handling of HEPA Filters
- DOE-HDBK-1169-2003Nuclear Air Cleaning Handbook, Appendix B, Receiving Inspection Direction and Checklist
- DOE-HDBK-1169-2003Nuclear Air Cleaning Handbook, Appendix C, Determination of HEPA Filter Life
- DOE-HDBK-1169-2003Nuclear Air Cleaning Handbook, Chapter 1, History of the Development of Air Cleaning Technology in the Nuclear Industry
- DOE-HDBK-1169-2003Nuclear Air Cleaning Handbook, Chapter 2, System Considerations
- DOE-HDBK-1169-2003Nuclear Air Cleaning Handbook, Chapter 3, Filters for the Nuclear Industry
- DOE-HDBK-1169-2003Nuclear Air Cleaning Handbook, Chapter 4, Housing Design and Layout
- DOE-HDBK-1169-2003Nuclear Air Cleaning Handbook, Chapter 5, External Components
- DOE-HDBK-1169-2003Nuclear Air Cleaning Handbook, Chapter 6, Small Air Cleaning Units
- DOE-HDBK-1169-2003Nuclear Air Cleaning Handbook, Chapter 7, Glovebox Filtration
- DOE-HDBK-1169-2003Nuclear Air Cleaning Handbook, Chapter 8, Testing
- DOE-HDBK-1169-2003Nuclear Air Cleaning Handbook, Chapter 9, Special Application Requirements
- DOE-HDBK-1169-2003Nuclear Air Cleaning Handbook (Introduction) (Part 1 of 15, links to all Parts)
Document text
Text extracted from the attached file. Refer to the original document for the authoritative version.
Section 1
10-1
CHAPTER 10
FIRE PROTECTION
10.1 Introduction
A separate chapter on fire protection is included in this Handbook because fire is the dominant public risk
accident in nuclear facilities. This chapter focuses on fire prevention and protection of the ventilation
systems in industrial and Government facilities such as energy production reactors, fuel processing and
reprocessing facilities, research establishments, special applications facilities, waste processing plants, and
storage and salvage sites. High-efficiency particulate air (HEPA) filters are extremely susceptible to damage
when exposed to the effects of fire, smoke, and water; it is the intent of this chapter to provide the designer
with the experience gained over the years from hard lessons learned in protecting HEPA filters from fire.
Fire protection for ventilation systems in commercial nuclear power plants is outside the scope of this
chapter.
The presence of water around fissionable materials is a potential cause of undesired nuclear criticality. The
primary agent used in the protection of HEPA filters from fire also happens to be water. This appears on the
surface to be a conflict, but the professionals in both subject areas have largely come to an understanding of
how the objectives of both fire protection and criticality safety can be achieved. The successful prevention of
fire damage and undesired criticality often involves human or procedural aspects that are difficult to quantify,
so careful analysis and coordination between these two important subject areas is of particular importance in
these situations. Appropriate guidance has been developed and can be found in the DOE Fire Protection
Design Standard, DOE-STD-1066-99.1
There are also two major issues with protecting confinement ventilation systems from the effects of fire: the
effect of water on the integrity of HEPA filter median and the potential of a criticality incident occurring with
the use of water in the vicinity of fissile materials. Experts have carefully developed the guidelines in this
chapter with consideration for both of these issues. Study of the history of fire and fire suppression system
behavior in actual fires and in research and testing has shown that HEPA filter media integrity can be assured
by following the recommendations in this Handbook. The prevention of criticality occurrences is more
situation-specific, however. While fire protection and criticality experts do agree on general acceptability of
means of fire protection of fissile materials, each specific situation must be evaluated individually by qualified
persons in both the fire protection and criticality safety fields. None of the criticality mishaps known to have
occurred in the world has been caused by water from a fire suppression system, but some fires have caused
extensive damage and contamination because water-based fire suppression systems were not present.
The ventilation air cleaning system of a nuclear facility is responsible for confining the radioactive smoke that
results from fires. There are three major objectives to fighting fires in or around ventilation systems in
nuclear facilities: (1) to keep the confinement ventilation system operable; (2) to suppress the fire; and (3) (if
the filtration function is no longer operable) to prevent the release of radioactive materials that may have
accumulated on the filters.
Section 2
A confinement ventilation system must be designed to fulfill its purpose, i.e., to prevent harmful products
(radioactive or otherwise) from escaping the system (sometimes referred to as the confinement) or facility,
impacting the public or workers, and doing environmental damage. This chapter describes methods to
ensure that confinement ventilation systems are designed, maintained, and operated in a manner to provide
Nuclear Air Cleaning Handbook U.S. Department of Energy
10-2
optimum protection against fires that could cause the confinement ventilation system to fail in its primary
function.
The potential effects of fire in or around confinement ventilation systems are: (1) penetration of the system,
and (2) release of hazardous materials to interior spaces outside the confinement volume. Large fires in
confinement ventilation systems will produce heat- and smoke-filled combustion products that can degrade
ventilation circuit components, ignite exposed materials, and/or plug the filters that prevent release of the
toxic components produced during normal operations, thus causing loss of confinement. [Note: Hot gas
transport can soften HEPA filter sealants, thereby weakening filter media in their frames. This, combined
with the pressure differential, can blow out the filters, resulting in confinement loss]1. Ignition of
combustibles in gloveboxes or rooms can result in flaming brands and glowing embers. They may be lifted
and carried by the design airflow to filter banks where they can burn through unprotected filters or ignite dust
coating the interior of the ducts or trapped by filters. In either event, the unprotected filters would no longer
be functional. If a fuel/air mixture filling even a small volume of a confinement system is ignited, the
resulting pressure pulse can explosively breach the system. Such events are generally limited to the local
elements of a system because of pressure pulse attenuation in the ducts and rapid fuel consumption during
the explosion.
Fires that start inside ventilation systems have different characteristics than those that start outside the
system, depending on how they are ignited. The performance of ventilation systems after ignition is
determined by the system design and the safety measures provided by codes and standards.
In this chapter, topics such as fire hazards and effects, and analytical techniques are discussed, followed by a
description of recommended fire safety features. In addition, a number of lessons learned from past fires at
both DOE sites and commercial nuclear facilities are discussed. This chapter also refers the reader to the
recognized codes and standards to be used in the fire protection design process and does not conflict with
those codes and standards. The user should recognize that this is a handbook and not a design standard.
10.2 Fire History
Fires in nuclear facilities have been caused by a variety of energy sources, including electrical energy and
spontaneous combustion of pyrophoric metals. While fixed fire suppression systems or operator intervention
have limited the size and consequences of most of these fires, some did propagate and cause significant
damage and material release. There have been numerous occurrences of fire in nuclear facilities since the
beginning of the Manhattan Project and many lessons learned from those fires. Some lessons have been
learned at great expense. A brief history is discussed here in the hope that the lessons will not be forgotten or
ignored by facility designers and operators.
Section 3
The most significant fires involving the HEPA filters of confinement ventilation systems have occurred at the
Rocky Flats Plant. In 1957, pyrophoric ignition of plutonium in a production line ignited combustible
cellulose filters in the production box and spread from there via laminated plexiglass window materials and
other unknown combustible materials in the ventilation system to involve and destroy combustible HEPA
filters in the final filter stage. Delays in fighting this fire were due to radiation safety concerns and delays in
using water due to criticality concerns allowed it grow. It was extinguished soon after water was used, but a
buildup of combustible vapors and dusts in the ventilation ductwork and the final filter stage ignited and
resulted in a small explosion. This severely damaged the HEPA filters in the final filter stage and allowed the
second-highest known plutonium release at Rocky Flats to occur.2, 3 A significant portion of the plutonium
released from this fire was deposited offsite.3 As a result of this event, fire-resistant glass fiber HEPA filters
were researched, developed, and put into service in the nuclear industry.
DOE-HDBK -1169-2003 Chapter 10
10-3
Another fire occurred at Rocky Flats in 1969 in a production line glovebox.2, 3 The exact cause of this fire is
unknown, but the area of origin included a storage cabinet that housed small, open metal containers filled
with plutonium machine turnings. The cabinets, which were constructed of high-density pressed wood
shielding material and plastic, were included in the production line to reduce radiation exposure to workers.
Heat detectors originally installed in the glovebox were removed to the underside of the glovebox floor to
accommodate the cabinet. A fire detector alarm alerted the fire department. When the firefighters arrived,
the building was smoke-filled, indicating the fire had escaped the confinement system. While localized
contamination was detected outside the building, no measurable contamination escaped the site.
History of Fire Involving Confinement Ventilation Systems
The following is a partial list of fires known to have occurred in nuclear facilities, involving nuclear materials,
and having some interaction with the facility confinement ventilation system or some other significance.
These come from U.S. Atomic Energy Commission (AEC) Serious Accident Reports. The AEC was a
predecessor of the U.S. Department of Energy. This list is by no means comprehensive or complete.
1. Fire in Ventilating System Filters. AEC, Serious Accidents, Issue No. 83, July 27, 1955
This fire involved a large bank of paper HEPA filters in wood frames (CWS Filters). Following
extinguishment of a fire that had been caused by sparks from welding, re-ignition occurred on each of the
following 2 days. About 2.5 tons of carbon dioxide was used to control the fire. Although no radiation
hazard was involved, suppressing this fire was difficult due to the reactivity of the dust (specifics not
given) in the ductwork with water.
2. Serious Ventilating System Incidents. AEC, Serious Accidents, Issue No. 110, November 8, 1956
Fire started from spontaneous combustion in zirconium powder that had accumulated in ductwork
incurring $150,000 in damage.
Six hundred grams of hydride powder in plastic bags spontaneously ignited near the intake of a
6 feet × 6 feet filtering unit incurring $21,093 in damage.
Section 4
Laboratory scale testing being run in oxides generated by combustion in air of NaK, were carried by the
ventilating system to a combustible filter. For unknown reasons, the NaK began splattering and ignited
the filters. A loss of $8,400 was reported.
3. Fire in British Windscale Facility. AEC, Serious Accidents, Issue No. 128, October 15, 1957
The fire started in the British graphite-moderated, air-cooled reactor at Windscale. Stack gas filters were
very effective in removing particulate matter from the airstream, and the radioactive contamination of the
surrounding area appears primarily concerned with iodine dispersed over about 200 square miles of
farmland.
4. Explosion in Glove-Box Line of Plutonium Facility. AEC, Serious Accidents, Issue No. 129, October 28, 1957
Vapor from a flammable lubricating and rust preventative chemical being used on a machine in the
glovebox line circulated throughout all the boxes, and sparks from an electric brush being used on
another machine ignited the vapors and caused an explosion. Loss not stated.
5. Small Metallic Plutonium Fire Leads to Major Property Damage Loss. AEC, Serious Accidents, Issue No. 130,
November 27, 1957
A small amount of plutonium spontaneously ignited within a dry box in a so-called “fireproof” building
that was relatively free of combustible material. More than $300K in losses were incurred. This is the
fire that occurred in September 1957, where most of the filter banks were destroyed. The initial fire
Nuclear Air Cleaning Handbook U.S. Department of Energy
10-4
released a significant quantity of flammable vapors into the confinement ventilation system, which
subsequently ignited and exploded.
6. Filter Fire. AEC, Serious Accidents, Issue No. 41, December 2, 1958 and Serious Accidents, Issue
No. 144, March 9, 1959
Fire started in a fume hood in a chemical laboratory involving an experiment with perchloric acid. The
fire involved a combustible filter under the hood and traveled through the exhaust system, reaching the
main filter bank on the second floor of the building. Loss estimated at $12,000.
7. Drybox Explosion Disperses Polonium Contamination. AEC, Serious Accidents, Issue No. 148,
October 8, 1959
After normal working hours, an explosion occurred in a sample hood that dispersed some polonium-
containing solution. The cause is not precisely known. Loss unknown.
8. Ventilating Air Filter Clogs During Fire. AEC, Serious Accidents, Issue No. 151, October 28, 1959
A fire in a room under construction at an AEC plant occurred. The ventilating system had been placed
in service for the room even though the room was not yet complete. The filters soon became plugged
with smoke and soot. The firefighters entered the obscured room and "chopped" out the filters. The
smoke soon cleared from the room, but had radioactive contamination been present, it would have been
exhausted out the ventilation system
9. Plastic Windows and a $125,000 Sprinkler Head. AEC, Serious Accidents, Issue No. 152, October 29, 1959
Fire occurred in a chemical laboratory in a walk-in type of hood, involving plastic doors and windows. A
sprinkler head controlled the fire and limited the damage to about $350.
10. Radiochemical Plant Explosion releases Plutonium Contamination Outside Facility. AEC, Serious Accidents Issue
No. 162, March 30, 1960
Section 5
This explosion occurred in a radiochemical pilot plant being used for processing spent power reactor
fuel. A small amount of plutonium was dispersed, contaminating nearby buildings and grounds. Loss
was about $360K, which includes decontamination costs.
11. Could Sprinkler Protection Have Reduced This $200,000 Radiochemistry Building Fire Loss? AEC, Serious
Accidents, Issue No. 175, April 5, 1961
A fire occurred on the inside of a cavern drybox designed for working with high levels of radioactivity.
The fire spread to other areas within the cavern involving plastics and wood. A minor amount of
radioactivity was dispersed. The loss was about $200,000.
12. Polyester Fibrous Glass Duct Fire causes $43K Damage. AEC, Serious Accidents, Issue No. 216,
January 31, 1964
Fire started in combustible laboratory fume hood ducting. The ducting was of polyester resin-bonded
fibrous structure. The fire began around a hot plate in a fume hood and then extended into the
ductwork. Fire damage was limited to the general area of ducting but smoke damage was extensive in
this 4,500 square foot, one-story and basement facility. Smoke damage may have been exacerbated by
the exhaust fanes having been turned off during the fire. The exhaust system was not filtered.
13. Filter Box Fire. AEC, Serious Accidents, Issue No. 217, February 7, 1964
This fire occurred in a filter box on the roof of a nuclear facility. The burning filters were manually
removed from the box by firefighters who then used carbon dioxide and dry chemical fire extinguishers
DOE-HDBK -1169-2003 Chapter 10
10-5
to extinguish the fire. Some smoke backed up into the plant as a result of shutting off the blower fans.
The fire was determined to have been caused by fine uranium chips which spontaneously ignited and
were drawn into the ventilation system. The burning uranium chips ignited the metal mesh in the
roughing filters and then the “absolute” filters as they are called in the report. The roughing filters had
been cleaned 6 weeks previously and there was no evidence of buildup of dust in the ductwork itself.
The “absolute” filters were less than one year old. A recommendation of this report was the use of fire-
resistive “absolute” filters.
14. Fire and the Reaction of Nitric Acid with Plutonium Ion Exchange Resin Leads to Major Property Damage. AEC,
Serious Accidents, Issue No. 237, December 4, 1964
At 1:23 am, a sudden reversal of airflow was noted in the facility during plutonium purification
operations. The purification operation was shut down immediately. The presence of a fire was
discovered after about 30 minutes. The use of water was not recommended due to criticality safety
concerns. The fire was extinguished in about 1.5 hours through the use of about 500 pounds of sodium
bicarbonate. It was later estimated that, if water fog had been used, it could have been extinguished in
5 minutes. The fire spread through open gratings to involve all four floors of the facility. The direct and
indirect loss was estimated at $397K. Although no direct mention is made of confinement ventilation
system performance, this is being included as it was a significant fire in a nuclear facility.
15. Explosion Within Glovebox Disperses Contamination. AEC, Serious Accidents, Issue No. 242,
January 11, 1965
Section 6
A methanol-air mixture in a glovebox ignited and exploded, pressurizing the glovebox and tearing off six
gloves. Plutonium oxide discharged from the open ports and spread throughout the operating areas of
the building. Some workers were contaminated to varying degrees. No mention is made of any
contamination being released from the building.
16. Burning Plutonium Chips Explode in Carbon Tetrachloride Degreasing Bath. AEC, Serious Accidents, Issue
No. 246, March 12, 1965
Plutonium chips immersed in carbon tetrachloride within a glovebox spontaneously ignited and burned
during operations. During the performance of the procedure in place to handle burning plutonium chips
in a container, some of the burning chips fell into a carbon tetrachloride bath in the glovebox, causing an
explosion with a shock wave. This ruptured the glovebox and dispersed plutonium throughout the
glovebox line. There was no direct impact on HEPA filters.
17. Cutting Wheel residues in Plutonium Waste Cause Explosion. AEC, Serious Accidents, Issue No 258,
December 17, 1965
During an operation involving oxidation of plutonium waste in a nitrogen-inerted glovebox, in which a
small amount of oxygen was introduced in a bell jar containing plutonium chips under partial vacuum,
the plutonium in the jar began to smoke and then an explosion occurred within the jar. Contamination
was limited to fragments thrown about the interior of the glovebox.
18. Hazardous Solvent Causes Explosion in a Glovebox. AEC, Serious Accidents, Issue No. 261, February 1966
During cleaning operations, using acetone, in a glovebox where plutonium was being processed, an
explosion occurred that blew out three gloves. The ensuing fire was extinguished with a 20-pound dry
chemical fire extinguisher. Some workers were contaminated, and contamination was spread throughout
the room. No contamination was detected outside of the building.
Nuclear Air Cleaning Handbook U.S. Department of Energy
10-6
19. Maintenance on Plutonium Machining Coolant Lines Leads to $17,500 Fire. Building 776/777, Rocky Flats, 1965,
AEC, Serious Accidents, Issue No. 262, March 4, 1966
Metallic plutonium lathe operations, utilizing a circulating oil cooling system, were being conducted
within a glovebox. During normal operations, oil that splashed or dripped accumulated in a drip pan
with a valve in its drain line. This valve was normally open, allowing the drain pan oil to flow back to the
suction side of the circulating pump. The drain line became clogged and attempts were made to unclog it
by first flushing it with carbon tetrachloride (unsuccessfully), then by using a welding rod to probe and
clear it. Some paper towels and a plastic pan were placed around the pipe to catch oil and prevent the
spread of contamination. During the probing, sparks were noticed when the rod contacted something
metallic in the line. Because the probing did not appear to be having much effect, a center punch was
inserted into the drain line and struck by a hammer. The first blow caused a light spark; the second blow
caused a lot of sparking accompanied by a fireball, igniting the plastic pan and paper towels. The copper
drain line began to glow, indicating a fire within it. This fire was controlled using a fire extinguisher.
Contamination from the fire spread throughout the Building 776 and 25,000 square feet of Building 777.
20. Fire During Glovebox Cleanup Leads to $23,000 Damage Via Contamination Spread. AEC, Serious Accidents,
Issue No. 269, July 8, 1966
Section 7
During operations to remove the paint from the inside of a glovebox in preparation for its disposal, fire
involving flammable solvents occurred in the airlock for the glovebox system. Unsuccessful attempts
were made to extinguish the fire by firefighters using carbon dioxide fire extinguishers, but the fire was
ultimately controlled by introducing solid carbon dioxide. Contamination was spread throughout the
ventilation system ductwork and over two floors of the building.
21. Fire Damages Hot Cell Window. AEC, Serious Accidents, Issue No. 275, November 4, 1966
An operation involving NaK in a shielded hot cell ignited some alcohol being used. A total-flooding
carbon dioxide extinguishing system was manually actuated which extinguished the fire. The HEPA
filters received some particulate contamination but not to the extent that they became plugged. The
window in the hot cell was cracked due to the heat from the alcohol fire. No significant amount of
contamination occurred.
22. Glovebox Explosion Causes $42,000 Damage and Plutonium 238 Contamination Spread. AEC, Serious Accidents,
Issue No. 293, August 26, 1968
An explosion in a series of gloveboxes where plutonium 238-contaminated wastes were being dried
caused extensive damage to the gloveboxes and room. Contamination was spread into adjoining rooms
and corridors. The explosion was caused by the overheating of rubber gloves, releasing flammable
vapors that ignited.
23. Waste Incinerator Incident Affirms Fire-Resistive Filter Value. AEC, Serious Accidents, Issue No. 292,
July 31, 1968
During normal operations within a glovebox that was part of the incinerator operation, smoke from the
feed-end of the incinerator indicated inadequate airflow was going through the glovebox. Maintenance
personnel called to correct the problem discovered that the filter-box port cover was hot and its wood
frame was smoldering. The fire department was called and the fire in the filter frame was extinguished
using carbon dioxide. The filter was removed for inspection. Only the top of the four wooden sides of it
were unburned. The filter medium collapse was attributed to the application of the carbon dioxide fire
extinguisher. No burning of the filter medium was observed. The secondary filters in this frame were
unaffected by this incident. No contamination was spread as a result of this fire.
DOE-HDBK -1169-2003 Chapter 10
10-7
24. Fire - Rocky Flats Plant - May 11, 1969. AEC, Serious Accidents, Issue No. 306, December 1, 1969
This fire occurred one afternoon in a glovebox line in Buildings 776-777. It moved rapidly through the
glovebox line due to large quantities of combustible polymer shielding in place. Carbon dioxide was
unsuccessfully used to try to extinguish the fire initially. Water was used as a suppression agent by the
fire department only as a last resort. Extensive damage occurred. Some contamination was detected on
the roof of an adjoining building, released due to a minor HEPA filter failure. Most contamination was
tracked out by firefighters during suppression operations.
25. Incinerator Fire at Rocky Flats, July 2,1980. Investigation Report, July 31, 19804
Section 8
Incinerator operators noted a temperature rise above normal in the operation of an incinerator in
Building 771 at Rocky Flats in the late morning. A temperature overheat alarm occurred in the
incinerator plenum about an hour and 15 minutes later. About 90 minutes after the initial temperature
rise indication, the operators received a phone call and noted other indications that there was a fire in the
plenum of the incinerator. Incinerator shutdown was initiated and the fire was mostly extinguished by a
water deluge system. The fire department completed extinguishing the fire. It was noted in the
investigation report that two of the four causes of the fire were nitric acid attacking the urethane sealing
the HEPA filter media to the frames, and the accumulation of metal fines on the HEPA filter media
material. The nitrated urethane seals exhibited a temperature rise that may have ignited the metal fines
on the filter media. This incident resulted in slight contamination inside the building, with no release
external to the building.
26. Fire in TRISTAN Experiment at HFBR at BNL, March 31, 19945
This fire occurred in an experiment on the experiment level of the High Flux Beam reactor at
Brookhaven National Laboratory on Thursday, March 31, 1994. It spread light contamination through
the experiment level of the reactor.
27. Cerro Grande fire effects on HEPA filters at LANL May 4, 20006
On May 4, 2000, a prescribed burn at Bandelier National Monument, New Mexico escaped control and
ultimately burned nearly 50,000 acres in and around the town of Los Alamos and Los Alamos National
Laboratory (LANL). The thick smoke from this fire impacted the confinement ventilation system
operations at several LANL facilities. The confinement ventilation systems in some nuclear facilities
were shut down or placed on minimum ventilation to prevent filter clogging. Some facilities whose
confinement ventilation systems were not shut down experienced filter clogging and had to replace
filters. The facilities that shut down or went to minimum operation subsequently had re-entry and restart
issues they had to address. No contamination escaped from LANL facilities as a result of these actions.
28. Cutting Operations Ignite Residue In Bottom Of Glovebox, Rocky Flats Environmental Technology Site,
Building 371, May 6, 2003
Exploratory cutting operations on the top of a glovebox in Building 371 at Rocky Flats Environmental
Technology Site (RFETS) ignited legacy combustibles in the bottom of a large, two-story glovebox that
also contained a service elevator. Fire extinguishers were used to extinguish the fire, but upon stirring of
the materials by the workers the fire re-ignited. The fire department arrived soon thereafter and used 600
to 800 gallons of water form hose streams to fully extinguish the fire. Some of the firefighters received
skin contamination. This incident was still under investigation at the time of the writing of this
document.
Nuclear Air Cleaning Handbook U.S. Department of Energy
10-8
10.3 Requirements and Guidelines
Decisions regarding the extent and nature of fire safety features for confinement ventilation systems are
predicated to a significant degree on the regulatory environment governing the facility. That environment can
be characterized as being regulated by DOE or the NRC. The applicability of any fire safety criteria to a
particular design will depend on the nature of the license application (for an NRC-regulated facility), the
contract (for a Federal facility) and the governing regulations (e.g., 10 CFR Part 70).7 Proceeding with an
individual design should not progress until the technical (safety) basis is clearly established.
Section 9
Fire protection requirements and guidelines for confinement ventilation systems are delineated in a number
of NRC and DOE source documents. These include NRC Regulatory Guides, Standard Review Plans,
Branch Technical Positions, and supplementary staff position papers. DOE directives include DOE Order
420.1A, Facility Safety,8 its Implementation Guide for Fire Protection,9 and DOE-STD-1066-99.1
While these criteria are expected to be implemented, a “variance” approval process exists within both the
NRC and DOE. The process generally includes a documented description of the condition, the justification
for literal nonconformance, and approval by the fire protection “authority having jurisdiction” (AHJ).
Despite the differences in scope between NRC and DOE fire safety directives related to confinement
ventilation systems, the following are significant common requirements:
• Compliance with applicable industry standards such as those promulgated by the National Fire
Protection Association (NFPA). Prominent among these is the 800 series of standards on fire protection
for nuclear facilities and NFPA Standard 90A, Installation of Air Conditioning and Ventilation
Systems.”10 [Note: Cost-effective alternative means of compliance are permitted under established
“equivalency” provisions.]
• Development of a comprehensive Fire Hazards Analysis (FHA). The FHA is required to consider—
under all operating modes—the potential adverse impact of the spread of combustion products through
the ventilation system.
• Implementation of combustible materials and ignition source controls to minimize the potential for fire.
• Use of generally noncombustible structural elements and “listed” fire protection system components that
are subjected to a quality assurance (QA)/quality control (QC) program.
• Provision of fire protection defense-in-depth. This means that multiple fire safety features are available
in the event that one is rendered inoperable.
• Reliance on both active (e.g., fire detectors and sprinklers) and passive (e.g., fire barriers) fire safety
features.
• A comprehensive inspection, testing, and maintenance program for installed fire safety features.
• A trained staff capable of responding in a timely and effective manner to fires and related emergencies.
Specific fire safety features that are stipulated in this body of criteria are considered acceptable minimums and
should be treated exactly as such. There may be, and often are, circumstances that warrant provision of
additional protective measures to compensate for elevated fire hazards or unusual risks. Such hazards and
risks may be revealed in conjunction with formulation of the FHA, application of fire modeling techniques,
and analysis of engineering survey results, as well as after development of the Documented Safety Analysis.
DOE-HDBK -1169-2003 Chapter 10
10-9
An issue that has created a degree of regulatory inconsistency concerns the retroactive application of industry
standards. DOE has established the concept of “codes of record,” defined as the codes and standards that
were in force at the time a facility design commenced.
Questions regarding the applicability of individual fire safety directives to a particular confinement ventilation
design, as well as requests for interpretation of the provision of industry standards to such designs, should be
directed to the cognizant NRC or DOE fire protection AHJ.
Section 10
10.4 Enclosure Fire Modeling in Fire Hazards Analysis
DOE has developed a useful framework for analyzing the fire hazard in a facility. This framework considers
all of the aspects of fire and its impact on facility personnel, continuity of operation, the environment, and the
public. The occurrence and spread of fire is a complex process that cuts across many design and operational
disciplines, making its control throughout the lifetime of a facility problematic in some respects.
The FHA should contain a conservative assessment of the following features of a confinement ventilation
system:
• Description of construction,
• Identification of high-value property,
• Description of fire hazards (including a design basis fire and its effects on the confinement ventilation
system) and the limits of the ability of the confinement ventilation system to withstand fires more severe
than the design basis fire,
• Protection of essential safety class systems,
• Life safety considerations,
• Critical process equipment,
• Identification of the damage potential: Maximum Credible Fire Loss (MCFL) and Maximum Possible
Fire Loss (MPFL),
• Analysis of fire department/brigade response and its adequacy,
• Potential for recovery from a fire,
• Potential for a toxic, biological, and/or radiation incident due to a fire,
• Analysis of emergency planning and its ability to mitigate a fire in a confinement ventilation system,
• Security and safeguards considerations related to fire protection,
• Impacts of natural hazards (earthquake, flood, wind) on fire safety, and
• Exposure fire potential, particularly as related to the potential for breaching the confinement ventilation
system due to a fire that is external to the system.
Nuclear Air Cleaning Handbook U.S. Department of Energy
10-10
The FHA considers everything involved in the design and operation of the facility. The essential analysis
tools are predictive models that can be applied to define the ranges of hazards from design basis events
(DBEs). An FHA can be applied during the design phase of new facilities and/or in conjunction with
changes or modifications of existing operations.
Use of Fire Modeling in FHAs
Validated and verified fire models approved by DOE for use in Authorization Basis documents must be
used.
Fire models for FHAs range from simple algorithms that predict thermodynamic changes in enclosures to
complex programs that can account for heat, mass transfer, and smoke production in multiple enclosures.
Many mathematical models have been installed in software codes and are available on the Internet bulletin
boards of various government agencies. These codes can predict the development and spread of fire and
smoke conditions through multiple rooms, and can account for changes in the structure and composition of
enclosures. Application of these models requires considerable understanding of their use and limitations,
statements of which are usually included in the instructional text published with the software codes.
Reduction of complex models to simple terms supported by empirical data is often useful in predicting
uncomplicated systems.
10.5 Fire Phenomena
Section 11
Fire is a complex phenomenon that involves the initiation of an event and subsequent actions that can
mitigate or exacerbate the event’s effects. The matrix in Table 10.1 covers: (1) the initiation and generation
of harmful products from a fire; (2) the means by which these harmful effects are transported throughout the
confinement ventilation system are discussed; and (3) the impacts of these harmful effects on the main
components of the confinement ventilation system are discussed. The material in this section indicates the
fire hazards that must be mitigated. The techniques for mitigation are presented in the next section.
Table 10.1 – Fire Phenomena Matrix
Heat Smoke Related Effects
Generation Fire growth Initial aerosol makeup Water vapor, chemical releases,
deflagrations
Transport Temps in ducts Change in aerosol with time and
temperature
Change with movement through ducts
Effects on filters Media failure Filter media plugging Filter media plugging and failure
10.5.1 Fires Occurring Outside a Confinement Ventilation System
Fires occurring outside a confinement ventilation system generate heat that exposes the outside of ducting as
well as produce combustion products that are drawn into the confinement ventilation system when it
operates as intended. These combustion products will affect the components of the confinement ventilation
system.
10.5.1.1 Generation of Heat, Smoke, and Related Products
Thermal Effects from Fire Initiation and Growth
Hot gases from a fire that originates outside of the confinement ventilation system will be entrained within it
and will be conveyed via the duct system to the filter banks. While a certain amount of heat dissipation and
DOE-HDBK -1169-2003 Chapter 10
10-11
dilution will occur, over time the gases may cause steady deterioration of the filter medium and may ignite
combustible framing. The designer of nuclear air cleaning systems must accurately characterize the design
basis fire. This characterization can be subjective, (i.e., the thermal effects of a fire are determined on the
basis of judgment and experience) or the thermal effects of a fire on HEPA filters can be calculated by
qualified individuals using fire models. In the latter case, the chosen fire must be sufficiently conservative
(i.e., severe) to be an upper boundary for the mitigative features protecting the function of the confinement
ventilation system.
Smoke Generation
Smoke contains particulates that can pose a significant “plugging” threat to HEPA filters. Smoke is a
suspension of solid and/or liquid particles and gases resulting from combustion and pyrolysis. Soot is an
intrinsic part of smoke. However, the term “soot” can be further refined to mean finely divided particles,
mainly carbon, produced and/or deposited during incomplete combustion of organic materials. Moreover,
the amount of smoke generated from any material is strongly influenced by the same conditions that effect
combustion efficiency. In general, smoke is a heterogeneous combination of solid and liquid particles of
varying size and composition. Their instantaneous character depends on the material of origin, combustion
conditions, environment, and flow dynamics. The sizes of particulates vary from 0.002 to 0.5 µm, depending
on the experience described above. Conditions related to incomplete combustion generally result in an
aerosol distribution of larger mean particulate size. However, if the smoke concentration is high, particle
agglomeration (smoke aging) proceeds rapidly, as does fallout and surface deposition.
Section 12
Agglomerated smoke aerosols can attain diameters as large as 10 µm in plumes from fires; however, visibility
is most influenced by particulates with diameters of -1.0 µm. Collections of data on smoke production rates
(g of soot/g of material burned) are available and can be used to estimate visible obscuration and smoke
detector response time.
Water Generation
The quantity of water generated in the fire is as important as the soot and other particulates. Water vapor can
condense on the particulates in smoke, both increasing their average diameters and leading to increased
agglomeration resulting in generally larger particulates. Larger particulates lead to more rapid HEPA filter
plugging.
Calculating the aspects of the phenomenon of water generation from combustion is an extension of the
processes described by Gottuk and Roby.11
Generation of Combustion Products from External Fires
Many methods exist to establish the thermal history of gaseous and particulate combustion products from a
postulated fire (in most cases, the type of fire experienced in a nuclear facility would be a ventilation-
controlled fire, rather than a fuel-controlled fire).
Once the masses of smoke and water generated for a given fire have been established, the temperature that
occurs at the HEPA filter will determine how much water remains in the gaseous state or how much is
condensed.
Nuclear Air Cleaning Handbook U.S. Department of Energy
10-12
10.5.1.2 Transport of Heat, Smoke, and Related Products
Heat Loss in Ducts
Hot gas from fires may enter the exhaust duct system and lead to excessive temperatures at the HEPA filters
if not mitigated. The two primary tools for analyzing the cooling of hot exhaust gas are: (1) dilution analysis
with additional exhaust streams, and (2) duct cooling by convective and radiative heat transport.
As the combustion products from a fire travel through
the length of a duct, losses occur (see Figure 10.1).
Thermal energy is added or lost through the walls of
the duct according to the temperature differential
between the products of combustion gases in the duct
and the atmosphere external to the duct. Solid and
liquid particulates are deposited along the duct interior
surfaces according to a number of factors.
Alvares12 studied heat transport in gases traveling
through ducts to determine the losses in a duct
external to a facility. Most ducts are not external to a
facility, so the designer must consider this in the
analysis.
Because confinement systems are part of the
enclosures that support operations with nuclear
materials, computer codes have been developed to
predict the results of accidents on the internal
conditions within the system. For fire events, the
room fire models discussed above can serve as the
source term for codes that treat the response of
components within the confinement ventilation
system. Modeling tools are available (e.g., CFAST) to
help analyze heat transport in the ducts.
The phenomena noted in this section will be adequately mitigated by implementation of the fire protection
provisions of DOE Standard 1066-99.1 In those rare instances when it can be clearly demonstrated in a
comprehensive FHA that these fire hazards are insignificant, alternate fire protection configurations can be
considered.
Smoke and Water Loss in Ducts
Section 13
A significant quantity of smoke and water may settle out in the ventilation ducts. In one configuration where
the duct was located outside the fire area, Alvares12 observed that about 60 percent of the aerosol mass
(including water) was lost between the duct entrance and the HEPA inlet (about 19 feet for a 2-foot × 2-foot
cross-section duct).12
Transport of related combustion products (e.g., smoke particulates) can be modeled using available
techniques. Analysis methods for the entrainment and transport of these products in confined situations
such as ducts are generally well understood. The form and dispersion characteristics of the combustion
products in question also must be understood. Once this is done, the effects on the HEPA filters can be
shown with time.
Figure 10.1 – Cooling Rate of Air in a
12-inch Diameter Duct Carrying 1,000 cfm
of Air with Inlet Temperature of 1,000
Degrees Celsius
DOE-HDBK -1169-2003 Chapter 10
10-13
10.5.1.3 Effects on Filters of Heat, Smoke, and Related Products
The impact of fires on the integrity of the HEPA filters can be determined through a sequence of analyses to
establish: (1) the dynamics of the design basis fire; (2) the generation of smoke, water, and heat (temperature)
that enters the confinement ventilation system; (3) the mitigation of smoke, water, and heat through the
ducting to the HEPA filters; and (4) the response of the HEPA filters to the smoke, water, and heat that
reach them. The interaction of smoke, water, and heat play a major role in the plugging of HEPA filters, as
well as the consequent rise in filter pressure drop and possible reduction in exhaust flow. This sequence of
analysis will determine the potential of the design basis fire for causing structural damage to the HEPA filters
and thereby increasing the filter penetration. Finally, the impact of the smoke and water loading and the air
temperature on the HEPA filters must be determined.
HEPA Filter Response to Temperature
Fire-resistant HEPA filters must meet the requirements of Underwriters Laboratory (UL)-586, High-Efficiency,
Particulate, Air Filter Units.13 Prefilters must meet the requirements of UL-900, Performance of Air Filter Units.14
These UL test methods qualify the construction materials for the filter, frame, and gaskets. To be listed by
UL under UL-58613 as a HEPA filter unit, HEPA filters are required to meet the following three criteria:
• Withstand 750 ± 50 degrees Fahrenheit heated airflow for 5 minutes at not less than 40 percent of rated
capacity.
• Have a greater than 97 percent test aerosol efficiency after exposure to the hot air test and cooling.
• Withstand a spot-flame test in which a Bunsen burner flame at 1,750 ± 50 degrees Fahrenheit is placed
on the filter with no after-burning when the flame is removed.
For the spot flame test, a horizontal Bunsen burner is touched to the filter at three locations for 5 minutes at
each site. Afterwards, the burner flame is moved to touch the filter frame, filter pack, and sealing materials.
To pass the test, flaming on the downstream side of the filter must cease within 2 minutes after removal of
the burner flame. Although this test indicates the fire performance of the filter, it is a small-scale test with a
limited, controlled heat source that does not replicate the temperatures experienced during actual exposure to
a more severe, full-scale fire. Many fires can reach higher temperatures and more severe conditions than this
test fire.
Section 14
Extended exposure to temperatures above 800 degrees Fahrenheit will cause destruction of the casing of
wood-cased filters and warping of the casing of steel-cased filters, allowing unfiltered air to bypass the filter.
The medium of HEPA filters is thin (0.015 inch) and can be destroyed by incandescent sparks, flaming trash,
or burning dust on its surface.
Although HEPA filters can withstand a temperature of 750 degrees Fahrenheit for an extremely limited time,
they should not be subjected to continuous exposure to temperatures higher than 250 degrees Fahrenheit.
Longer filter life and more reliable service, as well as a greater operational safety factor, can be obtained when
normal operating temperatures are below 200 degrees Fahrenheit and higher temperature extremes are
avoided.
Continuous operation of HEPA filters at higher temperatures is limited primarily by the filter sealant used to
seal the filter core into the filter case. At higher temperatures, the sealants lose their strength, causing the
filters to fail. For example, standard urethane seals are suitable for service at 250 degrees Fahrenheit, while
some silicone seals can withstand 500 degrees Fahrenheit.
Nuclear Air Cleaning Handbook U.S. Department of Energy
10-14
Because different sealants are available and different filter manufacturers rate their filters for different
temperatures, the best practice for ventilation system designers and operators is to determine the
manufacturer’s limiting continuous service temperature if continuous operation at high temperatures is
necessary. A decision to operate above 200 degrees Fahrenheit should be accompanied by controls requiring
replacement filters that have been proven to be acceptable for above-normal temperatures.
HEPA Filter Response to Smoke and Water Loading
Water from combustion plays a major role in potential HEPA filter clogging with smoke aerosols. The
temperature at the HEPA filter is important for determining the extent of water condensation from the fire
exhaust. The HEPA filter-plugging studies suggest using the following approach to analyze the potential of
fires to plug HEPA filters.
With the design basis fire and its combustion products previously established, transport of the hot gases,
smoke particulates, and water vapor through the duct system must be established. The characteristics of the
combustion products penetrating the prefilter or demister must be determined next. This process will yield a
mass of smoke aerosols for comparison to a reference mass holding capacity for HEPA filters. The amount
of water condensing on the smoke deposits is determined from the temperature at the HEPA filters and from
the combustion water loading.
The nature of the aerosols has a major effect on plugging of all filters, including deep-bed sand (DBS) filters,
prefilters, and HEPA filters. Previous studies have shown that, in addition to the mass of the smoke aerosols,
the particle size and the state of the aerosol (liquid or solid) significantly affect HEPA filter clogging.
Figure 10.2 and Table 10.2 illustrate some of the effects of particulates on HEPA filters.
In related tests using rolling prefilters (the media roll advances through the test duct as it plugs),
Bergman et al.,15 showed that, once a fire and the ventilation system have reached the point where the smoke
generated can plug a HEPA filter, plugging can occur within 1 min, as seen in Figure 10.3. Tests 2 through 5
Section 15
showed that they were not
effective in protecting the
HEPA filter from plugging
until the prefilter efficiency
was a minimum of
90 percent for milli-µm
particles. Figure 10.4 shows
the efficiency for the
different filter media used in
the tests in Figure 10.3.
Test 5, with insufficient
media replacement in the
roll, illustrates how rapidly
the HEPA filter plugs when
directly exposed to the
proper aerosols. The
plugging potential of the
smoke aerosols is so great
that it dominates all other
parameters. Figure 10.2 – Aerosol Loading of HEPA Filters by Smoke from
Composite Cribs for the Different Conditions Shown in Table 10.2
(composite cribs consist of 40 percent wood, 14 percent PVC,
29 percent FRP, 9 percent PMMA, and 8 percent polycarbonate)16
DOE-HDBK -1169-2003 Chapter 10
10-15
Table 10.2 – Test Conditions for the HEPA Plugging Measurements in Figure 10.4 16
Test
HEPA Size
(cfm)
Exhaust Flow
(cfm)
Fuel Burn
Rate (g/min)
Smoke
Concentration
(g/m3)
Temperature at
HEPA (degrees
Celsius)
HEPA wt.
Gain (g)
B-44 1,000 500 3,000 6.4 65 470
B-20 500 500 1,200 4.8 86 —
B-38 500 1,000 3,000 8.6 105 574
B-52 (free burn) 500 500 1,500 7.6 70 106
B-53 500 1,000 1,680 8.4 110 550
Figure 10.5 shows an electron micrograph of
the aerosols generated from composite burns.
The deposits show the smoke aerosols were
liquid because of the drop-like spheroid
coating the fibers. The deposits have
solidified because any liquid would not have
remained in the high vacuum of the scanning
electron microscope. Filter plugging with
solid aerosols, as shown in Figure 10.6, does
not show the same rapid increase in pressure
drop as the liquid aerosols.16
Prior Filter Exposure that Impacts
Filter Response
Water Exposure. Water is an effective
method for reducing temperature, but HEPA
filters are not designed to operate when wet
and will suffer structural damage. The HEPA
filter medium is treated with
water-repellent chemicals. Tests
have shown a reduction in water
repellency effectiveness with each
wetting of the medium. The
tensile strength of the filter
medium can be reduced to failure
levels with as little as one wetting.
Figures 10.7 and 10.8 further
illustrate the relationships between
particulates, temperature, and
water-saturated air. A properly
designed fire suppression system
will include demisters to prevent
water from reaching functional
filters. HEPA filters exposed to
water should be replaced
immediately. HEPA filters that
potentially could be exposed to
water should be replaced within
5 years—immediately if actually
exposed.
Figure 10.3 – HEPA Filter Plugging by Smoke
Aerosols with Various Rolling Prefilters15
Figure 10.4 – Efficiency of Different Layers of Prefilters as a
Function of Particle Size. (Efficiency Values Refer to the
ASHRAE Dust Spot Efficiency.15)
Nuclear Air Cleaning Handbook U.S. Department of Energy
10-16
Other Filter Types
Not all filter types are as subject to the thermal and
combustibility effects as typical HEPA filters with
combustible media. Plugging from smoke particulates can
be a concern for all types of filters, however.
10.5.1.4 Effects on Physical Integrity of the
Confinement Ventilation System
Components
Fires external to the confinement ventilation system may
not only damage the HEPA filters inside the confinement
ventilation system, they also may damage the integrity of
the confinement ventilation system ductwork and
enclosures. If the confinement ventilation system ductwork
or enclosures are breached, some or all of the functionality
of the confinement ventilation system will be impaired.
This must be considered in the design of the physical
components and the fire suppression systems provided in
the facility.
Section 16
10.5.1.5 Effects of Wildland Fires
Although documented evidence is lacking, recent wildland
fire experience such as at the Cerro Grande fire in
Los Alamos in 2001 demonstrated the potential for smoke
to adversely affect confinement ventilation systems.
Facilities in areas where this type of event may occur are required to analyze the hazard in their authorization
basis documents. During the 2001 Cerro Grande fire, some confinement ventilation systems in facilities at
the Los Alamos National Laboratory were shut down to prevent the rupture of HEPA filters due to clogging
from smoke. Other external situations (such as volcanic eruptions or the dust from denuded landscapes) can
also create abnormally dusty conditions that cause clogging of prefilters and HEPA filters and present serious
threats to confinement ventilation systems. System
designers and operators should implement features that
minimize the probability of having to shut down
confinement ventilation systems in other than extreme
emergency situations. During emergency situations, if
the Incident Commander determines that a
confinement ventilation system has been breached and
radioactive material is being released, a decision should
be made whether to shut the confinement ventilation
system down completely or operate it in a manner that
would minimize the impact. These hazards may reveal
the need for additional safeguards, including but not
limited to, administrative controls of the removal of
natural vegetation and other combustibles near filter
inlets, installing smoke removal systems such as an
electrostatic precipitator prefilter or installing additional
filtration to preclude ingress of particulate into the
building. NFPA Standard 1144, Protection of Life and
Figure 10.5 – Scanning Electron
Micrograph of HEPA Filter Media
Loaded with Smoke Aerosols from
Composite Crib Fires. (Note: the
drop-like globules attached to the filter
fibers that suggest the liquid nature of
the aerosol)17
Figure 10.6 – Scanning Electron
Micrograph of Sodium Chloride Aerosols
on Glass Fiber Prefilter.18
DOE-HDBK -1169-2003 Chapter 10
10-17
Property from Wildfire,20 provides guidance on minimum defensible spaces around all buildings. High-hazard
facilities would be expected to have defensible spaces exceeding these minimum values.
10.5.2 Fires Occurring within Confinement Ventilation Systems
Fire may originate from sources within the confinement ventilation system (e.g., glovebox-sized operations
and small hot-cells). The effects of fires occurring within confinement ventilation systems, although similar
to those resulting from fires external to the confinement ventilation system, may be different and thus require
different controls.
Figure 10.8 – Rapid Filter Plugging Due to Moisture Deposition on
Particle-loaded HEPA Filters19
Figure 10.7 Illustration of Rapid Pressure Drop Increase with Water
Saturated Air 19
Nuclear Air Cleaning Handbook U.S. Department of Energy
10-18
10.5.2.1 Generation of Heat, Smoke, and Related Products
Fire events occurring inside a confinement ventilation system may appear in a number of physical forms.
Fire may occur in ordinary combustible material. The amount of combustible material within a confinement
ventilation system generally would not be as much as in a larger room, so the fire growth characteristics may
be somewhat altered.
Section 17
Fire may occur in the radioactive materials in a confinement ventilation system, or a fire involving ordinary
combustibles may subsequently involve radioactive materials. A fire involving a flammable liquid or gas used
inside a confinement ventilation system also may occur. These events may take the form of a flame front
moving rapidly through a flammable vapor, a flame front moving rapidly enough to deflagrate and produce
some overpressure, or even a detonation if the conditions for such phenomena exist.
Filter fires can occur due to either decomposition of combustible dust deposits within the filter, organic
decomposition of chemical residue carried by the airstream from upstream processes, or spark/ember
introduction from an upstream source. While introducing a water spray within or prior to the duct inlet can
prevent the latter condition, fires originating at the filter itself cannot be satisfactorily mitigated by automatic
suppression methods. Consequently, reliance is placed on the manual deluge system and fire department
response.
Industrial and institutional loss experience has shown that over a period of time even “office dust”
accumulations can form highly combustible residues on filters that are sufficient to cause damage if ignited.
It also has been established that the concentration of these fuels need not be high to cause severe damage due
to the fragility of the media. Fire-retardant chemical preparations for the filter media may initially make
ignition difficult, particularly on clean media. However, this retardant material tends to become less effective
over time and does nothing to retard or reduce the combustibility of dust or residue deposits from the
airstream itself.
Administrative controls and alarm interlocks are designed to alert operators about impending change-out
intervals that have been established to maintain dust or residue inventories below radiological actions points.
It is not feasible, however, to eliminate the potential for direct filter fires or to practically reduce residue levels
below those that may damage the filter itself.
10.5.2.2 Transport of Heat, Smoke, and Related Products
The transport of hot gases, smoke, water vapor, and chemicals from an internal fire through a confinement
ventilation system can be modeled in much the same way as is done for an external fire. A fire occurring
within the confinement ventilation system may affect the transport mechanism by altering the airflow through
the system more than an external fire.
The transport mechanism also may be affected if the actual structural confinement barrier of the confinement
ventilation system is involved in the fire and is contributing to its spread. The accumulation of dust and
debris inside the air cleaning system ductwork over long periods of operation provides a mechanism for
transporting flames from an ignition source to the filters, and also can produce soot that can clog filters in a
fire.
10.5.2.3 Effects on Filters of Heat, Smoke, and Related Products
The effects of the products of combustion reaching the HEPA filters are the same for internal and external
fires. The same physical parameters affect the manner in which the filters are threatened.
DOE-HDBK -1169-2003 Chapter 10
10-19
10.6 Fire Hazard Controls and Design Features
10.6.1 Objectives and Requirements
There are three major objectives for fire protection of confinement ventilation system:
• To prevent fires from affecting the operation of the ventilation system;
Section 18
• To protect the filtration function; and
• To prevent the release of material that has accumulated on filters.
General Requirements
General requirements for the control of fire hazards that may affect the confinement ventilation system are
formalized in NFPA Standards 90109 and 801, Fire Protection for Facilities Handling Radioactive Materials,21 DOE
Order 420.1A,9 and DOE Standard 1066-99.1
Special hazards may cause exposure of the filters to the following: highly combustible dust loading;
pyrophoric materials; chemically reactive, explosive, or corrosive vapors; or high-moisture conditions that
may cause rapid degradation of HEPA filters. These should be evaluated on a case-by-case basis by a fire
protection engineer who understands the process sufficiently to determine the protection warranted.
A comprehensive fire protection scheme for filter housings will include the following principles:
• The ventilation system filter housing construction materials should be noncombustible.
• Process hazards inside and outside the ventilation filter housings should be controlled.
• General area sprinklers should be provided within all process areas.
• The final filter housing should be separated from the general building area by fire-rated construction.
• Automatic water spray should be installed upstream of a demister and before the first-stage filters.
• Manual water spray should be installed at the first-stage HEPA filter.
• Fire detection systems should be installed in the final filter housing to allow early warning and activation
of the extinguishing systems.
• Automatic flammable gas detection should be provided in filter housings where flammable or
combustible processes are performed.
The FHA for a confinement ventilation system may indicate the need for further fire protection measures.
Nuclear Air Cleaning Handbook U.S. Department of Energy
10-20
10.6.2 General Fire Hazard Control Features
10.6.2.1 Fuel Control
The flammability of materials must be considered in designing the confinement ventilation system. This is a
first line of defense against fire, without which any ignition will lead to a dangerous situation.
The NFPA Standards and DOE fire protection requirements provide guidance on how to do this. The FHA
also should address the issue of materials flammability.
If the process involves the presence of flammable vapors or liquids, the allowable concentration of flammable
vapors inside the filter enclosure must be limited and controlled. The maximum permissible concentration
(MPC) of flammable vapors is 25 percent of the lower flammable limit.
Control of Energy Sources
Ignition sources inside the filter enclosures must be limited to those necessary for operating the system.
Electrical systems must be installed in accordance with NFPA 70, the National Electrical Code.22 The presence
of flammable gases or vapors in the operation of the confinement ventilation system will require specialized
electrical equipment to prevent their ignition.
Section 19
A number of flame-producing incidents have occurred while using aerosol generating devices (sometimes
used in filter testing). Most of these incidents involved replacement aerosols with a lower auto-ignition
temperature than dioxytl phithalate (DOP). In one incident, the aerosol liquid flow through the heater was
initiated prior to establishing carrier airflow as recommended by the manufacturer. It ignited, shooting a
flame of several feet from the discharge port. Fortunately there were no injuries, and equipment damage was
limited to scorched insulation. The manufacturer modified the aerosol generator to reduce the heater block
set point below the auto-ignition temperature of the polyalphaolefin (PAO) being used, and the air valve was
modified to maintain minimal flow with the valve closed. Some generators use inert gas instead of air, but
this does not always avoid ignition. While shutting down a generator, the operator heard a loud “pop” and
observed smoke from the generator. An investigation revealed that flames were produced if the nitrogen
flow was interrupted before the aerosol liquid flow was shut off. A safety cover was installed to prevent
inadvertently shutting off the nitrogen switch, and the hose adapter was modified to preclude flaming if
nitrogen was lost. In another incident, several discharge hoses erupted in flame when the generator ran out
of aerosol liquid and the operators refilled the generator without deactivating it, allowing air to enter the
system. Neither the manufacturer’s instructions nor the operating procedure cautioned against this. The
aerosol generators used are not approved by either Factory Mutual (FM) Global or UL to verify the safety for
the intended use.
Challenge aerosols are not interchangeable. A new hazard analysis should be performed if the aerosol is
changed. Equipment tolerances and emergency cut-outs should be evaluated. The manufacturer should be
consulted. Training must emphasize procedural control, particularly valve sequencing. Critical warnings
should be included in the operating procedures and on the instrument. Where valve sequencing is the only
barrier preventing ignition, instruments should be replaced or modified by the manufacturer to make
improper sequencing impossible.
Controlling Oxygen
Some operations use atmospheres inerted with nitrogen or argon as a flammability control. This is discussed
for specific situations later in this section.
DOE-HDBK -1169-2003 Chapter 10
10-21
10.6.2.2 Passive Design Features and Fire Hazard Controls
Duct Runs
The design of the duct runs can greatly influence the effect of a fire in the facility or within the ductwork on
the ability of the confinement ventilation system to perform its function. This section will address the
physical configuration aspects of the ducts and filter housings. Ductwork and related equipment are required
to comply with the criteria of NFPA 90A10, Installation of Air Conditioning and Ventilation Systems and NFPA 91,
Standard for Exhaust Systems for Air Conveying of Vapors, Gases, Mists, and Noncombustible Particulate Solids.23 These
standards provide explicit requirements for integrating the ventilation system with the building construction,
as well as operational guidance for systems inspection, cleaning, and maintenance. Other sections address the
active fire protection or cooling systems that may be needed to maintain confinement ventilation system
functionality.
Section 20
Another significant consideration in the design and layout of an air cleaning system is provision of separate
systems for each building fire area. Buildings are subdivided into discrete fire areas to limit fire damage to
only one area. If fire area boundaries are penetrated to allow passage of the air cleaning ducts, the possibility
of fire spreading to multiple fire areas is introduced, potentially resulting in much more extensive fire damage.
Duct Response to Fire
There may be situations where fire dampers cannot be installed at firewall duct penetrations because of the
need to maintain confinement ventilation. In some cases, ducting may traverse other fire areas before
reaching the filter banks. The quality of the duct construction and installation are the most important factors
in maintaining the integrity of the ducting. A number of factors need to be considered:
• Where the duct penetrates a firewall, distortion during a fire may allow flames to pass through the wall
around the outside the duct. Investigators24, 25 performed full-scale fire testing that provided insight into
the performance of reinforced ducting under limited fire exposures.
• Conductive heat transfer through the duct may ignite combustible materials in adjacent fire areas. This
can be mitigated by insulating or enclosing the duct as determined by the FHA.
• Duct collapse can occur due to weakening of the duct or the hangers when heated. Additional hangers
and/or reinforcement will mitigate this potential problem.
• Where there are duct openings in a nonfire space, the FHA should consider the potential for fire spread
and the need for additional safeguards.
Air Supply and Extraction
The method of air supply and extraction profoundly influences the efficiency with which a fire burns. Most
gloveboxes are designed so that the air supply enters at the bottom on one side of the box and exits at the top
on the other side. This design ensures that a vigorous fire will persist so long as fuel and air are available. If,
the ventilation pattern is reversed and air enters at the top of the box and exits at the bottom, however,
combustion products will mix with the supply air to weaken and ultimately extinguish the fire. This tactic is
effective for all but very large enclosures.
Entrance Filters
Because the duct-entrance filter is the major dust collector, it is also the primary component in which a fire
could occur. Protection of the HEPA filter downstream from sparks and burning fragments from the
Nuclear Air Cleaning Handbook U.S. Department of Energy
10-22
duct-entrance filter may be needed if the distance between them is not great. If it is less than 20 to 30 feet, a
fine (20 to 30 mesh) screen may be installed downstream of the duct-entrance filter (such screens must be
located where they are convenient for periodic cleaning). Because lint tends to bridge the openings, screens,
and coarse filters (e.g., furnace filters), installation of fine-mesh screens on the face of the duct-entrance filter
is not recommended; however, this does not preclude installation of a mesh screen for physical protection of
the filter. For glovebox and hot cell applications, the duct-entrance filter should be designed for withdrawal
into and replacement from the contained space. The filter should also be afforded maximum protection
against the effects of or ignition by a fire in the contained space.
Prefilters
Section 21
Prefilters are usually provided in the central filter house in addition to or instead of duct-entrance filters.
Again, fire is more likely to occur in the prefilter than in the HEPA filter downstream. Prefilters should
never be mounted directly on the face of the HEPA filter or on the opposite side of a common mounting
frame with the HEPA filter (i.e., back to back). A spacing of at least 36 inches between the downstream face
of the prefilter and the upstream face of the HEPA filter is recommended—not only for maintainability, but
also to provide space where burning fragments and sparks can burn out or settle to the floor of the filter
house.
Filter Housings
HEPA filter housings should be protected from facility fires by fire-rated construction. High temperatures in
exhaust filter housings can be minimized by long runs of duct preceding the housings, by intake of dilution
air from streams from other contained or occupied spaces of the building, or by cooling the outside of the
duct with water spray. Cooling via water spray installed inside the duct has been employed in some
applications (discussed in Section 10.6.2.3). The intent is to place the HEPA filters where they are least likely
to be exposed to heat, hot sparks, and burning embers from a potential fire in the process line.
Fire Screens
A fire screen is a noncombustible sheet of meshed metal similar to a roughing filter that is intended to reduce
the potential for transporting glowing embers/burning brands through the airstream from the fire source to
the filter banks. The screen should be installed upstream from the prefilter(s) and ahead of the filter
housings. Specific design criteria for fire screens can be found in DOE Standard 1066-99.1
Materials
Ideally, all construction materials used in confinement ventilation system enclosures should be
noncombustible. Use of noncombustible materials for the enclosure will help limit the total amount of fuel
available to burn if a fire occurs. If suitable noncombustible materials cannot be used because of process,
shielding, corrosion-resistance, or other special purpose requirements, attempts should be made to minimize
the quantity and surface area of the installed combustible materials. If a combustible duct material is utilized,
installation of automatic sprinklers may be required according to DOE, NFPA, or FM Global requirements.
The preferred construction materials for ductwork are steel, stainless steel, or galvanized steel. If fiberglass
ductwork is needed because of corrosion issues, special ductwork that meets the flame-spread criteria in
NFPA 90A10 is required. Acoustic linings or duct silencing materials are combustible and are not permitted
inside air cleaning system ductwork.
DOE-HDBK -1169-2003 Chapter 10
10-23
Filter Construction
Wood is frequently used for HEPA filter casings. For this application, the wood is required to have
undergone a fire retardant treatment that results in a flame spread of 25 or less and a smoke-developed rating
of 50 or less when tested to American Society for Testing and Materials (ASTM) Standard E-84.26 This test
measures the speed at which flames will travel across the surface of the material being tested. As a
comparison, the flame spread of red oak boards is 100, while the flame spread of concrete or unpainted steel
is zero. Thus, even with the fire retardant treatment, wooden filter frames will burn in a sufficiently severe
exposure fire.
Section 22
Duct entrances and prefilters are required to be classified as Class 1 Air Filter units in accordance with UL
Standard 900.14 This is a different test method than is used for HEPA filters and is intended to evaluate the
combustibility and amount of smoke generated for air filter units of both washable and throwaway types
when they are clean. Class 1 filters, when exposed to flames, do not contribute fuel to the fire and will emit
only limited quantities of smoke. Class 2 Filters burn moderately and emit moderate amounts of smoke.
Either filter class will burn vigorously if it becomes dust loaded.
Fire Barriers
HEPA filter housings located within nuclear or hazardous process buildings are required to be separated
from the remainder of the building by a minimum of 2-hour-rated fire barriers. This requirement is intended
to ensure HEPA filters are protected from fires occurring in the process building. One common type of
2-hour-rated barrier is constructed of 8-inch-thick concrete block walls and a poured concrete ceiling.
Another way to provide this level of protection is to locate the filter housing outside of the process building.
If the filter housing is located in a separate building, no specialized fire barriers are necessary, provided the
housing is located at least 20 feet from the process buildings and the exterior walls of the buildings have no
unprotected openings. If the filter housing is located less than 20 feet but more than 5 feet from the process
building, the filter housing is required to be constructed as a 1-hour-rated fire barrier. Filter housings are
required to be installed in 2-hour-rated firewalls if they are less than 5 feet from the process buildings.
Small filter housings, which have a leading-edge surface area of 16 square feet or less, are not required to be
separated from the rest of the building, provided the building has area-wide automatic sprinklers and the
housing has an internal fire suppression system.
Penetrations through the air cleaning system enclosure fire barriers are only permitted for services necessary
to the operation of the filtering system. Where penetrations cannot be avoided, the openings created through
the fire barrier must be properly sealed with approved, fire-rated, noncombustible penetration seal materials.
Penetration seals are tested and approved under the requirements of ASTM E-814, Fire Tests of Through
Penetration Fire Stops.27 The penetration seals must also be compatible with and capable of continued exposure
to the types of materials and atmospheres present inside the filter enclosure. Doors in 2-hour-rated
enclosures are required to be Class B fire door assemblies. Doors in 1-hour-rated enclosures are required to
be Class C fire door assemblies. The requirements for construction and installation of fire doors are found in
NFPA 80, Fire Doors and Windows.28 HVAC ducts that penetrate 2-hour-rated enclosures must be protected
with UL-listed fire dampers. HVAC ducts that penetrate 1-hour-rated enclosures are not required to have
fire dampers. In some cases, it is necessary for ductwork that is part of the nuclear air cleaning system to
penetrate fire-rated barriers. Fire dampers cannot be installed in these ducts because their operation during a
fire would cause the dampers to close, sealing off the ductwork. This would prevent the filtration system
from continuing to operate. Because the air cleaning system is required to be functional at all times, an
alternative method of fire protection must be provided. It is recommended that a fire protection engineer be
consulted to evaluate such configurations on a case-by-case basis. [Note: DOE has granted an exemption on
the use of fire dampers for certain configurations of ductwork in an existing building where alterations would
have been difficult due to highly contaminated conditions.] Each of the above features requires the design to
Section 23
Nuclear Air Cleaning Handbook U.S. Department of Energy
10-24
be adjusted to the process under consideration. When changes are made to the process, each of the design
features needs to be reviewed to ensure that nothing has been introduced that would make the fire system
ineffective.
10.6.2.3 Active Design Features and Fire Hazard Controls
One of the goals of the nuclear industry has been to provide gloveboxes, caves, canyons, hot cells, fume
hoods, and other radiological confinement areas with practical ventilation exhaust systems that can remain in
service through a fire and can contain all the radioactive contamination made airborne by the fire. It has been
established by both consensus standards and industry/government regulations that ventilation components in
nuclear air cleaning systems should continue to perform their safety functions effectively under all conditions
by confining radioactive or other potentially dangerous materials. To realize this for fire protection purposes,
it is necessary to protect the filter housing in the exhaust system from heat, smoke, and burning material that
would be generated during a fire scenario. In the event of fire, the release of contaminated smoke through a
ruptured or damaged filter housing may have more serious consequences than any potential casualty losses
from the fire itself.
Fire Dampers
Fire dampers in ductwork penetrating fire-rated construction should not be utilized in confinement
ventilation systems with the following design features: (1) where the ducting is a integral part of the nuclear
air filter system, and (2) where equipment is required to continuously function. Such duct material
penetration of fire-rated construction without fire dampers should: (1) be made part of the fire-rated
construction by either wrapping, spraying, or enclosing the duct with an approved material, or by other means
of separating the duct material from other parts of the building with equivalent required fire-rated
construction by either wrapping, spraying, or enclosing the duct with an approved material; or (2) be qualified
by an engineering analysis for a 2-hour fire-rated exposure to the duct at the penetration location where the
duct maintains integrity at the duct penetration with no flame penetration through the fire wall after a 2-hour
fire exposure. 21
Fire Detection Systems
Detection equipment for early warning of fire conditions must be provided in all HEPA filter housings. Rate
anticipation heat detectors are most commonly used because of their good stability, low maintenance
requirements, and relatively quick response to heat.
Sampling types of smoke detection systems has been suggested as a means to provide early warning, however,
precautions must be taken to ensure they do not provide a leak path that bypasses the filters.
Alternative fire detection methods are possible depending on the specific design of the filter enclosure. If
flammable liquids or gases are used and the possibility of explosion exists, rapid detection using flame
detection devices may be needed.
NFPA Standard 7229 provides the requirements for the installation of fire detection devices and systems.
Automatic Fire Suppression Systems
Prior to the Brown’s Ferry nuclear power plant fire in 1975, the use of water on electrical fires was not
considered a safe practice by the nuclear power industry. Following the Brown’s Ferry fire (see NRC
NUREG-0050, Recommendations Related to the Brown’s Ferry Fire),30 in Factory Mutual (now FM Global) and
other organizations performed studies to test the use of water in electrical spaces (see Electric Power
Section 24
DOE-HDBK -1169-2003 Chapter 10
10-25
Research Institute (EPRI) NP-188131 and EPRI NP-2660).32 In addition, Sandia National Laboratories
(SNL) performed tests on cable tray protection schemes (see NRC NUREG/CR-2377,33 NUREG/CR-
2607,34 and NUREG/CR-3656).35 These studies by Factory Mutual and other organizations showed that
fighting fires in grouped cables could be accomplished efficiently using water (these tests were done on
unenergized electrical cables, however, the conclusions on the use of water as an efficient extinguishing agent
were confirmed). Following the Brown’s Ferry fire and the tests performed by Factory Mutual, SNL, and
others, the inhibition against using water to put out fires in all spaces with electrical equipment seemed to
subside, and fire protection engineers made more deliberate assessments of the type of electrical occupancy
when considering use of water as a fire suppressant.36, 37
Automatic fire suppression systems throughout a facility will control a fire in its early stages of growth, thus
mitigating fire effects that could affect the functionality of the confinement ventilation system. Wet pipe
sprinkler systems are the most common type of automatic fire suppression system and have a proven
experience record of fire extinguishment. Other types exist and are described further in this section.
Activation of a suppression system will extinguish an incipient fire and automatically alert dispatchers or the
fire department.
Consideration must be given during the design phase to testing and maintenance of fire suppression and fire
detection systems throughout the life of the system/facility. Consideration also must be given to avoiding
interference with or inhibition of the safety function of other safety features (i.e., water addition/criticality
controls, HEPA filters, etc.).
Wet Pipe Sprinkler Systems
Wet pipe sprinkler systems are used to control the fire potential in the areas being exhausted by the
confinement ventilation system. They will control the fire to limit the threat to the facility and the HEPA
filters, and also will prevent physical fire damage to the ductwork of the confinement ventilation system.
The need for wet pipe sprinkler protection is established by DOE or NRC requirements, or the FHA. The
design requirements for these systems are contained in NFPA Standard 13, Installation Of Sprinkler Systems.38
Deluge and Water Spray Systems
A deluge sprinkler system is one in which the sprinklers are normally open and water flow is controlled by a
valve in the line leading to the sprinkler heads. When this valve is opened, water is discharged from all the
open sprinklers at the same time.
Two types of deluge systems are required for protection of HEPA filter housings. The first type,
automatically-actuated deluge systems, are located upstream of the demisters. This type of system is also
called a water curtain, as it consists of closely spaced, open-head, deluge nozzles connected to piping located
in front of and above the demisters. When the system is activated, all of the nozzles spray water
simultaneously downward, forming a wall of water. This system is intended to cool incoming air, hot sparks,
and flames before the prefilters are threatened. The water curtain is located upstream of the demisters so the
water spray carryover can be diverted to prevent moisture from reaching the downstream HEPA filters.
Section 25
Operation of an automatic deluge spray system is initiated by a fire detection system located in the ducting—
usually heat detectors. The detection system opens a deluge valve, allowing water flow to the nozzles. The
spray nozzles are either open sprinkler heads from which the fusible link has been removed or special
purpose nozzles designed to produce a particular pattern. The automatic system is also equipped with a
locked bypass valve that can be manually opened if the detection system or the deluge valve fail to operate.
Closed-head pilot sprinklers are sometimes used in place of an electrically-operated heat detection system to
Nuclear Air Cleaning Handbook U.S. Department of Energy
10-26
open the deluge valve to the nozzles. In this case, the pilot sprinklers serve only as temperature sensors and
do not spray water.
Fires produce smoke that can cause rapid clogging of filters. Because the automatic spray deluge system
functions much like the scrubbers that are used to clean smoke stack exhaust, there is an expectation that the
automatic system may also reduce smoke clogging. However, the nozzles are not optimized for smoke
reduction. In limited research with spray nozzles, it was found that smoke clogging decreased in some cases,
but increased in others. Therefore, premature manual activation of the spray deluge system to reduce smoke
is not recommended without further research to quantify results for specific arrangements and combustible
contents. Operational procedures such as shutting down or throttling back the blowers to prevent rupture of
clogged filters during a fire should be addressed in the authorization basis documents. The generic
operational procedures provided here resulted from studies at a DOE site and are applicable to the
procedures at most sites. Use of these procedures should be preceded by a thorough design review to ensure
their specific applicability.
Demisters must be installed between the automatic spray nozzles and the HEPA filters. Demisters are
specially configured metal panels that redirect the water droplet trajectory toward the floor of the enclosure.
Performance criteria for demisters are contained elsewhere in this handbook. The demisters must be
positioned at least 3 feet upstream of the HEPA filters, and approximately 6 inches downstream of the
automatic deluge nozzles.
The second type of deluge system is a manual deluge spray system. This system is operated only if the filters
begin to burn because it discharges water directly onto the first filter system. Burning cannot only breach the
filters, but may also release particulate that has accumulated on the filters over time. Facilities without this
manual system must rely on firefighters to attack HEPA filter fires with hose streams. The manual deluge
system is intended to avoid unnecessary exposure of firefighters who must otherwise enter the hazardous
environment within the housing, and also to ensure a more gentle application of water to make it possible for
some filter stages to survive. The manual control valve for the manual deluge spray system is normally locked
in the closed position and only accessible to firefighters. Fire department training programs should address
operating procedures for these valves.
The potential for nozzle plugging or corrosion in housing deluge systems should be considered during design.
Potential remedies include, but are not limited to, strainers, blow-off caps, and corrosion control measures
such as use of special corrosion-resistant materials or coatings.
Section 26
The automatic extinguishing systems must be designed to comply with the requirements of NFPA 1338 and
NFPA 15, Water Spray Fixed Systems For Fire Protection.39 These standards provide the requirements for
designing the system and selecting components, as well as associated installation requirements. Research
conducted by Dow Chemical Company following the 1969 filter housing fire at Rocky Flats determined that
the minimum water supply for the system must be hydraulically calculated to provide at least 0.25 gpm/ft2
over the entire face area of the filters, or 1 gpm per 500 cfm of airflow, whichever is greater. The water
curtain must be located 6 in. before the demisters. Standard deluge-type sprinkler heads must be installed on
the piping at a minimum spacing of 4-foot intervals. The system must be activated by the rate-compensated
heat detection system or by pilot-operated sprinklers. A manually operated release must also be installed on
the deluge valve in the event a malfunction in the releasing system occurs. The use of corrosion-resistant
deluge heads and piping should be considered for all installations.
Water Mist Systems
New watermist technologies are being developed that use fine water sprays to efficiently control, suppress, or
extinguish fire using limited volumes of water. Their suitability for use in confinement ventilation systems
has not been demonstrated at this time (refer to NFPA 750, Standard on Water Mist Fire Protection Systems).40
DOE-HDBK -1169-2003 Chapter 10
10-27
Sprinklers within Ductwork
Provision of wet-pipe sprinkler systems within ducts or filter housings is the exception rather than the rule,
however, deluge sprinkler systems are routinely provided on carbon-filled adsorption systems in nuclear
power reactors. On deluge systems for adsorption filters, fog nozzles with as fine a droplet-size distribution
as possible are recommended for maximum cooling and smoke-particle capture. To limit the volume of
water discharged, consideration should be given to an automatic recycling deluge system.
Demisters and HEPA Filters
Water protection for HEPA filters has been controversial due to concerns about water plugging of the filters.
The research that led to this concern was based on conditions that are not reflected in an actual filter
installation. Specifically, the research involved soaking filters in pans of water. However, in a properly
designed confinement ventilation system, demisters prevent water from the automatic deluge system from
reaching the filters. Manual deluge systems are only operated after the filters begin to burn. Consequently,
water damage is no longer an issue. This topic is further discussed in DOE Standard 1066-99.1
Fire Department Standpipe Systems
Because the possibility of a fire that can affect the filters cannot be entirely eliminated; some provision for
manual fire fighting using a standpipe system (meeting the requirements of NFPA 14 Standard for the Design
and Installation of Standpipe and Hose Systems 41 is necessary. The fire department will almost always use its own
hose packs.
The use of a hose stream can only be considered when all other automatic and manual safeguards have been
determined to fail. Filters cannot be saved, but hose streams may prevent fire spread to subsequent stages of
filters and avoid failure of the final filter stage that could release contamination. In addition, a hose stream
can serve to prevent further damage to the filter mounting frames and housing, the duct, or the building.
Similar observations can be made for the common types of sprinkler systems, both automatic and manually
actuated, if they are installed inside the filter housing.
Section 27
Water Runoff Collection
Facilities protected by sprinklers or deluge systems must have a provision to collect and dispose of water used
for fire extinguishing. In addition, design of the water drainage system has to be consistent with the
characteristic of water as a neutron moderator.
Gaseous Agent Systems
Some spaces external to the ductwork of ventilation systems are protected with gaseous agent fire
suppression systems. There are NFPA standards for the design of these systems that include Halon
alternatives and carbon dioxide systems. Competent technical persons should be consulted to design these
systems.
Flammable Gas Detection
If flammable gases are used, the FHA may require flammable gas detection equipment in the ductwork or
filter housings. The installed gas detectors must be connected to an alarm system located at a continuously
attended position to ensure immediate corrective actions are taken if high flammable vapor concentrations
are detected. The effective design of systems to detect flammable gases depends on the gases themselves, the
airflow characteristics within the confinement ventilation system, the actions that must be taken in response
to unacceptable concentrations of flammable gases, and many other factors. Systems that do not adequately
Nuclear Air Cleaning Handbook U.S. Department of Energy
10-28
address the issues may either not work at all or will provide false alarms on a frequent basis which can be an
equally bad situation. Competent technical persons who are knowledgeable of the hazards present and the
design of such systems should be consulted to design these systems.
Protection of Carbon-Filled Adsorption Systems
To prevent loss of confinement for radioactive iodine and iodine compounds, carbon-bed temperatures must
be maintained at a level where impregnants and trapped radioiodine cannot desorb. This requires the bed(s)
to be large enough that specific loadings of iodine cannot exceed 2.5 mg/g of carbon, and that airflow
through the bed can be maintained at some level in excess of 6 (preferably 10) linear fpm. If bed
temperatures can be maintained below the level where desorption of impregnants and trapped radioiodine
takes place, carbon ignition is unlikely. If a fire should start, however, total flooding or dumping of the
carbon into a container of water is the only effective means of extinguishing a carbon bed fire that is known
at this time. Carbon dioxide and gaseous nitrogen are ineffective against activated carbon fires because the
fire feeds on the oxygen adsorbed in the pores of the carbon, and the quantity of liquid nitrogen required to
provide effective cooling would be unavailable in most cases.
Combustible Metals
Metal fires, particularly fires in water-reactive metals such as sodium, present special problems. Water and
inerting agents such as Halon alternatives cannot be used, and inert atmospheres such as nitrogen and carbon
dioxide require practically the total exclusion of oxygen to be effective. The fire must be treated in the
operating space before it can reach the ducts or filters, which requires an effective duct entrance filter,
preferably one of the HEPA type if the metal dusts are finely divided. However, most of the fire-
extinguishing agents that are effective against such fires produce copious clouds of dust that, when released,
rapidly threaten to plug the duct entrance filter. This in turn threatens overpressurization of the glovebox or
hot cell, resulting in blowback of contamination to occupied spaces of the building. Carbon microspheres5
have been shown to be extremely effective against plutonium, sodium, uranium, sodium-potassium,
magnesium, aluminum, lithium, and other types of fire that produce intense heat. The material can be
dispensed automatically or manually and produces essentially no dust when dispensed either way. In addition,
it has negligible chloride content (and so poses no threat to stainless steel equipment and cells), is very easy to
cleanup, is inexpensive, and is readily available.
Section 28
When combustible metals are being processed, the potential presence of combustible dusts in both the
airstream and inside the filter enclosure should be considered in the FHA. Appropriate hazard controls
should be provided as necessary (duct-entrance filters alone will not prevent dust from entering the ducting).
10.6.2.4 Discussion of Other Filter Types
Small Filter Assemblies in Plywood Enclosures
Some smaller HEPA filter assemblies are purchased as a single package. These are often self-contained in
assemblies constructed of plywood or other wooden composite material. These assemblies have male duct
connections on their inlet and discharge sides, and are easily dropped into place by clamping existing ducts
onto them. Given the lack of fire resistive properties of these filter assemblies, it is not recommended that
they be used in new construction.
High-Efficiency Metal Fiber Filter Systems
High-efficiency metal fiber (HEMF) filter systems have only been commercially available in the United States
since the mid-1980s. They are made of sintered stainless steel fibers that are welded into steel housings and
DOE-HDBK -1169-2003 Chapter 10
10-29
steel frames. These filters have been used in small, specialized exhaust systems, but have not yet been
sufficiently developed to be equivalent to HEPA filters.
In contrast to HEPA filters, HEMF filters are not weakened by moisture impingement. They can also
operate for longer time periods and in hotter conditions than HEPA filters because the metal filters contain
no flammable components, and are inherently resistant to high temperatures. However, the finely divided
filter media in a metal filter will not resist a direct flame impingement. The resistance of the metal filter to
moisture and heat makes this filter attractive for fire protection purposes. Because the use of HEMF filters is
relatively new to the DOE community, only limited experiential data on the behavior of these filters in actual
fires is available. They are also very expensive to purchase and operate.
Radioiodine Absorber Air Cleaning Systems
Although much discussion in the nuclear community has been generated in the past 40 years regarding fire
protection of absorbers, little consensus and few conclusions have been reached about the proper method of
extinguishing fires in absorbers with combustible material. Available methods include: (1) using a
combination of manual and automatic water spray systems, (2) limiting airflow to the absorbers, and (3) using
alternative noncombustible absorber media (e.g., silver zeolite). Absorber air cleaning systems are often used
in nuclear reactor emergency ventilation confinement systems where they are frequently referred to as
charcoal- or carbon-type filters. Other inorganic absorber materials are available for absorber media,
including silver oxide, silver nitrate, aluminum silicate, and silver zeolite. It is generally accepted that, as a
minimum, absorbers should be provided with fire detection equipment.
For carbon-type filters, American Nuclear Insurers, an insurance carrier for nuclear power plants,
recommends the following fire protection:
• Charcoal filters should have a hydraulically designed, automatic water spray system that uses directional,
solid-cone spray nozzles controlled by an approved deluge valve. The system should be capable of being
manually actuated from a suitably remote location.
Section 29
• Spray nozzles for horizontal beds or drawers should be oriented above each bed or drawer and should be
designed to distribute water evenly across the top of each bed or drawer at a minimum density of
0.25 gpm/ft2.
• Spray nozzles for vertical beds should be oriented at the top of the bed and should be designed to
distribute water evenly across the top of the bed at the rate of 3.2 gpm/ft2 of charcoal bed.
• A supervised, fixed-temperature detection system should be provided and connected to an annunciator in
the control room. The detectors should be located on the downstream side of the charcoal bed to
facilitate timely, automatic operation of the spray systems. The spray system should be equipped with a
local alarm and should be connected to an annunciator in the control room. The airflow should
terminate (with the fan shut off) upon water activation.
• For the pressure vessel-type charcoal filter, where a shut-off bypass arrangement is employed around
each tank, an automatic water spray system is not required. A hose connection should be available on the
side of the tank to allow the introduction of water.
Deep-Bed Fiberglass Filter Systems
Early designs of deep -bed, fiberglass filters did not address filter media replacement. Fiberglass filters plug
over time, resulting in combustible deposits that may contribute to fire risk. It is generally accepted that
water applied to this type of filter media will extinguish the fire. Precautions should be taken when water is
Nuclear Air Cleaning Handbook U.S. Department of Energy
10-30
applied to filter media containing radioactive material to prevent the water from being released to the
environment.
Deep-Bed Sand (DBS) Filter Systems
For the most part, DBS filters are fire-resistant, chemically inert, and require no special fire protection
systems. Sand filters are usually accompanied by HEPA filters. When a sand filter is used in series with a
HEPA filter, it should be upstream of the HEPA filter. In this position, the sand filter can protect the HEPA
filter that provides the final confinement barrier. However, HEPAs have been traditionally installed prior to
the sand filters for fear of sand fires carrying over and plugging the HEPAs.
Since plugging is a “worst case” scenario for both HEPA and DBS filter arrangements, both require
mitigation measures. It has been largely accepted that DBS filters, while expensive to construct,
decontaminate, and demolish, offer improved performance in their ability to operate in the presence of heat
and fire products. However, no quantitative test results have been found to confirm that a DBS filtration
system can withstand plugging by smoke particulates. While it has been empirically shown that DBS filters
can resist high heat conditions, and some qualitative testing has shown a high degree of resistance to plugging
compared to HEPA filters, this does not confirm how many particulates can be absorbed and the rate or
conditions under which a DBS arrangement can operate without loss of efficiency. Indeed, DOE reports to
this point are largely historical rather than experimental in nature. Tests on the physical properties of smoke
and its effect on DBS filters need to be performed to establish obstruction limits for DBS filters.
Self-Cleaning Viscous Liquid Filters
This type of filter uses a viscous liquid for cleaning purposes. These filters should be avoided where
radioactive materials are handled because they produce radioactive sludge that requires disposal. They also
require special fire protection systems because of the combustible nature of the liquid.
Section 30
Moving-Curtain Single-Pass Rolling Prefilters
One noteworthy type of prefilter is the moving-curtain single-pass rolling prefilter. This type of prefilter
involves manually or automatically feeding a fresh filter media across the face of the filter frame while the
dirty media is rewound onto a take-up roll. When the roll is exhausted, the takeup media is disposed of and a
new media roll is installed. In 1980, LLNL performed fire tests involving this type of prefilter utilizing a
modified commercial moving-curtain filter. The purpose of testing this type of filter was to find a way to
limit or eliminate the smoke that may be produced in a fire, thus reducing the potential for the smoke to plug
the HEPA filters. The tests validated that the moving-curtain single-pass rolling prefilter could reduce the
potential for aerosol plugging of HEPA filters during a fire. The final test report stated that prefilters of this
type were an “experimental prototype.” Those considering this type of design should obtain a copy of the
report and review the basis of the conclusions as they apply to a particular case.
Electrostatic Precipitator Prefilter
Another type of prefilter used at DOE facilities is the electrostatic precipitator (ESP) prefilter. This prefilter
imparts an electrical charge to particles in the airflow stream, causing them to adhere to collector plates. The
ESP prefilter has been used to extend the life of HEPA filters when processes involve larger-diameter airflow
particles. An ESP prefilter provides some fire protection, as long as the particles resulting from the
combustion products of a fire can be properly collected on the filter throughout the fire. Most commercially
available ESP prefilters cannot catch the smaller airborne particles and smoke particles associated with a
burning fire. However, more work needs to be done to understand which particle sizes associated with fire
can be effectively filtered by an ESP prefilter. When ESP prefilters are used, they should be made of
noncombustible materials and, as with any prefilter, the user should pay careful attention to preventing dust
DOE-HDBK -1169-2003 Chapter 10
10-31
loading on the prefilter during use. In addition, ESP prefilters should not be used where explosive
concentrations of gases or dusts are present.
Regenerable HEPA Filters
A study is being conducted at Savannah River Technology Center to develop a full-scale application of a
regenerable HEPA filter. Previous attempts at this task were made at LLNL and involved the stainless steel
matrix. These efforts proved less than satisfactory due to weight and efficiency considerations. The latest
effort at Savannah River is a ceramic matrix with a sintered stainless steel coating. A backwash system is also
provided for periodic in-place cleaning of the filters. This design holds a potential for long life similar to that
of conventional HEPA filters, with a reduced potential for catastrophic failure due to media breakthroughs,
moisture, or fires in the ventilation system. If fully validated at the demonstration level, this system could
provide a solution to many fire protection issues. Whether or not this technology can be adapted to building
ventilation systems with much larger airflow requirements has not been determined as of this writing. The
space, pressure drop, and resistance requirements still need to be improved to make this technology useable
on a widespread basis. With the development of such newer technologies, some design changes may be
expected to optimize performance.
Section 31
10.6.2.5 Fire Protection Concepts for Gloveboxes
Fire protection and prevention in gloveboxes is mainly accomplished via the following methods:
• Using noncombustible construction materials. (For information on gloves and windows, which are more
vulnerable to fire damage, refer to DOE Standard 1066-99.1)
• Adhering to acceptable housekeeping policies and procedures.
• Avoiding the use of flammable materials within the box wherever possible. (When no suitable
nonhazardous substance can be substituted, the amount of flammables is limited to the minimum
required for immediate use. The containers used for flammable substances are safest available for the
planned operation.)
• Maintaining a current in-box material inventory. (The box is not used for storage. Boxes usually are
inappropriate for storage, especially for chemicals.)
• Establishing a safer, nonoperative box configuration and periodically checking it to ensure that
nonoperating boxes are in a safe condition. (Precautions include isolating boxes by closing fire stops,
checking through-flow, checking port covers, disconnecting electrical equipment, and removing
corrosives.)
• Designing the box with down-draft ventilation (high air inlet, low outlet) to inhibit combustion while still
purging the box.
• Providing a protective atmosphere. (This measure is listed last because those preceding it apply to all
gloveboxes, whereas inerting is used only when there is too much risk involved in operating without a
protective atmosphere. Assessing the degree of risk involved in an operation is often a subjective
evaluation.)
Nuclear Air Cleaning Handbook U.S. Department of Energy
10-32
10.6.2.6 Protective Atmospheres
The inerting atmosphere system is designed for continuous operation, whereas the extinguishing system
usually has a one- or two-shot, single-incident application before reservicing is required to return the system
to the ready state.
Inerting with smothering agents may require that less than l percent oxygen be present in the glovebox
atmosphere. Process and product-purity considerations may require as little as 100 ppm of total atmospheric
impurities within the glovebox for successful operation. Since many of the detailed considerations are similar
for high-purity and fire protection inerting, and because of the widespread application of high-purity inerting,
most of this discussion will involve high-purity systems. The best single reference for design, construction,
and operational information is Inert Atmospheres 2 by White and Smith.17
Inert-atmosphere gloveboxes that contain radioactive material are operated at pressure differentials of 0.3 to
1.0 in.wg negative pressure relative to the surroundings. The gas flow rate is usually determined by the
atmospheric purity required and the purity of the incoming gas. The box atmosphere purity can be
compromised by air leakage into the box or into service connections, as well as leakage from process
equipment in the box.
Filter installation requirements in inert atmosphere gloveboxes are more stringent than those for
air-ventilated boxes because acceptable box air leakage rates are generally less than 0.0005 box volume/hr.2
To attain this standard, joints and fastenings between items of equipment and materials (gaskets and seals)
must have extremely low gas permeability. Full-welded joints are recommended for all permanent fixtures.
Gasketed joints may deteriorate in service, imposing continuing costs for periodic testing and repair.
Section 32
Low-leak systems require quality construction for all components including boxes, filters, and associated
ducts. Any in-leakage associated with the filter mounting or connecting duct will adversely affect the quality
of the inert atmosphere that can be maintained in the box, and thus the cost of inert gas purification.
Penetrations must be minimized in both number and size. The use of smaller HEPA filters allows smaller
ports for maintenance. Filter changes should be planned for times when other maintenance operations
(routine or special) are taking place inside the box to reduce interruptions to operations, to reduce the loss of
inert gas, and to minimize the time required to recondition box spaces.
For fire protection, the preventive step of inerting is more satisfactory, though more expensive, than
extinguishing a fire if it does occur. However, oxygen must be reduced below l percent before it fails to
support the burning of some pyrophoric metal.18 The use of dry air (relative humidity less than 20 percent)
reduces the hazard of pyrophoric metal fires, but does not eliminate it. Moisture in the presence of heated
pyrophoric or reactive metals, such as finely divided plutonium, increases the possibility of explosion by
generating hydrogen. The suitability and cost of an inert gas for the process are significant factors when
selecting this type of fire control. The gas flow rate in most inert gas boxes is kept as low as possible to be
consistent with required box-atmosphere purity levels; low-capacity filters are frequently used. The inert gas
may be purged on a once-through basis or recirculated through a purification unit. A word of caution
concerning commercially available (off-the-shelf) recirculating gloveboxes: on one occasion at a DOE
installation, there was a problem with oil mists developing in the recirculating pumps and being circulated
along with the inert gas. Off-the-shelf items cannot be used in a confinement-type ventilation system without
evaluation, nor can they be applied as “black boxes” by those responsible for operational safety.
DOE-HDBK -1169-2003 Chapter 10
10-33
10.7 Operations and Maintenance Practices for Fire Protection of
Confinement Ventilation Systems
10.7.1 Essential Elements
The protection of confinement ventilation systems during a fire situation depends on the reliable functioning
of the procedures, systems, and barriers as they were designed and intended to function. To retain that
design capability, it is critical that maintenance and surveillance of systems be accomplished on an established
schedule. Procedures must be practiced, and systems must be regularly inspected to locate problems that may
require alteration of the maintenance practices and operational procedures. If these things are not done, the
ability of the confinement ventilation system to function when needed may be impaired.
10.7.1.1 Fire Prevention
The most critical aspect of fire prevention is fuel control. The storage of any extraneous combustible
materials in filter enclosures or areas where radioactive materials are being handled must be prohibited.
Procedures for the use of flammable liquids and gases must be in place and followed. Quantities of
flammable liquids and gases must be limited to only those required to perform any task.
Accumulation of dust and debris inside the confinement ventilation system ductwork over long periods of
operation increases the consequences of any fires that might occur. Periodic cleaning is required to eliminate
the presence of undesired fuel.
Section 33
Appropriate procedures and controls must be in place and followed to prevent fire involving pyrophoric
radioactive materials. Much experience exists on the start of fires in nuclear facilities and confinement
ventilation systems. The lessons of the past should be applied to prevent fire from occurring in confinement
ventilation systems, or where a fire occurs, a loss of the first line of defense.
10.7.1.2 Procedures
Procedures for safe operation of a facility are required by law. All hazards and necessary controls must be
delineated in existing operational procedures. Fire protection procedures must complement a facility’s safety
documentation required by law or contractual obligations.
10.7.1.3 Inspection, Testing, and Maintenance
Inspection, testing, and maintenance requirements for fire detection and suppression systems are outlined in
the NFPA standards. A program should exist that follows either the NFPA standards or a carefully thought-
out alternative program that provides an equivalent degree of reliability.
Inspection, testing, and maintenance plans must have been established and implemented for all systems in the
facility and its confinement ventilation system, both passive and active.
Limited life materials that will wear out in a relatively short time should be identified and replaced according
to an established plan.
It is important that water-based fire suppression systems be designed such that they do not have to discharge
water on HEPA filter media. Any exposure to water will significantly weaken the filter media and can result
Nuclear Air Cleaning Handbook U.S. Department of Energy
10-34
in an undesired loss of filtration due to the filter media physically failing. Systems must be designed such that
they can be discharge tested without having to actually spray water on the filter media.
10.7.1.4 Impairment Planning
A program must exist to handle situations where fire detection and suppression systems are impaired. Pre-
plans must be developed and instituted to guide facility operations when these systems are not functioning as
they should. Impairment plans also must exist for other critical facility systems. The occurrence of an
impairment is not the time to develop such plans. All impairment plans must be analyzed to identify and
control to the greatest possible extent the hazards that may exist under a given condition.
Impairment plans should be exercised on a regular basis to maintain proficiency in their execution.
10.7.1.5 Modifications
Modifications in a nuclear facility must follow the protocols for Unreviewed Safety Question determination.
This is a somewhat roundabout means of identifying the impact to the established safety basis and all that
goes with that, but it is what the current culture understands and accepts. Configuration control must be
maintained when modifications are made so that all changes are tracked across all affected documentation
and all impacts are identified and understood.
10.7.1.6 Other Considerations
Emergency Planning
The successful mitigation of a fire in a nuclear facility containing a confinement ventilation system requires
emergency planning and exercises involving all entities that may be called on to mitigate a fire situation. Post-
fire recovery plans should exist to aid in the resumption of work in the facility after a fire.
Technical Safety Requirements Tie -in
Maintenance and operational procedures may be formalized in the nuclear facility’s Technical Safety
Requirements.
Section 34
Quality Assurance
All aspects of operations should be tied in to the facility’s Quality Assurance Program, which covers all of the
areas required to produce quality work and to operate safely.
Assessments
Periodic management and independent assessment are necessary to ensure that established requirements are
adequate and are properly implemented.
10.8 Generic Firefighting Procedures
The following recommendations apply to firefighting procedures and instructions. They provide a strategy
that minimizes the likelihood of losing filtered, forced ventilation during a fire. These procedures were
derived from extensive work at Rocky Flats and are included here because they are generically applicable to all
DOE facilities where active fire protection measures are installed for filter housing protection.
DOE-HDBK -1169-2003 Chapter 10
10-35
A special need for nuclear facilities with confinement ventilation systems is smoke venting. Obviously,
smoke cannot be vented to the exterior, but there may be methods to use the confinement ventilation system
to assist in removing some smoke from the fire area to enable more rapid intervention in manual suppression
of the fire.
10.8.1 Control Ventilation Configurations, Volumes, and Flow Rates in the Field
An individual who is responsible for ventilation control (and successors or alternates in case of unavailability)
must be established in the facility emergency planning documentation. This individual must work in
consultation with the fire department sector officer stationed in the control room or at the housing to ensure
a fire emergency will be successfully mitigated with minimal impact.
Differential pressure (DP) changes in the initial filter stages must be continuously monitored, even if the DP
gauge readout is exceeded. Most gauges have a maximum capability of 4 to 6 in.wg, but a rapid drop from an
off-scale high reading to a lower reading will confirm stage failure, as will a significant rise in DP for the next
downstream stage. Attention should be focused on the first stage and the next downstream stage until a first
stage failure is indicated. A rise in DP may be due to progressive filter plugging from fire particulates or
wetting of the filters from deluge spray. Because the initial filter stages are usually (but not always) viewed as
sacrificial, the DP may be allowed to rise to the maximum achievable by the fan. If there is only one stage of
filtration, then this is not applicable.
For housings with four stages, the SOE should monitor the second- and third-stage DP at the first indication
of a loss of first-stage filter integrity. The third and fourth stage DP should be monitored if the second stage
fails.
Ventilation on the affected housings should be throttled when DP across the final filter stage reaches 2 to
4 in.wg (4 in.wg is the current filter change-out criterion for normal operation).
Failure of initial stages and erosion of margin in the final filter stage is permitted if continued ventilation is
necessary to support effective firefighting in the facility. If the fire department officer in charge judges that
ventilation no longer provides a substantial advantage in controlling or containing the fire, and the emergency
commander (generic term) validates that position, action should be taken to protect housing margin
(e.g., ventilation should be discontinued at 2 in.wg DP on the final filter stage). Throttling, if selected, should
be performed in a manner that maintains the actual DP reading on scale within the 2- to 4-in.wg readings at
all times. In no case should ventilation be continued when 4 in.wg DP is reached across the final filter stage.
Section 35
At the first indication of an explosion, the first-stage DP should be monitored for a rapid or complete loss of
DP as an indication of failure. The second-stage DP should be immediately monitored under such
conditions and the filters should be visually inspected if possible. If the second-stage DP is less than
0.5 in.wg, or greater than 4 in.wg, or if there is visible damage to the second stage, ventilation on the affected
housing should be discontinued. The decision to shut down ventilation should be preplanned and well
thought out. Explosive conditions that could clearly impact multiple stages are judged to present too great a
risk to any remaining stage to warrant any attempts to maintain ventilation.
Ventilation should be restored to an affected housing only by the decision of the Emergency Commander or
an approved Recovery Plan.
Restoration of ventilation should be considered likely to result in a forced convection release from the facility
unless other recovery efforts have confirmed no airborne contamination is present in the facility. The
decision to restore ventilation also should be preplanned and well thought out.
Nuclear Air Cleaning Handbook U.S. Department of Energy
10-36
10.8.2 Activation of the Manual Deluge System
The manual deluge system provides an important emergency capability should the first-stage filters be in
danger of being consumed by fire. However, manual deluge system activation will likely result in loss of the
first stage of filters either through plugging or media failure. Consideration may be given to intermittently
flowing the deluge systems with the fans shut down when doing so for short time periods. Before actuating
the manual deluge system, the following recommendations should be followed:
• Direct impingement of flame or burning embers on the first stage filters should be visually confirmed, if
possible.
• The manual deluge system should be activated only when it is clearly required, because activation is likely
to damage the filters, could cause plugging, and could stop ventilation. Early activation of manual deluge
as a precautionary measure is considered imprudent. If the viewing ports are accessible, they should be
used to facilitate confirmation of filter integrity (i.e., visible flaming or smoldering of filter media). Where
viewing ports are inaccessible, the inner access doors to the airlocks should be used as alternative viewing
ports.
• The manual deluge system should be activated only when the fire department officer in charge decides it
is necessary, based on a determination from the available evidence that flame is present in the first stage
of filters.
• The person in charge of ventilation control at the facility should be authorized to initiate the manual
deluge system as necessary prior to fire department arrival. Possible filter plugging and shutdown of
ventilation should be anticipated once manual deluge is activated.
• The initial filter stages should be monitored for evidence of plugging or blowout of the first-stage filter
(DP changes) and for evidence of either particulate buildup/wetting (DP changes) or flame (visual) on
the second and subsequent stages. If flame is confirmed on any downstream stage, all fans connected to
the affected housing should be secured immediately.
10.8.3 Deluge System Flow Times
The following recommendations address when the deluge system flow should be terminated.
Section 36
• The housing deluge system flow should be discontinued upon visual verification by the fire department
incident commander or other authorized personnel if:
– (automatic system) there is no visible smoke in the housing upstream of the spray nozzles and
temperatures in the filter housings have dropped to safe levels; or
– (manual system) the fire involving the first stage is extinguished and the spray duration is judged
to have sufficiently cooled the filter media and frame.
• Only the fire department incident commander or other authorized personnel should terminate the flow
prior to meeting these criteria. Ventilation should only be restored to the affected housing following a
decision by Emergency Commander or in accordance with an approved Recovery Plan.
• If filter plugging is preventing effective ventilation, removal of the plugged media should restore
ventilation. However, restoration of ventilation is likely to result in a forced convection release from the
facility unless other recovery efforts have confirmed there is no airborne contamination in the facility.
DOE-HDBK -1169-2003 Chapter 10
10-37
The removal of plugged filter media in a confinement ventilation system during a fire situation is fraught
with hazards, of course, and should only be done in extreme circumstances.
10.8.4 Manual Activation of the Automatic Deluge System
Early activation of the automatic deluge system could increase the potential for the first filter stage to survive.
For this reason, the automatic deluge system may be activated manually rather than waiting for high-
temperature actuation where early activation provides an advantage. The decision to activate the system
should be made by the fire department incident commander and/or the authorized person in charge of
ventilation control at the facility based on initial assessment of the fire condition. Small fires that are under
control and expected to be quickly extinguished would not challenge the HEPA filters sufficiently to warrant
activation of the system. In addition, the limited available data indicate that early activation is not beneficial
in reducing the potential for smoke-induced plugging for those housings equipped with fog jet nozzles for
automatic deluge, and the procedures should not call for early activation of the automatic deluge system for
those housings. Extensive preplanning should be conducted to define as much as possible the situations in
which the automatic deluge system would be manually actuated.
Nuclear Air Cleaning Handbook U.S. Department of Energy
10-38
10.9 References
1. DOE (U.S. Department of Energy), 1999, Fire Protection Design Criteria, DOE-STD-1066-99,
Washington, DC, July.
2. ChemRisk®, 1992, Health Studies on Rocky Flats, Phase I: Historical Public Exposures, Reconstruction of
Historical Rocky Flats Operations & Identification of Release Points, Project Tasks 3 & 4, McLaren/Hart,
Alameda, CA, August.
3. ChemRisk®, 1992, Health Studies on Rocky Flats, Phase I: Historical Public Exposures, Draft Report,
Estimating Historical Emissions from Rocky Flats, Project 5, McLaren/Hart, Alameda, CA, November.
4. Rockwell International, 1980, Final Report of Incinerator Plenum Fire, Building 771 on July 11, 1980.
5. DOE (U.S. Department of Energy), 1994, Interoffice memorandum, To: Tara O’Toole, Assistant
Secretary for Environment, Safety and Health, From: Cherri Langenfeld, Manager Chicago Operations
Office, Subj: Investigation Report for the Type B Investigation of the March 31, 1994 Fire and
Contamination at the Tristan Experiment, High Flux Beam Reactor (HFBR) Brookhaven National
Laboratory (BNL), Upton, NY, May 20.
Section 37
6. DOE (U.S. Department of Energy), 2000, Initial Joint Review of Wildland Fire Safety at DOE Sites,
Washington, DC, December.
7. 10 CFR 70 (Code of Federal Regulations), 2003, Modification and Revocation of Licenses, U.S. Nuclear
Regulatory Commission, Washington, DC.
8. DOE (U.S. Department of Energy), 2002, Facility Safety, DOE Order 420.1A, Washington, DC, May.
9. DOE (U.S. Department of Energy), 1995, Fire Safety Program for Use with DOE Order 420.1 and DOE Order
440.1, DOE-G-440.1-5, Washington, September.
10. NFPA (National Fire Protection Association), 2002, Installation of Air Conditioning and Ventilation Systems,
NFPA Standard 90A, Quincy, MA.
11. Gottuk, D. T. and R. J. Roby, 1995, “Effect of Combustion Conditions on Species Production,” Section
2, Chapter 7, SFPE Handbook of Fire Protection Engineering, 2nd Edition, National Fire Protection
Association, Quincy, MA.
12. Alvares, N. J., 1986, “Assessment of Thermal Damage to Polymeric Materials by Hydrogen Deflagration
in the Reactor Building,” ACS Symposium Series 293 (the Three Mile Island Accident).
13. UL (Underwriters Laboratory Inc.), 1996, High-Efficiency, Particulate, Air Filter Units, UL-586, Northbrook,
IL.
14. UL (Underwriters Laboratory Inc.), 1999, (amendment 4), Performance of Air Filter Units, UL-900,
Northbrook, IL.
15. Bergman, W., W. D. Kuhl, W. L. Russel, R. D. Taylor, H. D. Hebard, A. H. Bierman, N. J. Alvares,
D. G. Beason, and B. Y. Lum, 1980, Electrofibrous Prefilters for Use in Nuclear Ventilation Systems, Lawrence
Livermore National Laboratory, Livermore, CA.
DOE-HDBK -1169-2003 Chapter 10
10-39
16. Kovach, J. L., 1987, Review of Fires and Fire Control Methods for Nuclear Air Cleaning Systems, 19th Department
of Energy/Nuclear Regulatory Commission Nuclear Air Cleaning Conference, Seattle, WA.
17. White, P. A. F. and S. E. Smith, 1962, Inert Atmospheres in the Chemical, Metallurgical and Atomic Energy
Industries, Washington: Butterworths.
18. DOE (U.S. Department of Energy), 1994, Primer on Spontaneous Heating and Pyrophoricity, DOE-HDBK-
1081-94, Washington, DC, December.
19. Ricketts, C. I., V. Rüdinger, and J. Wilhelm, 1990, “Aspects of the Increase in Pressure Drop of High-
efficiency Particulate Filters under Fog Conditions,” Nuclear Technology, Vol. 92, November/October.
20. NFPA (National Fire Protection Association), 2002, Protection of Life and Property from Wildfire, NFPA
Standard 1144, Quincy, MA.
21. NFPA (National Fire Protection Association), 2003, Fire Protection for Facilities Handling Radioactive
Materials, Standard NFPA 801, Quincy, MA.
22. NFPA (National Fire Protection Association), 2002, National Electrical Code, NFPA 70, Quincy, MA.
23. NFPA (National Fire Protection Association), Standard for Exhaust Systems for Air Conveying of Vapors,
Gases, Mists, and Noncombustible Particulate Solids, NFPA 91, Quincy, MA.
24. Gewain, R., J. Shanley Jr., P. DiNenno, J. Scheffey, and B. Campbell, “Evaluation of Duct Opening
Protection in Two-hour Fire Walls and Partitions,” Fire Technology, National Fire Protection Association,
Quincy, MA.
25. Gewain, R., B. Campbell, J. Shanley Jr., J. Scheffey, “Protection of Duct Openings in Two-hour Fire
Resistant Walls and Partitions,” ASHRAE Journal, American Society of Heating, Refrigerating and Air
Conditioning Engineers, Inc., Atlanta, GA.
26. ASTM (American Society for Testing and Materials), 2000, Standard Test Method for Surface Burning
Characteristics Of Building Materials, (ANSI 2.5, NFPA 255, UBC 8-1, UL 723), ASTM Standard E84, West
Conshohocken, PA, May.
Section 38
27. ASTM (American Society for Testing and Materials), 2000, Fire Tests of Through Penetration Fire Stops,
ASTM Standard E-814, West Conshohocken, PA.
28. NFPA (National Fire Protection Association), 1999, Fire Doors and Windows, NFPA 80, Quincy, MA.
29. NFPA (National Fire Protection Association), 2002, National Fire Alarm Code, NFPA Standard 72,
Quincy, MA.
30. NRC (U.S. Nuclear Regulatory Commission), Recommendations Related to Brown’s Ferry Fire, NUREG-0050,
Washington, DC.
31. EPRI (Electric Power Research Institute), 1982, Categorization of Cable Flammability: Intermediate-Scale Fire
Tests of Cable Tray Installations, EPRI NP-1881, Factory Mutual Research Corp., Norwood, MA, August.
32. EPRI (Electric Power Research Institute), Hill, J. P., 1982, Fire Tests in Ventilated Rooms, Extinguishment of
Fire in Grouped Cable Trays, EPRI NP-2660, Factory Mutual Research Corp., Norwood, MA, December.
Nuclear Air Cleaning Handbook U.S. Department of Energy
10-40
33. NRC (U.S. Nuclear Regulatory Commission), Williamson, R. B. and F. L. Fisher, 1981, Tests and Criteria
for Fire Protection of Cable Penetrations, SAND 81-7160, NUREG/CR-2377, NRC, Washington, DC,
October.
34. NRC (U.S. Nuclear Regulatory Commission), Dube, D. A., 1987, Fire Protection Research Program for the
Nuclear Regulatory Commission, 1975-1981, SAND 82-0431, NUREG/CR-2607, NRC, Washington, DC,
April.
35. NRC (U.S. Nuclear Regulatory Commission), Chavez, J. M. and D. Lambert, 1986, Evaluation of
Suppression Methods for Electrical Cable Fires, SAND 83-2664, NUREG/CR-3656, NRC, Washington, DC,
October.
36. Sawyer, et al., “Cable Fire at Brown’s Ferry Nuclear Plant,” Fire Journal, Vol. 70 #4, July 1976.
37. Pryor, Andres J., “Brown’s Ferry Revisited,” 1977, Fire Journal, Vol. 71 #3, May.
38. NFPA (National Fire Protection Association), 1999, Installation of Sprinkler Systems, NFPA 13, Quincy,
MA.
39. NFPA (National Fire Protection Association), 2003, Water Spray Fixed Systems for Fire Protection, NFPA 15,
Quincy, MA.
40. NFPA (National Fire Protection Association), 2003, Standard on Water Mist Fire Protection Systems,
NFPA 50, Quincy, MA.
41. NFPA (National Fire Protection Association), 2003, Standard for the Design and Installation of Standpipe and
Hose Systems, NFPA 14, Quincy, MA.
DOE-HDBK -1169-2003 Chapter 10
TABLE OF CONTENTS
CHAPTER 10
FIRE PROTECTION .........................................................................................10-1
10.1 Introduction............................................................................................................................... 1
10.2 Fire History ...............................................................................................................................2
10.3 Requirements and Guidelines ....................................................................................................8
10.4 Enclosure Fire Modeling in Fire Hazards Analysis ....................................................................9
10.5 Fire Phenomena....................................................................................................................... 10
10.5.1 Fires Occurring Outside a Confinement Ventilation System .....................................................................10
10.5.1.1 Generation of Heat, Smoke, and Related Products...............................................................10
10.5.1.2 Transport of Heat, Smoke, and Related Products .................................................................12
10.5.1.3 Effects on Filters of Heat, Smoke, and Related Products ....................................................13
10.5.1.4 Effects on Physical Integrity of the Confinement Ventilation System
Section 39
Components...............................................................................................................................16
10.5.1.5 Effects of Wildland Fires ..........................................................................................................16
10.5.2 Fires Occurring within Confinement Ventilation Systems .........................................................................17
10.5.2.1 Generation of Heat, Smoke, and Related Products...............................................................18
10.5.2.2 Transport of Heat, Smoke, and Related Products .................................................................18
10.5.2.3 Effects on Filters of Heat, Smoke, and Related Products ....................................................18
10.6 Fire Hazard Controls and Design Features .............................................................................. 19
10.6.1 Objectives and Requirements.........................................................................................................................19
10.6.2 General Fire Hazard Control Features ..........................................................................................................20
10.6.2.1 Fuel Control ...............................................................................................................................20
10.6.2.2 Passive Design Features and Fire Hazard Controls...............................................................21
10.6.2.3 Active Design Features and Fire Hazard Controls ................................................................24
10.6.2.4 Discussion of Other Filter Types ............................................................................................28
10.6.2.5 Fire Protection Concepts for Gloveboxes ..............................................................................31
10.6.2.6 Protective Atmospheres ............................................................................................................32
10.7 Operations and Maintenance Practices for Fire Protection of Confinement Ventilation Systems33
10.7.1 Essential Elements...........................................................................................................................................33
10.7.1.1 Fire Prevention ..........................................................................................................................33
10.7.1.2 Procedures ..................................................................................................................................33
10.7.1.3 Inspection, Testing, and Maintenance.....................................................................................33
10.7.1.4 Impairment Planning.................................................................................................................34
10.7.1.5 Modifications..............................................................................................................................34
10.7.1.6 Other Considerations................................................................................................................34
Section 40
10.8 Generic Firefighting Procedures .............................................................................................. 34
10.8.1 Control Ventilation Configurations, Volumes, and Flow Rates in the Field ............................................35
10.8.2 Activation of the Manual Deluge System ......................................................................................................36
10.8.3 Deluge System Flow Times ............................................................................................................................36
10.8.4 Manual Activation of the Automatic Deluge System...................................................................................37
Nuclear Air Cleaning Handbook U.S. Department of Energy
10-42
10.9 References ............................................................................................................................... 38