DOE-HDBK-1169-2022, Handbook for Use with DOE-STD-1269-2022
This handbook is a companion document to DOE-STD-1269-2022, Air Cleaning Systems in
DOE Nuclear Facilities (referred to hereafter as “the Standard”). It identifies good practices drawn from operational experience at DOE components and commercial nuclear facilities, industry input, and the advice of technical experts that can be used to meet the Standard’s requirements and guidance. It also offers general technical advice on topics related to air cleaning systems needed for nuclear and worker safety. The handbook provides clarification of the rationale for some provisions in the Standard and cites references to assist all DOE components and their contractors in applying the Standard. With respect to the Standard’s requirement statements, the handbook should be viewed as an implementation aid, not as an interpretation of the requirements.
Version history and related documents
Superseded by
A newer version replaces this document.
Supersedes
Earlier documents this one replaced.
Related documents
Document text
Text extracted from the attached file. Refer to the original document for the authoritative version.
Section 1
i
DOE-HDBK-1169-2022
April 2022
DOE HANDBOOK
HANDBOOK FOR USE WITH
DOE-STD-1269-2022, “AIR CLEANING
SYSTEMS IN DOE NUCLEAR
FACILITIES”
U.S. Department of Energy
Washington, D.C. 20585
NOT MEASUREMENT
SENSITIVE
DOE-HDBK-1169-2022
ii
FOREWORD
This handbook is approved for use by all Department of Energy (DOE) components and
their contractors. It provides advice and recommended good practices for implementing
DOE-Standard (STD)-1269-2022, Air Cleaning Systems in DOE Nuclear Facilities. It does not add
any new requirements to those stated in DOE-STD-1269-2022, nor does it alter in any respect
that standard’s requirements or recommended practices. Taken together, DOE-STD-1269-2022
and this handbook replace DOE-HDBK-1169-2003, Nuclear Air Cleaning Handbook, which is now
archived and may be viewed at https://www.standards.doe.gov/.
Comments (recommendations, additions, and deletions), as well as any pertinent data that may
be of use in improving this document, should be emailed to: nuclearsafety@hq.doe.gov or sent
to:
Office of Nuclear Safety (EHSS-30)
Office of Environment, Health, Safety and Security
U.S. Department of Energy
19901 Germantown Road
Germantown, MD 20874
Phone (301-903-2996)
https://www.standards.doe.gov/
mailto:nuclearsafety@hq.doe.gov
DOE-HDBK-1169-2022
iii
Table of Contents
1.0 Introduction ..................................................................................................................... 1
1.1 Purpose........................................................................................................................ 1
1.2 Applicability ................................................................................................................. 1
1.3 Organization................................................................................................................. 1
2.0 Terminology ..................................................................................................................... 2
2.1 Acronyms & Abbreviations............................................................................................ 2
3.0 System Design .................................................................................................................. 3
3.1 Introduction ................................................................................................................. 3
3.2 Contaminants ............................................................................................................... 3
3.3 Environmental Conditions............................................................................................. 6
3.4 Backup Power .............................................................................................................10
3.5 Work Area Ventilation .................................................................................................10
3.6 References ..................................................................................................................14
4.0 Component Level Guidance and Best Practices ................................................................16
4.1 Filtration Components and Filter Testing ......................................................................16
Section 2
4.1.1 Introduction: Filtration Components .....................................................................16
4.1.1.1 Air Filter Types ..............................................................................................16
4.1.1.2 Filtration.......................................................................................................17
4.1.1.3 Particle Collection by Filters ..........................................................................17
4.1.1.4 Particle Retention in Filters ...........................................................................19
4.1.1.5 Airflow Resistance of Filters ..........................................................................20
4.1.1.6 HEPA Filters: Historical Background ...............................................................20
4.1.1.7 Filter Medium ...............................................................................................21
4.1.1.8 HEPA Filter Construction ...............................................................................21
4.1.1.9 Separators ....................................................................................................22
4.1.1.10 Filter Case...................................................................................................22
4.1.1.11 Sealants ......................................................................................................23
4.1.1.12 Gaskets.......................................................................................................23
4.1.1.13 Faceguards .................................................................................................24
4.1.1.14 Separatorless HEPA Filters...........................................................................24
4.1.1.15 Mini-Pleat HEPA Filters................................................................................25
4.1.2 HEPA Filter Classes and Sizes ................................................................................27
4.1.2.1 Filter Construction Grades.............................................................................27
4.1.2.2 Filter Performance Levels ..............................................................................27
4.1.2.3 Enclosed Filters .............................................................................................28
4.1.2.4 Cylindrical Filters...........................................................................................29
4.1.2.5 Filter Sizes ....................................................................................................30
4.1.2.6 Filter Weight.................................................................................................30
DOE-HDBK-1169-2022
iv
4.1.3 HEPA Filter Performance Characteristics ...............................................................31
4.1.3.1 Airflow Resistance ........................................................................................31
4.1.3.2 Dust-Holding Capacity ...................................................................................31
4.1.3.3 Shock and Blast Resistance............................................................................32
4.1.3.4 Heat from Fire and Explosion ........................................................................33
4.1.3.5 Moisture and Corrosion Effects .....................................................................34
4.1.3.6 Radiation Resistance .....................................................................................35
Section 3
4.1.4 HEPA Filter Performance Testing for Nuclear Service.............................................36
4.1.4.1 Airflow Resistance ........................................................................................37
4.1.4.2 Quality Control/Assurance Considerations.....................................................38
4.1.5 Effects of Aging, Wetting, and Environmental Upsets on HEPA Filter Performance .39
4.1.5.1 Aging ............................................................................................................39
4.1.5.2 Upset Environmental Conditions ...................................................................40
4.1.5.3 In-Place Testing of Filter Installations ............................................................41
4.1.5.4 Packaging, Storage, and Handling of HEPA Filters...........................................41
4.1.6 Medium Efficiency Filters (Prefilters) for HEPA Filters ............................................42
4.1.6.1 Filter Descriptions .........................................................................................42
4.1.6.2 Classes, Sizes, and Performance Characteristics of Medium Efficiency Filters ..43
4.1.6.3 Commercial and Industrial Grade Filters Performing as Medium Efficiency
Filters ............................................................................................................44
4.1.6.4 Electrostatic and Electrified Filters.................................................................45
4.1.6.5 Operation and Maintenance of Medium Efficiency Filters (Prefilters) .............46
4.1.7 Deep-Bed Filters...................................................................................................46
4.1.7.1 Deep-Bed Sand Filters ...................................................................................47
4.1.7.2 Deep-Bed Glass Fiber Filters ..........................................................................48
4.1.7.3 Deep-Bed Metal Filters .................................................................................49
4.1.7.4 Moisture Separators (Demisters)...................................................................50
4.1.8 Testing .................................................................................................................51
4.1.8.1 Introduction .................................................................................................51
4.1.8.2 Proof of Design – HEPA Filter Design Qualification Testing for Nuclear Service
.....................................................................................................................52
4.1.8.2.1 Penetration (Efficiency) ..............................................................................52
4.1.8.2.2 Airflow Resistance......................................................................................53
4.1.8.2.3 Aerosol Test ...............................................................................................53
4.1.8.2.4 Resistance to Rough Handling Qualification Test .........................................53
4.1.8.2.5 Moisture and Overpressure Resistance Qualification Test ...........................54
4.1.8.2.6 Fire and Hot Air Resistance Qualification Test .............................................54
4.1.8.2.7 Spot Flame Resistance................................................................................54
4.1.8.2.8 Quality Control, Inspection and Testing of HEPA Filters ...............................54
Section 4
DOE-HDBK-1169-2022
v
4.1.9 Filter Qualification, Quality Assurance Inspection, and Testing of HEPA Filters .......55
4.1.9.1 Introduction .................................................................................................55
4.1.9.3 In-Place Component Tests and Criteria ..........................................................55
4.1.9.4 Component Acceptance Testing ....................................................................55
4.1.9.5 Duct and Housing Leak Test...........................................................................57
4.1.9.6 Mounting Frame Pressure Leak Test ..............................................................57
4.1.9.7 Airflow Capacity and Distribution Test ...........................................................58
4.1.9.8 Air-Aerosol Mixing Uniformity Test................................................................58
4.1.9.9 Duct Damper Bypass Test..............................................................................59
4.1.9.10 System Bypass Test .....................................................................................60
4.1.9.11 Duct Heater Performance Test ....................................................................60
4.1.10 Surveillance Testing............................................................................................60
4.1.10.1 Introduction................................................................................................60
4.1.10.2 In-Place System Leak Test, HEPA Filter Banks ...............................................61
4.1.10.3 In-Place Testing for Adsorbers .....................................................................62
4.1.10.4 Nonradioactive Tracer Gas Test ...................................................................63
4.1.10.5 Radioactive Iodine Tests..............................................................................63
4.1.10.6 Test Sequence and Frequency .....................................................................64
4.1.10.7 In-Place Testing for Multistage Systems .......................................................64
4.1.10.8 First-stage Downstream Sample ..................................................................65
4.1.10.9 In-Place Testing for Multistage Adsorber Systems ........................................66
4.1.10.10 Test Aerosol/Gas Injection, throughout Second-Stage Upstream Sample ....66
4.1.11 Adsorbent Sampling and Laboratory Testing .......................................................68
4.1.11.1 Sampling.....................................................................................................68
4.1.11.2 Laboratory Testing ......................................................................................69
4.1.11.3 Frequency of Testing ...................................................................................70
4.1.12 Testing of Deep Bed Sand Filters .........................................................................71
4.1.13 Testing Portable HEPA Filtration Systems ............................................................71
4.1.13.1 General Testing and Periodic Maintenance Considerations ..........................71
4.1.13.2 Portable Filtration Systems Testing Applications ..........................................72
4.1.13.3 Testing Problems and Special Considerations...............................................73
Section 5
4.1.14 Testing HEPA Filter Vacuum Cleaners ..................................................................73
4.1.14.1 Description of Radiological Vacuum Cleaners...............................................74
4.1.14.2 Operation ...................................................................................................75
4.1.14.3 HEPA Filter Vacuum Cleaner Tests ...............................................................75
4.1.15 References .........................................................................................................76
4.2 Glovebox Filtration ......................................................................................................81
4.2.1 Introduction: Filtration Components .....................................................................81
4.2.2 Glovebox Types and Characteristics ......................................................................81
DOE-HDBK-1169-2022
vi
4.2.3 Importance of Glovebox Ventilation and Filtration ................................................83
4.2.4 Design of Glovebox Ventilation Systems ...............................................................83
4.2.4.1 Introduction .................................................................................................83
4.2.4.2 Blowers ........................................................................................................84
4.2.4.3 Filter Housings ..............................................................................................85
4.2.5 Dilution of Evolved Gases .....................................................................................90
4.2.6 Heat Dissipation ...................................................................................................90
4.2.7 Empirical Flow Rates ............................................................................................90
4.2.8 Exhaust Requirements..........................................................................................91
4.2.9 Vacuum-and Pressure-Surge Relief .......................................................................92
4.2.10 Glovebox Exhaust Manifold ................................................................................93
4.2.11 Exhaust Cleanup Criteria.....................................................................................93
4.2.12 HEPA Filters .......................................................................................................93
4.2.12.1 HEPA Filter Selection Criteria.......................................................................95
4.2.13 Medium Efficiency Filter (Prefilter) Selection.......................................................96
4.2.14 Inlet HEPA Filters................................................................................................96
4.2.15 Roughing Filters .................................................................................................97
4.2.16 Filter Replacement .............................................................................................98
4.2.17 Protection Against Fire and Explosion ............................................................... 100
4.2.17.1 General Guidance ..................................................................................... 100
4.2.17.2 Detection.................................................................................................. 101
4.2.17.3 Suppression .............................................................................................. 101
4.2.17.4 Inert Environments ................................................................................... 102
Section 6
4.2.18 Control and Instrumentation ............................................................................ 102
4.2.19 Challenge Aerosol Testing of Glovebox Filters ................................................... 106
4.2.20 Glovebox Shielding ........................................................................................... 109
4.2.21 Criticality Considerations .................................................................................. 109
4.2.22 References ....................................................................................................... 110
4.3 Small Air Cleaning Units ............................................................................................. 111
4.3.1 Introduction ....................................................................................................... 111
4.3.2 Housings ............................................................................................................ 113
4.3.3 Component Installation ...................................................................................... 113
4.3.4 Housing Construction ......................................................................................... 117
4.3.5 Bagging .............................................................................................................. 118
4.3.6 Housing Installation............................................................................................ 120
4.3.7 Cylindrical Filter Elements .................................................................................. 121
4.3.8 Installation and Human Factors .......................................................................... 126
4.3.9 Fume Hoods....................................................................................................... 127
4.3.10 Portable Air Cleaning Units ............................................................................... 127
DOE-HDBK-1169-2022
vii
4.3.10.1 Operational Considerations ....................................................................... 128
4.3.10.2 Component Considerations ....................................................................... 129
4.3.10.3 Construction ............................................................................................. 131
4.3.10.4 Testing and Inspection .............................................................................. 132
4.3.10.5 Vacuum Cleaning Systems ......................................................................... 133
4.3.11 References ....................................................................................................... 133
4.4 Housing Design and System Layout ............................................................................ 135
4.4.1 Introduction ....................................................................................................... 135
4.4.2 Housing System Design....................................................................................... 135
4.4.2.1 Man-entry Housing System Design .............................................................. 136
4.4.2.2 Arrangement and Location .......................................................................... 137
Section 7
4.4.3 Component Installation ...................................................................................... 139
4.4.3.1 General ...................................................................................................... 139
4.4.3.2 Housing Construction.................................................................................. 139
4.4.3.3 Potential Housing Leakage .......................................................................... 140
4.4.3.4 Paints and Protective Coatings .................................................................... 140
4.4.4 Man Entry Housing ............................................................................................. 141
4.4.4.1 General ...................................................................................................... 141
4.4.4.2 Structural ................................................................................................... 141
4.4.4.3 Structural Design ........................................................................................ 142
4.4.4.4 Mounting Frame Configuration ................................................................... 143
4.4.4.5 Frame Fabrication ....................................................................................... 145
4.4.4.6 Clamping and Sealing .................................................................................. 145
4.4.4.7 Filter Support.............................................................................................. 149
4.4.4.8 Size and Arrangement of Filter and Adsorber Banks ..................................... 150
4.4.4.9 Vertical Filter Banks .................................................................................... 150
4.4.4.10 Location of Filters on Mounting Frame ...................................................... 151
4.4.4.11 Size of Banks ............................................................................................. 152
4.4.4.12 Arrangement of Banks............................................................................... 152
4.4.4.13 Floor Plan of Filter Banks ........................................................................... 153
4.4.4.14 Steel Housings .......................................................................................... 153
4.4.4.15 Masonry and Concrete Housings ............................................................... 158
4.4.4.16 Housing Floor............................................................................................ 158
4.4.4.17 Housing Doors .......................................................................................... 159
4.4.4.18 Housing Drains.......................................................................................... 160
4.4.4.19 Other Housing Requirements .................................................................... 163
4.4.5 Design of Side-Access Housings .......................................................................... 167
4.4.6 Recommended Design Features.......................................................................... 167
DOE-HDBK-1169-2022
viii
4.4.7 Differences Between Nuclear Filtration Systems and Commercial/Industrial
Filtration Systems ............................................................................................... 169
Section 8
4.4.8 Advantages of Stainless Steel Over Heavy Carbon Steel Construction .................. 170
4.4.9 Side-Access Housings For Radial Flow Cylindrical HEPA Filters ............................. 170
4.4.10 References ....................................................................................................... 173
4.5 External Components ................................................................................................ 174
4.5.1 Introduction ....................................................................................................... 174
4.5.2 Ductwork ........................................................................................................... 174
4.5.2.1 Functional Design ....................................................................................... 174
4.5.2.2 Mechanical Design ...................................................................................... 175
4.5.2.3 Engineering Analysis ................................................................................... 181
4.5.2.4 Engineered Ductwork.................................................................................. 182
4.5.2.5 Materials of Construction............................................................................ 183
4.5.2.6 Paints and Protective Coatings .................................................................... 183
4.5.2.7 Supports ..................................................................................................... 184
4.5.2.8 Thermal Insulation and Acoustic Considerations .......................................... 184
4.5.2.9 Ductwork Leakage ...................................................................................... 184
4.5.3 Dampers and Louvers ......................................................................................... 186
4.5.3.1 Damper Descriptions................................................................................... 186
4.5.3.2 Design and Fabrication................................................................................ 190
4.5.3.3 Structural Design ........................................................................................ 191
4.5.3.4 Design and Construction Considerations...................................................... 191
4.5.3.5 Damper Operators ...................................................................................... 191
4.5.3.6 Limit Switches............................................................................................. 192
4.5.3.7 Performance Requirements ............................................................................. 192
4.5.3.8 Qualification Testing........................................................................................ 193
4.5.3.9 Louvers ........................................................................................................... 194
4.5.4 Fans and Motors ................................................................................................ 195
4.5.4.1 Fan Types and Applications ......................................................................... 195
4.5.4.2 Fan Performance ........................................................................................ 196
4.5.4.3 Fan Leakage Flexible Connection Leakage .................................................... 200
4.5.4.4 Fan Construction......................................................................................... 204
4.5.4.5 Qualification and Testing............................................................................. 204
4.5.4.6 Fan Reliability and Maintenance.................................................................. 205
4.5.4.7 Special Duty Considerations Temperature, Pressure, and Humidity .............. 205
Section 9
4.5.5 Air Intakes and Stacks......................................................................................... 206
4.5.5.1 Locating Intakes and Stacks ......................................................................... 206
4.5.5.2 Sizing Intakes and Stacks ............................................................................. 207
4.5.5.3 Structural Design Aspects............................................................................ 208
DOE-HDBK-1169-2022
ix
4.5.6 Instrumentation and Control .............................................................................. 209
4.5.6.1 Codes and Standards Requirements ............................................................ 209
4.5.6.2 Functional Requirements ............................................................................ 209
4.5.6.3 Airflow Control ........................................................................................... 209
4.5.6.4 Pressure Control ......................................................................................... 211
4.5.6.5 Qualification and Testing............................................................................. 211
4.5.7 References ......................................................................................................... 211
5.0 SPECIAL TOPICS ............................................................................................................. 214
5.1 Fire Protection of Air Cleaning Systems ...................................................................... 214
5.1.1 DOE Fires Affecting Air Cleaning Systems ............................................................ 214
5.1.2 Fire Phenomena ................................................................................................. 215
5.1.2.1 Smoke Generation ...................................................................................... 215
5.1.2.2 Water Generation ....................................................................................... 216
5.1.2.3 Heat Loss in Ducts ....................................................................................... 216
5.1.2.4 Smoke and Water Loss in Ducts ................................................................... 216
5.1.2.5 Effects on Filters of Heat, Smoke, and Related Products............................... 217
5.1.2.6 HEPA Filter Response to Temperature ......................................................... 217
5.1.2.7 HEPA Filter Response to Smoke and Water Loading ..................................... 218
5.1.2.8 Filter Exposure to Water ............................................................................. 218
5.1.2.9 Effects on Physical Integrity of the Confinement Ventilation System
Section 10
Components ................................................................................................ 219
5.1.2.10 Effects of Wildland Fires ............................................................................ 219
5.1.2.11 Fires Occurring within Confinement Ventilation Systems............................ 219
5.1.2.12 Generation of Heat, Smoke, and Related Products ..................................... 219
5.1.2.13 Transport of Heat, Smoke, and Related Products ....................................... 220
5.1.2.14 Effects on Filters of Heat, Smoke, and Related Products ............................. 220
5.1.3.1 Objectives and Requirements...................................................................... 221
5.1.3.2 Fuel Control ................................................................................................ 221
5.1.3.3 Control of Energy Sources ........................................................................... 222
5.1.3.4 Passive Design Features .............................................................................. 222
5.1.3.5 Duct Response to Fire ................................................................................. 222
5.1.3.6 Air Supply and Extraction ............................................................................ 223
5.1.3.7 Entrance Filters........................................................................................... 223
5.1.3.8 Medium Efficiency Filters ............................................................................ 223
5.1.3.9 Filter Housings ............................................................................................ 224
5.1.3.10 Fire Screens .............................................................................................. 224
5.1.3.11 Materials .................................................................................................. 224
5.1.3.12 Wood Filter Frames................................................................................... 224
5.1.3.13 Fire Barriers .............................................................................................. 225
DOE-HDBK-1169-2022
x
5.1.3.14 Active Design Features and Fire Hazard Controls........................................ 226
5.1.3.15 Fire Dampers ............................................................................................ 226
5.1.3.16 Fire Detection and Suppression Systems.................................................... 226
5.1.3.17 Wet Pipe Sprinkler Systems ....................................................................... 227
5.1.3.18 Deluge and Water Spray Systems .............................................................. 227
5.1.3.19 Water Mist Systems .................................................................................. 229
5.1.3.20 Sprinklers within Ductwork ....................................................................... 229
5.1.3.21 Demisters and HEPA Filters ....................................................................... 229
5.1.3.22 Fire Department Standpipe Systems .......................................................... 230
5.1.3.23 Water Runoff Collection ............................................................................ 230
5.1.3.24 Gaseous Agent Systems ............................................................................ 230
5.1.3.25 Flammable Gas Detection ......................................................................... 230
5.1.3.26 Protection of Carbon-Filled Adsorption Systems ........................................ 231
5.1.3.27 Filter Assemblies in Plywood Enclosures .................................................... 232
5.1.3.28 High-Efficiency Metal Fiber Filter Systems.................................................. 232
5.1.3.29 Radioiodine Absorber Air Cleaning Systems ............................................... 232
5.1.3.30 Deep-Bed Fiberglass Filter Systems............................................................ 233
5.1.3.31 Deep-Bed Sand Filter Systems ................................................................... 233
5.1.3.32 Self-Cleaning Viscous Liquid Filters ............................................................ 234
5.1.3.33 Electrostatic Precipitator Prefilter.............................................................. 234
5.1.3.34 Ceramic HEPA Filters ................................................................................. 234
Section 11
5.1.4 Fire Protection Concepts for Gloveboxes............................................................. 234
5.1.4.1 Protective Atmospheres.............................................................................. 235
5.1.5 Operations and Maintenance Practices for Fire Protection of Confinement
Ventilation Systems............................................................................................. 236
5.1.5.1 Essential Elements ...................................................................................... 236
5.1.5.2 Fire Prevention ........................................................................................... 237
5.1.5.3 Procedures ................................................................................................. 237
5.1.5.4 Inspection, Testing, and Maintenance ......................................................... 237
5.1.5.5 Impairment Planning................................................................................... 238
5.1.5.6 Modifications.............................................................................................. 238
5.1.5.7 Emergency Planning.................................................................................... 238
5.1.5.8 Technical Safety Requirements Tie-in .......................................................... 238
5.1.5.9 Quality Assurance ....................................................................................... 238
5.1.5.10 Assessments ............................................................................................. 238
5.1.6 Generic Firefighting Procedures.......................................................................... 238
5.1.6.1 Control Ventilation Configurations, Volumes, and Flow Rates in the Field..... 239
5.1.6.2 Activation of the Manual Deluge System ..................................................... 240
5.1.6.3 Deluge System Flow Times .......................................................................... 241
DOE-HDBK-1169-2022
xi
5.1.6.4 Manual Activation of the Automatic Deluge System..................................... 241
5.1.7 References ......................................................................................................... 241
5.2.1 Introduction ....................................................................................................... 244
5.2.2 DOE Order 420.1C and DOE Guide 420.1-1A ....................................................... 244
5.2.3 DOE-STD-1020-2016 and DOE-HDBK-1220-2017 ................................................. 244
5.2.4 Additional References ........................................................................................ 244
5.3 Occupational Safety and Health ................................................................................. 245
5.3.1 Introduction ....................................................................................................... 245
5.3.2 Confined Space Entry ......................................................................................... 245
5.3.3 Excessive Noise .................................................................................................. 246
5.3.4 Excessive Heat ................................................................................................... 246
5.3.5 Hazardous Biological and Chemical Substances ................................................... 247
5.3.6 Respiratory Protection ....................................................................................... 248
5.3.7 Radiation Exposure and the ALARA Principle ....................................................... 249
Section 12
5.4 Deep-Bed Sand Filters................................................................................................ 250
5.4.1 Introduction ....................................................................................................... 250
5.4.2 Overview of Deep-Bed Sand Filters ..................................................................... 250
5.4.3 Deep-Bed Sand Filter Design............................................................................... 253
5.4.4 Deep-Bed Sand Filter Plugging ............................................................................ 255
5.4.5 Spent Media Disposal ......................................................................................... 255
5.4.6 Burial in Place .................................................................................................... 256
5.4.7 Decontamination ............................................................................................... 256
5.4.8 References ......................................................................................................... 256
DOE-HDBK-1169-2022
1
1.0 Introduction
1.1 Purpose
This handbook is a companion document to DOE-STD-1269-2022, Air Cleaning Systems in
DOE Nuclear Facilities (referred to hereafter as “the Standard”). It identifies good practices
drawn from operational experience at DOE components and commercial nuclear facilities,
industry input, and the advice of technical experts that can be used to meet the Standard’s
requirements and guidance. It also offers general technical advice on topics related to air
cleaning systems needed for nuclear and worker safety. The handbook provides clarification of
the rationale for some provisions in the Standard and cites references to assist all DOE
components and their contractors in applying the Standard. With respect to the Standard’s
requirement statements, the handbook should be viewed as an implementation aid, not as an
interpretation of the requirements.
1.2 Applicability
The handbook applies to new and existing Category 1, 2, and 3 nuclear facilities.
1.3 Organization
The handbook follows the format and organization of the Standard.
DOE-HDBK-1169-2022
2
2.0 Terminology
2.1 Acronyms & Abbreviations
This document uses a large number of acronyms and abbreviations. Some are well-known in
the nuclear industry at large (such as DOE, NRC, and ASTM) while others such as HEPA and
ASHRAE are familiar to any engineer working on air cleaning systems. In each case where a less
familiar acronym or abbreviation is used (e.g., DAC for derived air concentration), an
explanation is provided on first use.
DOE-HDBK-1169-2022
3
3.0 System Design
3.1 Introduction
Design of an air cleaning system in a nuclear facility is a complex task that requires the careful
integration of numerous primary and support systems. The system should be capable of
providing a clean, healthy working environment for personnel in the facility, contain radioactive
and chemical hazards in both normal and accident conditions, and remain operational when
challenged by events such as earthquakes or fires. This section of the handbook provides a wide
range of guidance on system design, based upon many decades of DOE experience dating back
to the Manhattan project.
3.2 Contaminants
Section 13
Intake air cleaning systems or supply systems filter the atmospheric dust and other
contaminants brought into the facility. Recirculating systems, if used, clean the air in a building
or location and return the air to that location. Other sources of particulate and gaseous
contamination are infiltration and “people-generated” particulates (e.g., lint, skin, hair) and off-
gassing of materials such as paint, solvents, carpets, and furniture. All of these factors should be
considered in determining the parameters for proper system design. These contaminants may
become radioactive when exposed to certain environments (e.g., by adsorption of radioactive
vapors or gases or by agglomeration with already radioactive particles). Because particles in the
size range of 0.05 to 5 micrometers (µm) tend to be retained by the lungs when inhaled, they
are of primary concern in operations that involve radioactive material. They are also recognized
as among the health hazards of nonradioactive air pollution. As shown in Table 3.1, over 99
percent, by count, of typical urban air samples have a mean particle size of 0.05 µm.
Reports of dust concentrations in air are generally based on the masses of the particulate
matter present. As shown in Table 3.1, mass accounts for only a negligible portion of the total
number of particles in the air. This is important in filter selection because it indicates that some
filters with a high efficiency based on weight may be inefficient on a true count basis. That is,
the filters are efficient for large particles, but inefficient for small (less than 0.75 µm) particles.
This is true of most common air filters used as medium efficiency filters. On the other hand, the
High-Efficiency Particulate Air (HEPA) filter is highly efficient for all particle sizes down to and
including the smallest shown in Table 3.1. The 99.97 percent minimum efficiency for these
filters is actually for the most penetrating size particles, i.e., those ranging in size from 0.07 to
0.3 µm. Dust concentrations vary widely from place to place and, for the same location, from
season to season and from time to time during the same day. Concentrations in the
atmosphere may vary from as low as 20 micrograms per cubic meters (µg/m3) in rural areas to
more than 20 mg/m3 in heavily industrialized areas.
DOE-HDBK-1169-2022
4
Table 3.1: Distribution of Particles in Typical Urban Air Sample
Mean Particle
Size (µm)
Particle Size
Range (µm)
Approximate Particles Count
per Cubic Foot of Air
Percent by
Weight
Percent by
Count
20.0 50-10 12.5 x 103 28 1 x 10-10
7.5 10-5 10 x 104 63 8 x 10-10
2.5 5-1 12.5 x 106 6 1 x 10-7
0.75 1-0.5 10 x 107 2 8 x 10-7
0.25 0.5-0.1 12.5 x 109 1 1 x 10-4
0.05 0.1-0.001 12.5 x 1015 <1 99.9999
Dust-producing operations may generate concentrations as great as several thousand g/m3 at
the workplace. Because the weight percent determinations on which these concentrations are
based account for only a small fraction of the number of particles present, the true count of
particles smaller than 5 µm may number in the billions per 1000/ft3. Atmospheric dust
concentrations can vary significantly through the year. Filter selection, particularly medium
efficiency filter and building supply filter selection, should be based on the atmospheric dust
concentrations that can be encountered at a particular site at any time of the year.
Section 14
Figure 3.1 below, “Distribution of Particles,” shows the distribution of particles (by weight
percent) in atmospheric air as a function of particle shape. Variations in particle shape, mean
particle size, particle size range, and concentration affect filter life, maintenance costs, and
operational effectiveness. The size range of various types of particles, the technical
nomenclature of various types of aerosols, and the applicability of various types of air cleaning
devices as a function of particle size are shown in Figure 3.2. A major source of the lint often
found on filters is derived from the operations, which generate droplets and solid abrasion of
clothing as people move about. In addition, a person at rest gives off more than 2.5 million particles
(e.g., skin, hair) and moisture droplets/minute in the size range of 0.3 to 1 mm3.
Figure 3.1: Distribution of Particles
DOE-HDBK-1169-2022
5
Figure 3.2: Characteristics of Atmospheric and Process-Generated
Particulates, Fumes, and Mists and Effective Range of Air
DOE-HDBK-1169-2022
6
Process-generated airborne contaminants fall into two general size ranges. Those produced by
machining, grinding, polishing, and other mechanical operations are generally large, (from one
to several hundred µm), based on the process. Particles less than 100 microns can be picked up
by the respiratory tract through the nose and mouth. Particles greater than one micron can be
removed effectively by commercial air filters or other conventional air cleaning techniques. The
other size particle range includes those produced by evaporation/condensation and other
processes that are less than one micron in size. Nuclear-grade HEPA and Ultra Low Penetration
Air (ULPA) filters provide a higher cleaning efficiency to remove those submicron particles;
ULPA filters can remove 99.999 percent of sub-micrometer particles. The need for ULPA filters
at DOE sites is only occasionally seen and is site-specific to the DOE application. HEPA filters are
less expensive than ULPA filters and are acceptable for removing submicron particles in most
applications.
For reactor operations, process-generated contaminants include radioactive noble gases and
halogens. Because of their chemical inertness, limited reactivity with available sorbents, and
the great difficulty of separating them, the noble gases (xenon and krypton) have been treated
in the past by simple holdup to allow time for radioactive decay of the shorter half-life
elements, as well as dilution with clean air before discharge to the atmosphere. They can also
be separated by cryogenic fractionation, charcoal adsorption, or fluorocarbon adsorption and
stored until a significant degree of radioactive decay takes place. Halogen gases, essentially
elemental iodine and certain volatile organic iodides are captured by adsorption either on
activated carbon or certain synthetic zeolites.
3.3 Environmental Conditions
Although some air cleaning system components are prequalified to operate in a given
temperature range, the air cleaning system designer should verify all components of the system
will function between the maximum and minimum temperature conditions for the specified
application. If the temperature range of the specific application exceeds the components’
design qualification temperature, requalification is necessary to meet the operational and
design life requirements of the system.
Section 15
In general, continuous operation at high temperature (greater than 250 degrees Fahrenheit) is
detrimental to both HEPA filters and activated carbon adsorbers. At high temperatures, the
shear strength of adhesives and binders used in the manufacture of HEPA filters and filter
media may diminish, thereby limiting the safe pressure drop to which they can be subjected.
The limiting temperature varies with the specific adhesive and binders used. Filter
manufacturers have designed HEPA filters for temperatures above 250 degrees Fahrenheit (a
500-degree Fahrenheit filter is also available). The filter manufacturer should provide objective
data that the filters are qualified for the higher-temperature environments of the specific
application. Alternatively, for high-temperature applications, particulate filtration can be
DOE-HDBK-1169-2022
7
accomplished with the use of metal filters constructed of sintered metal or metal mesh.1
Ceramic filters are an emerging alternative (see Section 5.1.3.34).
Metal filters are manufactured for medium efficiency and HEPA efficiency ranges. Due to their
relatively high cost, metal filters should be considered only for those applications where
standard glass fiber filters would not meet the environmental or design conditions.
The limiting temperature of adsorbents for capturing radioactive iodine and iodine compounds
is related to the desorption temperature of the adsorbed compound and the chemicals with
which it has been impregnated to enhance its adsorption of organic radioiodides. For example,
the limiting temperature of adsorbents impregnated with chemicals (e.g., triethylene-diamine-
and potassium iodine-impregnated activated carbon) is 280 degrees Fahrenheit.
When temperatures higher than the operating limits of air cleaning system components need
to be accommodated, chilled water coils, heat sinks, dilution with cooler air, or some other
means of cooling should be provided to reduce temperatures to levels that the components can
tolerate. Environmental qualification of an air cleaning system should address thermal
expansion and the heat resistance of ducts, dampers, filter housings, component mounting
frames and clamping devices, and fans. Operational consideration also should be given to the
flammability of dust collected in the ducts and on the filters.
The complexity of the air cleaning system needed to provide satisfactory working conditions
for personnel and to prevent the release of radioactive or toxic substances to the atmosphere
depends on the following factors:
• Nature of the contaminants to be removed (e.g., radioactivity, toxicity, corrosivity,
particle size and size distribution, particle shape, and viscidity);
• Temperature (e.g., process heat, fire);
• Moisture (e.g., sensible humidity process vapors, water introduced from testing);
• Radiation (e.g., personnel exposure and material suitability considerations);
• Other environmental conditions to be controlled; and
• Upset or accident hazard considerations.
In designing an air cleaning system, development of the environmental operating conditions is
the first step. Before appropriate individual system components can be environmentally
qualified, the designer should consider all environmental parameters on an integrated basis.
This may require additional qualifications.
Section 16
The facility owner normally identifies the design and environmental parameters that are
compatible with the overall facility design. These parameters should be identified prior to
system design because they are the basis for the equipment design. If the environmental
parameters are carefully considered, a detailed analysis of cost versus long-term operation will
1 The construction and performance requirements for metal filters will be found in Section FI, Metal Media Filters,
of ASME AG-1 (Code on Nuclear Air and Gas Treatment).
DOE-HDBK-1169-2022
8
provide an environmental maintenance schedule for replacing components and parts
throughout the intended operational life of the system. This will ensure that the system will
perform its intended function properly, efficiently, and cost-effectively. Table 3.2 lists some
common system environmental parameters that should be considered for system design.
Table 3.2: Environmental Parameters for System Design
Parameters Examples
Types of gases treated Air, hydrogen, oxygen, nitrogen, and argon.
Flow rate(s) The maximum and minimum operating flow rates for normal
and accident conditions.
Pressure and pressure drop The external pressure and/or vacuum pressure at the inlet
and/or outlet of the system; the maximum system pressure,
usually accident or upset mode; the maximum allowable
pressure drop across the air cleaning system components.
Temperatures The maximum and minimum operating temperatures of the
airstream and equipment.
Radiation The maximum expected alpha, beta, and gamma radiation dose
rates (rads/hour) and cumulative levels (rads).
Relative humidity,
condensation, and direct
introduction of liquids
The maximum and minimum relative humidity of the gas
entering the air cleaning system, condensation with potential for
wicking.
Contaminants that may be
removed (or not) from the
gas stream
Removal efficiencies for particulate, gaseous, entrained water,
chemical, radiological, volatile organic chemicals, and other
materials, as well as considerations of other materials’
capabilities for air contaminants.
Seismic requirements Seismic response curves for the expected equipment location.
Pressure-time transients Deflagration, detonation (internal), and tornado (external).
Design life and operating life Projected facility and equipment operating life [e.g., filter service
life].
Concentration of
contaminants within the
facility or area to be
ventilated
Specified amounts of identified contaminants, in curies per
volumetric unit, grams per volumetric unit, or particles per
volumetric unit.
Allowable concentrations of
contaminant in the occupied
areas of the facility
Specified amounts of identified contaminants, in curies per
volumetric unit, grams per volumetric unit, or particles per
volumetric unit.
Regulatory limits for stack
release of contaminants
Specified amounts of identified contaminants, in curies per
volumetric unit, grams per volumetric unit, or particles per
volumetric unit. This may also be expressed in dose units of
exposure to radiation.
DOE-HDBK-1169-2022
9
Many radiochemical operations generate acid or caustic fumes that can damage or destroy
filters, system components, and construction materials. Some products of radiochemical
operations can produce shock-sensitive salts (e.g., perchlorate acid salts and ammonium
nitrate) that should be considered in the design and operation. The air cleaning system designer
should select components and materials of construction suitable for the corrosive environment
to ensure high levels of system performance and reliability. Acid-resistant medium efficiency
filters and HEPA filters are available. These filters utilize media constructed with Nomex® or
Kevlar® fibers mixed with glass fibers during manufacturing, epoxy-coated separators to extend
the life of the aluminum separators, and stainless-steel frames.
Section 17
Metal filters with a demonstrated suitability for a moist corrosive atmosphere, in accordance
with ASME AG-12 code requirements, are recommended for hydrogen fluoride or other highly
acidic applications. Hydrogen fluoride is a concern because it will attack the glass media. Wood-
case filters are vulnerable to attack by nitric acid that will form nitrocellulose and negatively
affect filter performance.
Stainless steel is recommended for ductwork and housings when corrosion can be expected.
Since this material may be insufficient in some cases, coated (e.g., vinyl, epoxy) stainless steel
or fiber-reinforced plastics may be necessary.3 The system designer can either: (1) use existing
databases containing information about the performance of materials (including the filter
media) exposed to various concentrations of corrosive contaminants, or (2) perform actual
testing to validate the air cleaning system design.
Scrubbers or air washers may be employed to pretreat the air or gas before it enters the air
cleaning system or to scrub the airstream of perchlorate and ammonium nitrate salts and other
corrosive materials, but consideration should also be given to moisture carryover if the
scrubbers or air washers are not designed and operated properly. ASME AG-1 moisture
separators are recommended ahead of the filters.
Corrosion is not always an obvious threat. In activated carbon-filled adsorbers, for example,
even trace amounts of nitrous oxide or sulfur dioxide will concentrate in the adsorbent over
time, and negatively affect the ability of the carbon to remove radioactive contaminants. In the
presence of moisture, these compounds can form nitric or sulfuric acids that are capable of
corroding the stainless-steel parts of the adsorber, i.e., the perforated metal screens. Aluminum
and carbon steel are subject to corrosion when in contact with moisture-laden carbon. For this
reason, stainless steel is always specified for adsorber cells and for adsorber-cell mounting
frames.
Electrical and electronic components are particularly susceptible to corrosive atmospheres.
Plastics become brittle over time, and contacts can corrode. For this reason, all electronic
components are environmentally qualified for the intended application.
2 ASME AG-1, Code on Nuclear Air and Gas Treatment, 2019 ed.
3 Corrosion-resistant coatings are covered by ASTM D5144, Standard Guide for Use of Protective Coating Standards
in Nuclear Power Plants.
DOE-HDBK-1169-2022
10
Care should be exercised in selecting and using gaskets, as some gasket material reacts with the
moisture in the airstream and releases chlorides that can corrode steels (including stainless
steel). Gasket material selection should also include consideration of the effects of the
material’s use in acidic, radioactive, or other harsh environments. Note that radiation may
cause undesirable reactions such as decomposition of TeflonTM into hydrofluoric acid. The
ASME AG-1 Code (Articles FC-3120 and FK-3120) contains specifications for acceptable gasket
material.
3.4 Backup Power
Backup electrical power is required when specified by facility design and safety documentation.
The amount of backup power needed for fans, dampers, valves, controls, and electrical heaters
to control the relative humidity of the effluent airstream (as dictated by the facility design
requirements) should be estimated for both off-normal and accident conditions. Close
coordination between the system designers of both the air cleaning and electrical systems is
needed to ensure that there is adequate backup power available.4
Section 18
3.5 Work Area Ventilation
Work area ventilation systems should be designed to ensure that concentrations of radioactive
gases and aerosols in the air of occupied and occasionally occupied areas do not exceed the
derived air concentrations (DAC) established for occupationally exposed persons under normal
or abnormal operating conditions.
Workroom ventilation rates are based primarily on heating and cooling requirements, the
potential combustion hazard, and the potential inhalation hazard of substances that are
present in or could be released to the workroom. Releases to the atmosphere should not
exceed permissible limits for nonoccupationally exposed persons (see 40 Code of Federal
Regulations (CFR) Part 61 Subpart H). Because radioactive gases and aerosols might be released
accidentally in the event of an equipment failure, a spill, or a system upset, the ventilation and
air cleaning facilities should be designed to maintain airborne radioactive material within
prescribed limits during normal operations. In addition, the ventilation and air cleaning facilities
should perform in accordance with expectations established during the evaluation of potential
accident conditions.
The current DACs for radioactive substances in air are specified in 10 CFR Part 835, Appendix A.
These DACs should be applied to the design of a ventilation system using a hazard
categorization process where the level of ventilation control is commensurate with the
radiological risk present in the proposed operation. (In a similar manner, the same conceptual
process can also be applied to non-radiological airborne hazards.) NRC’s rule 10 CFR Part 20
provides regulatory guidance on the use of DACs.
Based on the guidance cited above, one approach would be to group the material in use into
the hazard classes shown in Table 3.3, and then to zone the facility ventilation systems based
4 See NFPA 110, “Standard for Emergency and Standby Power Systems” and IEEE 446-1995, “IEEE Recommended
Practice for Emergency and Standby Power Systems for Industrial and Commercial Applications.”
DOE-HDBK-1169-2022
11
on the criteria shown in Table 3.4.5 An alternative approach would be to classify the risk based
on the anticipated airborne and surface contamination levels, as shown in Table 3.5. The user
should note that these criteria are based on the potential for the activity to generate airborne
radioactive materials; they do not consider the direct radiation from the material, which would
require separate shielding considerations. By introducing such indexes of potential hazards and
limitations on the quantities of materials that can be handled, it is possible to establish a basis
for ventilation and air cleaning requirements in various parts of a building or plant. Figure 3.3
illustrates a typical zoning plan for a nuclear facility. Not all of the confinement zones listed in
Table 3.4 would be required in all buildings, and an entire building could possibly be designated
a single zone. Confinement zones are defined with respect to function and permitted
occupancy in the following paragraphs.
Confinement Zones
Section 19
As shown in Figure 3.3, the general approach is to establish ventilation zones in a three-tiered
manner. Multizone buildings are usually ventilated so that air flows from the less contaminated
zone to the more contaminated zone. The interiors of exhaust and recirculating ductwork are
considered to be of the same hazard classification as the zone they serve. Airflow should be
sufficient to provide the necessary degree of contaminant dilution and cooling and to maintain
sufficient pressure differentials between zones where there can be no backflow of air spaces of
lower contamination, even under upset conditions. The pressure differentials should be
determined during the facility’s design and should be in accordance with the applicable
standards. Substantially higher differentials are often specified between Primary and Secondary
Confinement Zones (see below) than for other boundaries.
Table 3.3: Hazard Classification of Radioisotopes
Hazard Class Relative Hazard DAC, Air (µCi/ml)
1 Very High >10-6
2 High 10-8 to 10-6
3 Moderate 10-10 to 10-8
4 Negligible <10-10
Table 3.4: Zoning of Facilities Based on Radiotoxicity of Materials Handled
Quantity of Material Permitted in Zone at any One-Time a, b
Radiotoxicity of
Isotopes Primary Confinement Secondary
Confinement
Tertiary
Confinement
Very High > 10 mCi 0.1 µCi-10mCi 0-0.1 µCi
High > 100 mCi 1.0 µCi-100mCi 0-1.0 µCi
Moderate >1 Ci 10 µCi-1 Ci 0-10 µCi
Negligible >10 Ci 100 µCi-10 Ci 0-100 µCi
5 The limits given in the tables are guides and should not be considered absolute.
DOE-HDBK-1169-2022
12
a There are practical upper limits to the quantities of materials in any particular zone, based on the type of material
and design of the confinement systems. For example, criticality safety concerns may restrict the amount of fissile
material that can be handled at one time, fire protection concerns may limit the amount of pyrophoric materials,
and shielding considerations may limit the amount of materials when penetrating radiation is emitted. An activity-
specific hazards analysis should always be conducted to determine the actual limits to be applied in practice.
b These criteria are based on the potential for the activity to generate airborne radioactive materials.
Table 3.5: Zoning of Facilities Based on Contamination Levels
Anticipated Contamination Levels
Type of Contamination Primary Confinement Secondary
Tertiary
Airborne a >100 x DAC 1 x DAC to 100 x DAC < 1 x DAC
Removable Surface b >>RSCV c >RSCV c <RSCV
a For airborne contamination, the DAC value is listed in 10 CFR Part 835, Appendix A, for the type and chemical
form of the material being handled.
b For removable contamination, the RSCV is the removable surface contamination value listed in 10 CFR 835,
Appendix D, for the type of the material being handled.
c Removable surface contamination levels do not always directly lead to an increasing level of airborne
contamination. The level of airborne contamination strongly depends on the potential for the particular activity to
resuspend the deposited particles into the atmosphere. For this reason, it is difficult to establish a generic
correlation. If the RSCV is the main consideration for differentiating between a secondary and primary
confinement specification, then the approach established in Tables 2.3 and 2.4 should be applied.
Section 20
Areas from which air is not recirculated include areas that produce or emit dust particles, heat,
odors, fumes, spray, soot, smoke, or other contaminants that cannot be sufficiently treated and
could be potentially injurious to health and safety of personnel or are potentially damaging to
equipment. These areas are 100 percent exhausted. Recirculation within a zone (circulating the
air through a high-efficiency air cleaning system before discharge back to the zone) is
permitted, but recirculation from a zone of higher contamination back to a zone of lesser
contamination is typically prohibited.
The methodology used above is based on the DACs for radioactive substances in air, as
specified in 10 CFR Part 835. For toxics and noxious substances, the DACs should be replaced
with Permissible Exposure Limits (PEL), including irritant and nuisance substances, as specified
in 29 CFR 1910. The federal PELs are obsolete in some cases. A more convenient (and generally
more current) tabulation of occupational exposure limits is published by the American Council
of Governmental Industrial Hygienists (ACGIH) in the annual issue of Threshold Limit Values
(TLV). The latter reference includes a procedure for determining TLVs for mixed toxicants, as
well as limit values for heat stress, nonionizing radiation, and noise. DOE Order (O) 440.1B,
Worker Protection Management for DOE Federal and Contractor Employees, specifies how to
select PELs and TLVs.6
Primary Confinement Zone
The primary confinement zone comprises those areas where high levels of airborne
contamination are anticipated during normal operations. Facility personnel do not normally
6 See Section 4m.(9) of the Order.
DOE-HDBK-1169-2022
13
enter primary confinement zones. When entry is necessary, it is done under tightly controlled
conditions. This zone includes the interior of a hot cell, glovebox, piping, vessels, tanks, exhaust
ductwork, primary confinement HEPA filter plenums, hood, canyon, or other confinement for
handling highly radioactive material. Confinement features should prevent the spread of
radioactive material within the building under both normal operating and upset conditions up
to and including the Design Basis Accident (DBA) for the facility. Complete isolation (physical
separation) from neighboring facilities, laboratories, shop areas, and operating areas is
necessary. Unavoidable breaches in the primary confinement barrier should be compensated
for by an adequate inflow of air or safe collection of the spilled material.
The exhaust system should be sized to ensure an adequate inflow of air in the event of a
confinement breach. An air exhaust system that is independent of those serving surrounding
areas is desirable. HEPA filters are typically required in air inlets, and independent testable
HEPA filters should be installed in the exhaust, depending on the application. The exact number
of testable stages is determined by safety analysis.
Secondary Confinement Zone
Section 21
The secondary confinement zone comprises those areas where airborne contamination could
be generated during normal operations or as a result of a breach of a primary confinement
barrier. This zone consists of the walls, floors, ceilings, and associated ventilation systems that
confine any potential release of hazardous materials from primary confinement. Related areas
include glovebox operating areas, hot cell service or maintenance areas, and the ventilation
system servicing the operating areas. Pressure differentials should be available to produce
inward airflow into the primary confinement should a breach occur. These pressure
differentials should be established in conjunction with particle recommended capture velocities
across boundaries between primary and secondary confinement zones. A rule of thumb for
capture velocities is 100 fpm. Penetrations of the secondary confinement barrier typically
require positive seals to prevent migration of contamination out of the secondary confinement
zone. Air locks or a personnel clothing-change facility are installed at the entrance to the zone.
Restricted access areas are generally included in the secondary confinement zone.
Tertiary Confinement Zone
The tertiary confinement zone comprises those areas where airborne contamination is not
expected during normal facility operations. This zone consists of the walls, floors, ceilings, and
associated exhaust system of the process facility. It is the final barrier against release of
radioactive and toxic material to the environment. The secondary and tertiary boundaries may
exist in common, as in a single-structure envelope.
DOE-HDBK-1169-2022
14
Figure 3.3: Typical Process Facility Confinement Zones
3.6 References
1. 10 CFR Part 20 (Code of Federal Regulations), 2019, Energy: Standards for Protection
Against Radiation, Appendix B, Washington, DC.
2. 10 CFR Part 835 (Code of Federal Regulations), 2019, Occupational Radiation Protection
Program, U.S. Department of Energy, Washington, DC.
3. 29 CFR §1910 (Code of Federal Regulations), 2019, Occupational Safety and Health
Standards, Occupational Safety and Health Administration, Washington, DC.
4. 40 CFR 61 (Code of Federal Regulations), 2019, National Emission Standards for Hazardous
Air Pollutants, Subpart H, Washington, DC.
5. ACGIH (American Conference of Governmental Industrial Hygienists), Annual Issue, TLVs—
Threshold Limit Values for Chemical Substances and Physical Agents in the Workroom
Environment, Cincinnati, OH.
6. ACGIH (American Conference of Governmental Industrial Hygienists), 2001, Industrial
Ventilation – A Manual of Recommended Practices, 28th Edition, Cincinnati, OH.
7. AIHA (American Industrial Hygiene Association), Laboratory Ventilation, ASSP/AIHA Z9.5-
2012.
8. ASHRAE (American Society of Heating Refrigerating and Air Conditioning Engineers), 2017,
Fundamentals Handbook of HVAC Systems, [I-P Edition] Atlanta, GA.
9. ASHRAE (American Society of Heating, Refrigerating and Air Conditioning Engineers), 1993,
Heating, Ventilating and Air Conditioning Design Guide for Department of Energy Nuclear
Facilities, Atlanta, GA.
DOE-HDBK-1169-2022
15
10. ASHRAE, 2017, Method of Testing General Ventilation Air Cleaning Devices for Removal
Efficiency by Particle Size, Standard 52.2-17, Atlanta, GA.
11. ASME (American Society of Mechanical Engineer), 2019, Code on Nuclear Air and Gas
Treatment, ASME AG-1, New York, NY.
Section 22
12. ASTM (American Society for Testing and Materials), 2016, Standard Guide for Use of
Protective Coating Standards in Nuclear Power Plants, Standard D5144-(08), West
Conshohocken, PA.
13. Burchsted, C. A., 1968, “Environmental Properties and Installation Requirements for HEPA
Filters,” Symposium on Treatment of Airborne Radioactive Wastes,” IAEA, Vienna, Austria.
14. DOE, 2012, Nonreactor Nuclear Safety Design Criteria and Explosive Safety Criteria Guide for
use with DOE O 420.1A, DOE G 420.1-1A, Washington, DC.
15. DOE, 2013, Worker Protection for DOE Contractor Employees, DOE O 440.1B, Washington,
DC.
16. DOE, 2018, Facility Safety, DOE O 420.1C, Washington, DC.
17. First, M. W., and L. Silverman, 1962, “Cost and Effectiveness of Air Cleaning Systems,”
Nuclear Safety, 4(1), pp. 61-66.
18. Harrington, R. E., 1974, “Fine Particulates—The Misunderstood Air Pollutant,” Journal of Air
Pollution Control Association 24(10), pp. 927-929, Pittsburgh, PA.
19. IEEE (Institute of Electrical and Electronic Engineers), 2003 (R2008) Standard for Qualifying
Class 1E Electrical Equipment for Nuclear Power Generating Stations, IEEE Standard 323,
New York, NY.
20. IEEE (Institute of Electrical and Electronic Engineers), 2013, Recommended Practice for
Seismic Qualification of Class 1E Equipment in Nuclear Generating Stations, IEEE Standard
344, New York, NY.
21. ASME N511-2017, “In-Service Testing of Nuclear Air-Treatment, Heating, Ventilating, and
Air-Conditioning Systems.”
22. ANSI/ISA 84.00.01-2004, Functional Safety: Safety Instrumented Systems for the Process
Industry Sector.
23. ERDA 76-21, Nuclear Air Cleaning Handbook: Design Construction, and Testing of High-
Efficiency Air Cleaning Systems for Nuclear Applications, 1979.
DOE-HDBK-1169-2022
16
4.0 Component Level Guidance and Best Practices
4.1 Filtration Components and Filter Testing
4.1.1 Introduction: Filtration Components
Filters are widely used in nuclear ventilation, air cleanup, and confinement systems to remove
particulate matter from air and gas streams. Air filters are defined as porous structures through
which air is passed to separate out entrained particulate matter. The word “filter” is derived
from a word for the fabric called felt, pieces of which have been used for air and liquid filtration
for hundreds of years.
The porous structures of a filter may also be composed of granular material such as sand or
fibers derived from cotton, minerals (glass, asbestos), ceramics, metals, or a wide selection of
plastic materials. For filtration purposes, although all filters do not contain fibers, fibers in filters
may be woven or felted into a cloth or formed into a paper-like structure. Filters may also be
constructed in the form of highly porous fibrous beds of considerable depth. Additional
information on ceramic filters is contained in Section. 5.1.3.34. The porous structure can be
produced as high strength media with a fiberglass woven fabric laminated to one or both sides
of the media for added strength and durability.
Other kinds of air cleaning devices (e.g., adsorbers, liquid scrubbers, electrostatic precipitators
(ESP)) are sometimes referred to as “filters” because they are capable of removing particles
from an airstream. For clarity, the strict definition of a filter (given above) will be used in this
chapter.
4.1.1.1 Air Filter Types
Section 23
Air filters of many types and materials of construction have been designed, manufactured, and
applied to meet a wide variety of industrial and commercial requirements for clean air. The
nuclear industry makes full use of all filter types. Commercially available filters are divided into
three distinct categories based on how they operate to remove suspended particulate matter
from the air passing through them.
The largest category, often referred to as ventilation or heating, ventilation, and air
conditioning (HVAC) filters, is composed of highly porous beds of resin-bonded glass or plastic
fibers with diameters ranging from 1 to 40 micrometers (µm). The fibers act as targets for
collecting airborne dust. As their name indicates, HVAC filters are widely used for air cleaning in
mechanical ventilation systems. They are almost all single-use, disposable items, and are used
in all sectors of the nuclear industry, including as medium efficiency filters that reduce the
amount of coarse dust reaching more efficient filters located downstream.
A second category also is comprised of single-use, disposable filters called HEPA filters. By
definition, a HEPA filter is a throwaway, extended-medium, dry-type filter with a rigid casing
enclosing the full depth of the pleats, with a minimum efficiency of 99.97 percent when tested
with an aerosol of 0.3-µm diameter test aerosol particles. (Filters of different flows and
resistances are allowable by the ASME AG-1, Code on Nuclear Air and Gas Treatment.) A filter
of identical construction and appearance but having a filtering medium with a retention of
DOE-HDBK-1169-2022
17
99.999 percent for 0.1 µm particles, is referred to as an ULPA. The filtering medium of HEPA
filters is thinner and more compressed and contains smaller diameter fibers than HVAC filters.
HEPA filters are widely used throughout all phases of the nuclear industry.
A third category of commercial air filters is known as industrial cleanable cloth filters. As the
designation indicates, these filters have built-in mechanisms for periodically cleaning the
filtering surfaces of accumulated dust. Unlike the first two types, industrial cleanable cloth
filters rely on building a thick layer of dust on the surface of the cloth to provide a high-
efficiency filtering medium. This type of filter is used in the nuclear industry for ore processing
and refining and for similar tasks involving high concentrations of coarse mineral dusts.
There are also special types of particulate filters for chemical and combustion operations. These
include deep beds of sand in graded granular sizes, deep beds of glass fibers, and stainless-steel
membranes formed from compressed and sintered granules or fibers. Stainless steel membrane
filters operate like industrial cleanable cloth filters in that they depend on a dust layer for high-
efficiency particle removal and should be cleaned periodically, usually by reverse compressed
air jets.
4.1.1.2 Filtration
The high porosity of air filters is associated with low resistance to airflow (e.g., low-resistance
HVAC filters contain approximately 97 percent voids). In a uniformly dispersed filter medium,
the individual fibers are relatively far apart—so far apart that the gaps between them are larger
than the particles removed from the air. This means that sieving (particle removal via openings
that are smaller than the particle dimensions) is not an important filtration mechanism. In fact,
a sieve would make a poor air filter, even one containing sub-micrometer openings, because
each collected particle closes a sieve opening so that very soon no air can pass through.
Section 24
In contrast, filters collect particles from air and gas streams in well-defined ways that are
associated with the dynamic properties of airborne particles. The filters respond to the physical
forces present as an aerosol passes through a porous medium composed of small granules,
fibers, or other shapes.
4.1.1.3 Particle Collection by Filters
Figure 4.1 shows the streamlines around a spherical granule or a single filter fiber lying normal
to the flow direction. A particle entering the flow field surrounding the fibers should follow the
curved path of the streamlines so it can pass around the obstacle. When particles possess
sufficient inertia, they resist following the curvature of the airstream and come in contact with
the fiber because of their higher momentum relative to that of the conveying gas molecules.
The capturing effect of inertial impaction (I in Figure 4.1) becomes greater as both aerodynamic
equivalent diameter7 and the velocity of the air approaching the fiber increase.
When suspended particles are very small, however, they tend to follow the curved streamlines
closely; that is, they have little inertia, but are in vigorous, random (Brownian) motion (II in
7 The aerodynamic equivalent diameter can be defined as that of a sphere with a certain density and settles in still air at the
same velocity as the particle of interest. This does not necessarily correlate to specific particle sizes listed throughout this
handbook.
DOE-HDBK-1169-2022
18
Figure 4.1). Therefore, when a streamline passes close to the fiber surface, the random
movements around the streamline may result in some of the particles contacting the fiber and
adhering to it. This sets up a concentration gradient between the zone close to the fiber and the
bulk of the aerosol which, in turn, results in particle diffusion in the direction of the fiber
surface. The smaller the particles, the more vigorous their Brownian motion and the more
effective their filtration by diffusion. Because the rate at which small particles cross streamlines
under the influence of diffusional forces is slow compared to rate of the effects of inertial force
on large particles, separation of small particles by diffusion is enhanced by slower velocities
through a filter.
Figure 4.1: Streamlines Around a Filter Fiber
DOE-HDBK-1169-2022
19
Particle collection by interception (III in Figure 4.1) occurs when a particle traveling in a
streamline that approaches a fiber within one particle radius contacts the fiber and adheres to
it. Interception is independent of flow velocity and is enhanced when the diameter of the
collecting fiber or granule approaches the geometric diameter of the particle.
The several filtration mechanisms of importance are shown together in Figure 4.2, where
penetration (equal to 100 minus collection efficiency) is plotted against particle size. The
penetration lines are not cumulative, as particles can be collected but once; however, the net
effect can be approximated by the redlined summation curve. Figure 4.2 makes it clear there is
a particle size where both inertial and diffusional forces are minimal and only interception is
unaffected. This explains the concept of a minimum filterable particle size. The exact minimum
size depends on fiber diameter, filter construction, and flow velocity. The effect of flow velocity
on particle penetration for HEPA filter medium also shows a minimum efficiency point.
Figure 4.2: The Effects of Inertia, Diffusion, and
Interception on the Penetration-Velocity Curve
Section 25
4.1.1.4 Particle Retention in Filters
After an airborne particle contacts a filter element, retention forces prevent re-entrainment
under the influence of the drag of the air. For small particles, the principal retentive force is a
surface phenomenon called the Van der Waals force, which is proportional to the total area of
DOE-HDBK-1169-2022
20
contact. For small spherical particles, the fraction of the total surface area in contact with a
filter fiber will be relatively large, resulting in a retention force that exceeds the re-entrainment
force of the air drag.
4.1.1.5 Airflow Resistance of Filters
Filter resistance is directly related to airflow rate and filter construction details. Decreasing the
diameter of filter fibers or granules produces higher resistance for the same overall unit volume
of the solid fraction of the filter medium. Greater filter depth at the same porosity increases
resistance in proportion to the increase in depth.
As particles collect on the surfaces of fibers or granules or become entrapped in the interstices
between upstream elements of the filter, the collected particles tend to form a coherent dust
layer known as a filter cake. When this occurs, particle collection gradually shifts from media
filtration (i.e., particle removal by individual filter fibers or granules) to cake filtration, and the
filter shares the characteristics of the industrial cloth filter because the original structure now
has the sole function of providing support for the filter cake and the filter cake completely takes
over the particle separation function. This transformation produces two important changes: (1)
efficiency increases in proportion to the increase in thickness of the cake; and (2) after
formation of a coherent filter cake, resistance of the filter to airflow, which initially increased at
a slow, steady rate as particles accumulated, now increases at an accelerating rate in response
to additional particle deposition and narrowing of the pathways.
4.1.1.6 HEPA Filters: Historical Background
The original specifications for HEPA filter media and cased filters were concealed under a veil of
military secrecy because of their use for chemical, biological, and radiological defense purposes.
Following World War II, the Atomic Energy Commission (AEC) chose the military's HEPA filters
as their principal device for particle removal in all exhaust air systems of nuclear facilities.
Eventual expansion of the use of HEPA filters for nonmilitary applications required
declassification and release of information about HEPA filter components and manufacturing
methods. For this reason, military standards MIL-F-51068, MIL-F-51079 (filter construction and
filter medium preparation), and MIL-STD-282 (filter testing) were issued in an unclassified
format.
MIL-F-51068 and MIL-F-51079 were withdrawn by the U.S. Department of Defense (DoD) and
replaced by ASME AG-1 and DOE-STD-3020-2015. While MIL-F-51068 and MIL-F-51079 were
active, the Edgewood Chemical and Biological Center in Maryland prepared a procurement
guide for military and nuclear agencies, the Qualified Products List (QPL), which is based on
exhaustive tests of manufacturers’ filter media and filters. The QPL referenced available
American Society for Testing and Materials (ASTM), Technical Association of the Pulp and Paper
Industry (TAPPI), and other standard test procedures and equipment in its documentation of
products. Though the process remains basically the same, Edgewood now issues letters to
manufacturers after qualification testing in accordance with DOE STD-3020-2015.
Section 26
DOE-HDBK-1169-2022
21
4.1.1.7 Filter Medium
HEPA filter media used for nuclear service consistently provide collection efficiencies greater
than 99.99 percent when qualified in accordance with ASME AG-1 and DOE STD 3020-2015. By
increasing the fraction of fine glass fibers in the paper that are less than 0.25 µm in diameter, it
is possible to obtain efficiencies in excess of 99.999 percent for 0.1- to 0.3-µm particles with a
modest increase in filter resistance—typically about 25 percent.
4.1.1.8 HEPA Filter Construction
HEPA filter units have historically been constructed via a continuous length of filter medium
folded back and forth into pleats and corrugated separators are inserted between each fold.
The assembly is then sealed into a rigid, open-faced rectangle. Additionally, separatorless
designs, radial designs, metal media filters, and ceramic filters have different methods of
construction. The components of a fabricated HEPA filter include: (1) extensively pleated filter
medium, (2) separators that provide air passages and keep adjacent pleats apart, (3) a rigid
filter case that encloses and protects the fragile filter medium, (4) sealants used to bond the
filter pack (consisting of the assembled pleated medium and separators) to the filter case and
to eliminate leak paths between filter pack components, and (5) gaskets attached to the filter
case on one or both open faces to provide an airtight seal between the filter and the mounting
frame. Some filter construction methods form the filter medium on the papermaking machine
using an interval means to keep the adjacent folds apart, thereby eliminating a need for
corrugated separators. These filters are called separatorless HEPA filters, discussed in Section
4.1.1.14., Figure 4.3 shows the assembled components of an open-face, deep-pleat HEPA filter
with corrugated separators.
DOE-HDBK-1169-2022
22
Figure 4.3: Open-Face Deep-Pleat HEPA Filter – Type A Filter Pack
4.1.1.9 Separators
The most widely used material for the interleaved corrugated separators is tempered aluminum
foil. The aluminum foils currently used for separators are identified as ASTM B209, Standard
Specification for Aluminum and Aluminum Alloy Sheet and Plate. ASME AG-1 provides specific
guidance on allowable alloys, depending on whether the separators are aluminum or acid
resistant aluminum. When corrugating the aluminum sheet into separators, edges are often
hemmed (turned back on themselves) to prevent the sharp edges from puncturing or tearing
the part of the filter medium folded around the separator. When greater chemical resistance is
required, a plastic coating of an epoxy, thermo-set vinyl (or a similar compound) is applied to
the aluminum sheet.8 A dye should be added to clear coating materials so that defects in the
plastic coating can be easily detected. ASME AG-1 FC-4150 should be consulted for additional
information on separator coatings. According to ASME AG-1, any coatings are required (a) to
meet a 3A rating of ASTM D3359, (b) not provide excessive off-gas volatiles, and (c) pass a
flexibility test in accordance with FED-STD-141C.
4.1.1.10 Filter Case
The filter case is constructed of materials that correspond to the specific application,
decontamination requirements, and considerations of disposal ease and cost. Commonly used
8 If significant radiation is a concern, the use of organic materials may not be appropriate.
DOE-HDBK-1169-2022
23
Section 27
case materials include fire-retardant plywood9 and stainless steel in accordance with ASME AG-
1 Article FC-3000. The minimum thicknesses required to maintain rigidity under compressive
loads ranging up to 1,400 pounds when the filter is clamped to a mounting frame, are 3/4 inch
for wood and 14-gauge sheet metal. Grade A-C, American Plywood Association (APA) PS-1 fire-
retardant-treated plywood is acceptable, but the “A” face should be on the inside, facing the
pack, and should be assembled with this face completely coated with a sealant to close off any
leak paths. For wooden case filters, case panels are joined with rabbeted joints, which are
assembled by gluing with an adhesive and double nailing or doubling screwing with coated box
nails, corrosion-resistant plated screw nails, or flat-head wood screws. Metal cases should be
used in instances of potential wetting or high humidity at elevated temperatures and when the
filter will be exposed to corrosive chemicals.
4.1.1.11 Sealants
Sealants used to provide a leak-free bond between the filter pack and case should be resistant
to heat and moisture, noncombustible, fire-resistant, or self-extinguishing, as well as capable of
maintaining a reliable seal under continuous exposure to design operating conditions. Rubber-
based adhesives compounded with chlorine or bromine to ensure self-extinguishing when
exposed to ignition are acceptable, but catalytically cured solid and foamed polyurethanes
containing additives for combustion suppression are the sealants of choice for most filter
manufacturers.
Sealants should maintain their integrity over a wide temperature range. Filters designed to
operate at temperatures above 392 degrees Fahrenheit (200 degrees Celsius) have been sealed
with compression-packed glass fibers and with ceramic cements reinforced with glass fibers and
have been hardened thermally. Room temperature vulcanizing silicone rubber sealants have
been used successfully at operating temperatures up to 392 degrees Fahrenheit (200 degrees
Celsius). Additional materials may be used as research and operations experience indicate is
appropriate. The continuous updating and re-issuance of ASME AG-1 will reflect these latest
advances. ASME AG-1 Sections FC and FK contain additional information on sealants.
4.1.1.12 Gaskets
Filters should be installed so that even the smallest volume of air or gas does not escape
filtration; therefore, gaskets sealing filter units to the mounting frames play a critical role in the
satisfactory operation of HEPA filters. The most widely used sealing method is a flexible gasket
attached to the open face of the filter case and pressed against the flat face of the mounting
framework. The second most popular method is referred to as a “fluid seal.” This method uses a
channel formed or routed in the peripheral face of the filter case that is filled with a highly
viscous, very low volatility, nonflammable (or self-extinguishing), odor-free, non-Newtonian
fluid such as a silicone. The fluid flows around and over imperfections yet does not relax or
separate from the surfaces it contacts. For installation, the matching framework face is
equipped with a continuously protruding knife-edge that mates with the fluid-filled channel in
the filter case.
9 The use of plywood casing is discouraged in DOE nuclear facilities.
DOE-HDBK-1169-2022
24
Section 28
Gaskets should be oil- and ozone-resistant. Closed-cell sponge gaskets composed of synthetic
rubber (neoprene) that conforms to grade 2C3 or 2C4 of ASTM D1056, Sponge and Cellular
Rubber Products, are required by Article FC-3000 of ASME AG-1. Gaskets should have a
minimum thickness of 1/4 inch and width of 3/4 inch. The gasket face attached to the filter case
should be free of any adhesion-resistant mold-release contaminant that may have been
acquired when the gasket material was molded. To ensure an absence of residual mold release
chemical, only cut surfaces are permitted on both gasket faces. Gaskets may be cut out of a
sheet of stock as a single piece or may be made of strips joined at the corners by dovetail or
other interlocking arrangement. Joints are sealed against air leakage with a rubber-base
adhesive, usually the same adhesive used to attach the gasket to the filter case. Manufacturers
of neoprene gaskets recommend a shelf life not to exceed 3 years.
4.1.1.13 Faceguards
To guard against damage from careless handling and faulty installation, a recessed faceguard
across both faces of the filter is required according to ASME AG-1 Article FC-4160 and Article
FK-4160. Woven or expanded 4X4 mesh metal have proven satisfactory in largely preventing
the inadvertent intrusion of hands or other objects into the filter pack. In addition, a metal
mesh faceguard provides added strength to the filter unit, increasing resistance to
transportation damage and shock overpressure. ASME AG-1 requires faceguards conforming to
either galvanized steel ASTM A740, or 304 stainless steel ASTM A580.
4.1.1.14 Separatorless HEPA Filters
A separatorless HEPA filter design, shown in Figure 4.4, is constructed without corrugated
spacers inserted between the folds of the filter medium. Instead, a continuous sheet of filter
medium is molded on the papermaking machine with corrugations at intervals. When it is
folded back and forth upon itself, it becomes a self-supporting pack where the peaks of the
interval corrugations of successive layers contact each other to form a honeycomb-like filter
pack. For the same filter frame size, a separatorless filter contains more useful filter medium
surface than the corrugated separator type, and thus provides greater airflow capacity at equal
resistance. Tests of Type C filters conducted at Mississippi State University10 have suggested
that failures may occur under certain accident conditions. These filters are no longer being
manufactured.
10 19-REP-DOE-SEP/SEPLESS-FINAL, December 17, 2019, Mississippi State University Institute for Clean Energy Technology, work
performed under DOE Contract DE-EM0003163.
DOE-HDBK-1169-2022
25
Figure 4.4: Separatorless Style Filter – Type C Filter Pack
A similar filter with more useful filter medium is the ASME Type D filter. This filter does not
have a metal separator but contains glass ribbons for support. It is regularly used in nuclear
installations and has shown excellent operating performance. The Type D filter is commonly
referred to as a “separatorless filter” since there is no metal filter, but it does have a glass
ribbon that functions as a separator. Separatorless HEPA filter designs can be more susceptible
to pleat collapse than separator filters as documented in DOE Operating Experience-3: 2013-02
“Laboratory Tests Indicate Conditions that Could Potentially Impact Certain Type of HEPA Filter
Performance”.
4.1.1.15 Mini-Pleat HEPA Filters
Section 29
Mini-pleat filter construction methods utilize 7/8 to 1 1/4-inch-deep pleats with very narrow air
spaces (1/8-inch) between, making it possible to pack more filter medium into the standard
frame sizes than can be done with deep-pleat, corrugated separators, or even by using
separatorless construction methods. Abutting folds are separated by threads, ribbons, tapes,
strips of medium, or continuous beads of glass, foam, or plastic spaced across the width of the
medium. Mini-pleat filters contain almost twice as much filter medium as deep-pleat,
corrugated separator filters of equal frame size (Figure 4.5). They are rated to have an airflow
DOE-HDBK-1169-2022
26
resistance of 0.25 Kilopascals (kPa) when operated at 3,060 cubic meters per hour (m3 /hr),
compared to the same resistance for a flow rate of 1,700 to 2,040 m3/hr for deep-pleat
corrugated separator filters. This gives the user of mini-pleat filters the option of utilizing space-
saving higher airflow or extending filter life by operating at lower than rated airflow capacity.
This is called downrating a filter.
When a mini-pleat filter rated for 3,060 m3/hr is downrated to service at 1,700 m3/hr, it
theoretically should extend service life more than threefold before it reaches its final
permissible resistance increase. In practice, filter life extension is 1.6-fold due to the higher
media velocity affecting efficiency, and dust bridging across the very narrow air passages
between the paper pleats to form a filter cake covering the face area. An efficient medium
efficiency filter might be used to prevent the formation of a surface filter cake and extend the
service life of the mini-pleat filter. Cased mini-pleat HEPA filters are formed from
subcomponents assembled in a continuous “V” array.
Figure 4.5: Mini-Pleat (Thread Separator) Filter – Type B Filter Pack
DOE-HDBK-1169-2022
27
The subcomponents are panels that hold the pleated filter medium in metal frames
approximately 23.62 inches wide, 11.81 inches high, and the depth of the paper pleats. A seal is
made between framed filter packs and the standard frame using rubber-based adhesives,
polyurethane, or some other plastic-based material, all of which are chemically compounded to
inhibit their support of combustion.
4.1.2 HEPA Filter Classes and Sizes
In addition to being the workhorse filter for the nuclear industry, HEPA filters have found many
important applications in the industrial, medical, pharmaceutical, and microelectronic sectors.
These diverse applications have resulted in a number of industrial and governmental
specifications. In general, these specifications can be grouped into five construction grades and
three performance types that provide a range of materials, manufacturing techniques,
performance characteristics, and costs for different applications and user preferences. A
standard covering the grades and types of HEPA filters has been issued by the Institute of
Environmental Sciences and Technology (IEST) as IEST-RP-CC001.3. This standard lists the
classifications described below.
4.1.2.1 Filter Construction Grades
Grade 1 – Fire-Resistant Filters. Filters of this grade contain fire-resistant materials that may
ignite when the filter is exposed to hot air or fire but will not continue to burn once the ignition
source is removed. The filter should exhibit a specified retention efficiency after exposure to no
more than 700 ± 50 degrees Fahrenheit (371 ± 10 degrees Celsius). These filters comply with
ASME AG-1, Section FC or FK.
Section 30
Grade 2 – Semicombustible Filters. This grade costs less but provides a lower level of
protection against elevated temperature than Grade 1. For this reason, the user should
evaluate application of this filter grade with the individual fire propagation hazards in the area
of use. This filter type will fail at temperatures much lower than Grade 1. These filters comply
with Underwriters Laboratories (UL) UL 586.
Grade 3 – Combustible Filters. This grade covers filters required for certain service
requirements that permit acceptance of the combustibility hazard. Grade 3 filters are readily
combustible and are used only where high-value product recovery by incineration is desirable,
disposal of volumes are critical, or exposure to chemical atmospheres might be incompatible
with the use of a HEPA filter incorporating a medium of glass fibers. These filters comply with
UL 900.
4.1.2.2 Filter Performance Levels
IEST-RP-CC001 classifies filter performance levels as:
Type A Filter Performance. Sometimes referred to as industrial types, these filters are tested
for overall penetration at rated flow only. The filter retention (inverse of penetration) should
exceed 99.97 percent for 0.3-µm particles.
Type B Filter Performance. In addition to the basic requirements for Type A filters, Type B units
are certified free of significant pinhole leaks that would cause penetration at low flow rates.
DOE-HDBK-1169-2022
28
This type is tested at 20 percent of rated airflow as well as at rated flow with the filter
encapsulated to disclose casing or gasket leaks. This type is sometimes referred to as “nuclear-
type.”
Type C Filter Performance. In addition to the performance required of Type A filters, Type C
filters, are tested with the use of air-generated test aerosols at 80 to 100 feet per minute (fpm)
face velocity. The units are fully face-scanned to detect and eliminate all significant leakage
streams greater than 0.01 percent of the upstream test aerosol concentration to which the
filter is subjected.
Type D Filter Performance. In addition to the testing required for Type C filters, Type D filters
should be retested at their rated airflow and penetration, which should be no more than 0.001
percent of the upstream concentration. The filter unit should be encapsulated so that all
components, including the filter pack, frame, and gasket, are subjected to testing. In the U.S.,
laser spectrometers are used to measure efficiencies of ULPA filters (>99.999 percent).
Type E Filter Performance. Type E filters are designed, constructed, and tested in strict
accordance with military specifications for HEPA filters intended for biological use. This type is
for application in air cleaning or filtering systems involving toxic chemical, carcinogenic,
radiogenic, or hazardous biological particulates. This type is referred to as a “biological unit.”
Type B filters are recommended for most nuclear applications, particularly in single-pass
systems, and should be qualified in accordance with UL-900. These units comprise a large part
of those manufactured by industry and are used extensively in nonnuclear industries as well.
Type C filters are common in clean room applications where laminar flow requirements are
coupled with low particle penetration and should be qualified in accordance with UL-900. Type
D filters presently are used in printed-circuit or microprocessor clean rooms and should be
qualified in accordance with UL-900.
4.1.2.3 Enclosed Filters
Section 31
Most HEPA units are used in the open-face configuration (Figure 4.3). When used in this
manner, the filter is secured firmly to a rigid framework by a pressure device such that a leak-
free seal exists between the unit and the framework. The HEPA filter may also be placed
completely within an enclosing casing that is equipped with nipples at both ends for
attachment to existing ventilation ducts (Figure 4.6). Enclosing casings may be metal or
plywood, but care should be taken to ensure the casing material is compatible with UL
requirements for resistance of the filter to heated air and flame. The enclosing casing forms the
leak-free pressure boundary in addition to the filter case, and care should be taken to ensure
that it is treated as an encapsulated design for both performance and leak-acceptance testing.
Enclosed HEPA units have significantly higher resistance to airflow than the open-faced design
because of the added restrictions of the duct transitions.
DOE-HDBK-1169-2022
29
Figure 4.6: Enclosed HEPA Filter
Enclosed filters are sometimes referred to as encapsulated (nipple-connected, closed-face, or
self-contained) HEPA filters. ASME AG-1, Section FK contains information on Special HEPA
Filters, including radial flow filters that may be considered a subset of encapsulated HEPA
filters. Specific guidance applicable to nipple-connected filters is currently not available but is
under development by ASME for inclusion in ASME AG-1.
4.1.2.4 Cylindrical Filters
Cylindrical filters may be either open-faced cylindrical axial (Figure 4.7) or radial flow (Figure
4.8). Filters fabricated with cylindrical cases are easily mounted in circular ducts and offer
significant advantages regarding simplified gasketing and automated filter-changing techniques.
A “push-through filter system” permits changing of cylindrical filters by loading a clean filter
that has gaskets on the top and bottom filter flanges into the filter housing tube from the
“clean side,” then pushing it through until it ejects the old, contaminated filter into the “dirty
side” of a cell or glovebox.
Figure 4.7: Open-Faced, Cylindrical Axial Flow HEPA Filter
DOE-HDBK-1169-2022
30
Figure 4.8: Radial Flow HEPA Filter
4.1.2.5 Filter Sizes
The physical dimensions shown in Table 4.1 have been standardized for the HEPA filters
currently used in nuclear service and by U.S. Government agencies. Other sizes can be
manufactured and purchased but are considered “special orders.” Special applications such as
clean rooms, biological safety cabinets, and medical facilities, generally use the same filter
height and depth dimensions shown in Table 4.1 but may have lengths up to 72 inches. Filter
configurations for computer applications use many different sizes and shapes depending on the
volume available within the computer cabinet.
Table 4.1 (from ASME AG-1, Section FC-4100, “HEPA Filters,” by permission)
Table FC-4110-1 Nominal Sizes and Ratings
Number Designation
Size Minimum Rated Airflow Maximum Resistance
in. mm scfm m3/h in. wg Pa
1 8 × 8 × 31∕16 203 × 203 × 78 25 40 1.3 320
2 8 × 8 × 57∕8 203 × 203 × 150 50 80 1.3 320
3 12 × 12 × 57∕8 305 × 305 × 150 125 210 1.3 320
4 24 × 24 × 57∕8 610 × 610 × 150 500 850 1.0 250
5 24 × 24 × 111∕2 610 × 610 × 292 1000 1700 1.0 250
6 24 × 24 × 111∕2 610 × 610 × 292 1250 2100 1.3 320
7 24 × 24 × 111∕2 610 × 610 × 292 1500 2500 1.3 320
8 24 × 24 × 111∕2 610 × 610 × 292 2000 3400 1.3 320
9 12 × 12 × 111∕2 305 × 305 × 292 250 420 1.3 320
Section 32
4.1.2.6 Filter Weight
The weight of a filter unit is an important factor in design and maintenance. Table 4.2 lists the
weight of clean, open-faced filters and enclosed filters of rectangular design (ASME AG-1
Section FC). The weights for radial, metal, and ceramic filters differ. For design purposes, the
weight of a dirty filter that is ready for change-out is approximately 4 pounds heavier per 1,000
cubic feet per minute (cfm) of rate capacity. Because many applications employ multiple filter
units in banks that are as many as 6 to 10 units in height, minimal filter weight without loss of
performance is critical to the ease of original installation and replacement. New and modified
DOE-HDBK-1169-2022
31
ventilation system designs should consider the recommendation in USNRC11 Regulatory Guide
1.52 that filter housings are no more than 3 HEPA units high for ease of maintenance and
changeout.
Table 4.2: Weight of Unused HEPA Filters
Filter Size (inches)
Nominal Airflow Capacity
(cfm)
Approximate Weight (pounds) of Filters
Wood Case Steel Case
Open-face
8 x 8 x 5-7/8 50 3.6 5.8
12 x 12 x 5-7/8 125 4.8 7.3
24 x 24 x 5-7/8 500 17 22
24 x 24 x 11-1/2 1000, 1250, 1500 32 40
24 X 24 X 11-1/2 2000 NA 85
Enclosed
8 x 8 cross-section 25 5 9
8 x 8 cross-section 50 7 10.5
12 x 12 cross-section 125 17 20
24 x 24 cross-section 500 64 72
24 X 24 cross-section 1000 78 95
4.1.3 HEPA Filter Performance Characteristics
4.1.3.1 Airflow Resistance
Resistance to airflow (pressure drop) of a clean nuclear-grade, 1,000 cfm capacity filter should
not exceed 1 inch water gauge (in. wg) when tested at rated airflow for ASME AG-1 Section FC,
HEPA Filters. See Table 4.1 for additional filter capacities and pressure drops. Pressure drop
may vary for other filter types, e.g., metal, radial flow, and ceramic filters. For these filters,
higher initial pressure drop may result in higher rated flow. The pressure drop for ULPA filters is
frequently greater than for standard HEPA filters, and this feature is subject to negotiation
between customer and vendor. Resistance increases with particulate loading. A new nuclear-
grade filter is qualified by a wet overpressure test up to 10 in. wg for 1 hour; however, this
should not be confused with normal in-service operating pressures. Normal in-service pressures
should be limited to 3 to 5 in. wg above startup pressure to maintain reliable operation.
4.1.3.2 Dust-Holding Capacity
The dust-holding capacity of a filter is a function of the type, shape, size, and porosity of the
filter as well as the aerosol size, shape, and concentration characteristics to which the filter is
exposed. As HEPA filters are designed to filter out the smallest particles, they can accommodate
only extremely light particulate loadings without experiencing a rapid pressure drop increase.
HEPA filters are affected particularly adversely by fibers, lint, and other materials that exhibit a
11 U.S. Nuclear Regulatory Commission
DOE-HDBK-1169-2022
32
large length-to-diameter ratio because they tend to bridge the air entrance gaps between the
adjacent pleats of medium, thereby preventing particles from accessing the full depth of the
filter. A HEPA filter can be protected by a medium efficiency filter capable of removing the bulk
of large particles and fibers, thereby extending its useful lifetime.
Section 33
As noted earlier, a dust-holding capacity of 4 pounds per 1000 cfm of rated airflow capacity
may be assumed for design purposes for ASME AG-1 Section FC, HEPA Filters. Different dust-
holding capacities should be considered when using emerging technology filters, such as metal,
high-strength, or ceramic filters. An increase in dust accumulation on the filter medium
improves filtration efficiency and increases resistance to airflow. One of the limitations of HEPA
filters is their low-dust-holding capacity and their need for frequent replacement when exposed
to high aerosol concentrations. The pressure rise curve experienced by HEPA filters also
depends on the particulate composition and concentration of the atmosphere to which it is
exposed. A filter installed in a moderately contaminated urban area will show as much as a six-
fold increase in resistance in a year's time, whereas a unit in a clean room application may last
ten years or longer before reaching a sixfold pressure increase. The use of a medium efficiency
filter (described in Section 4.1.5) increases the service life of HEPA filters and helps make the
combined filtration system cost effective.
For high dust-loading applications, bag house filters are useful due to the ability to self-clean by
intermittent back-pulsing of the filters.
4.1.3.3 Shock and Blast Resistance
The resistance of HEPA filters to shock and blast is important because these filters are often the
final barrier between a highly contaminated enclosure and the environment. Shock stress may
occur from disruptive natural phenomena (e.g., earthquakes) or from internal and external
explosions.
The values listed in Table 4.3 are the maximum shocks that can be tolerated without visible
damage or loss of filtration efficiency. These data show that: (1) filters with faceguards on both
faces had about a 40 percent greater resistance to shock than those without faceguards; (2)
dirt-loaded filters had 15 percent less shock resistance than clean filters; (3) the smaller the
filter face area, the greater the resistance to shock; (4) the greater the filter depth, the greater
the resistance to shock. At overpressures exceeding those listed in Table 4.3 by 0.5 to 1.0 psi,
the filter medium ruptured or experienced cuts on the downstream face. At pressures 2 pounds
per square inch (psi) greater than those listed in Table 4.3, extensive damage occurred. At
pressures above 5 psi, the entire filter pack within the frame was dispersed. No significant
differences were found between successive tests of increasing shock force on the same filter
and a one-shot test of the same force—both procedures produced the same failure modes.
DOE-HDBK-1169-2022
33
Table 4.3: Shock Overpressure Resistance of Open-face HEPA Filters
Filter Dimensions (inches) Overpressure (psig)
Recommended Design Limit for Used Filters
Face Depth Overpressure at Failure a With Faceguards Without Faceguards
8 x 8 3 1/16 3.7 b 2.0
8 x 8 5 7/8 4.5 b 2.5
12 x 12 5 7/8 3.6 b 2.0
24 x 24 5 7/8 2.2 1.7 1.2
24 x 24 11 1/2 3.2 1.7 1.8
a Clean filter with 4 by 4 mesh faceguards on both faces.
b These filters when tested did not have faceguards.
4.1.3.4 Heat from Fire and Explosion
Section 34
Grade 1 fire-resistant filters as defined by IEST are fabricated from a glass medium with flame-
inhibited or self-extinguishing adhesive or sealant, aluminum alloy separators, and fire-
retardant wood or metal frames. Nevertheless, the material that collects on the filters poses
special fire and explosion hazards when it contains substantial amounts of organic or
pyrophoric substances. Fires from this source can produce undiluted hot gases that attain
temperatures as high as 1,830 degrees Fahrenheit. The softening point of glass fibers used in
currently manufactured HEPA filter media is about 1,250 degrees Fahrenheit, and direct
impingement of a 1,700 degrees Fahrenheit flame will cause immediate melting. A glowing
solid particle that lands on HEPA filter media will perforate it if it continues to burn. Explosions
that could destroy or seriously damage the filter from high pressure, shock waves
(overpressures), or an excessive temperature excursion can also occur from ignition of organic
or pyrophoric dusts, vaporized organics, or combustible gas products of combustion. The spark
and flame arresters installed upstream of the filters are designed to alleviate this problem.
Spark arresters constructed of coarse glass fibers provide reasonable protection at low cost.
Spark and flame arresters constructed of grids or heavy wire mesh that provide graduated
openings are required to provide a 2-minute delay before flame penetration. Filters using
emerging technologies, such as ceramic pre-filters, may also be used to prevent direct flame, or
burning ember, impingement on HEPA filters. See DOE STD-1066 and Section 5.1.3.34 for
additional information.
The recommended limitation for filter operating temperature is 250 degrees Fahrenheit. The
filter media binder is assumed to be the HEPA filter component that is most susceptible to
failure resulting from elevated temperature. The binder begins burning off at 350 degrees
Fahrenheit. Commonly used sealants are also highly susceptible to elevated temperatures.
Tables 4.4 and 4.5 list continuous-service temperatures for wood- and steel-cased filters. At
temperatures well below the char point of an elastomeric sealant, the sealant loses its shear
strength, resulting in a reduction from approximately 6,000 kPa at room temperature to a low
of 100 kPa at 300 degrees Fahrenheit. HEPA filters exposed to thermal stress will begin to
release contaminates at temperatures above 300 degrees Fahrenheit.
DOE-HDBK-1169-2022
34
Table 4.4: Recommended Limited-Service Temperatures for Steel-Framed Fire-Resistant HEPA
Filter Units Sealed with Elastomeric Adhesives
Temperature to Which Filter was Exposed (degrees Fahrenheit)
Sealant Used
Up to 10 Min a
Up to 2
Hours Up to 48 Hour Up to 10 Days > 10 Years
HT-30-FR b 750 350 325 300 260
Z-743 c 750 325 300 275 200
EC-2155 d 750 250 220 200 200
Polyurethane foam 750 325 300 275 230
a Some reduction in efficiency may occur after 5 minutes of exposure.
b Goodyear.
c Pittsburgh Plate Glass.
d Minnesota Mining and Manufacturing (3M).
Table 4.5: Recommended Limited-Service Temperatures for Wood-Framed Fire-Resistant
HEPA Filter Units a
Frame Material Temperature to Which Filter was Exposed (degrees Fahrenheit)
Up to 10 Min Up to 2 Hours Up to 48 Hours Up to 10 Days b > 10 Years a
¾ inch thick plywood a, c 750 300 275 200 180
a Subject to sealant limitations given in Table 4.4
b Maximum temperature of 120 degrees Fahrenheit where relative humidity is 75 percent or higher.
c Exterior grade, fire-retardant-treated.
Section 35
4.1.3.5 Moisture and Corrosion Effects
Water exposure is unquestionably an important factor leading to the deterioration of HEPA
filters. Detrimental effects occur as a result of repeatedly wetting the filter and drying it.
Repeat wetting and drying of a HEPA filter causes a loss of strength. There also are very strong
effects of operational time on the behavior of HEPA filters under wet conditions. In such
conditions, the binder starts to get soft and dissolves at high differential pressures. One of the
most serious issues dealing with HEPA filters in DOE facilities is their potential for rupture
during accidental fires and the resulting release of radioactive smoke and soot particulates.
Moisture and corrosion effects may be minimized by the use of emerging technology filters,
such as metal media and ceramic filters.
The most likely scenario for filter damage in these systems involves filter plugging by the water
spray, followed by fan pressure blowing out of the medium. Water repellency is important for
units that are used in laboratory and industrial applications. Repellency is measured by the
height of a water column that does not leak through the paper. A water repellency of 20 in. wg
is required for filters that are operated in high-humidity conditions and stream-containing
DOE-HDBK-1169-2022
35
atmospheres. In the absence of adequate water repellency characteristics, liquid contaminants
that collect on the filter medium can be carried through it by air pressure or capillary action and
become re-entrained into the downstream air.
Humidity
High relative humidity can result in high pressure drop and a corresponding decrease in media
strength, the combination of which can lead to structural damage and a loss of filter efficiency.
The most frequent failure mode is rupture of the downstream pleat. With particle deposits, the
filter would absorb water at a lower relative humidity and would rupture even with a demister
installed to protect the filter.
Corrosion
For many industrial applications, a moisture- and chemical-resistant filter should be capable of
withstanding attack by acids, most gas-phase alkalis, and solvent droplets and vapors. However,
fine glass fibers have poor resistance to hydrogen fluoride (HF), only moderate resistance to
other concentrated acids, and fair resistance to water and milder chemical corrosive agents. On
occasion, corrosive chemicals in the airstream will condense on the filter medium, accelerating
the attack on the finest fibers. Airstreams containing some residual HF and droplets of liquid
carryover after treatment by an alkali scrubber produce a severe attack on the glass fiber filter
medium.
A wooden case is more resistant to chemical attack than is a steel case. Exterior-grade material
should be specified, however, because interior-grade plywood is unsuitable for outdoor filter
operation or for continuous interior operation in very humid (90 to 100 percent relative
humidity) environments at temperatures above 131 degrees Fahrenheit (55 degrees Celsius),
particularly when operation and shutdown periods alternate and the environment returns to
room temperature. During cooling, moisture may condense on the surfaces of the wooden case
and infiltrate the structure, causing swelling of the elements and a separation between the seal
and frame. Most exterior-grade wood products employ a moisture-impermeable phenolic resin
bonding agent, while water-soluble urea-formaldehyde resins are used as bonding chemicals
for interior-grade products. Stainless steel is recommended when a metal frame is required.
Mildew growth may occur on the sealant and frame interface in high humidity while the filter is
in storage, causing filter degradation.
Section 36
4.1.3.6 Radiation Resistance
Most applications for HEPA and ULPA filters in the electronics and other industries do not
involve exposure to high levels of ionizing radiation. However, post-accident cleanup by nuclear
reactor containment systems and some fuel reprocessing applications of facilities can involve
exposure of filters to high levels of radiation. Reactor accidents can result in an integrated beta-
gamma dose to the Engineered Safety Feature (ESF) filters of 3.5 x 107 rads. This radiation level
can result in a significant reduction in tensile strength, an increase in penetration, and an
impairment of water repellency. For these reasons, emerging technology filters, including metal
media and ceramic filters, are better suited to high radiation environments.
DOE-HDBK-1169-2022
36
When samples were tested for degradation of water repellency as a function of gamma dose,
half of the samples showed hydrophilic action in less than 10 seconds and the remainder in 60
to 100 seconds. The ASME AG-1, Section FN Filter Media: High Efficiency, requires filter media
to support a 6-inch column of water after exposure to an integrated gamma dose of 6.0 to 6.5 x
106 rads. Other tests exposed small HEPA filters to a range of radiation doses, and then
exposed them to a flowing steam-air mixture to determine the residual resistance to plugging
and rupture. Plugging was found to be inversely proportional to radiation dose (e.g., filters
exposed to 6 x 10 6 rads ruptured in 100 seconds) but a sample irradiated to only 1 x 106 rads
withstood the steam-air mixture for 250 seconds before failure. Despite some blinding (water
vapor interference with particulate capture), unirradiated samples did not rupture under the
same flow regimen. These tests verified the need to provide filter systems with reliable
protection from wetting wherever exposure to spray or condensing steam is possible,
particularly when water exposure may be coupled with high levels of radiation.
4.1.4 HEPA Filter Performance Testing for Nuclear Service
HEPA filters for nuclear service undergo a qualification procedure and two testing regimens.
The first regimen consists of a stringent visual examination and penetration tests at the place of
manufacture. The second regimen is an in-place leak test performed at the place of utilization.
DOE requires an additional independent inspection and penetration tests at the designated
DOE Filter Test Facility (FTF) prior to installation at its destination, in accordance with DOE-STD-
3025.
The manufacturer’s testing regimen involves two distinct phases: (1) a quality control (QC)
routine to ensure careful manufacture of the product, and (2) a series of tests to verify filter
compliance with standards and performance criteria related to collection efficiency and
resistance to airflow. When all factors are within the tolerance limits set by applicable
specifications, the manufacturer certifies that each filter unit meets the specification
acceptance criteria.
Section 37
In addition, DOE-STD-3020 and DOE-STD-3025 provide additional information on DOE
mandated independent inspection and penetration testing for specific types of filter purchases.
Testing is currently required for filters installed in Hazard Category 1 and 2 facilities that
perform a safety function, and a statistical approach for the balance. The filters are tested for
compliance with the requirements for physical characteristics, efficiency, and airflow
resistance. This testing is conducted at the DOE-supported independent FTF before the filters
are released to the customer’s facility. The purchaser/customer should request that the
manufacturer’s test report and a Certificate of Compliance be forwarded for documentation.
Filters failing to meet the FTF specification acceptance criteria are rejected and turned over to
the purchaser for disposition; typically, they are returned to the manufacturer for credit. Both
DOE and the NRC do not permit repairs of HEPA filters intended for nuclear service.
In addition to the two regimens, qualification of HEPA filters is performed by the Edgewood
Chemical and Biological Center at Aberdeen Proving Grounds, MD. The required qualification
tests are specified in DOE-STD-3020-2015.
DOE-HDBK-1169-2022
37
4.1.4.1 Airflow Resistance
The resistance of a filter to airflow, often expressed as “pressure drop” and “back pressure,” is
almost always measured as the height of a water column that exerts an equal pressure. The
characteristic flow regime through HEPA filter media is aerodynamically described as laminar.
For this reason, the airflow resistance of these filters changes in direct proportion to changes in
air volume throughput (expressed as feet per unit area), even though the air approaching the
filter may be turbulent. The direct proportionality of resistance to flow rate is not a
characteristic of medium efficiency filters. For medium efficiency filters, resistance is a power
function of airflow with an exponent larger than 1, but not exceeding 2.
The test protocols used to qualify HEPA filters for nuclear service are described below. Testing
of all new filters intended for nuclear service in the United States (U.S.) is conducted with a 0.3-
µm test aerosol in a rig called a Q107 penetrometer that was designed by the U.S. Army
Chemical Corps during the 1950s. Construction and operation are described in MIL-STD-282,
Method 102.9. The complete penetrometer consists of test aerosol generator, an instrument
that measures the size and uniformity of the particles formed, a clamping device to seal the
filter under test into the test rig, a total scattering photometer to measure test aerosol
penetration, and a manometer to measure filter resistance at rated airflow.
The Q107 penetrometer is used for filters of 1,700 m3/hr rated capacity, and the Q76
penetrometer tests smaller filters. When testing a 1,700 m3/hr filter, about 2,400 m3/hr of
outside air is drawn into the system and divided into 3 parallel ducts that carry approximately
170, 500, and 1,350 m3/hr, respectively. The remainder, approximately 350 m3 /hr, is exhausted
through another path. The 170 m3/hr duct contains electric heaters that raise the temperature
of the air to 374 degrees Fahrenheit (190 degrees Celsius). Other electric heaters keep the
liquid test aerosol reservoir heated to approximately 392 degrees Fahrenheit (200 degrees
Celsius). The test aerosol is vaporized from the reservoir into the heated airstream as it sweeps
across the liquid surface and is mixed with the air in the 500 m3 /hr duct that contains both
cooling units and reheaters to provide partial dilution and temperature control of the test
aerosol vapor stream.
Section 38
The temperature of the test aerosol liquid reservoir establishes the mass concentration of the
aerosol; a liquid temperature of 392 degrees Fahrenheit (200 degrees Celsius) produces 80 to
100 µg/L of test aerosol when diluted with 2,400 m3 /hr of air. The particle size of the aerosol is
determined by the temperature differential between the evaporated test aerosol vapor stream
and the much cooler diluting stream—the greater the temperature differential, the smaller the
resulting particle size. Temperature fluctuations in both airstreams influence particle size
distribution; the greater the fluctuation, the wider the size distribution. The combined flows
from the 170- and 500-m3 /hr ducts are diluted further with the air in the 1,350-m3 /hr duct to
produce the final aerosol concentration used for filter testing. Baffles are placed upstream and
downstream to help mix the aerosol entering and leaving the filter being tested.
The test aerosol particle size is determined by passing a sample through an optical particle-
sizing instrument called an OWL and noting the degree of polarization of a light beam. A
polarization angle of 29 degrees indicates a particle diameter of 0.3 µm when the aerosol is
monodispersed.
DOE-HDBK-1169-2022
38
The optical device used to measure particle concentration is a forward-angle, light-scattering
photometer capable of measuring scattering intensity over a range of at least five orders of
magnitude. Current commercial instruments can give a useful signal with a concentration as
low as 10 particles/cm when finely tuned and used by a skilled operator. For routine testing, a
downstream concentration of 10-4 mg/m can be measured with reliability when the upstream
concentration is 10 mg/m, indicating a filter efficiency of 99.99 percent for the test aerosol. This
level of measurement is considered adequate for nuclear applications (in view of the lesser
efficiency credit regularly assigned to filters by regulatory authorities), however, manufacturers
of microelectronic chips have sought filters with much higher retention efficiency.
ULPA filters have an efficiency of 99.999 percent for particles in the 0.1-µm range, which is the
minimum filterable particle size for currently manufactured HEPA filters operating at their
design airflow. This degree of efficiency is beyond the range of the Q107, but a laser
spectrometer has been developed that can measure filter performance at much higher
efficiencies and for smaller particle diameters. This device measures the sizes of individual
particles in an aerosol and displays the particle-size distribution on a screen and a printout.
When used with a polydisperse aerosol challenge, it can measure penetration values as low as
1x10- 9 in a range of particle diameters from 0.07 to 3.0 µm. Use of duplicate instruments
upstream and downstream permits the determination of a “particle size-collection efficiency”
table or chart for individual filters at a modest cost and within a reasonable period of time.
Laser spectrometers can also be used to determine such important filter performance
parameters as maximum penetrating size, efficiency of filters in series, and the optimum
formulation of filter fibers. Operator training is still an important issue, as is recognition that
most lasers are calibrated using polystyrene latex (PSL) rather than the test aerosol. The
properties of PSL (e.g., refractive index) are not identical to the test aerosol. This can produce
inaccurate results unless operators understand the differences and set up the equipment
properly. Upstream concentration is also critical because lasers can be blinded by the passage
of too many particles to the counter. Most successful applications use calibrated particle
diluters to ensure the laser is not overwhelmed.
Section 39
4.1.4.2 Quality Control/Assurance Considerations
Systematic QC and quality assurance (QA) testing are conducted at all stages of the product
cycle from development to use. The filter medium receives the most rigorous and extensive
control and evaluation, perhaps because its development and manufacture necessarily demand
a degree of art as well as science. Performance of the filtration medium is determined by a
thermally generated monodispersed aerosol generated by a Q127 penetrometer, a smaller
version of the Q107 used to test cased filters. The physical characteristics of the medium are
controlled by a battery of standard test protocols developed by the TAPPI, ASTM, and ASME
AG-1.
After fabrication, in addition to measuring the efficiency and airflow resistance of the filter
assembly with a Q107 or a Q76 penetrometer (depending on the rated airflow capacity and
physical size of the filter), a series of physical tests described in ASME AG-1, Section FC and FK,
are applied to filter prototypes for qualification. These include tests of dimension tolerances
DOE-HDBK-1169-2022
39
and resistance to rough handling, pressure, heated air, flame, and unfavorable environments
(temperature and moisture extremes).
Nebulized Sodium Chloride
The standard test method used in Great Britain for new HEPA filters utilizes a dried sodium
chloride aerosol generated from solution with a compressed air nebulizer. An emission-flame
photometer is used to measure the quantity of sodium chloride entering and leaving the filter
being tested. The dried aerosol particles have a concentration of about 3 mg/m3, a mass median
diameter of 0.65 µm and a geometric standard deviation of 2.1. The test rig and test procedures
employed do not differ significantly from those used in the U.S., Germany, and a number of
other countries.
Nebulized Uranine
The French standard test method, AFNOR NFX 44.011, uses dried particles of uranine, a
fluorescent material generated from a solution with a compressed air nebulizer. The aerosol
concentration for the test is about 8 × 10-3 mg/m. The mass median diameter of the particles is
0.15 µm, with a geometric standard deviation of 1.55. Aerosol samples are extracted from the
test apparatus upstream and downstream of the filter being tested and are collected on filter
media. After the sampling period has expired, the filter media are extracted in water and
analyzed by fluorimetry. Filter efficiency is expressed as the percent by weight of fluorescent
particles collected by the filter. Because of the need to collect samples over some averaging
period (e.g., 10 minutes) and then to extract the uranine quantitatively from the filters and read
the fluorescence intensity in a fluorimeter, about 30 minutes is required for an analysis. Direct
readout of filter efficiency is characteristic of most other standard test procedures.
4.1.5 Effects of Aging, Wetting, and Environmental Upsets on HEPA Filter Performance
Intuitively, the aging of filters in storage or in use in-place should lead to a higher probability of
media or structural failure. With aging, HEPA filters lose strength and water repellency but do
not necessarily become less efficient. Logically, it follows that filter efficiency depends on the
physical geometry of the filter media and is not significantly affected when the organic binders
and sealants become brittle or degrade with age. Filter strength prevents structural failure
during events that produce high stress across filter media, e.g., when particle deposits and
water accumulation cause filter plugging.
Section 40
Historical measures of filter strength are: (1) the tensile strength of the paper in combination
with a 10-inch overpressure test on the filter, and (2) burst strength. Burst strength (the
pressure required to tear open the media) quantitatively measures two-dimensional stretches
as compared to the one dimension used to measure the tensile strength. The brittleness of the
media, which is measured by flexing it, is a third major strength measurement, although it is
not generally measured in aging studies.
4.1.5.1 Aging
The deterioration mechanisms involved in HEPA filter aging are:
• Aging and weakening of glass fibers.
DOE-HDBK-1169-2022
40
• Deterioration of the resin binder and the organic sealant.
• Corrosion of the aluminum separators.
• Moisture damage.
• Mechanical stresses caused by handling the filter and airflow pulses.
Aging of filters leads to degradation in performance. It has generally been accepted that a
conservative approach indicates that the maximum total life (storage and in-service) of HEPA
filters for consistently removing greater than 99.97 percent of 0.3-micron particles from highly
hazardous aerosols is 10 years from the date of manufacture for applications in dry systems,
and 5 years in applications where the filter can become wet more than once for short periods
of time. If a filter gets wet it should be replaced expeditiously. Guidance and recommendations
can be found in ASME AG-1 Non-Mandatory Appendix FK-A, Determination of HEPA Service
Life. Ongoing research12 on HEPA filter shelf and service life has begun publication (Refs 20, 21,
22, 59, 60, and 61) and can be referred to as guidance in developing a HEPA filter Service Life
program. See also the graded-approach PNNL document TPD-012 for HEPA filters.13 Note that
service life as used herein refers to storage and service of the HEPA filter, and thus the
manufactured date of the HEPA filter is critical.
The date of manufacture may not be retrievable for currently installed filters. If this information
is available (without having to remove the filter to retrieve the data on its frame), the filter
service life can be determined based on the date of manufacture. If the date of manufacture is
not available, the date of installation will be used. If neither is available, the filter will be
assumed to be over 10 years old and should be considered for replacement.
4.1.5.2 Upset Environmental Conditions
Document 12.5 of the Lawrence Livermore National Laboratory (LLNL) Environment, Safety, and
Health Manual, HEPA, HEGA, and ULPA Filter System Design for LLNL Applications, states that
continuous exposure to the following operational environments will permanently damage or
compromise HEPA filters:
• Moisture: 95 to 100 percent relative humidity.
• Hot Air: Temperatures higher than 275 degrees Fahrenheit.
• Fire: Direct fire or high concentrations of particulate matter produced by fire.
• High Pressure: 8.0 in. wg or more, internal or differential across the filter media.
• Corrosive Mist: Dilute moist or moderately dry concentrations of acids and caustics.
• Any acid and some caustics will attack uncoated aluminum separators.
• Hydrofluoric acid will attack the media.
12 For further information, see “Effects of Aging on Nuclear Grade HEPA Media and Filters Summary Report, 21-REP-DOE-
AGING-FINAL, July 2021 prepared by Mississippi State University Institute for Clean Energy Technology”
13 https://www.researchgate.net/publication/326882075_PNNL_Technical_Position_Document_TPD-
012_Regulated_HEPA_Filters
Section 41
https://www.researchgate.net/publication/326882075_PNNL_Technical_Position_Document_TPD-012_Regulated_HEPA_Filters
https://www.researchgate.net/publication/326882075_PNNL_Technical_Position_Document_TPD-012_Regulated_HEPA_Filters
DOE-HDBK-1169-2022
41
• Nitric acid will attack wooden boxes making highly flammable nitrocellulose.
• Shock Pressures: More than 1.7 psig.
In addition, the filter exterior should not be exposed directly to outdoor environments.
The following criteria are recommended:
• Wetting: A single occurrence of filter exposure to water including entrained droplets
from actuation of sprinklers in the area upstream of the filters, rain or groundwater, or
condensation from a leak of steam or hot water.
• Moisture and Hot Air: HEPA filters may be operated continuously at 180 degrees
Fahrenheit and between 5 and 75 percent relative humidity, or at 120 degrees
Fahrenheit and between 75 and 95 percent relative humidity. HEPA filters are not to be
used for installations where there is a possibility of condensation forming on them. They
will provide maximum service life when operated below 100 degrees Fahrenheit and 75
percent relative humidity.
• Fire: A single occurrence of direct flame impingement.14
• High Differential Pressure: A single occurrence of a differential pressure across a single
filter of 8.0 in. wg or more.
• Shock Pressure: A single exposure to more than 1.7 psig.
• Corrosive Mist: Prolonged exposure (more than 4 weeks) to dilute moist or moderately
dry concentrations of acids and caustics.
4.1.5.3 In-Place Testing of Filter Installations
An in-place leak test is done after filters are installed at a nuclear facility to ensure the
performance of the confinement ventilation system. The in-place leak test is used both for an
acceptance and for surveillance leak testing of the installed HEPA filter bank. An in-place leak
test and visual inspection of HEPA filters are performed initially upon installation to detect
bypasses and damage to filters and periodically to establish current condition of a nuclear air
cleaning system and its components. Specific objectives of in-place filter testing are (1) to test
the aggregate performance to filters in a filter bank, (2) to evaluate the effectiveness of seals
between the filter gasket and the filter housing, (3) to assess the leak-tightness of the filter
housing, and (4) to determine whether bypasses exist around the filter housing. Each time
repairs are made, the system should be retested until it meets the established criteria for leak-
tightness.
4.1.5.4 Packaging, Storage, and Handling of HEPA Filters
The manufacturer should have a quality program such as ASME NQA-1 for the packaging,
shipping, handling, and storage of HEPA filters. HEPA filters are normally packaged in
14 Filters subjected to smoke from fires should have an in-place leak test performed on them immediately by the
responsible in-place testing group (i.e., within 24 hours) and should be replaced if the filter fails the in-place leak
test.
DOE-HDBK-1169-2022
42
Section 42
corrugated cardboard cartons that conform to shipping regulations. Additional internal pieces
are inserted to protect the filter faces from damage during handling and transit. Palletizing
crating should be constructed for ease of disassembly. For multiunit shipments, individual
cartons should be crated and palletized to minimize handling, particularly at trans-shipment
points when using public carriers. For very large shipments, sealed and dedicated trailers are
recommended. Note that filters shipped in less-than-truckload amounts using common carriers
are often rearranged incorrectly by the carriers, resulting in damaged filters. Upon delivery at
the destination, mechanical warehousing equipment should be used for unloading and
transferring the shipment. Cartons should be placed in clean, dry, interior storage until used.
They should be positioned as directed on the carton exterior, and no more than three filter
cartons should be stacked atop each other.
When a filter is inserted in the cardboard shipping container, the pleated folds should be
oriented in the vertical direction, except for Type B filters as defined in ASME AG-1, Article FC-
4100). For filters including Type B, both the filter frame and the enclosing carton should be
labeled with a vertical arrow or the notation, “This Side Up.” When handling a filter inside a
carton, the box should be tilted on one corner, picked up, and carried by supporting it at
diagonally opposing corners. Removing the filter from its shipping carton without damaging the
medium is best accomplished by opening and folding back the top flaps of the carton, inverting
the carton onto a clean surface, and lifting the carton off the filter. Then the filter unit can be
grasped by the outer frame surfaces without the danger of personnel coming into contact with
the filter pack enclosed within the frame. Additional details can be found in ASME AG-1 Article
FC-7000, Packaging, Shipping and Storage. For special HEPA filters, similar information can be
found in ASME AG-1 Article FK-7000, Packaging, Shipping and Storage.
4.1.6 Medium Efficiency Filters (Prefilters) for HEPA Filters
4.1.6.1 Filter Descriptions
The service life of HEPA filters can often be extended by using less efficient filters that
selectively remove the largest particles and fibers from the incoming airstream. In some cases,
HEPA filter lifetimes can be increased by as much as four times with multiple medium efficiency
filter changes during the interval between HEPA filter changes. It is recommended that HEPA
filters be protected from: (1) particles larger than 2 µm in diameter, (2) lint, and (3) particle
concentrations greater than 2.3 mg/m. Selection of an appropriate medium efficiency filter
includes consideration of: (1) the rapidity of filter resistance buildup and associated energy
costs, (2) the size and complexity of the resulting filtration system, (3) the fact that replacement
filters and associated costs generally increase with increasing medium efficiency filter
efficiency, and (4) the disposal costs for contaminated HEPA filters and potentially
uncontaminated medium efficiency filters.
It has been estimated that, with frequent medium efficiency filter replacements, savings in filter
system operation could be as much as one-third the cost of operating without medium
efficiency filters. Assessment of an acceptable combination of medium efficiency filters and
HEPA filters depends on the dust-loading and efficiency characteristics of the different filter
Section 43
DOE-HDBK-1169-2022
43
types available for the particular aerosol to be filtered. The clogging susceptibility of HEPA
filters will vary with the dust and filtration characteristics of the medium efficiency filters.
The types of filters used as medium efficiency filters are also widely used for cleaning
ventilation supply air in conventional HVAC systems. The important advantage of filtering
ventilation supply air for many operations that generate radioactive particles is a reduction in
the dust load that reaches the final contaminated filters. This helps extend the service life of
the exhaust filters, thereby reducing overall system costs because the supply air filters can be
changed without resorting to radiation protection measures—often the costliest aspect of a
contaminated exhaust filter change. These filters have a wide range of efficiencies, including 5
to 10 percent for warm air residential heating systems; 35 to 45 percent for ventilation of
schools, stores, and restaurants; and 85 to 95 percent for fully air-conditioned modern hotels,
hospitals, and office towers.
ASME AG-1 provides information on emerging technology media that can be used for medium
efficiency filters, such as metal media and ceramic filters. Section 5.1.3.34 of this Handbook
also provides further information.
The user/owner of the facility should incorporate written specifications on the service life of
the HEPA filters for change-out criteria based on the use and availability of medium efficiency
filters.
4.1.6.2 Classes, Sizes, and Performance Characteristics of Medium Efficiency Filters
Table 4.6 shows cross-reference and application guidelines for air cleaners with particulate
contaminants. For comparison purposes, the HEPA filter is rated at 100 percent for both the
stain-efficiency and artificial dust arrestance tests. Because the atmospheric dust test is based
on the staining capacity of the dust that penetrates the filter, compared to the staining capacity
of the entering dust, it is not a true measure of particle-removal efficiency for any one particle-
size range.
Values stated in Table 4.6 for dust-holding capacity were determined with resuspended
synthetic dust mixtures. Dust-holding capacity varies with the nature and composition of the
particles (e.g., carbon black, cotton linters). Dust-holding capacity under service conditions
cannot be predicted accurately on the basis of manufacturers’ data. Air resistance is the
primary factor in medium efficiency filter replacement. Although manufacturers recommend
specific values of resistance for medium efficiency filter replacement, loss of adequate airflow is
often a more reliable indicator of system performance and is also more cost effective. Panel
filters will plug rapidly under heavy loads of lint and dust. An accumulation of surface lint may
increase the efficiency of an extended-medium efficiency filter by adding “cake” filtration
principles to the existing physical mechanisms.
The extended-medium efficiency filter will plug readily in an airstream carrying profuse smoke
and soot from a fire. Operation at airflows below rated capacity will extend the service lives of
filters and be more cost effective by reducing the frequency of filter replacement. On the other
hand, when airflow exceeds rated values, dust-loading rate and system costs begin to increase
exponentially along with proportional increases in airflow. ASHRAE’s Standard 52.2-2017 gives
methods for testing filter efficiency by particle size using optical particle counters, including
Section 44
DOE-HDBK-1169-2022
44
lasers, and defines MERV as the minimum efficiency reporting value corresponding to a specific
intended dust spot efficiency.
Table 4.6: Dust-Holding Capacity
4.1.6.3 Commercial and Industrial Grade Filters Performing as Medium Efficiency Filters
As previously discussed, medium efficiency filters (prefilters) provide protection for HEPA filters
and extend their service life by removing large particles and other particulate matter in the
flowing air stream. In addition to medium efficiency filters that satisfy the requirements of
ASME AG-1 Section FB, ANSI/AHRI Standard 850 (I-P)-2013, provides information and classifies
commercial and industrial grade filters that perform the same function. These filters are
classified into groups:
Group I - Unit or panel
Group II - Extended surface
Group III - Electronic Air Cleaner
Group IV - Air Filter Media
Group V - Self-cleaning, Self-renewable Air Cleaner, or any combination thereof
Group I panel filters (viscous impingement filters) are shallow, tray-like assemblies of coarse
fibers (glass, wool, vegetable, or plastic) or metal mesh enclosed in a steel or cardboard casing.
The medium is usually coated with an inhibited viscous oil or adhesive to improve trapping and
retention of particles. Single-use disposable and cleanable-reusable types are available. The
DOE-HDBK-1169-2022
45
latter have metal mesh and generally are not used in nuclear applications for effluent or
process air cleaning because of the high labor costs associated with cleaning and disposal of
entrapped radioactive materials. A disposable panel filter has a fairly high dust-holding
capacity, low airflow resistance, low initial and operating costs, and high removal efficiency for
large particles. It is particularly effective against fibrous dust and heavy concentrations of visible
particles but is ineffective for smaller particles. For nuclear service, it is less cost-effective than
the more costly Group II or V filters that provide better protection for the HEPA filter.
Group V (moderate-efficiency) and Group II (high-efficiency) filters are usually comprised of
extended-medium, dry-type, single-use disposable units. The filter medium is pleated or
formed into bags or socks to provide a large filter surface area with minimal face area. They are
not coated with adhesive. The particle size efficiency of Group V filters is moderate to poor for
sub-micrometer-sized particles, but often approaches 100 percent for particles greater than 5
µm. In most cases, the pressure drop of extended-media Group V filters varies directly with
efficiency. Group II filters are recommended for high lint- and fiber-loading applications. The
large filter area relative to face area permits duct velocities equal to or higher than those of
panel filters. For high dust-loading applications, bag house filters are useful due to the ability to
self-clean by intermittent back-pulsing of the filters.
Group II filters are preferred when higher efficiency for smaller particles is desired. The dust-
holding capacity of Group II filters usually is lower than that of Group II filters.
Group II filters are recommended for nuclear applications, and ASME AG-1 Section FB, Medium
Efficiency Filters, should be consulted for additional guidance on the design, manufacture,
operation, and maintenance of medium efficiency filters.
4.1.6.4 Electrostatic and Electrified Filters
Section 45
An electrostatic charge may be induced on filter fibers by triboelectrification and by
sandwiching the fiber bed between a high voltage and a grounded electrode. Tribo-
electrification can be used to induce a high electrostatic charge on suitable high dielectric
materials, but under practical-use conditions, the charge is subject to rapid dissipation due to
air humidity, oily particles, fiber-binding particles, and other interference. Continuously
activated electrodes can induce a more permanent charge.
Electrofibrous filters provide greater efficiency and longer service life for the medium efficiency
filters used to protect HEPA filters. They have been used in gloveboxes and for other
applications. Laboratory tests conducted at LLNL using test and sodium chloride aerosols have
shown that an electrofibrous medium efficiency filter increases in efficiency from 40 to 90
percent as 10 kV is applied to the electrode. A comparison of uncharged, triboelectrically
charged, and permanently charged fibrous filters demonstrated the higher collection efficiency
of the permanently charged filter design for sub-micrometer particles. When continuously
charged electrofibrous filters were applied as medium efficiency filters for HEPA filters in
exhaust air systems or gloveboxes used to burn uranium turnings, they significantly prolonged
the life of the final filters.
DOE-HDBK-1169-2022
46
4.1.6.5 Operation and Maintenance of Medium Efficiency Filters (Prefilters)
All medium efficiency filter construction materials should be compatible with those of the
downstream HEPA filters they are designed to protect. Therefore, they should conform to the
rigorous physical properties prescribed for HEPA filters (e.g., resistance to shock, vibration,
tornado, earthquake, moisture, corrosion, and fire). Survivability under the specific operational
conditions and requirements should be addressed when medium efficiency filters are selected
because moisture or corrosive products in the airstream may limit the choice of filter. Although
many filter media will not withstand acid or caustic attack, glass fibers are corrosion-resistant
except for fluorides. However, the casing and face screen materials may be less so. Aluminum
may deteriorate in marine air, from caustics, or from carbon dioxide. Plastics have poor heat
and hot air resistance and generally will not satisfy UL requirements. Condensation from high
humidity and sensible water may plug a medium efficiency filter and result in more frequent
replacement. In general, a medium efficiency filter made of construction materials identical to
those in the HEPA filter will have equivalent corrosion and moisture resistance. Any increase in
resistance from moisture accumulation will be greater for MERV 17-20 filters than for MERV 9-
16 filters (ASHRAE 52.2, Table E-1).
Most types of medium efficiency filters are suitable for continuous operation at temperatures
not exceeding 149 to 248 degrees Fahrenheit (65 to 120 degrees Celsius). Other types with
glass-fiber media in steel or mineral board frames may be used at temperatures as high as 392
degrees Fahrenheit (200 degrees Celsius). Users of high-temperature medium efficiency filters
should take a conservative view of performance claims, particularly claims related to efficiency
at high operating temperatures.
Section 46
Because of waste disposal requirements, the preferred choice of a medium efficiency filter for
nuclear applications is the single throwaway cartridge. A replaceable-medium efficiency filter
offers an advantage over the throwaway because the bulk of material that needs to be
discarded is smaller and handling and disposal costs are minimized. However, re-entrainment of
contaminants and contamination of the peripheral area are possible because the medium is
removed from the system and prepared for disposal. The replaceable-medium type is not
recommended for toxic exhaust systems. The cleanable-medium efficiency filter is undesirable
for nuclear systems because of the extensive downtime of the system that is required for
changing and decontaminating areas in proximity to the filter installation. For this type of
application, ASME AG-1 Section FB contains guidance that should be considered for DOE
facilities.
4.1.7 Deep-Bed Filters
Deep-bed filters were designed, built, and placed in service early in the development of nuclear
technology for treating off-gassing from chemical processing operations. The first, a sand filter,
was constructed at the Hanford, Washington, nuclear facility in 1948, and deep-bed glass fiber
filters were constructed soon after. These were not considered competitive with then-current
versions of the HEPA filter but were thought to have a different function. With the thin-bed
filters, the intent is usually to replace or clean the filter medium periodically. The deep-bed
filter, on the other hand, usually has as its objective the installation of a unit which will have a
DOE-HDBK-1169-2022
47
long life, in the dust capacity sense, of say 5 to 20 years, corresponding to either the life of the
process or the mechanical life of the system. Thus, when resistance starts increasing rapidly,
instead of replacing or cleaning the filter medium, the entire filter installation would be
abandoned and replaced with a new unit.
A partial explanation for this longevity is the original design concept that deep-bed filters would
be used where the total aerosol concentration was usually on the order of or less than normal
atmospheric dust concentrations. An important reason for selecting sand for the initial bed
material was a need to filter large volumes of wet corrosive aerosols for which more usual filter
materials would prove unsatisfactory. Deep beds of crushed coke had been used by the
chemical manufacturing industry for many years to remove sulfuric acid mist from the effluent
gas of sulfuric acid manufacturing plants prior to 1948.
4.1.7.1 Deep-Bed Sand Filters
Initially, sand filters were installed at the Hanford Reservation and at the Savannah River Site
(SRS). Following their success, more were added at Hanford and SRS and others were
constructed at nuclear facilities in Morris, Illinois, and Idaho Falls, Idaho. The Argonne National
Laboratory compiled a bibliography (ANL-7683, Sand-Bed Filtration of Aerosols: A Review of
Published Information on Their Use in Industrial and Atomic Energy Facilities) of Deep-Bed Sand
(DBS) filters. These DBS filters had collection efficiencies for particles greater than or equal to
0.5 µm that compared favorably with the HEPA filters of that era. Their advantages for the
nuclear programs at these sites included large dust-holding capacity, low maintenance,
chemical resistance, high heat tolerance, fire resistance, and a capability to withstand large
shock and gross pressure changes without operational failures. They also had disadvantages
such as high capital costs, need for large areas and volumes, inability to maintain the granular
fill, and lack of a reasonable means of disposing of the contaminated fill.
Section 47
DBS filters contain up to 10 feet of rock, gravel, and sand constructed in graded layers that
diminish granule size by a factor of 2 as the layers go from bottom to top. Airflow direction is
upward so that granules decrease in size in the direction of flow. A top layer of moderately
coarse sand is generally added to prevent fluidization of the finest sand layer underneath. The
rock, gravel, and sand layers are positioned and sized to provide the desired structural strength,
particle collection ability, dirt-holding capacity, and long service life. Ideally, the layers of the
largest granules, through which the gas stream passes first, remove all the large airborne
particles, whereas the fine sand layers on top retain the finest smallest particles at high
efficiency. Below the granular bed there is a layer of hollow tile that forms passages for air
distribution. The use of an elevated steel grating platform can also be used for this purpose, as
identified in ASME AG-1, Section FL. The total bed is enclosed in a concrete-lined pit. The
superficial velocity is generally 5 to 7 feet per minute, and pressure drop across the seven
layers, sized 3 1/2-inch average diameter down to 50 mesh, is from 7 to 11 in. wg. Collection
efficiencies as high as 99.98 percent for test aerosols have been reported. More details on DBS
Filters are provided in Section 5.4 of this handbook.
Detailed guidance on DBS filters is contained in ASME AG-1, Section FL, Deep Bed Sand Filters.
This guidance is based on operational experience from the use of DBS filters at SRS.
DOE-HDBK-1169-2022
48
4.1.7.2 Deep-Bed Glass Fiber Filters
The rapidly emerging glass fiber technology of the late 1940s shifted attention to the use of
very deep beds (1 or more meters thick) of graded glass fibers as a satisfactory substitute for
sand filters when treating gaseous effluents from chemical operations. They proved to be more
efficient, less costly, and to have a lower airflow resistance than the DBS filters they replaced. In
addition, these Deep-Bed Glass Fiber (DBGF) filters employ a medium that has more
controllable physical features and more assured availability than the DBS to permit a larger
airflow per unit volume at lower pressure drop, lower operating costs, and potentially lower
spent-filter disposal costs. DBGF filters have been used at Hanford for several decades on their
PUREX process effluent streams. However, the DBGF filters do not have the corrosion
resistance of the DBS, particularly from HF, and are less fire-resistant. The DBGF is also less of a
heat sink and has less capability to resist shock and high-pressure transients.
The intake segment of the DBGF filter system was designed with layered beds of uniform-
diameter glass fibers to a total depth of 8 to 84 inches. Each layer in the direction of airflow was
compressed to a higher density and enclosed in a stainless-steel tray with impermeable walls
and a perforated screen above and below. Capacity varied from 200 to 200,000 cfm (350 to
350,000 m3/hr). Although the first unit constructed at Hanford was small (400 m3/hr (240 cfm),
many of the 25 subsequent units were much larger and experienced extensive usage from
nuclear fuel processing to hot cell ventilation. The glass fiber of preference for this application
was Owens-Corning's 115-K, a 29-µm-diameter, curled glass fiber that resisted clumping,
settling, and matting. A system that was designed for downward airflow became inoperative
from precipitation of ammonium nitrate at the filter face. Subsequent units were designed with
air flowing upward and were equipped with water sprays directed from below to dissolve salt
precipitation on the intake face to reduce pressure drop buildup.
Section 48
The design airflow velocity of a typical DBGF was 50 feet per minute, and clean pressure drop
was close to 1.5-in.wg. The final pressure drop, after a total particle loading estimated at 10,500
pounds, was 8-in.wg. The final stage of a second-generation DBGF filter system employed two
12-mm blankets of 3.2-µm- and 1.2-µm-diameter glass fibers fabricated as a twin-layer bag
stretched over a stainless-steel framework. Airflow from the first stage passed through the
filtration blankets from the outside to the inside, then was exhausted from inside the metal
framework. The number of bag filters was proportional to the capacity of the intake segment of
the DBGF filter. Later designs of the DBGF filter's cleanup stage substituted HEPA filters in a
group of manifolded caissons (encapsulating filter holders), and a comparable increase in
collection efficiency was realized.
Provision for periodic backflushing will often extend the life of the total filter. Most DBGF filter
systems, contained in vaults below ground, are resistant to shock and overpressure from
natural phenomena. The dust-holding capacities of DBGF filters are very large, and many units
have operated for years without attendance or maintenance. Pressure drop sensors can often
predict evolving difficulties and indicate when it is time for backflushing, precipitate dissolution,
or other preplanned remedial actions. Just as for DBS filters, decontamination and disposal is
difficult for small systems and nearly impossible for the larger systems.
DOE-HDBK-1169-2022
49
4.1.7.3 Deep-Bed Metal Filters
Deep beds of metal fibers have a number of applications in the nuclear industry, particularly
where maximum resistance to fires, explosions, and overpressure shocks are essential. In off-
gas systems containing substantial concentrations of HF, use of stainless-steel metal fibers has
been studied as a substitute for glass.
In most cases, the objective when using metal fiber filters is to obtain particle collection
efficiencies that duplicate those obtainable with HEPA filters. However, the unavailability of
metal fibers with diameters close to or below 1 µm makes it necessary to provide great filter
depth as a substitute for small fiber collection efficiencies. For sodium fire aerosols, high
collection efficiency can be obtained with relatively large diameter metal fibers because the
combustion products in air, sodium oxide, and carbonate rapidly form large flocs that are easily
filtered. The ease of filtration results in the extremely rapid formation of a high-resistance filter
cake that severely limits the amount of sodium aerosol particles that can accumulate in the
filter before the limit of the fan's suction pressure is reached. Here, the requirement is for a
graded-efficiency, deep-bed, metal filter with a large storage capacity in the initial layers of the
filter for the fluffy sodium aerosol particles, a high efficiency for small particles in most
downstream layers of the filter, and the elimination of abrupt interfaces between graded fiber
layers where a filter cake might form.
This is a different filtration requirement than obtaining high efficiency for low concentrations of
small, non-agglomerating particles—instead, the requirement is for uniform particle storage
throughout the depth of the filter. Here also, uniform diameter fibers can be used in great
depths, as in the DBGF filters, to substitute for the presence of very small-diameter filter fibers.
Section 49
Other types of metal filters have been constructed by sintering stainless steel powders or fine
fibers into a sieve-like structure that function very much like a conventional pulse-jet-cleaned
industrial cloth filter. The metal membrane has an inherent high efficiency for particles greater
than a few micrometers but depends on the formation of a filter cake to obtain high efficiency
with sub-micrometer particles. Clean airflow resistance is high and increases rapidly as cake
thickness builds up. It is cleaned periodically by backflow jets of compressed air. Efficiencies are
comparable with those of HEPA filters when the sintered metal filters are precoated with filter
aids. Because of their high-temperature resistance and ability to handle high concentrations of
mineral dusts, these types of filters have been used in nuclear incinerator off-gas cleaning
systems, particularly when heat recovery from the hot filtered gases is desired. However, care
should be exercised to avoid releasing tar-like combustion products to sintered filters that are
operated at high temperatures because the tarry material tends to lodge in the pores and turn
to cake that cannot be removed by chemical means or by elevating the temperature to the limit
of the metal structure.
Another type of sintered filter construction for high-temperature applications has been
prepared from a mixture of stainless steel and quartz fibers. The composite material has the
same efficiency and pressure drop as HEPA filter glass paper but has 4 times the tensile
strength and can operate continuously at temperatures up to 932 degrees Fahrenheit (500
degrees Celsius).
DOE-HDBK-1169-2022
50
Ongoing research at several laboratories worldwide is ongoing for metal media filters. A future
edition of ASME AG-1 Code will contain applicable sections on this topic.
4.1.7.4 Moisture Separators (Demisters)
Liquid droplet entrainment separators, known as moisture separators or demisters, are
required in the standby air treatment systems of many water-cooled and -moderated power
reactors to protect the HEPA filters and activated-charcoal adsorbers from excessive water
deposition should a major high-temperature water or stream release occur as a result of an
incident involving the core cooling system. Droplet entrainment separators are also used in fuel
processing operations to control acid mists generated during dissolving operations and
subsequent separation steps.
Entrainment separators consisting of a series of bent plates are widely used in HVAC
applications for controlling water carryover from cooling coils and humidifiers; but for nuclear
applications, their droplet removal efficiency is inadequate. Therefore, fiber-constraining
demisters with a much greater efficiency for small droplets are standard for nuclear service.
Entrainment separators utilizing fiber media remove droplets by the same mechanisms that are
effective for dry fibrous filters, but they should have the additional important property of
permitting the collected water to drain out of the cell before it becomes clogged. Should
clogging occur and the pore spaces fill with water, the pressure drop across the separator will
rise and some of the water retained in the pore spaces will be ejected from the air discharge
side to create sufficient passages for air to pass through. The ejected water can become
airborne again by this mechanism.
Section 50
Droplets from condensing vapors originate as sub-micrometer-sized aerosols, but the droplets
may grow rapidly to multi-micrometer size by acting as condensation centers for additional
cooling vapors and by coagulation when the concentration of droplets exceeds 10 droplets/ml.
Firefighting spray nozzles, confinement sprays, and other devices that mechanically atomize
liquid jets yield droplets that predominantly range from 50 to more than 1,000 µm in diameter.
In USNRC Regulatory Guide 1.52, NRC recommends the use of entrainment separators for
engineered safety systems when the air may be carrying entrained liquid droplets or a cooling
and condensing vapor. As previously discussed, HEPA filter medium is treated for water
repellency, however high-water loadings rapidly saturate the paper leading to degradation of
filter performance and potential catastrophic failure of the filter. Therefore, the criteria for
entrainment separators used for nuclear service call for: (1) at least 99.9 percent retention by
weight of entrained water and condensed steam in the size range 1 to 2,000 µm diameter, at a
duct velocity from 250 to 2,500 linear feet per minute, and water delivery rate of 8 gallons per
minute (gpm) per 1000 cfm of installed HEPA filter capacity; (2) at least 99 percent retention by
count of droplets in the 1- to 10-µm-diameter range, at a duct velocity from 250 to 2,500 linear
feet per minute; (3) no flooding or water re-entrainment at a water-steam delivery rate of 8
gpm at a duct velocity of 2,500 linear feet per minute; and (4) a temperature tolerance at least
to 320 degrees Fahrenheit (160 degrees Celsius) and gamma radiation exposure up to 8x107
rads integrated dose without visible deterioration or embrittlement of the materials of
construction. ASME AG-1 Section FA, Moisture Separators, should be consulted for the specific
design criteria for moisture separators.
DOE-HDBK-1169-2022
51
An entrainment separator with these characteristics will provide long-term protection for a
downstream HEPA filter. Entrainment separators are usually constructed of deep layers of high-
porosity metal and glass fibers, either packed or woven into stable batts, and arranged in
graded sizes and packing density to give the desired small droplet collection capability with
excellent resistance to flooding and re-entrainment. Details of construction can be found in
ASME AG-1, Section FA.
4.1.8 Testing
4.1.8.1 Introduction
Testing of high-efficiency nuclear air cleaning systems is required to achieve and maintain high
performance and continued safe operation of nuclear facilities. In nonreactor nuclear facilities
throughout the DOE complex, HEPA filters in confinement ventilation systems can be constantly
challenged with radioactive aerosols. Nonreactor nuclear facilities comprise the bulk of DOE
nuclear facilities, and failure of their air cleaning system components can lead to uncontrolled
atmospheric release of radioactive aerosols. Thus, maintaining nuclear facility operability
depends on the performance of these air cleaning components. At the same time that HEPA
filters and adsorbers were being developed for nuclear applications, methodologies were being
developed to assure their performance. These methodologies eventually evolved into a
performance assurance program with three major components: (1) design qualification of
individual components through destructive testing, (2) QA of individual components through
nondestructive testing, and (3) performance assurance of nuclear confinement ventilation
systems through in-place testing. This overall performance assurance program was designed to
be hierarchical because components were built on a foundation laid down by preceding
components. Design qualification assured that filters produced according to a manufacturer’s
design met specific performance criteria for normal and off-normal operation.
Section 51
HEPA filters for DOE nuclear service now undergo four tests: (1) design qualification test
performed by a qualified laboratory, (2) production inspection and testing at the manufacturer,
(3) DOE-required QA inspection and testing at a DOE-designated FTF, and (4) receipt inspection
and system leak test at the facility where the filter will be used. Manufacturers submit
prototype filters for design qualification testing. This testing examines areas such as media
penetration and resistance to airflow, rough handling, pressure, heated air, and spot flame. The
filter medium receives the most rigorous and extensive control and evaluation. The U.S. Army’s
Edgewood Chemical and Biological Center performs the tests required for qualification, with
the heated air and spot flame test being performed at UL in accordance with UL-586. This
testing is required to be repeated every 5 years. Manufacturers receive a letter stating whether
their filter designs passed the qualification tests. Further information can be found in DOE-STD-
3020 and 3025.
After being installed at a DOE nuclear facility, an in-place leak test is done to ensure the
performance of the confinement ventilation system. Unlike bench tests for new filters that are
designed to determine filter quality via a penetration test utilizing an aerosol containing a
substantial fraction of particles in the range of the minimum filterable size, in-place tests are
designed to reveal the presence of defects in the filter unit that result from such things as
DOE-HDBK-1169-2022
52
rough handling during transportation, paper and gasket damage during installation, inadequate
pressure against intact gaskets, and penetrations through the housing to which the filter units
are attached. Procedures are conducted to locate and correct the defects. Such procedures
include increasing gasket compression; examining gaskets for breaks and tears; replacing
broken filters (repairs are not permitted for nuclear service in the U.S.); and welding closed any
unauthorized penetrations, cracks, and open seams in the filter house and mounting frames
(patching with caulking compounds is not permitted for nuclear service in the U.S.). Following
each repair, the system should be retested until it meets the established criteria for leak
tightness. ASME AG-1, Section TA, Field Testing of Air Treatment Systems, contains information
on repairs and required in-place tests after repairs, and ANSI N-511 contains information on in-
service testing. When repairs require re-qualification of equipment, the applicable sections of
AG-1 apply.
The performance of the periodic/surveillance in-place test cannot be overemphasized. The in-
place leak test described by ASME/ANSI N-510 has been used to conduct a periodic surveillance
to reconfirm the performance of the filter system. This standard is no longer published through
ASME and has been superseded by ASME AG-1, Section TA, Field Testing of Air Treatment
Systems. This Code section should be referenced for any in-place leak testing done at any DOE
facility. The in-place leaks test confirms the safety basis assumptions “system efficiency.” The
final result is a measure of efficiency that forms the basis for removal efficiency assumed in the
safety bases. The in-place test results may also be credited by the radcon and air emission
permits for removal of respirable particles. Unlike the filter penetration test which validates the
filter design assumption using a mono-disperse aerosol test, the in-place leak tests use a poly-
dispersed (0.7 mean diameter) and determines the system efficiency where the system
components (i.e., gaskets, frame, housing) are challenged. The test is performed under actual
conditions and at operational airflow. The criteria for the in-place leaks tests are typically
provided by the safety basis or other operating licenses/permits. The test results may also be
used as a service life indicator.
Section 52
4.1.8.2 Proof of Design – HEPA Filter Design Qualification Testing for Nuclear Service
As discussed previously, the U.S. Army’s Edgewood Chemical and Biological Center tests
prototype HEPA filters to qualify the designs for use in DOE nuclear facilities (this testing is
required to be repeated every 5 years). ASME AG-1, Section FC and Section FK, requires quality
product qualification testing for efficiency, airflow resistance, rough handling, overpressure,
heated air, and spot flame. The following subsections discuss each design qualification test and
associated acceptance criteria.
4.1.8.2.1 Penetration (Efficiency)
The performance of a HEPA filter may be expressed either as a particulate collection efficiency
(percent of particulate concentration stopped by the filter) or as a penetration. Penetration
where the total aerosol penetration through the filter medium, frame, and gasket of a filter
that has been encapsulated should be no greater than 0.03 percent of the upstream
concentration at rated airflow and at 20 percent of rated airflow (except for filters rated at 125
cfm or less). The reason for the 20 percent flow test is to increase sensitivity for pinhole
determination. Concentration may be given by particle count per unit air volume (emphasizing
DOE-HDBK-1169-2022
53
the smallest particles present), particle weight per unit air volume (emphasizing the largest
particles present), ionizing radiation intensity per unit volume of air (particle size effect is
indeterminate), or light-scattering intensity per unit air volume (emphasizing small particle
sizes).
4.1.8.2.2 Airflow Resistance
The resistance of a filter to airflow, often called “pressure drop” and “back pressure,” is usually
given as the height of a water column (measured in in. wg) that exerts an equal pressure. The
characteristic flow regime through HEPA filter media is aerodynamically described as laminar.
For this reason, the airflow resistance of these filters changes in direct proportion to changes in
air volume even though the air approaching the filter may be turbulent. Resistance to airflow at
the rated airflow of the filter should be no greater than 1.0 in. wg for filter sizes 4 and 5, and 1.3
in. wg for filter sizes 1, 2, 3, 6, 7, 8, and 9. (See ASME AG-1, Section FC for filter definitions.)
ASME AG-1 also includes information on resistance to airflow for other HEPA filter
configurations.
4.1.8.2.3 Aerosol Test
Equipment and procedures to aerosol test HEPA filters can be found in ASME AG-1, DOE-STD-
3025, IEST-RP-CC034, and previous versions of this Handbook (with reference to Military
Standard MIL-STD-286). Room air is drawn through filters and split into three streams. One
stream of 85 cfm is heated to 365 degrees Fahrenheit and is passed over liquid test aerosol
heated to 390 ± 20 degrees Fahrenheit. As the heated air passes over the surface of the hot test
aerosol, it becomes saturated with aerosol vapor. Traditionally the test aerosol of choice was
dioctyl phthalate (DOP). Other non-carcinogenic test aerosols, such as poly-alpha olefin (PAO)
are allowable as indicated in ASME AG-1 and DOE-STD-3025. When the test-aerosol-saturated
air contacts the second airstream (265 cfm held at approximately 71 degrees Fahrenheit), the
condensation aerosol is formed. The third stream of diluent air (850 cfm) is introduced in a
mixing chamber to dilute and disperse the aerosol-laden air. A forward light-scattering
photometer is used to measure test aerosol penetration, and a manometer is used to measure
filter resistance at rated airflow. Modern penetrometers that use jet impactors to obtain the
same aerosol without heating the test aerosol liquid are commercially available.
Section 53
4.1.8.2.4 Resistance to Rough Handling Qualification Test
In accordance with ASME AG-1 Section FC and FK, new, unused test filters (at least 2 of the size
and design to be qualified) should undergo rough handling for 15 minutes at a total amplitude
of 0.75 inches (using sharp cut-off cams that result in both a slow and an instantaneous 0.75-
inch drop) and a frequency of 200 Hertz (Hz), with pleats and filter faces in vertical orientation.
The filters should withstand this treatment without visible damage (cracked or warped frames,
loose corners or joints, cracked adhesive, loose or deformed medium) or a decrease in filtration
efficiency from 99.97 percent, as determined with nominal 0.3 rim test aerosol at full and 20
percent flows.
DOE-HDBK-1169-2022
54
4.1.8.2.5 Moisture and Overpressure Resistance Qualification Test
At least four new, unused filters of the type to be qualified should be aged a minimum of 24
hours under static conditions at 95 ± 5 degrees Fahrenheit and 95 ± 5 percent relative humidity
after which they should be installed in a wind tunnel that has been modified to permit the
introduction of water spray. After conditioning, the filters should withstand a spray of 1.25
pounds per 1,000 cfm, adjusted to produce a 10-in.wg pressure drop across the filter, and a
flow environment of 95 degrees Fahrenheit. The minimum test duration under these specified
conditions is 1 hour. After the test and the filters are dried out, there should be no visible
evidence of failure. Within 15 minutes after completion of the pressure test and while still wet,
the 0.3-rim test aerosol efficiency at full and 20 percent rated flow should be a minimum of
99.97 percent. This is the most stringent test an assembled HEPA filter will undergo and is
limited to a 10-in.wg pressure drop. Additional details can be found in ASME AG-1, Section FC
and FK.
4.1.8.2.6 Fire and Hot Air Resistance Qualification Test
New, unused filters should be exposed to heated air in a wind tunnel at 700 ± 50 degrees
Fahrenheit for 5 minutes. After exposure to heat, the filters should be cooled down and tested
in-place, with the filter remaining in the heated air tester. An aerosol generator and
photometer may be used for the aerosol test. The penetration at equal to or greater than 40
percent of rated flow should be less than 3 percent. Additional details can be found in ASME
AG-1 Section FC and FK.
4.1.8.2.7 Spot Flame Resistance
In this test, the HEPA filter is inverted in a test duct and operated at its rated airflow. A gas
flame from a Bunsen burner is directed against the upstream face of the HEPA filter. The
Bunsen burner is adjusted to produce a flame with a blue cone 2.5 inches long with a tip
temperature of 1750 ± 50 degrees Fahrenheit. The tip of this flame is applied so that it is not
less than 2 inches from the filter face. The flame is applied for 5 minutes at each of 3 separate
locations on the filter face. The Bunsen burner flame then is directed into the top corner of the
filter unit so that the tip of the blue flame cone contacts the frame, filter pack, and pack
sealant. The flame is applied for a period of 5 minutes. After the removal of the test flame at
each point of application, there should be no sustained flaming (burning) on the downstream
face of the unit. Additional details can be found in ASME AG-1 Section FC and FK.
4.1.8.2.8 Quality Control, Inspection and Testing of HEPA Filters
Section 54
The manufacturer’s qualification procedure involves two distinct phases: (1) a QA/QC routine
intended to ensure careful manufacture of a quality product, and (2) a series of tests to verify
filter compliance with preset standards concerning the properties of components and the
physical characteristics of the assembled filter, as well as a set of performance criteria related
to collection efficiency and resistance to airflow. When all of these factors are within the
tolerance limits set by ASME AG-1 Section FC and Section FK (and other applicable sections),
the manufacturer certifies that each delivered filter unit meets all acceptance criteria. The
manufacturers required tests for HEPA filters are prescribed in ASME AG-1, Section FC, and in
ASME AG-1, Section FK for special HEPA filters.
DOE-HDBK-1169-2022
55
4.1.9 Filter Qualification, Quality Assurance Inspection, and Testing of HEPA Filters
4.1.9.1 Introduction
The operating policy of DOE's filter testing program, contained in DOE-STD-3025, Quality
Assurance Inspection and Testing of HEPA Filters, calls for testing all HEPA filters intended for
environmental protection at DOE contracted FTF. Specifications for HEPA filters to be used by
DOE contractors are contained in DOE-STD-3020-2015, Specifications for HEPA Filters Used by
DOE Contractors.
The QA activities and testing performed at the DOE contracted FTF are considered defense-in-
depth and should not be relied upon to substitute for onsite receipt inspection, or other QA
activities, that would normally be conducted for NQA-1 procured equipment or components.
4.1.9.2 Visual Inspection
Visual inspection is an integral and vital part of every acceptance or surveillance test. A careful
visual examination should be made of each internal and external component prior to
installation to verify that the items have been received in satisfactory and serviceable
condition. After installation, the system should be checked as part of the acceptance test
procedure to make sure that all required items have been properly installed. A required visual
inspection checklist is contained in ASME AG-1, Mandatory Appendix TA-I. A suggested checklist
is provided in Section 5 of ASME N510, which may be used to verify that system design and
construction are in accordance with ASME N509. ASME AG-1 also provides guidance for visual
inspection in Section 5.0 and Appendix 1 of Section AA.
4.1.9.3 In-Place Component Tests and Criteria
System tests fall in two broad categories: (1) prestart up acceptance tests to verify that
components have been installed properly and without damage and that the system can operate
as intended, and (2) surveillance tests made periodically after the system has been placed in
operation to demonstrate its ability to continue performing its intended air cleaning function.
Surveillance tests are leak tests of the HEPA filter and adsorber installations. ASME AG-1
Section TA, Field Testing of Air Treatment Systems, contains requirements for general
inspection, field acceptance tests, corrective actions, and necessary instrumentation to perform
acceptance tests. DOE facilities conduct surveillance tests with procedures that are adapted to
their facility. For nuclear power stations, USNRC Regulatory Guides 1.52 and 1.140 provide
guidance that can be used by DOE facilities to prepare their procedures.
4.1.9.4 Component Acceptance Testing
Section 55
Acceptance tests also fall into two broad categories: (1) those that relate to the permanent
elements of the system, ducts, housing, mounting frames, and location of test ports, and (2)
those that verify the installation and condition of the primary air cleaning components (HEPA
filters and adsorbers). Tests in the first category include leak tests of ducts, housings, and
primary-component mounting frames; airflow capacity and distribution tests; gas residence
time tests for systems containing adsorbers; duct-heater tests for systems containing heaters;
and air-test aerosol mixing-uniformity tests. The acceptance test program for a particular
DOE-HDBK-1169-2022
56
system may contain any or all of these tests, depending on the nature of the system and its
importance (i.e., the potential consequence of a failure.
The basic precepts of acceptance testing as specified ASME AG-1, Section TA are:
• All components such as medium efficiency filters, mist eliminators, HEPA filters, and
adsorbers are qualified and tested as individual components. Their original efficiency is
established, and “as-installed” tests do not require further “efficiency testing.” The in-
place test is conducted to ensure the integrity of components is maintained and that no
bypass exists.
• The housing is of the desired strength and integrity, which can be measured by isolating
the unit envelope housing and leak testing under the specified pressure differential
conditions.
• The framework integrity (framework holding critical components such as HEPA filters
and adsorbers) can be measured by using blank off plates and pressure differential leak
tests.
For clarity, it should be reiterated that the definition of the “Air Cleaning Unit” is an assembly of
components that together comprise a single subdivision of a complete air cleaning system,
including all the components necessary to achieve the air cleaning function of that subdivision.
A unit includes a single housing, with the internal components (e.g., filters, adsorbers, heaters,
instruments) installed in or on that housing.
Acceptance tests are outlined in ASME AG-1, Section TA. Before assembly, personnel should
assure that all components meet the specified criteria. Typical QA acceptance only assures that
paperwork is available. This paperwork should be checked both for original supply and for
replacement parts. Before installing components, personnel should perform the following tests:
• Visual Inspection,
• Duct Leak Test,
• Housing Leak Test,
• Mounting Frame Leak Test.
During and immediately after installation of components, personnel should perform the
following tests:
• Visual Inspection,
• Airflow Capacity and Distribution Test,
• Air/Aerosol Mixing Uniformity Test,
• In-Place Leak Test HEPA Stage,
• Remove Adsorbent and Perform Laboratory Testing (to establish baseline carbon
efficiency),
• In-Place Leak Test Adsorber Stage, and
• Duct Damper Bypass Leak Test (if required).
DOE-HDBK-1169-2022
57
4.1.9.5 Duct and Housing Leak Test
The level of duct and housing leak tightness (and therefore the acceptance criterion for the
test) is based on the type of construction and the potential hazard (consequence) of a leak.
Recommended maximum permissible leak rates for various duct and housing constructions are
given in AG-1, Mandatory Appendix TA-III, Duct and Housing Leak Test Procedures. The
designer may specify tighter requirements based on the confinement requirements of the
system.
Section 56
Duct leak tests may be conducted by testing the entire ductwork system at one time or by
testing one section at a time and blanking off the ends of the section under test. The second
method is more practical for larger systems. When segmented, the permissible leak rate for the
individual sections is based on the proportionate volume of that section. The apparatus and
procedure for leak testing levels 1 and 2 ducts are described in the Sheet Metal and Air
Conditioning Contractors’ National Association (SMACNA) HVAC – Duct Design. ASME AG-1
offers two test methods for housing leak test: (1) the Pressure Decay Method (the most
convenient for larger duct and housing systems) and (2) the Constant Pressure Method (the
most effective for smaller volumes).
Test methods for level 3, 4, and 5 ducts and for housings are described in ASME AG-1. If the
specified leak tightness cannot be met, leaks are located, repaired, and retested by one of the
methods described in ASME AG-1. When performing the unit housing leak test, it is important
to follow the normal procedures (e.g., closing doors) and thereby avoid creating a once-in-a-
lifetime condition that does not resemble normal operating procedures and conditions. The
test is supposed to demonstrate that the unit housing will maintain the specified leak-tightness
during its operating life. To ensure the leak integrity of the housing is maintained due to
deterioration of door gaskets, or occurrence of sprung doors, damaged threads on closures,
and leaks due to maintenance work on the unit, personnel should perform periodic retesting
(every 10 years). Other methods such as acoustical monitoring or tracer gas monitoring may be
appropriate when entry into the housing is precluded.
4.1.9.6 Mounting Frame Pressure Leak Test
This test is performed to ensure the installed HEPA filter/adsorber mounting frame is installed
with no leak paths through the structure. This is considered an optional test because the same
evaluation is done after the filters are installed, and an in-place leak test is performed on the
bank. However, this test may be useful for determining gross leakage prior to filter installation,
and thus maximize the ease of any needed repairs prior to filter component installation. Any
repairs required should be done before installation of any HEPA filter/adsorber. This test is also
the first check for any other leak paths through conduits, drains, etc., which communicate
between the upstream and downstream side of a single bank of HEPA filters or adsorber banks.
Realistic test performance requires the unit housing leak test to be performed and the specified
leak criterion to be met. The acceptance value set in the specifications should always be
realistic.
These tests are conducted to verify there are no leaks through the HEPA filter and adsorber
mounting frames or through the seal between the mounting frames and the housing. The tests
DOE-HDBK-1169-2022
58
also verify there is no bypassing of the mounting frames through electrical conduits, drains,
compressed air connections, and common anterooms of the housing, or other inadvertent leak
paths. Familiar sources of leaks are weld cracks and incomplete welds. A properly designed
mounting frame should have no penetrations (via conduits, piping, or ducts), and lighting, drain,
and other ancillary systems should be designed so that no bypassing of the HEPA filters and
adsorbers can occur. Nevertheless, unauthorized modifications are often made in the field. The
purpose of this test is to disclose such occurrences, as well as any leaks caused by poor
workmanship or shipping damage. The test is recommended for any installation, whether duct
and housing leak tests are performed or not, but it is particularly necessary when subsequent
in-place tests of the HEPA filter and adsorber stages will be performed using a shrouded
method.
Section 57
This test is conducted by first blanking off all openings for filters and adsorbers and closing or
blanking off all openings in the housing, then conducting a soap-bubble or spray test aerosol
leak test around all welds and other potential leak paths (as described in ASME AG-1). After all
leaks have been repaired, individual chambers of the housing should be checked by a pressure
leak rate test to verify there are no bypasses that were not disclosed by the leak detection
check. It is unnecessary to perform these tests from the upstream side of the mounting frame,
and it is quite acceptable to test two mounting frames simultaneously by blanking off the
openings of both and pressurizing the space between. Because the mounting frame pressure
leak test is a chamber-by-chamber test of the housing, it can replace the need for a housing
leak test.
4.1.9.7 Airflow Capacity and Distribution Test
This test is used: (1) to verify that the specified volumetric flow rate of the air can be achieved
with the installed fan under actual field conditions at maximum and minimum filter pressure
drop, and (2) to verify that the airflow distribution across each HEPA filter or adsorber stage is
within the specified uniformity at the designed volumetric flow rates. ASME AG-1, Section TA
contains additional information on these tests.
The air distribution test is an acceptance test (presuming the airflow capacity is both an
acceptance and a surveillance test, as it should be). The unit should be operated for 15 minutes
prior to the test to achieve steady-state conditions. In many existing units, there is inadequate
space to perform the test downstream of the banks. Any test performed on the entry side of
these banks should be more conservative for the HEPA filter banks because of the flow-
straightening characteristics of HEPA filters. Therefore, if such a test meets the criteria, it
should be acceptable.
4.1.9.8 Air-Aerosol Mixing Uniformity Test
The purpose of this test is to verify that the aerosol or challenge gas is introduced in order to
provide uniform mixing in the airstream approaching the HEPA filter bank or adsorber stage to
be tested. The test method described here includes tests to establish the adequacy of the test
aerosol injection and upstream sampling port locations but does not generate data reflecting
the adequacy of the downstream sampling port location. Undoubtedly, the test should be a
prerequisite for performance of any in-place test of a HEPA filter bank and adsorber bank stage.
DOE-HDBK-1169-2022
59
The verified locations of injection and upstream sample ports should be documented, and the
locations should be tagged to indicate the date, method used, as well as the tests to be
conducted. All other ports found to be unsatisfactory should be tagged to prevent later
accidental use of incorrect injection or sampling ports.
The aerosol/vapor injection point for the first HEPA bank and the adsorber stage should always
be ahead of any unit or system bypass line, and the downstream sampling point for the second
stage HEPA filter bank and for challenge aerosol/vapor should always be downstream of the
return of the bypass line into the main duct.
Section 58
Good testability requires provision of permanent test aerosol injection and sample ports or
other planned and pre-established means for injecting the test aerosol and for taking reliable,
well-mixed samples. Details of the air-aerosol mixing test are described in ASME AG-1. It is
essential that the air and test agent’s mixture challenge to the filters (adsorber) is thoroughly
mixed so that the concentrations entering all points of the filters, including the upstream and
downstream sample points, are essentially uniform. Adequate mixing upstream usually can be
obtained by introducing the test aerosol at least ten duct diameters upstream of the filters or
adsorbers, or by introducing it upstream of the baffles or turning vanes in the duct.
When neither of these methods is practical, a Stairmand disk located four to six duct diameters
upstream will provide satisfactory mixing. A Stairmand disk is a plate with the same geometric
shape as the duct section that blocks the central half of the duct area. Air flowing past the disk
creates vortices on the leeward side that compel turbulent and thorough mixing. The disk is
placed into the duct for testing. At other times it is either removed, swung out of the way, or
turned on a pivot so the long axis is parallel to the direction of flow. When duct arrangement
makes it necessary to introduce the test aerosol directly into the filter housing, extraction of
the downstream sample at a point several duct diameters downstream of the fan will usually
provide a well-mixed sample.
Fan-shaft leakage should be considered in sampling downstream of the fan. Since leakage at
the shaft will be in-leakage, sufficient air to dilute the downstream sample can be drawn in if
the shaft annulus is large (yielding a low downstream concentration reading), or dust may be
drawn into the fan to provide a high downstream reading (which may be particularly prevalent
during construction). Application of a shaft seal, or at least a temporary seal, is recommended
during testing. If this is not practical, a photometer leak reading should be taken with and
without the aerosol generator “on” to establish shaft seal leakage. ASME AG-1 Section TA
contains additional information on this test.
4.1.9.9 Duct Damper Bypass Test
The duct damper bypass test evaluates the potential of bypass leakage paths, through closed
dampers or valves, to ensure that radioactive gases or particulates do not escape treatment
through the HEPA and/or adsorber banks. This test allows testing of the potential leak path
during the test aerosol or Halide test on the HEPA/adsorber banks, assuming the injection
sample ports are located such that the potential bypass is included in the test envelope.
Otherwise, the bypass (damper) may be tested using conventional pressure-testing techniques.
ASME AG-1 Section TA contains additional information on this test.
DOE-HDBK-1169-2022
60
4.1.9.10 System Bypass Test
A system bypass test challenges all potential bypass leakage paths and all portions of the
nuclear air treatment system (including the housing stages) during the test sequence, which
could potentially defeat the purpose of high efficiency nuclear air treatment components. All
potential bypass leakage paths around the HEPA/adsorber banks should be included as a single
overall leak test of the sum of the individual tests on the separate banks. In dealing with a
series of HEPA or adsorber banks, each bank should be tested individually to ensure that
contaminated air does not bypass the filter banks or escape treatment. ASME AG-1 Section TA
contains additional information on this test.
Section 59
4.1.9.11 Duct Heater Performance Test
The duct heater performance test evaluates the humidity control system for the carbon
adsorber bank (which prevents water buildup on the carbon) to be tested to ensure satisfactory
performance. For example, the voltage always has to be checked to make ammeter readings
meaningful. The temperature should be checked sufficiently upstream and downstream of the
heater to ensure an adequate rise in air temperature. The readings obtained also should be
evaluated by a cognizant individual to ensure the desired relative humidity can be achieved
with the potential minimum and maximum environmental temperatures in the inlet stream.
ASME AG-1 Section TA contains additional information on this test.
4.1.10 Surveillance Testing
4.1.10.1 Introduction
There are three types of surveillance tests: (1) in-place leak tests of HEPA filter banks using an
accepted test aerosol, (2) in-place leak tests of adsorber stages using a slightly adsorbable gas
such as the fluorocarbon Refrigerant-11, and (3) laboratory tests of samples of adsorbent
withdrawn from the system to establish its remaining adsorption capacity. These tests are also
employed as part of the acceptance procedure for new installations, with the exception that
laboratory tests are made on samples of adsorbent taken from batch material as furnished.
Surveillance tests of HEPA filter and adsorber systems should be made at regular intervals after
installation to detect deterioration and leaks that may develop under service conditions.
Regular in-place testing of standby systems is necessary because deterioration can take place
even when the systems are not being operated. Aside from component damage, frequently
discovered causes of failure to meet in-place test requirements include loose clamping bolts;
inadequate clamping devices such as C-clamps; foreign material trapped between gaskets and
mounting frames, rough or warped mounting frame surfaces; cracked welds; unwelded joints in
mounting frames; incorrectly installed components (e.g., HEPA filters installed with horizontal
pleats); inadequate seals between mounting frames and housings; poorly designed mounting
frames; and bypasses through or around conduits, ducts, or pipes that penetrate or bypass the
mounting frames.
In-place tests should be made by introducing a test aerosol upstream of the bank to be tested.
The concentrations of test aerosol upstream and downstream (upstream concentration is
considered 100 percent) should then be determined, and penetration should be calculated
DOE-HDBK-1169-2022
61
from the ratio of concentrations. The reliability of this test is determined by: (1) the ability to
properly introduce the test aerosol and obtain representative samples, and (2) the availability
of physical access to the banks being tested. The first can be verified by an air-aerosol mixing
test.
Additional information on all of the surveillance tests described here can be found in ASME AG-
1, Section TA.
4.1.10.2 In-Place System Leak Test, HEPA Filter Banks
Section 60
There are three major types of in-place system testing methods. The first test method uses a
light-scattering photometer with a polydispersed aerosol. The second method uses a shroud
and/or scanning test technique, and the third uses a laser spectrometer in lieu of the forward
light-scattering photometer. Measurements can be obtained manually or by automatic scans of
the downstream side of the filters. The in-place system test is made by challenging the
upstream side of the filter or filter bank with test aerosol smoke, then measuring and
comparing (using a light-scattering photometer) the test aerosol concentration in samples of
downstream (filtered) and upstream (unfiltered) air. If the system exceeds the specified
maximum permissible penetration value, the downstream faces of the filters and mounting
frame can be scanned with the photometer probe to locate localized high concentrations of
test aerosol, indicating leaks.
Polydispersed aerosol may be generated thermally or by compressed air. Compressed-air
generators are widely used for testing small systems. A rule of thumb for determining
generator capacity is not to exceed one Laskin nozzle per 500 cfm of installed filter capacity.
Compressed-air generators are suitable for systems up to about 3,000 cfm; above this size they
become cumbersome. Gas thermal generators are generally used for testing systems of 6,500
cfm installed capacity and larger.
A manifold is installed in the upstream and downstream shroud. The upstream shroud should
be placed over a filter, and the generator turned on. It is important to verify that the aerosol
mist is filling the shroud using an upstream sample/challenge manifold located in the shroud.
When the 100 percent upstream concentration is obtained, the meter is set to 0 and the
downstream reading is taken. If the downstream shroud method is used, the sample tube
should be connected to the downstream shroud manifold, and the downstream shroud should
be placed against the frame of the filter to be tested for a minimum of 15 ± 5 seconds as
determined by the photometer operator. If the downstream scan method of testing is used,
each filter and gasket should be probed. The photometer is then read, and the highest leak rate
reading is recorded “as found.” The final leak rate readings are recorded.
A detailed description of the procedure for conducting an in-place test of HEPA filters is given in
ASME AG-1, Appendix TA. An acceptance criterion of 0.05 percent maximum leakage for the in-
place system test is recommended for systems that are designed in accordance with this
handbook.
DOE-HDBK-1169-2022
62
4.1.10.3 In-Place Testing for Adsorbers
The in-place leak test of the adsorber bank (stage) measures bypass (mechanical) leakage
around or through the installed adsorber bank. This test may be performed: (1) as an
acceptance test to verify system design function following initial field installation; (2) after an
abnormal incident, replacement, repair, or modification that may affect design function; or (3)
as a periodical in-service (surveillance) test to monitor system condition and operational
readiness.
Bypass leakage around the adsorber bank (stage) may result from mounting frame weld
degradation, damaged or poorly compressed gaskets, common drains between housing
compartments, common electrical conduits between housing compartments, and inadequately
dampered bypass ducts. Bypass leakage through the adsorbent media may be due to poor
adsorbent filling technique and subsequent settling from system vibration and air or gas
pulsation.
Section 61
Since the in-place leak test only provides a measure of bypass leakage, this test should be
performed in conjunction with the laboratory test of the adsorbent media. Assuring that the
adsorber bank meets bypass leakage acceptance criteria and the adsorbent media itself
performs adequately provides the necessary information required to determine whether the
adsorber bank is performing as designed.
There are two methods commonly used for in-place leak testing of the adsorber bank stage.
One uses a fluorocarbon refrigerant gas or an alternative tracer gas. The other uses a
radioactive tracer gas (iodine or methyl iodide). The first method, developed by Savannah River
Laboratory, is the most frequently used, particularly in commercial applications. The second
method involves the use of radioactive isotopes and personnel licensed to handle these
isotopes.
For commercial nuclear power plants, typical bypass leakage acceptance criteria for the
adsorber bank (stage) range from 1.0 percent to 0.05 percent, depending on specific plant
license bases and the plant technical specifications. NRC Regulatory Guide 1.52 specifies that in-
place leak testing for adsorbers be performed: (1) initially; (2) at least once each 18 months; (3)
following the removal of an adsorber sample for laboratory testing if the integrity of the
adsorber section is affected; (4) after each partial or complete replacement of a carbon
adsorber in an adsorber section; (5) following detection or evidence of penetration or intrusion
of water or other material into any portion of an ESF atmosphere cleanup system that may
have an adverse effect on the functional capability of the adsorber; and (6) following painting,
fire, or chemical release in any ventilation zone communicating with the system that may have
an adverse effect on the functional capability of the system. The Regulatory Guide further
specifies that the in-place leak test should be performed in accordance with ASME AG-1 Section
TA and the in-place leak test should confirm a combined penetration and bypass leakage
quantity around or through the adsorber of 0.05 percent or less of the test gas at system rated
flow of ± 10 percent.
DOE-HDBK-1169-2022
63
4.1.10.4 Nonradioactive Tracer Gas Test
The non-radioactive tracer gas test is made by challenging the upstream side of the adsorber
with a slightly adsorbable and readily desorbed fluorocarbon gas [usually Refrigerant-11,
trichloro mono fluoromethane], then determining the concentrations immediately upstream of
the adsorber bank and at a point downstream of the adsorber bank where satisfactory mixing
with air occurs. Bypass leakage is calculated from the ratio of downstream-to-upstream
reading. Since it is the ratio of concentrations that matter, the units may be expressed in terms
of peak height or some other measure directly related to tracer concentration, although the
measure may not necessarily reflect the actual volumetric or mass tracer concentration.
Refrigerant-112 was originally used but is no longer produced. Refrigerant-112 was more
strongly adsorbed by the adsorbent bed than Refrigerant-11 and allowed testing of banks under
conditions of high relative humidity or elevated adsorbent moisture content. With the
introduction of ASME AG-1, alternative, substitute tracer gases are allowed (permitting tracer
gases with stronger adsorption potentials than Refrigerant-11), providing the selection is made
in accordance with the AG-1, Nonmandatory Appendix TA-C, Challenge Gas and Aerosol
Substitute Selection Criteria, and ASME N511, Appendix B, Challenge Gas Substitute Selection
Criteria.
Section 62
4.1.10.5 Radioactive Iodine Tests
Two tests are used, one with radioactively traced elemental iodine, and the second with
radioactively traced methyl iodide. Equipment requirements for controlling the injection and
sampling flows during elemental iodine testing include an iodine injection tube, two sampling
units, a sample extraction pump, and two calibrated flowmeters. The sampling units are filled
with charcoal of known efficiency for elemental iodine. The test gas is Iodine-127 containing the
iodide-131 tracer.
A combination of injected radioactivity (in microcuries), sampling rate, and counting technique
(usually dictated by the kind of counting equipment available) should be developed to give the
required test precision. Sampling rates as low as 0.03 percent of the system flow rate have
been used, but sampling rates of about 1.0 cfm per 1,000 cfm (0.1 percent) of rated adsorber
capacity are recommended.
The amount of iodine required, and the size of the injector tube are not critical. The radioactive
iodine source is prepared by mixing the required quantities of Iodine-127 and Iodine-131 as
sodium iodine, precipitating the iodine fraction of palladium iodide by treatment with acidified
palladium chloride, then decomposing the palladium-iodide under vacuum. The liberated
iodide-127 and iodide-131 is collected in a liquid-nitrogen-cooled U-tube and transferred to a
glass ampule that is installed in the injector. Preparation of the iodine and loading of the
injector should be carried out in a laboratory equipped for handling radioactive materials. To
inject iodine during the test, the injector tube is crushed, breaking the ampule, and releasing
the iodine vapor. Heat may be applied to the injector tube prior to its being crushed and during
the test to assist in vaporizing the iodine source. Compressed air is passed through the tube at a
carefully controlled rate for 2 hours.
DOE-HDBK-1169-2022
64
After system flow and background radioactivity levels are established, iodine is injected far
enough upstream to ensure adequate mixing with the main airstream, and samples are
withdrawn simultaneously through the upstream and downstream sampling units. Injection of
iodine is continued for approximately 2 hours, but system airflow and downstream sampling
are continued for another 2 hours to catch any iodine that may desorb from the beds, in
addition to that which penetrates immediately. Exhaust air from the sampling units is usually
dumped back into the upstream side of the main system. The iodine content of the carbon in
the samplers is determined by direct gamma spectroscopy, and the bypass leakage is
determined from the following equation.
The methyl iodide test for determining the efficiency of adsorbers for organic radioiodine
compounds is similar to the test for elemental iodine and uses the same equipment, except for
the injector. The injector used for the methyl iodide test is a U-tube and a vapor expansion
chamber. Sampling and analytical procedures are the same as those for the elemental iodine
test. The test vapor is methyl iodine-127 containing methyl iodine-131 tracer. Because the
methyl iodine test determines a different property of the adsorbent and depends on a different
sorption mechanism, it cannot be used in place of the elemental iodine test. Therefore, both
tests may be needed for a complete evaluation of impregnated charcoal adsorbers. Both of
these tests suffer from the limitations of using radioactive tracers in the field and from the
number of variables that should be controlled to achieve reliable results.
Section 63
4.1.10.6 Test Sequence and Frequency
ASME AG-1, Section TA, and ASME N511 for Periodic In-Service Programs, provide guidance on
testing sequence and frequency. Section TA is used for equipment qualification and acceptance
testing after field installation, while ASME N511, is used for in-service testing to verify
equipment availability and to obtain data for operational considerations. ASME N511 also
provides procedures for surveillance (interval) testing to satisfy technical specifications or
specific site surveillance requirements.
Due to the potential for unauthorized flow adjustment and duct damage, all air cleaning
system airflows should be rebalanced at least every 5 years. Regularly scheduled testing and air
balancing properly verifies the safe, effective operation of air cleaning systems and ensures that
design parameters are being met and systems are operating within specified acceptance
criteria. ASHRAE STD 111, Practices for Measurement, Testing, Adjusting and Balancing of
Building Heating, Ventilating, Air Conditioning and Refrigeration Systems, should be followed.
4.1.10.7 In-Place Testing for Multistage Systems
HEPA filters are sometimes used in series to increase system reliability or to reduce the effluent
air concentrations released from transuranic materials-handling operations. Two questions of
importance arise when HEPA filters are employed in series: (1) how can they be tested in place,
and (2) what will be the ultimate DF?
With a lower size detection limit at 0.1 µm and excellent analytical characteristics, laser
spectrometer counting, and sizing instruments have been proposed as a feasible and
satisfactory method for testing two or more HEPA filters in series when it is not possible to test
each individually. Some uncertainties, however, remain. To have an adequate number of
DOE-HDBK-1169-2022
65
particles downstream for a statistically reliable penetration measurement, high upstream
particle concentrations are required; this, in turn, calls for an accurate aerosol dilution device to
reduce the particle concentration entering the laser spectrometer to a point where coincidence
counting becomes insignificant. This often calls for a reducing concentration by 2 to 4 orders of
magnitude, a difficult procedure. In addition, overall tests fail to indicate the status of individual
filters in the series. This is important because there are no agreed-upon criteria for permissible
penetration through two or more filters in series.
Systems that contain two or more HEPA filter stages and/or two or more adsorber stages in
series in the same housing give special problems because of the difficulty of obtaining a
representative single-point sample downstream of the first bank and the difficulty of
introducing the second-stage test aerosol at a point where good mixing can be achieved. Some
series banks are too close, so neither of these objectives can be achieved in the normal manner.
Because of the high collection efficiency of the first-stage elements, sufficient test aerosol
cannot be introduced upstream of the first stage to permit effective testing of the second stage.
It has been shown that accepted test aerosols have no adverse effect on activated carbon or
other adsorbents when used for testing nuclear air cleaning systems, and the refrigerant gases
used to date have no adverse effect on HEPA filters.
4.1.10.8 First-stage Downstream Sample
Section 64
The first-stage downstream sample can be obtained by using a multiple sampling technique. For
testing multistage HEPA filter banks, scanning the downstream face of the stage to be tested is
an approved technique, in accordance with the procedure outlined in Section 4 of IEST-RP-CC-
034 (2016). The recommended scanning pattern for each filter in the bank is shown in Figure
4.9. Prior to starting scanning, the upstream side of the stage is challenged with test aerosol
and the photometer is adjusted to read 100 percent. A high concentration will always exist
directly downstream of a leak. During the downstream scan, the relative magnitude of each
leak is determined by turning the scale shift knob of the instrument until a reading about
halfway between half and full scale is obtained. The reading is recorded, and the leak flow for
that point is calculated from the following equation.
Defective filters should be replaced, and installation deficiencies should be corrected before the
final test is conducted. This method is considered more sensitive than the usual method of
HEPA filter testing and is recommended for multistage systems with plutonium or transuranic
element source terms.
DOE-HDBK-1169-2022
66
Figure 4.9: Recommended Scanning Pattern
4.1.10.9 In-Place Testing for Multistage Adsorber Systems
Systems containing two or more adsorber stages in series in the same housing pose the same
problems as multistage HEPA filters. The same techniques can be used for gas injection and
testing as used in the aerosol HEPA filter systems described above. Additionally, since any
tracer gas injected upstream of the adsorber bank is only temporarily adsorbed, additional
difficulty with desorption interference may be encountered when attempting to test
subsequent adsorber stages. Normally, it is advantageous to start with the downstream bank
when testing series adsorber banks to minimize desorption interferences. It may be possible to
perform individual bank leak testing of series adsorber banks by using temporary or
permanently installed sampling manifolds or by providing a temporary jumper duct to bypass
airflow around the second stage to either the system fan or to a temporary auxiliary fan.
4.1.10.10 Test Aerosol/Gas Injection, throughout Second-Stage Upstream Sample
When the test aerosol/gas is introduced through an auxiliary duct, the upstream sample can be
taken any place in the auxiliary duct (upstream of the bank to be tested), assuming the auxiliary
duct is long enough to ensure good mixing and medium efficiency filters are not installed.
When using an auxiliary blower, a downstream sample can be taken downstream of the blower.
Another method of ensuring proper mixing of the test aerosol/gas with air is to shroud adjacent
filters (adsorbers) and introduce the agent to each filter element (adsorber cell) individually by
using a multiple discharge distributor, as shown in Figure 4.10. The X cross sections are used as
the injection ports. The upstream sample is taken downstream of the perforated distribution
plate. The downstream sample is taken with a multipoint sampling probe (Figure 4.11). The
penetrations of the individual filters (adsorbers) are averaged to find the gross bank
penetration.
This method requires that a mounting frame pressure leak test be made, usually at the time of
acceptance testing, and that the air-containing test gas be passed through a unit (filter or
adsorber cell) or group of units one at a time. This method has the advantage of substantially
reducing the total quantity of test aerosol/gas introduced to the system if scanning is required
to locate leaks; however, it requires more time than the usual method of taking single-point
Section 65
DOE-HDBK-1169-2022
67
upstream and downstream samples. The vapor test gases have no adverse effect on HEPA
filters, and it is possible to inject the gas upstream of the HEPA filters when testing adsorbers.
Modern air cleaning systems should be designed to eliminate back-to-back series adsorber
elements within a single housing. Gasketless deep-bed adsorbers or series adsorbers contained
in separate, testable housings may be used when the design requires bed depths in excess of
the standard two inches. ASME AG-1 Section FE contains additional information on deep bed
activated carbon adsorbers.
Figure 4.10: Adsorber Tray Mounting Frame
Figure 4.11: Multiple Point Sample Probe
DOE-HDBK-1169-2022
68
4.1.11 Adsorbent Sampling and Laboratory Testing
4.1.11.1 Sampling
The effectiveness of the adsorbent may be impaired due to aging, weathering, and/or poisoning
by chemical contaminants. The charcoal ages as a result of oxidation of the adsorptive sites at
the adsorbent surface. Aging may occur in the drum (static) or in the operating air cleaning
system (dynamic). Weathering typically occurs during system operation when the adsorbent is
exposed to normal atmospheric, low-level contaminants in the airstream, e.g., oxides of
nitrogen and sulfur and outgases from plant materials and equipment. Moisture adsorbs on the
activated carbon plays a significant role in degrading carbon performance. Poisoning generally
refers to an acute exposure of the adsorbent to chemical compounds that temporarily or
permanently impair its ability to remove radioiodine and radioiodides. Periodic sampling of the
adsorbent provides a means of providing a representative sample of adsorbent for radioiodine
testing. The radioiodine laboratory test, together with the in-place adsorber leak test, provides
a means of assessing overall adsorber system health.
Flow-through cartridges should be provided and installed in an area of the bank where air will
flow through them, and not in obvious low-flow areas such as the outside edge of the mounting
frame. If sample cartridges are not provided, other means of sampling are necessary. ASME AG-
1 contains additional information on obtaining representative samples of carbon from a carbon
bed. In a multicell system, samples can be obtained by removing and emptying a cell, taking a
sample of the loose adsorbent, refilling the cell (using a qualified filling procedure), and
reinstalling it in the bank. For some adsorber systems, it may be possible to take a “grain thief”
sample. In small adsorber installations, when considering the cost of the tests and labor
involved in obtaining the sample, it may be beneficial to simply replace the adsorbers or
adsorbent. Some users have found it more economical to replace the adsorbent at the
stipulated sampling frequency rather than making surveillance sample tests.
When using a “grain thief” as described in ASME AG-1, multiple samples should be taken from
all sections of the adsorber bank. For deep bed adsorbers, it is important to sample from below
the tops of screens so that carbon from the overfill is not commingled with the service carbon.
In filters with a bed thickness greater than two inches (50.8 mm), samples should be taken from
the center of the bed. Samples taken from the inlet side of a carbon bank will show more
radioiodine penetration than samples taken from the exit side. Therefore, samples should be
taken symmetrically from the exit screen side, the entrance screen side, and the middle of the
bed. When sampling Type II adsorber trays, the entire tray should be emptied, and the contents
mixed to yield a homogeneous composite sample. A smaller, grab sample may be taken from
the tray contents for laboratory testing. If the bank is not being replaced, a new tray should be
installed in the bank and marked as “Not Representative for Future Sampling.”
Section 66
Sample canisters may be used to take a representative carbon sample from the adsorber bank.
Sample cartridges should be provided in sufficient numbers to permit taking samples at
specified intervals for the life of the adsorbent. Sample cartridges should be designed so that
bed depth, airflow, and pressure drop across the cartridges are the same as for the adsorber
stage. Properly designed sampling canisters should have the same bed depth as the main bank
and be filled with adsorbent identical to that installed in the main adsorbent bed. Sampling
DOE-HDBK-1169-2022
69
canisters should be mounted vertically so that any bed settling within the canisters will not
create a mechanical bypass of the carbon media.
Carbon samples taken from the adsorber bank should be thoroughly mixed and packed into
vapor-tight containers such as a plastic bottle. At least 125 ml of carbon for each two inches of
bed thickness are required for the laboratory test. All samples that are to be sent to a testing
laboratory should be marked with the following minimum information:
• Utility/Company.
• System Identity.
• Sample Date.
• Purchase Order Number.
• Test Standard.
• Test Temperature.
• Test Humidity.
• Face Velocity.
• Adsorbate (methyl iodide).
• Pressure.
• Bed Thickness.
• Contact Person/Telephone Number.
Test results for samples sent to a laboratory for radioiodine penetration analyses should be
available within 30 days of their sampling date.
4.1.11.2 Laboratory Testing
Radioiodine penetration analysis is conducted in the laboratory using the ASTM D3803-2019
standard test method (or later versions of ASTM 3803 as discussed in ASME AG-1). Testing is
conducted in sophisticated environmental chambers that are capable of precisely controlling
the temperature and humidity. The activated carbon sample is loaded into stainless steel
testing canisters, one canister for each two inches of adsorber bank bed depth. Along with two
more canisters containing new carbon, the canisters with the activated carbon sample are
assembled into a canister stack for testing. The canister stack is placed into the environmental
chamber and plumbed into the testing system. The system environment is adjusted to the
required temperature and humidity, normally 90 degrees Fahrenheit and 95 percent relative
humidity. All test parameters are monitored by a computer monitoring system for the duration
of the test.
After an initial thermal equilibration period, humid airflow is started through the carbon beds
for the duration of the pre-equilibration and equilibration periods. The loading period begins
with the introduction of methyl iodide into the airstream. The methyl iodide is fed into the
system for a period of 60 minutes, called the loading period. After completion of the loading
period, the injection of methyl iodide is stopped, and the humid air continues for an additional
60 minutes. This is called the “post sweep.” The carbon canisters are then disassembled and
carbon from them is loaded into plastic counting canisters for analysis. Each carbon sample is
counted in a gamma spectrometer to determine the amount of radioactivity contained in each
DOE-HDBK-1169-2022
70
carbon canister. Knowing the amount of radioiodine present in each carbon canister allows
calculation of the radioiodine penetration in percent penetration.
Section 67
Detailed descriptions of the penetration measurement may be found in ASTM D3803-2019 and
referenced in ASME AG-1. The actual test method and parameters, as well as the acceptance
criteria, will be found in plant specific documents such as technical specifications or site-specific
operating procedures.
4.1.11.3 Frequency of Testing
The following test schedule (Table 4.7) is suggested for both continuous and intermittent online
adsorber systems designed in accordance with this Handbook.
Table 4.7: Test Schedule for Adsorbers
Application Frequency
All systems. Before system startup, following any major system
repair or modification, and following each filter
(adsorber) replacement.
Radiochemical plants, fuel reprocessing plants,
and laboratory fume hoods.
Semiannually or quarterly where high moisture
loadings or high temperatures are involved. In some
systems, frequent (even monthly) testing is often
specified where the environment is particularly
severe. The frequency may be reduced if experience
indicates a lesser frequency is satisfactory.
Reactor post-accident cleanup systems and
post-accident cleanup systems of fuel
reprocessing plants.
Annually or 720 hrs of system operation, whichever
comes first (as specified in NRC Regulatory Guide
1.52).
Zone III or tertiary confinement areas of
facilities that handle radioactive materials.
Annually.
Zone II or secondary confinement areas of
plants and laboratories that handle radioactive
materials.
Annually.
Zone I or primary confinement areas (glovebox
lines, hot cell exhaust, etc.) of laboratories and
plants that directly handle moderate to large
quantities of radioactive materials.
Semiannually unless experience indicates that annual
testing is sufficient. If filters (adsorbers) are replaced
at short (less than 6-month) intervals to limit exposure
of personnel to radiation during a filter (adsorber)
change, or to permit contact maintenance of the
system by limiting the amount of radiation that can be
collected in the filters (adsorbers), systems should be
in-place [i.e., leak-tested following each filter
(adsorber) change]. Laboratory testing of adsorbents
may not be necessary if the adsorbent is replaced
frequently.
DOE-HDBK-1169-2022
71
Application Frequency
All systems. Before system startup, following any major system
repair or modification, and following each filter
(adsorber) replacement.
Systems that are continually on standby but
are operated occasionally during plant
maintenance to ventilate the system.
At least semiannually.
4.1.12 Testing of Deep Bed Sand Filters
Deep bed sand filters are not true HEPA filters, although their efficiency approaches that of a
true HEPA filter when tested for aerosol penetration. The test method used, which is the same
method used to leak test HEPA filter systems, uses a poly-dispersed aerosol with a light
scattering mean diameter of 0.7 micron. Aerosol should be injected into the system as far
upstream of the sand filter as possible for good mixing. An Air-Aerosol Mixing Uniformity Test,
as described in ASME N510, should be performed to determine the best injection point and
sample points. Although ASME N510 may be used as guidance, supply and return tunnels for
deep bed sand filters are generally underground. It is not practical to add injection or sampling
points after operation begins, so these injection and sampling points need to be included in the
original design of the system to ensure adequate mixing. A perforated dip tube designed and
installed per ANSI/HPS N13.1 should be used upstream and downstream of the sand filter to
further ensure a representative sample of the aerosol concentration is used. Due to the large
volumetric flow rates of deep bed sand filters, multiple generators working in parallel are
needed to obtain the necessary concentrations to perform adequate testing.
Section 68
The upstream and downstream concentration of background aerosols (dust test) that may
interfere with the test results should be performed prior to the introduction of aerosol into the
system. The background test is performed by setting the aerosol photometer’s internal
calibration feature to reference the instrument to a concentration equivalent of 100
micrograms of aerosol per liter of air. The background concentration is then measured
upstream and downstream (upstream first) and recorded. The background levels should be
stable and allow for detection of aerosol penetration smaller than the maximum allowable
penetration. The aerosol should be injected into the sand filter for a period of 15 to 30 minutes,
depending on the size and cfm of the sand filter, prior to the test sampling to allow time for
distribution of the challenge aerosol throughout the sand filter.
4.1.13 Testing Portable HEPA Filtration Systems
4.1.13.1 General Testing and Periodic Maintenance Considerations
Problems with operating portable HEPA filtration systems (PHFS), are often not visually
observable or detectable by onboard instrumentation. Therefore, filter replacement and testing
are important to the continued safe operation of the unit. In-place testing is designed not only
to validate the HEPA filter, but also to verify the integrity of associated seals, gasketing, ducting,
and housings regarding leakage.
DOE-HDBK-1169-2022
72
HEPA filters used in the system should be tested by the DOE FTF before initial use. In addition,
the device should be leak-tested after installation at the site and prior to operation. Most
importantly, a thorough leak test should be conducted every 6 months or any time the unit is
jarred or bumped. Leak tests are conducted by first injecting an aerosol challenge into the inlet
of the PHFS and measuring the aerosol challenge concentration at the inlet to establish a 100
percent baseline. Then the detector samples particle free air to establish a 0.000 percent
baseline. With these two baselines, created samples of the PHFS outlet can be sampled to
measure any aerosol leakage.
PHFS tend to be overlooked when it comes to maintenance and testing. Many standards and
procedures address maintenance and testing of permanent HVAC HEPA filtration systems.
However, no national standards and procedures are available for PHFS. Worse, because of their
size and portability, personnel assume they are functioning correctly. Ironically, these units are
capable of discharging contamination over the specific areas of the work site they are supposed
to be protecting if filter bypass leakage is occurring.
These units by their very nature are prone to leakage. This is mainly because they are small and
portable, and thus are transported from workplace to workplace in the back of trucks and are
subjected to substantial rough handling by workers. This action creates leaks in units that were
previously tested, giving personnel a false sense of security. For this reason, these units should
be tested anytime they are transported to another workplace. When testing PHFS, test
personnel should apply the same rigorous procedures outlined in ASME AG-1 for the
permanent HVAC HEPA filtration systems.
4.1.13.2 Portable Filtration Systems Testing Applications
There are two basic designs for these systems: those that “pull” air through the HEPA filter and
those that “push” air through it. Therefore, some units locate the HEPA filter upstream of the
motor/blower assembly, and others place the HEPA filter downstream of the motor/blower.
The advantages and disadvantages of each design concept are summarized in Table 4.8.
Section 69
Table 4.8: Downstream/Upstream HEPA Filter Locations in PHFS
(+) Advantages, (-) Disadvantages (+) Advantages, (-) Disadvantages
Type A DOWNSTREAM HEPA Type B UPSTREAM HEPA
(+) Easier access to HEPA filter for scanning or
leak testing
(-) Difficult access to HEPA filter for scanning or
leak testing
(+) May not require mixing chamber to assure
uniform mixing of test aerosol
(-) Requires mixing chamber to assure uniform
mixing of test
(-) Motor/blower may become contaminated (+) Motor/blower should stay uncontaminated
unless filter leaks
(-) Cabinet interior may become contaminated (+) Cabinet should stay uncontaminated unless
filter leaks
DOE-HDBK-1169-2022
73
Design, materials, specifications, and quality of construction vary widely among PHFS. These
variables have a tremendous impact on overall performance and effectiveness. In particular,
the cabinet material should remain rigid and undistorted during shipping, handling, and the
rigors of daily operation to prevent the contaminated air from bypassing the HEPA filter. The
type and gauge of metal fabrication methods, braces, holes, cracks, fasteners, welds, gaskets,
and seals should be designed, specified, and assembled with potential leakage, durability in
service, and maintenance in mind. Many of the above items may not be applicable to units
constructed and certified to ASME AG-1 criteria.
4.1.13.3 Testing Problems and Special Considerations
Some of the designers and manufacturers of PHFS have not put much thought or effort into
creating units with integrity leak tests in mind. Not only do they unintentionally “design in”
leaks, but they also often overlook the inclusion of features that allow access to areas that are
critical for leakage testing. Access to the downstream face of the HEPA filter for the purpose of
scanning is virtually impossible in most units where the blower is downstream of the HEPA
filter. A mixing chamber with baffles is necessary at the inlet of this type of unit to provide
adequate challenge aerosol mixing. Downstream measurements of the exhaust airstream can
be subject to error due to channeling—the opposite of mixing. The aerosol from a specific leak
may simply remain concentrated in a segment of the exhaust airstream. Therefore, sampling
should be done at various points across the face of the exhaust air outlet, in effect a “scanning”
of the opening. A single-point sample is usually not representative of what is in the exhaust
airstream because the leak becomes diluted with the particle free air. The same considerations
are included in making air velocity measurements across the exhaust opening or duct in
accordance with ANSI/ASTM 41-2 (1987). A single-point reading is not representative, as
discussed in ACGIH’s Industrial Ventilation – A Manual of Recommended Practice.
The following potential problems may be detected by testing PHFS:15
• Poor design.
• Poor workmanship and inadequate QC by the manufacturer.
• Leaks in the filter media itself.
• Leaks due to failure of the adhesive bond between the filter media and its frame.
• Leaks between the filter frame and cabinet sealing frame seals.
• Leaks between the cabinet main frame and the cabinet housing.
• Leaks in the cabinet or housing due to damage in transit or handling.
• Leaks from misalignment or misassembled components.
• Leaks resulting from incorrect or inadequate maintenance.
• Leaks resulting from improper installation and operation of the PHFS at the work site.
Section 70
4.1.14 Testing HEPA Filter Vacuum Cleaners
HEPA filtered vacuum cleaners (HEPA-Vacs) are most commonly used to control particulate
before it becomes airborne. They are also used to control airborne particles and liquids in and
15 Units constructed and certified to ASME AG-1 criteria are less likely to have these problems.
DOE-HDBK-1169-2022
74
around work areas and to provide localized control of loose debris when work operations could
potentially spread contamination. When used in the nuclear industry, HEPA-Vacs are commonly
referred to as nuclear or radiological vacuum cleaners.
4.1.14.1 Description of Radiological Vacuum Cleaners
Radiological vacuum cleaners are generally well-constructed, well-sealed devices with a HEPA
filter on the exhaust. They are normally mounted on a cart with a comfortable handle and
lockable, steerable wheels for portability and control during use. The power module consists of
a blower powered by an electric motor and controlled by an onboard switch. The filter module
consists of a positively mounted and sealed HEPA filter protected by a medium efficiency filter.
All units should have a positive plenum (tank)-to-vacuum head seal. Vacuums that have latches
but provide a loose tank-to-head seal that depends on the vacuum force to provide a positive
seal (as in many commercially available shop vacuums) should not be used.
Some vacuum cleaners are equipped with controllers that allow the worker to regulate the
flow. This works well in providing negative ventilation in small glove bags. Using HEPA filtered
vacuum cleaners can significantly improve how contamination is controlled.
An inline HEPA filter can be installed in the suction hose to collect radioactive material before it
reaches the vacuum cleaner. Fittings can be made to connect the vacuum cleaner hose to the
HEPA filter. As debris is sucked into the hose, it is deposited on the inline HEPA filter instead of
the HEPA filter inside the vacuum cleaner. Temporary shielding should be installed around the
inline filter before operation, as the filter becomes highly radioactive.
If a large amount of debris will be collected, installation of a waste drum in the suction hose
should be considered to ensure the debris collects in a waste drum and not the vacuum
cleaner. Commercial systems are available, or one can be made by welding two pipes into a
spare drum lid. As each drum is filled, the lid can be installed on a new drum and a regular lid
can be installed on the full drum. Personnel doses are reduced because the debris is collected
directly into the waste drum instead of the vacuum cleaner.
Vacuum cleaners should be constructed of a material that is easily decontaminated without
damage to components. Units that use silicone-based material to prevent leakage should not
be used. All hose connections should provide positive seals and should be constructed of a
material that will not be damaged by repeated use or rough handling.
HEPA filters should have a positive seal and pass in-place leak testing. The filter hold-down
clamps should provide the required force (20 psi) to seal the filter and prevent dislodging
during rough handling and repeated use. They should be constructed of a material that will not
warp or bend with repeated use.
Section 71
The HEPA filter replacement method should be both simple and achievable in minimum time to
reduce exposure and the chance of radioactive contamination. The vacuum cleaners should be
designed to ensure HEPA filter integrity under all conditions of use and to prevent unauthorized
or accidental access to the inner surfaces of the vacuum. Units should be constructed with no
sharp edges or burrs that could injure personnel or damage protective clothing.
DOE-HDBK-1169-2022
75
HEPA filters used in HEPA-Vacs should meet the efficiency and construction requirements for
HEPA filters listed in ASME AG-1 or IEST-RP-CC001, 021, and 034. The maximum flow rate of the
device should not exceed the flow rate at which the HEPA filter was efficiency-tested.
4.1.14.2 Operation
HEPA-Vacs are used to cleanup radioactive debris. Improper use of HEPA-Vacs may result in
generation of airborne radioactivity, loose surface contamination, or high dose rates. HEPA-
Vacs used for radioactive material should be marked, “For Radioactive Service Only.” A nuclear
safety review should be performed and documented prior to use of a HEPA-Vac for fissile
material.
HEPA-Vacs should be appropriate for the type and amount of radioactive material involved. The
health physicist is responsible for determining the levels of filtration required on the exhaust.
Programmatic organizations are responsible for the following items:
• Maintaining control of HEPA-Vacs.
• Ensuring that HEPA-Vacs are properly labeled, controlled to avoid improper use, and
serviced or emptied only by individuals trained to do so, and that the health physicist is
contacted before they are opened.
• Ensuring that HEPA-Vacs (a) undergo visual inspection by the operator prior to each use,
and (b) are leak-tested every six months, after HEPA filter replacement, and after being
subjected to mechanical trauma (e.g., dropped, tipped over, struck by hard object). (See
Section 4.1 of DOE-STD-1269-2022.).
HEPA-Vacs used in contaminated areas should be equipped with HEPA-filtered exhausts or with
exhausts that are directed to installed systems that are equipped with HEPA filters. Such
provisions may not be necessary when these systems are used in areas where only tritium or
radioactive noble gases are present or when the material to be vacuumed is wet enough to
prevent the generation of airborne radioactive material or removable surface contamination.
Extended use of air handling equipment may cause a significant buildup of radioactive material
in the ductwork and filters. Periodic sampling of the exhausted air and surveys of the accessible
surfaces of the equipment should be performed to assess the radiological impact of equipment
operation. While use of the devices discussed above has been proven effective in reducing
contamination spread and associated decontamination costs, these benefits should be weighed
against the potential costs. Use of engineering controls may require expenditure of worker
doses to set up, work in, maintain, and remove the device. There may be financial costs
associated with device purchase or manufacture, worker training, possible reduced
productivity, and device or component maintenance and disposal.
4.1.14.3 HEPA Filter Vacuum Cleaner Tests
Numerous suppliers manufacture HEPA-Vacs, and each supplier has several models available.
This leads to unique characteristics that should be considered when performing in-place
testing. As in the permanent HVAC systems, a thorough visual inspection by trained personnel
of the unit to be tested should be performed before conducting the test. This inspection should
be done using a checklist tailored to the specific make and model to be tested. These units
Section 72
DOE-HDBK-1169-2022
76
should also be tested for proper flow and suction capabilities. Generally, a 4-to-6-inch diameter
duct or flex hose 8 to 10 feet long is used to introduce the challenge aerosol to the input of the
HEPA-Vacs under test. An upstream probe can be fitted close to the end of the hose for
transition to the inlet connector on the unit under test. The output of the aerosol generator
should be directed to the other end of this hose. This configuration usually allows adequate
aerosol-air mixing of the aerosol challenge.
The greatest challenge to testing HEPA-Vacs is obtaining a representative downstream reading.
For most HEPA-Vacs, downstream air is discharged radially in all directions rather than through
a duct (as in permanent HVAC systems). To accomplish this, test personnel usually fabricate a
collection hood to collect all of the downstream air discharged from the unit under test and
connect a duct or hose to the hood. The hose or duct can be fitted with a downstream probe
located at least 10 diameters downstream of the hood. After the upstream/one hundred
percent baseline and the 0 percent baselines have been established, a downstream reading
should be taken both with and without the aerosol generator operating. This is done to verify
whether there is a background leakage reading. Some HEPA-Vacs generate significant amounts
of particles due to their design configuration. If a background reading is detected, it should be
recorded and deducted from the downstream reading obtained with the aerosol generator
operating.
4.1.15 References
1. ACGIH (American Conference of Government Industrial Hygienists), 2015, Industrial
Ventilation – A Manual of Recommended Practices for Design, 28th Edition, Cincinnati, OH.
2. Adams, R. E. and W. E. Browning, Jr., 1965, Iodine Vapor Adsorption Studies for the NS
‘Savannah’ Project, WSAEC Report ORNL-3726, Oak Ridge, TN.
3. Adley, F. E., Progress Report, 1996, “Factors Influencing High Efficiency Gasket Leakage,”
9th Air Cleaning Conference, Atomic Energy Commission Report CONF-660904, National
Technical Information Service, Springfield, VA.
4. Anderson, W. L and T. Anderson, 1966, “Effect of Shock Overpressure on High Efficiency
Filter Units,” 9th Atomic Energy Commission Air Cleaning Conference, USAEC Report CONF-
660904, National Technical Information Services, Springfield, VA.
5. ANSI (American National Standards Institute)/HPS (Health Physics Society), 2011, Sampling
and Monitoring Radioactive Substances of Nuclear Facilities, ANSI/HPS N 13.1, New York,
NY.
6. ANSI/AHRI Standard 850 (I-P) -2013, Standard for Performance Rating of Commercial and
Industrial Air Filter Equipment, Arlington, VA.
7. ASHRAE, 1992, Gravimetric and Dust Procedures for Testing Air Cleaning Devices Used in
General Ventilation for Removing Particulate Matter, Standard 52.1-92, Atlanta, GA.
8. ASHRAE, 2017, Method of Testing General Ventilation Air Cleaning Devices for Removal
Efficiency by Particle Size, Standard 52.2-2017, Atlanta, GA.
DOE-HDBK-1169-2022
77
9. ASHRAE, 2017, Measurement, Testing, Adjusting, and Balancing of Building HVAC
Systems. ASHRAE STD 111-2008 (R2017), Atlanta, GA.
10. ASHRAE (American Society of Heating, Refrigerating, and Air-Conditioning Engineers), 2018,
Standard Methods for Air Velocity and Airflow Measurement, ASHRAE 41-2, Atlanta, GA.
11. ASME (American Society for Mechanical Engineers), 2019, Quality Assurance Requirements
for Nuclear Facility Applications, ASME NQA-1, New York, NY.
Section 73
12. ASME (American Society of Mechanical Engineers), 2002, Nuclear Power Plant Air Cleaning
Units and Components, ASME N509, New York, NY.
13. ASME (American Society of Mechanical Engineers), 2007, Testing of Nuclear Air-Cleaning
Systems, ASME N510, New York, NY.
14. ASME (American Society of Mechanical Engineers), 2019, Code on Nuclear Air and Gas
Treatment, ASME AG-1, New York, NY.
15. ASTM (American Society for Testing and Materials International, 2014, Standard Test for
Nuclear Grade Activated Carbon, ASTM D3803-91(2014), West Conshohocken, PA.
16. ASTM (American Society for Testing and Materials), 1998, Standard Specification for
Hardware Cloth (Woven or Welded Galvanized Steel Wire Fabric), ASTM A740, West
Conshohocken, PA.
17. ASTM (American Society for Testing and Materials), 2014, Standard Specification for
Aluminum and Aluminum Alloy Sheet and Plate, ASTM B209-14, West Conshohocken, PA.
18. ASTM (American Society for Testing and Materials), 2014, Standard Specification for
Flexible Cellular Materials-Sponge or Expanded Rubber, ASTM D1056-14, West
Conshohocken, PA.
19. ASTM (American Society for Testing and Materials), 2018, Standard Specification for
Stainless or Heat-Resisting Steel Wire, ASTM 580, West Conshohocken, PA.
20. Bergman, W. and Hune, 1999, “Maximum HEPA Filter life,” UCRL-AR-134141, Lawrence
Livermore National Laboratory, Livermore, CA.
21. PNNL (Pacific Northwest National Laboratory) 25703-1, 2017, DGL Moleta, JM Barnett, VA
Sabandith, CL Ensign, Interim Status of HEPA 10-Year Lifetime Evaluation.
22. PNNL (Pacific Northwest National Laboratory) TPD-012, 2018, JM Barnett, Regulated HEPA
Filters.
23. BSI (British Standard Institute), 1969, Method for Spot Flame Test for Air Filters, BSI-3928.
24. Defense Nuclear Facilities Safety Board, 2000, Improving Operation and Performance of
Confinement Ventilation Systems at Hazardous Facilities of the Department of Energy,
DNFSB/TECH-26.
25. DoD, Military Standard, 2015, Military Standard Filter Units, Protective Clothing, Gas Mask
Components, and Related Products: Performance/Test Methods, MIL-STD-282 Methods
102.9 and 105.9.
DOE-HDBK-1169-2022
78
26. DoD, 1995, Filter Units, Protective Clothing, Gas Mask Components and Related Products:
Performance Test Methods, U.S. Military Specification MIL-STD-282(4), Edgewood
Biological Center, MD.
27. DOE, 2015, Specification for HEPA Filters Used by DOE Contractors, DOE-STD-3020,
Washington, DC.
28. DOE, 2007, Quality Assurance Inspection and Testing of HEPA Filters, DOE-STD-3025,
Washington, DC.
29. Dupoux, J. and A. Briand, 1977, Méthode de Mesure de L’efficacité des Filtre au Moyen d’un
Aérosol d’Uranine (Fluorescéine), Seminar on High Efficiency Aerosol Filtration, AFNOR NF X
44-011 Standard, Commission of the European Communities, Luxembourg, pp. 249.
30. First, M. W. (Harvard University), 1980, “Performance of 1,000 and 1,800 CFM HEPA Filters
on Long Exposure to Low Atmospheric Dust Loadings II,” 16th Department of Energy
Nuclear Air Cleaning Conference, DOE Report CONF-801038, National Technical
Information Service, Springfield, VA.
31. First, M. W., 1996, Aging of HEPA Filters in Service and in Storage, Journal of the American
Biological Safety Association.
32. Fretthold, J. K., 1997 Evaluation of HEPA Filter service life, Rocky Flats Environmental
Technology Site Report, RFP-5141, Boulder, CO.
Section 74
33. Gilbert, H., J. K. Fretthold, F. Rainer, W. Bergman, and D. Beason, February 1995,
“Preliminary Studies to Determine the Shelf Life of HEPA Filters,” 23rd DOE/NRC Nuclear
Air Cleaning Conference, CONF-940738, pp. 613-638, National Technical Information
Services, Springfield, VA.
34. Hinds, W., M. W. First, D. Gibson, and D. Leith, 1979, Size Distribution of ‘Hot DOP’ Aerosol
Produced by ATT Q-127 Aerosol Generator, 15th Department of Energy Nuclear Air
Cleaning Conference, CONF-780819National Technical Information Service, Springfield, VA.
35. IEST (Institute of Environmental Sciences and Technology), 2007, Testing ULPA Filers, IEST-
RPCC007.3, Mt. Prospect, IL.
36. IEST (Institute of Environmental Sciences and Technology), 2017, HEPA and ULPA Filter Leak
Tests, IEST-RP-CC034, Schaumburg, IL.
37. IEST (Institute of Environmental Sciences and Technology), 2009, Testing HEPA and ULPA
Filter Media, IEST-RP-CC021, Schaumburg, IL.
38. IEST (Institute of Environmental Sciences and Technology), 2016, HEPA and ULPA Filters,
IEST-RP-CC001, Schaumburg, IL.
39. J. K. Fretthold, M. Dykes, and J. Slawski, “Standardized Methods for In place Filter Testing,”
24th DOE/NRC Nuclear Air Cleaning Conference, National Technical Information Services,
NUREG/CP-0153, CONF-960715, Springfield, VA.
DOE-HDBK-1169-2022
79
40. Johnson, J. S., D. G. Beason, P. R. Smith, and W. S. Gregory, 1989, The Effect of Age on the
Structural Integrity of HEPA Filters, 20th DOE/NRC Nuclear Air Cleaning Conference, CONF-
880822, National Technology Information Service, Springfield, VA.
41. LaMer, V. K. and D. Sinclair, 1943, A Portable Optical Instrument for the Measurement of
Particle Size in Smokes, (The OWL); and, An Improved Homogeneous Aerosol Generator,
OSRD 1668, Office of Technical Services, Washington, DC.
42. Linck, F. J. and J.A. Greer, 1975, “In-Place Testing of Multiple Stage HEPA Filter Plenums,”
13th AEC Air Cleaning Conference, Energy Research and Development Administration
Report CONF-740807, National Technical Information Service, Springfield, VA.
43. LLNL Environment, Safety, and Health Manual, Adverse Operating Conditions to Avoid,
Document 12.5, HEPA, HEGA, and ULPA Filter System Design for LLNL Applications,
Lawrence Livermore National Laboratory, Livermore, CA.
44. Mecca, J. E. and J. D. Ludwick, 1970, In-Place Testing of the Hanford Reactor Charcoal
Confinement Filter Systems Using Iodine Tagged with Iodine-131 Tracer, U.S. Atomic Energy
Commission Report DUN-SA-105, Douglas United.
45. Molker, B. V. and R. Scripsick, 1994, High Efficiency Filter System—General Observations,
1992-1993, LA-12763-SR, Los Alamos National Laboratory, Los Alamos, NM.
46. Muhlbaier, D. R., 1967, Standardized Nondestructive Test of Carbon Beds for Reactor
Confinement Application, U.S. Atomic Energy Commission Report DP-1082, Savannah River
National Laboratory, Aiken SC.
47. NRC, Generic Letter, 99-02, 2002, Laboratory Testing of Nuclear Grade Activated Charcoal.
48. NRC, 2012 Design, Testing, and Maintenance Criteria for Engineered -Safety-Feature
Atmospheric Cleanup System Air Filtration and Adsorption Units of Light-Water-Cooled
Nuclear Power Plants, NRC Regulatory Guide 1.52 (Rev. 4), Washington, DC.
49. NRC, 2016, Design, Inspection, and Testing Criteria for Air Filtration and Adsorption Units of
Normal Atmosphere Cleanup Systems in Light-Water-Cooled Nuclear Power Plants,
Regulatory Guide 1.140, Revision 3, Washington, DC.
Section 75
50. Ortiz, J. P., “In-place Testing of Multiple Stage Filter Systems Without Disruption of Plant
Operations in the Plutonium Facility at Los Alamos,” 18th DOE/NRC Nuclear Air Cleaning
Conference, CONF 840806, National Technical Information Services, Springfield, VA.
51. Pearson, J. R., et al., 1994, Replacement Tracer Agents for the In-Place Leak Testing of
Adsorbers in NATS,” 23rd DOE/NRC Air Cleaning Conference, National Technical Information
Services, NUREG/CP-0141, CONF 940738, Springfield, VA, July.
52. Ricketts, C. I., V. Rüdinger, and J. G. Wilhem, 1987, “HEPA Filter Behavior Under High
Humidity Airflows,” 19th DOE/NRC Nuclear Air Cleaning Conference, Springfield VA, CONF-
860820, NTIS, pp. 319-52, May.
DOE-HDBK-1169-2022
80
53. Robinson, K. S., C. Hamblin, R. C. Hodierne, and M. J. S. Smith, 1986, “In-service Aging Effects
on HEPA Filters,” Gaseous Effluent Treatment in Nuclear Installations, Graham and Trotman,
London, England.
54. Rüdinger, V., C. I. Ricketts, and J. G. Wilhelm, 1985, “Limits of HEPA Filter Application
Under High Humidity Conditions,” 18th DOE/NRC Nuclear Air Cleaning Conference.
55. Scripsick, R. C. and S. Soderholm, 1987, “Final Report: Evaluation of Methods,
Instrumentation, and Materials Pertinent to Quality Assurance Filter Penetration Testing,”
LANL LA-10748.
56. SMACNA (Sheet Metal and Air Conditioning Contractors’ National Association), 2006, HVAC
– Duct Design, 4th Edition, Arlington, VA.
57. UL (Underwriters Laboratory), 2017, Standard for Safety High Efficiency, Particulate, Air
Filter Units, UL 586, Northbrook, IL.
58. UL (Underwriters Laboratory), 2015, Standard for Air Filter Units, UL 900, Northbrook, IL.
DOE-HDBK-1169-2022
81
4.2 Glovebox Filtration
4.2.1 Introduction: Filtration Components
Gloveboxes are enclosures that enable operators in various industries to use their hands to
manipulate hazardous materials through gloves without exposure to themselves or subsequent
unfiltered release of the material to the environment. In the nuclear industry, gloveboxes
provide primary confinement for radioactive material handling and process protection and are
used to handle a diverse range of chemical, oxygen-sensitive, pyrophoric, hazardous, and
nuclear materials. There are many other factors, such as seismic hazards, that could affect
glovebox filtration design and operation. Secondary confinement may be provided by the room
or building where the gloveboxes are located.
Ventilation is the heart of the glovebox system. Nuclear materials requiring handling inside a
glovebox usually present little or no penetrating radiation hazard but emit radioactive particles
that could be dangerous if inhaled. Gloveboxes prevent operators from inhaling radioactive
particles as they work with various nuclear materials and help provide a clean, controlled, safe
working environment. For glovebox ventilation to be effective, however, proper design
pressures and flow criteria need to be maintained. Glovebox pressures range from mostly
negative (for confinement) to positive pressure environments (for process protection). Failure
to maintain correct operational pressures or to follow established operational procedures could
render a glovebox both ineffective and unsafe.
4.2.2 Glovebox Types and Characteristics
Section 76
To understand the importance of glovebox filtration, a clear understanding of glovebox
characteristics and functions is necessary. A glovebox is a windowed, airtight (sometimes gas-
tight) enclosure that may be capable of both positive or negative internal pressure. It is
equipped with one or more flexible gloves for manipulation of materials and performance of
operations inside the enclosure from the outside, uncontaminated environment. Figure 4.12
defines and lists characteristics of gloveboxes, with a focus on their use in the nuclear industry.
Originally, many gloveboxes were vendor-designed, so the designs were proprietary. As a
result, many older boxes have unique ventilation designs. Later on, professional societies such
as the American Glovebox Society (AGS) issued documents such as AGS-G001, Guidelines for
Gloveboxes, and AGS-G006, Standard of Practice for the Design and Fabrication of Nuclear
Application Gloveboxes, written by experts who design, manufacture, and operate gloveboxes.
This document contains useful information on subjects ranging from the need for a glovebox to
QA acceptance programs.
DOE-HDBK-1169-2022
82
Figure 4.12: Characteristics of Gloveboxes
Gloveboxes generally have several common characteristics. Gloveports (window-mounted or in
the stainless-steel shell) are usually available in multiples of two at various locations in the
glovebox walls. Interior workspace is reserved for primary operating purposes on the box floor
between the gloveports and within reach of a gloved hand.
Gloveboxes are normally kept at a negative pressure of 0.3-to-0.5 in. wg relative to their
surroundings. The maximum safe operating differential pressure between the interior and
exterior of the box is usually less than 4 in. wg; greater differential pressure may damage or
rupture a glove or window, causing subsequent loss of confinement. Operators experience
fatigue when pressures inside a glovebox are greater than 0.5 in. wg, and performance of
intricate tasks becomes tedious. However, alternate 16 operating pressures may be used if
evaluated and based on system effects, operating conditions, hazard mitigation, and protection
of worker. Material and HEPA filter transfers between glovebox interiors and exteriors are
commonly made through a bagging port which, although time-consuming and user-dependent,
is still the safest practical way of maintaining confinement. New versions of this technology use
a banding system. Other material transfers use rapid transfer ports (RTPs), which allow simple
docking from glovebox to glovebox. This is a reliable method of maintaining confinement, as
long as the seals are maintained and undamaged.17 Gloveboxes with RTPs are still equipped
with bagging ports for filter changes and waste disposal.
16 Reference AGS-G001-207, Sections 5.6.1 and 9.4.2 on normal operating differential pressures range from -0.5 to -1.5 in w.g.
17 Transfers of powders can egress past the seals if exposed. Such powders should be contained in a secondary
container and the seals protected during operations.
DOE-HDBK-1169-2022
83
Special atmospheres such as inert gas and dry air are often used in gloveboxes for fire
suppression and for oxygen-sensitive and/or moisture-sensitive materials and processes. Gas
purification systems are commonly used in conjunction with inert environments to maintain
environmental control. These units purify and dry the environment to prevent consumption of
large volumes of inert gas and desiccant. These devices should be protected from
contamination because they constantly recirculate the volumes of the gloveboxes they serve.
Section 77
4.2.3 Importance of Glovebox Ventilation and Filtration
Operations conducted in gloveboxes often provide the elements for unstable conditions (e.g.,
fire and pressurization). A properly designed and operated glovebox ventilation system
minimizes these instabilities as well as the possibility of an accidental release of airborne
radioactive material. Room air is a safe glovebox environment for many applications. On the
other hand, operations with pyrophoric materials such as plutonium or the presence of reactive
gases such as hydrogen may require a special environment (e.g., nitrogen, low oxygen, inert
gas, and moisture control).
For air-atmosphere boxes, ventilation at relatively low flow rates provides sufficient dilution of
the limited combustible volatiles found in well-operated gloveboxes. The correct airflow
volume, along with the proper location of supply and exhaust filters, minimizes the likelihood of
fire while providing sufficient dilution to prevent the buildup of explosive gases. Good glovebox
ventilation dictates that HEPA filters are operated at their designed airflow. HEPA filters should
be tested and certified at the manufacturers’ rated airflow.
Normal air changes through a glovebox remove some of the heat generated by equipment
inside the box and help maintain reasonable working temperatures for the operator. However,
this convective cooling may be insufficient to remove all of the process heat generated in the
box, and auxiliary cooling or higher airflow volume may be required.
Most glovebox ventilation systems include some form of pressure relief and adequate pressure
control to maintain proper pressure differentials between the glovebox and its surroundings. If
a glove should tear or accidentally come off, there should be an assured, sufficient ingress of air
through the gloveport to prevent egress of contamination until the port is closed. This safety
feature is inherent if the glovebox ventilation is designed and operated properly. Pyrophoric
operations, however, should have appropriate safeguards to prevent air intake from starting a
severe reaction.
Proper instrumentation should be provided to warn of inlet/exhaust filter blockage and loss of
pressure/confinement. Pressure gauge/transducer line filters should be used to protect this
instrumentation.
4.2.4 Design of Glovebox Ventilation Systems
4.2.4.1 Introduction
The principals of glovebox confinement are basic. Airflow of 125 ± 25 feet per minute (fpm)
through a breached (8-inch diameter) gloveport will maintain confinement. This is an inherent
DOE-HDBK-1169-2022
84
(defined as “real time, at the moment of failure”) safety feature that should be incorporated
into the glovebox system. Most nuclear, biological, and pharmaceutical facilities in the U.S. are
designed to provide this capability (within a range of 10 percent).
The air change rate is an important consideration for all gloveboxes. As glovebox volume
increases, airflow should increase. Nonetheless, the inherent safety feature of 125 ± 25 fpm
through a gloveport should be maintained. For normal operations, flow rate is based on the
dilution of evolved combustible or corrosive gases and heat dissipation, as well as prior
experience. The exhaust capability should be sufficient to provide safety under postulated
abnormal conditions, including the gloveport breach. In certain other applications, the exhaust
capability should be sufficient to provide safe access for planned activities.
Section 78
Operating personnel, industrial hygienists, and radiation specialists can assist the designer in
establishing realistic requirements, particularly when an existing system is being replaced or
revised. The types and quantities of materials to be used inside the box and their toxicity and
state (e.g., wet slurry, dry powder) should be considered when establishing the air exchange
rate and velocity. When exposed radioactive material is handled inside a glovebox, the box
becomes the primary confinement. When handling nuclear and pyrophoric materials,
consideration should be given to whether pressure inside the glovebox should be positive or
negative.
A positive-pressured glovebox provides a motive force for airborne contamination to leak from
the box into the secondary confinement (the room or facility). Negative pressure inside the box
is essential to maintain glovebox confinement when working with radioactive material. It is not
usually acceptable to design a normal operating condition that allows a primary confinement
area to be positive to the secondary confinement area. However, in a unique or unusual
application where an inert environment is used to control fire and explosion, the box may be
slightly positive or even neutral, and the facility becomes the primary confinement. This
suggests the need for a secondary confinement and also flags the need for personal protective
equipment and appropriate procedures to protect the worker. The designer should design for
failure (i.e., using the worst-case scenario) to predict the consequences of a glovebox failure.
The designer also should consider test and acceptance criteria.
4.2.4.2 Blowers
Regardless of the type of blower or manufacturer, the required airflow and pressure
requirement needs to be attained for safe operation of a glovebox. Another criterion for blower
selection and design is selection of a blower that does not exceed the pressure limits of the
glovebox. Depending on their size, most stainless-steel gloveboxes with 7-gauge walls are
designed and tested at -4 in. wg. Exceeding this pressure may cause damage to the glovebox
windows, seals, and shell. If the blower exceeds this limit, the glovebox should be equipped
with a pressure relief device. loading the exhaust filter will prevent the blower from quick
recovery. Exhaust filter and gloveport sizes also influence recovery. This is the reason for
maintaining the inherent safety feature at the design phase of a glovebox project. If larger
gloveports (greater than 8-inch-diameter) are selected, the need for additional airflow should
DOE-HDBK-1169-2022
85
be engineered. Site-specific filter housings and filters may not address the need for increased
airflow.
Blower location depends on several variables in glovebox applications. If a scale or other
vibration-sensitive device is used in the glovebox, the blower should be isolated from the
glovebox shell with vibration isolators and a flexible inlet/exhaust connection. Although this
works in most applications, some may require remote location of the blower away from the
glovebox. Blower noise should be considered to prevent annoying the workers. Noise levels
should be kept to less than 80 decibels A-weighted.
4.2.4.3 Filter Housings
Section 79
A filter housing design should consider safety, ergonomics, and reliable operation. Filter
change-out should be simple and should maintain a safe level of confinement. The design
should prevent any form of contamination from reaching the downstream ductwork or
secondary confinement (the facility). The design should satisfy the ergonomic requirements of
filter changes and allow the operator to perform the operation safely (without exposure or
injury). A top-mounted filter housing should be located as close to the front of the glovebox as
possible and should be aligned with a gloveport. Process activities and materials could block the
exhaust filter. Without the exhaust filter airflow, it would be difficult to maintain confinement.
The filter housings on gloveboxes differ from most filter housings in that they are very small
due to ergonomic limitations and low airflow requirements. Changing a glovebox filter is
difficult because it has to be performed through a gloveport with limited operator movement.
Use of larger filters should be avoided because they are difficult to handle safely inside a
glovebox without special tooling.
Types of Housings
The types of filter housings selected for use on gloveboxes have always been application-
specific.
“Pressure recovery” is a term that evolved from quick insertion and removal of operators’ arms
into and out of the gloves, although the blower will deal with most of the volumetric changes
caused by glove movement. As many nuclear facilities functions under different directives, filter
housings have evolved to suit their respective applications. Early gloveboxes often had
externally mounted HEPA filters. Because of the potential for spreading contamination during
filter changes, this practice should be avoided.
Internal filter installations range in design, however, and all have a mechanism to restrain the
filter (a HEPA filter) and a sealing mechanism. These mechanisms also vary; however, it is
critical that the mechanism be free of sharp edges that can easily cut gloves. Cracks and
crevices should be kept to a minimum since the location makes cleaning difficult. Filter housing
construction typically requires clean, smooth finishes to allow cleanup of contaminated or
potentially contaminated areas. Experience has shown that areas exposed to contamination
can be difficult to clean. The rougher the surface of the housing, the more difficult it is to clean.
Valves, located to the outside, are used to isolate the spent filters during filter changes. Most
DOE-HDBK-1169-2022
86
applications use a medium efficiency filter to protect the HEPA filter, as well as a fire screen
when there is a potential for fire.
The last basic requirement is a means and method to remove the contaminated filter from the
glovebox. The most common method is the bag-in/bag-out method. Push-through filter
housings differ in that they hold the standby filter in the filter housing. (See Figure 4.13 for
push-through filter housing). The filter is a cartridge type with chevron seals located at the inlet
and the exhaust of the round cartridge filter. One of its advantages is that it is designed to
maintain confinement during a filter change. A new filter displaces the spent filter as it is
pushed through. The old filter and spacer are displaced to the inside of the glovebox. The inner
pipe “tube” of the housing is honed to obtain a smooth, round surface. The chevron seal, which
is larger than the internal diameter of the tube, creates the seal.
Section 80
Figure 4.13: Push-through Filter Housing
Although this system has been used with great success, seal quality and tube finish are critical
to its proper operation. This filter housing design is vulnerable, however, when it is used for
applications involving light, easily airborne materials. Such materials, if surface-deposited on
the inside tube, can bypass the seals during a filter change because the seal can “roll over” the
material. Another potential drawback of this design is its orientation. It should be installed in a
vertical position for proper sealing. A horizontal installation will enable the seals to “take a set”
and eventually bypass the filter. This filter housing has been used at nuclear facilities in the U.S.
for many years with good reliability; however, its limitations should be noted.
DOE-HDBK-1169-2022
87
Cartridge filters can be used for glovebox operations for both radioactive and nonradioactive
applications. These filters incorporate the filter housing and filter as a single unit and are
supplied from the manufacturer with options for pipe nipple connections on both the inlet and
exhaust or on one end only. Test ports should be specified when ordering, as these filters range
in size and airflows. A valve should be located on the outside of the glovebox filter housing.
Radioactive Applications
In some radioactive applications, the cartridge filter should be located on the inside of the
glovebox for safe filter changing. The isolation valve is located on the outside of the glovebox
filter housing.
Bag-in/bag-out side-access filter housings are used in some glovebox applications. They are
available in sizes from 35 cfm on up and in rectangular or round configurations, as discussed in
Chapter 4. For radioactive applications, it is desirable to mount the housing as close to the
glovebox as practical. Long ducting or plenum runs are not desirable due to their lack of access
for cleaning. Mounting the filter housing directly to the glovebox reduces the potentially
contaminated surface area.
Redundant filter housings (Figure 4.14) are used when working with materials that, if released
through the exhaust system, would be detrimental with respect to both safety and associated
cleanup costs. All nuclear facilities use a secondary exhaust before discharging to the outside
air. In some older facilities, manifold systems were not designed for safe, clean
decontamination. If contamination migrates into these systems’ ducting, cleanup is both costly
and time-consuming. As a result, use of a redundant filter should be considered. The design of a
redundant system requires the use of an in-place-tested primary and secondary HEPA exhaust
filter installation. Figure 4.14 shows two redundant filter housings—one filter changed from
inside the glovebox (primary); the other (secondary) is shown as a bag-in/bag-out type changed
from the outside.
DOE-HDBK-1169-2022
88
Figure 4.14: Redundant Filter Housings
Materials
It is important to understand (a) the construction materials used on the filters and filter
housings for gloveboxes, particularly chemical processing gloveboxes, and (b) which chemicals
and gases will be introduced into the airstream of the glovebox and where they will be
processed if processing is required. If a bag-in/bag-out port is used, the bag material is subject
to the same exposure to chemicals and gases as the rest of the ventilation. If the process
performed in the glovebox changes or other materials are introduced into the glovebox system,
the compatibility of the materials should be re-evaluated. Simply put, the materials, ducting,
and blower unit need to be compatible with the chemicals and gases exposed to the exhaust
airstream.
Section 81
In-Place Test Ports
A glovebox filter housing is relatively small compared to most filter housing installations. As
with any HEPA filter installation, test ports should be placed on the filter housing to validate the
installation. The criteria for testing gloveboxes focus on the proper location to inject the
challenge aerosol, upstream, and downstream samples. The test ports should be designed to be
sealed after each use and to be as cleanable as possible. This is usually a 3/8- to 1/2-inch half-
coupling/nipple with the appropriate plug/cap. The weld and finish of a test port should
emphasize clean smooth surfaces, especially from the inner diameter of the port to the filter
housing. Cracks and crevices in this area are next to impossible to clean via access through
gloveports.
DOE-HDBK-1169-2022
89
Bag-in/Bag-out Ports
Bagging ports are used on gloveboxes for multiple purposes such as transferring materials and
equipment and removing the waste generated during operations. Significantly, they are also
used to transfer new or spent filters while maintaining confinement. The bagging port should
be sized to accomplish this purpose. Use of a cylindrical bagging port is preferred because this
design is “operator friendly.” A typical bagging port should have two outer-raised ribs around
the outer circumference to prevent the bag from being easily pulled off during operations. The
ribs are normally raised approximately 1/4- to 3/8-inch above the outer circumference and 1 to
1.5 inches apart.
A safety-restraining strap should be used to prevent the bag from being easily pulled off. It
should be installed whenever the bagging port is being used and should be removed only when
performing the bag-in/bag-out (new bag installation) procedure. The strap is secured between
the two ribs. A cinching strap may be used to prevent the bag from being sucked into the
glovebox due to negative pressure. It is installed when the bagging port is not being used. An
internal access door may be used to isolate pressure surges and to act as a secondary
confinement for the bag. The door should have a seal to prevent egress of contamination from
the glovebox. An external cover may also be used to protect the bag and keep it out of the way
of other operations. A “bagging kit” should be supplied with a bagging port. It should contain
the components, tools, and procedures to perform the operation.
Sealing Mechanisms
There are multiple sealing methods for filter housings and filters used on gloveboxes. These can
be application-specific or site-specific and either gasket- or fluid-sealed. The designer should
consider chemical, gas, radioactivity, and heat as deciding factors in determining which sealing
mechanism to employ. In some applications, the filter housing is welded and incorporated into
the glovebox. In others, the filter housing is a bolted, gasketed installation. The bolted design is
more versatile by design; however, a potential crack at the gasket interface may make
decontamination difficult. It should be noted that a push-through filter housing should be
bolted due to the housing manufacturing process. Filter seals vary by application. HEPA filters
can be supplied with many different gaskets and fluid sealing systems.
Blower Connections
Section 82
If a dedicated blower is to be installed on a glovebox, several installation considerations should
be addressed, including vibration, exhaust connection configuration, and blower discharge
configuration. It is generally accepted practice to use a flexible connection in most ventilation
applications. Vibration from the blower will transmit to the filter housing and subsequently to
the glovebox. If a flexible connection is used to isolate vibration from the blower, there is a
potential for heat damage to the connector. Noncombustible materials should be selected for
this application. Blower designs vary. Selection of the exhaust and inlet connection should
prevent severe effects on blower capacity. Obstructions at the immediate inlet and outlet will
grossly affect blower capacity. Elbows and tees at the inlet will also affect capacity and should
be avoided.
DOE-HDBK-1169-2022
90
4.2.5 Dilution of Evolved Gases
A high air exchange rate is often required to dilute fumes generated in an air-ventilated
glovebox. When evolved gases, vapors, and particles are not flammable, toxic, or corrosive,
flow rates sufficient to maintain a negative pressure (with differentials from 0.3 to 0.5 in. wg in
the box) may be employed. However, when fumes or vapors are hazardous, a higher ventilation
rate is necessary. The maximum generation rate of hazardous substances is determined to
establish the minimum airflow needed for dilution.
4.2.6 Heat Dissipation
Heat removal affects glovebox ergonomics. Operators access the inside of the glovebox using
gloves that are often awkward to use and gloveports that limit their operations. When higher
than normal heat conditions exist in a glovebox, it leads to higher fatigue levels. This limits the
operations that can be performed in the glovebox environment. For worker comfort, sufficient
air should be exchanged through the box to limit the inside temperature to no more than 15
degrees Fahrenheit above room temperature. When the calculated airflow for cooling exceeds
the exhaust cfm, consideration should be given to higher airflow (larger filters or more filters),
supplementary cooling, better insulation of heat sources, cooling coils, or chill blocks for hot
materials. In the design phase of a glovebox project, the designer should be aware of the heat
load presented by the equipment located in the glovebox. It is desirable, when practical, to
determine whether items like electric motors can be placed to the outside of the glovebox. This
can reduce the heat load inside the glovebox significantly, as well as simplify maintenance and
serviceability and reduce disposal costs.
Operations to be performed in a glovebox should be determined ahead of time. Airflow
velocities can affect the operation of sensitive equipment and cause materials like powders to
become airborne.18 There are practical limits to the amount of cooling that can be
accomplished by airflow, since high airflow can create strong air currents if not properly
diffused. Where possible, operators should be protected from objectionable sources of radiant
heat by surrounding the heat source with reflective shields or conductive jackets. Exhaust
airstreams may be routed through such shields to permit the maximum pickup of convection
heat before leaving the box.
Long-term operation of high-heat-producing equipment can damage filters when exhaust air
temperatures approach the temperature limit of the filters for continuous exposure to heat.
4.2.7 Empirical Flow Rates
Section 83
The ventilation system should be designed to provide a safe, ergonomically practical, and
reliable unit. Experience has shown that filter pressure drops will vary, ductwork loss will be
greater, and blower performance may be slightly different in actual working conditions (other
variables also are discussed in this chapter). If the glovebox ventilation system does not
18 Negative pressure also can cause equipment problems.
DOE-HDBK-1169-2022
91
perform as designed, it should not be used or commissioned until it meets the minimum safety
requirements of this document and other referenced documents.
Troubleshooting an installation should include the inspection of the ductwork and installation
of the blower (including wiring); the medium efficiency filter, inlet, exhaust HEPA filters; and
the manifold (if equipped). Common problems with new installations include debris lodging in
the ducting, blower housing, and filter housing and finding the blower motor wiring reversed.
Long flexible connections will also affect performance since a bend can dramatically choke off
airflow.
4.2.8 Exhaust Requirements
The maximum airflow from the glovebox determines the required capacity of the filters and the
size of the equipment for the entire downstream portion of the ventilation system. The airflow
resistance of the exhaust-air path needs to be sufficiently low so that pumping of gloves
(pressure recovery) by operators in the box will not result in positive pressurization. In small
low-flow boxes such as those with an inert atmosphere, pressure surges due to glove pumping
may be a serious problem. Fast insertion of the gloves can cause the glovebox to reach a zero or
positive pressure. Typically, the glovebox is fitted with an inlet and exhaust filter in a room air
application. Another filter “emergency discharge” is added and fitted between the blower
discharge and the inlet air filter. The blower installation connects the exhaust filter housing to
the negative side of the blower, and the inlet filter installation connects to the positive side.
When the installation is complete, the emergency discharge filter is in a standby condition. The
ventilation unit basically recirculates the inert gas. If a breach or leak occurs, the emergency
discharge filter becomes naturally activated. The path of least resistance during a breach
discharges exhaust air through the emergency standby filter since the inlet is now the
gloveport. This filter should also be sized for the gloveport “inherent safety feature.” The filter
should be rated for twice the cfm or half the pressure drop of the inlet filter. If the two filters,
inlet, and emergency standby, have the same airflow and pressure drop, the airflow will be
directed to both instead of the emergency standby filter. If air is to be exhausted from the
emergency standby filter, a bleed vent is necessary to prevent removing the inert gas and
imposing additional negative pressure.
When the glovebox ventilation unit is activated, there should be no flow through the
emergency standby filter. If the secondary exhaust system is directly connected without a bleed
vent, the glovebox pressure will become extremely negative. The vent allows room air to be
removed until the emergency standby filter requires exhaust.
Section 84
The maximum rate of exhaust flow from a room-air-ventilated glovebox is usually based on the
required inlet flow when a glove is ruptured or inadvertently removed. The air velocity into the
open gloveport should be at least 125 linear fpm. Good contamination control is more easily
achieved in a glovebox with low air leakage. Gloveboxes should have a leakage of less than 0.02
to 0.5 percent box volume per hour, depending on the application requirements. In some
applications, such as inert environments, a helium leak test is performed to ensure the integrity
DOE-HDBK-1169-2022
92
of the glovebox. The method, technique, and criteria for testing are given in AGS-G004-2014.
Section 5.3 (Helium Mass Spectrometer Leak Detection) and Section 6.2 (Pressure Decay Test).
4.2.9 Vacuum-and Pressure-Surge Relief
In some applications, gloveboxes need to be protected against physical damage resulting from
excessive pressure or vacuum. The exhaust and inlet supply system should be able to handle
slowly manifested pressure or vacuum disturbances. Each glovebox containing service
connections or internal equipment whose malfunction might cause a pressure surge should be
equipped for prompt surge relief. This also applies to fire suppression systems, as outlined in
DOE-STD-1066-2016. The response time and pressure-flow characteristics of the surge-relief
device will depend on the flow and pressure characteristics of the pressure source, the free
volume, and the relative strength of the gloves and glovebox. The relative strength is defined as
the lowest pressure differential that will cause rupture of the glovebox pressure boundary at its
weakest point. Depending on the design of the box, the weakest point will usually be a window
or a glove. The surge-relief device can be a liquid-filled U-tube, as shown in Figure 4.15. The
surge-relief flow capability should exceed the flow from the largest possible source of
pressurization at the design relief pressure. The HEPA-filtered surge-relief line should not be
connected to a glovebox exhaust manifold because this line will be subjected to the same
pressure as the normal glovebox exhaust connection. A liquid storage reservoir is provided to
handle the blown seal fluid.
Figure 4.15: Glovebox Vacuum-Pressure Surge Relief Device
The filter and ductwork should be sized in accordance with the required cfm and pressure drop
based on the pressure surge. The filter should be protected from impingement of the seal fluid.
If room air cannot be tolerated in the glovebox, as is the case in some inert-atmosphere
applications, a different vacuum surge-relief system is used. A U-tube can be devised to restore
its seal after relieving the surge, but such a system includes a feature to alert the operator that
a pressure surge has occurred so that he can make the necessary safety checks. An inlet filter
may provide surge relief if no backflow device or other restriction is provided. The filter face
area would have to be about four times the area of an unfiltered port to achieve an equal
venting effect.
DOE-HDBK-1169-2022
93
4.2.10 Glovebox Exhaust Manifold
A glovebox exhaust manifold is used when multiple gloveboxes will share a common ventilation
system. This method reduces the amount of exhaust ventilation components for dedicated
exhaust systems. The glovebox exhaust manifold includes all of the glovebox exhaust system
downstream from the point where the exhaust from two or more gloveboxes joins and the
airflow is combined.
Section 85
The glovebox exhaust manifold draws air or exhaust gas from each connected glovebox at a
controlled pressure and airflow (interdependently), houses secondary treatment facilities, and
transmits the air for further treatment or exhausts it to the outside atmosphere. Primary
exhaust treatment should be applied inside or as close to the glovebox as possible and, in all
cases, before connection of the exhaust line to the exhaust manifold. It is critical to protect the
manifold from contamination due to the difficulty of cleaning and decontamination. In some
systems, a portion or most of the cleaned or treated exhaust gas may be recirculated back to
the gloveboxes.
The manifold system should be sized and controlled for the maximum flow, based on (1) the
maximum normal flow from each box, (2) the largest maximum flow under removed glove
conditions from one of each of five connected boxes, and (3) an allowance for system growth.
The low extreme is the sum of the minimum flows from each box. An allowance for system
growth should be provided at not less than 20 percent of (1) plus (2) above for a new system. If
this allowance exceeds 50 percent of (1) plus (2), other provisions such as installing an
equivalent dummy flow should be considered.
4.2.11 Exhaust Cleanup Criteria
Providing as Low as Reasonably Achievable (ALARA) exposure to radioactive material is the
guiding principle for determining the design of a glovebox ventilation unit. Protecting the
exhaust downstream of the primary HEPA filter is paramount for nuclear installations.
Experience has shown that exhaust systems are not only difficult to decontaminate but have
led to unnecessary operator exposures. It is also true that, after filter breakthrough, nuclear
particles can migrate to all the gloveboxes in the chain.
Installations employing redundant HEPA filters need to have features allowing in-place testing.
The requirements are provided in ASME AG-1, Section TA.
4.2.12 HEPA Filters
A single-HEPA-filtered exhaust path is defined as a glovebox that does not involve highly toxic
aerosols or potent, toxic, or radioactive materials, i.e., materials that do not pose a hazard to
the operator during a filter change-out. A multiple-filtered exhaust path is defined as a
glovebox requiring more than one line of defense from particle penetration. This occurs when
the exhaust ductwork or manifold needs to be protected or the Most Penetrating Particle Size
is well below the efficiency particle mean of the filters.
DOE-HDBK-1169-2022
94
When continuous airflow is essential, two exhaust connections should be provided to avoid
interruption of exhaust flow during a filter change and to provide standby protection in the
event of system upset. The purpose of multiple exhaust connections is to allow an emergency
connection to be made. Figure 4.16 illustrates single- and multiple-filtered exhaust connections
for a glovebox.
Multiple-filtered exhaust connections should be used when interconnected gloveboxes or a
large enclosure with several compartmented work areas are needed. Compartmenting doors
between work areas or between single boxes in an interconnected line should not isolate a
work area with only one filtered exhaust connection. The multiple exhaust points required to
handle total airflow in a line of interconnected boxes should be sized for maximum flow and
valved individually for flow control.
Figure 4.16: Single-Stage and Two-Stage Filtration
Section 86
The glovebox designer should understand the limitations imposed by ergonomics. There is an
art to designing the glovebox, ventilation service, and internal equipment operation and
DOE-HDBK-1169-2022
95
service. Some facilities build mockups of the glovebox concept to determine whether the
operations can be done in a practical manner. It is critical to prove the practicality in some
operator-intensive, hands-on operations and long-term production activities. Tasks performed
within the confines of a glovebox should factor in the weight of the objects handled and the
location of the operation(s) to be performed within. It is better to demonstrate the activities at
the design phase than to wait for the glovebox to be built. Failure to do this can be very costly
to repair and can seriously compromise operator safety.
The fatigue factor is high when working in a glovebox. The working pressure, heat, glove
sleeves, gloveport location, and operations where the arms are outstretched all add to fatigue.
Intricate or sensitive work significantly adds to fatigue because the operator cannot feel
through the gloves. If visibility is poor or nonexistent, operations will be very difficult, if not
impossible, to perform. Some operations with older gloveboxes used mirrors to perform some
operations. In glovebox terms, “extended reach” is used to describe an occasional operation
where something is pulled forward to a working position or a simple operation such as turning
a switch off or on (e.g., lowering or pulling out a spent filter for disposal). Extended reach
should be avoided in repetitive or routine operations.
4.2.12.1 HEPA Filter Selection Criteria
The characteristics listed below should be considered when selecting filters.
• A standard-size HEPA filter is located in the back- or end-wall of the glovebox.
• Inside box space is maximized by partially recessing the filter in the wall.
• Provides adequate space to transfer the HEPA filter out of the glovebox (see Table 4.9
below).
• A simple clamping method is used that has no removable pieces and is operable with a
gloved hand by a simple, clean clamping mechanism.
• A retainer is used that serves as a face shield for the filter and permits attachment of a
steel-cased medium efficiency filter by a flexible magnetic strip, accessible from the
front, hence the filter remains in position after being unclamped because of the folded
lip at the top.
Table 4.9 – Glovebox Bag-Out Port Sizes for Transfer of Standard Open-faced HEPA Filters
Filter Size Required Port Size (inches)
Round (diameter) Rectangular
8 x 8 x 2 1/16 9 3/4 8 1/2 x 4 1/2
8 x 8 x 5 7/8 10 3/4 8 1/2 x 6 1/2
12 x 12 x 5 7/8 14 12 1/2 x 6 1/2
24 x 24 x 5 7/8 26 25 x 6 1/2
24 x 24 x 11 1/12 27 3/4 25 x 12
DOE-HDBK-1169-2022
96
4.2.13 Medium Efficiency Filter (Prefilter) Selection
Medium efficiency filters are used to extend the life of the HEPA filters located at the inlet and
exhaust filter housings. This can be determined by noting the sensitivity of glove movement and
pressure recovery. In easily airborne powder applications where a significant amount of dust is
airborne in a glovebox, removing the medium efficiency filter may be the only means to restore
safety (negative pressure) to the glovebox during a powder mishap.
Section 87
Medium efficiency filters for gloveboxes come in a range of sizes and configurations. Some
facilities use simple cut, in-place pads, and some use HEPA filters (not tested) to perform the
medium efficiency filter function. For some applications where air entering the glovebox is
HEPA-filtered and there is little or no dust loading in the glovebox, an exhaust medium
efficiency filter may not be needed. A medium efficiency filter should be considered on the inlet
HEPA filter on the glovebox unless the glovebox resides in a cleanroom. Medium efficiency
filters are manufactured from a fiberglass media similar to the HEPA filters. As a result, they are
susceptible to the same chemicals, fumes, and heat damage. Some medium efficiency filters are
manufactured with a beverage board (coated cardboard) frame, which should be avoided if fire
is a concern.
Holding devices for medium efficiency filters should be manufactured from the same material
as the glovebox or a material that is resistant to the chemicals and fumes that will be present in
the airstream. Retaining fasteners, when used, should be made of dissimilar materials that do
not gall. It is better to dispose of a 302 stainless steel wing nut than to replace a 304-L stainless
steel stud welded on a glovebox. The frame should be designed to minimize air bypass around
the medium efficiency filter yet allow enough clearance between the HEPA filter and medium
efficiency filter to prevent media contact. An independent holding frame should be
incorporated in the design to prevent disturbing another filter installation.
4.2.14 Inlet HEPA Filters
Work performed in gloveboxes frequently requires supply air that is free of airborne
contaminants. Inlet HEPA filters help maintain clean conditions inside and, when chosen
properly, also serve three other useful functions: (1) extending the service life of the exhaust
filter by protecting them from atmospheric dirt loading, (2) preventing the spread of
contamination from the glovebox to the room in the event of a glovebox pressure reversal, and
(3) providing overpressure relief.
The design of the inlet filter installation is relatively simple for air-ventilated nonrecirculating
gloveboxes. Since no duct connections are required, open-faced filters may be used with an
installation and clamping method that leaves one face completely exposed. Typical methods of
installation are shown in Figure 4.16(a, b). Because they are less likely to be contaminated, inlet
air filters are easier to replace than exhaust filters; therefore, they provide fewer problems and
less risk during changes. Whether mounted to the glovebox internally or externally (external
mounting is preferred), the same high-quality mounting, clamping, and sealing are required.
DOE-HDBK-1169-2022
97
The open face of the filter needs to be protected from physical damage and fire. Plugging of the
inlet filter by smoke is a secondary concern, however, since one recommendation for glovebox
fire suppression is to reduce normal airflow. Locating the inlet connection (or an attached inlet
duct) high in the box tends to reduce the amount of air drawn into the box during a fire
because of the chimney effect. This ventilation flow pattern of top to bottom keeps
contamination away from any breathing zone and closer to the floor. The result is protection of
the workers, use of engineered controls instead of personal protective equipment, and support
for implementation of good ALARA principles.
Section 88
4.2.15 Roughing Filters
In some installations, it is desirable to recover material from the filters for either reprocessing
or waste minimization. Roughing filters may be used for this purpose. The filter medium is
typically less efficient than that of the HEPA filter or the medium efficiency filter. Construction
materials may be suitable for the recovery process (Category 3 - combustion, acid dissolution),
but cannot present a hazard to the downstream medium efficiency filter and HEPA filters. Fire
screens and other measures may be used to prevent roughing filters from affecting
downstream medium efficiency filters or HEPA filters.
Figure 4.16a: Open-Face Filter Installation, Method (a)
DOE-HDBK-1169-2022
98
Figure 4.16b: Open-Face Filter Installation, Method (b)
4.2.16 Filter Replacement
Safe replacement of a contaminated glovebox filter should be planned in the design phase to
facilitate proper execution. The filter change method and other maintenance functions, if not
site-specific, should be determined and planned. The designer should prepare a written
preliminary filter change procedure along with the design documents. If the design is
questionable due to an extreme custom nature, the glovebox should be mocked up so that an
operational demonstration can be performed. In applications where controlled inert
atmospheres are present, filter changes should be planned for times when other routine or
special maintenance operations are taking place inside the box to reduce interruptions to
operations and loss of inert gas, and to minimize the time required to reintroduce the inert gas
into the box spaces.
Replacement of a HEPA filter inside an air-ventilated box involves many steps that should be
performed sequentially. Site-specific Standard Operating Procedures should be written, and the
filter change team should be trained to perform the operations in a safe, controlled manner.
Close coordination between maintenance and operating personnel is necessary to establish a
mutually satisfactory date and time for the filter change, to identify the boxes and systems
involved, to procure the necessary materials, and to schedule personnel. The health and safety
requirements of the industrial hygienist, health physicist, and safety engineer should be
established. One of these specialists should be designated the health and safety supervisor and
should be available to monitor the operation and assist as necessary.
DOE-HDBK-1169-2022
99
When the necessary materials and tools are ready, and all personnel have been instructed in
their specific duties, final permission should be secured from the responsible operator to alter
the airflow and replace the filters. The flow path of the exhaust system should be thoroughly
understood, and persons responsible for related exhaust systems that will be affected should
be forewarned. For instance, if two glovebox exhaust systems manifold to the same blower,
final filters, and stack, the removal of one system from service for a filter change will affect the
system flow and pressure characteristics of the other system. Safety clothing and respiratory
protection should be worn as directed by the health and safety supervisor. The following steps
are suggested for changing a filter and placing a box back in service:
1. Cease all glovebox operations and contain unsafe materials in suitable containers.
2. Cut off gas flow to the glovebox affected and adjust flow through the remaining
Section 89
branches to restore a safe negative pressure and flow rate in each.
3. Bag a clean replacement filter (and medium efficiency filter if used) in a small, clear
plastic bag with sufficient tape to hold the spent filter and medium efficiency filter with
all of the hand tools required, as shown in steps A, B, and C of Figure 4.17. It is
recommended that the hand tools needed for filter changing be introduced the first
time the filters are changed, and then left in the glovebox for subsequent use if space
and environment permit. Decontamination is often more costly than tool replacement.
4. Using the glovebox gloves, remove the dirty filter and medium efficiency filter from
their mounting frame.
5. Insert the dirty filter and medium efficiency filter into an empty plastic bag along with
any residual materials, slowly expel excess air, and seal with tape or use heat sealing as
shown in steps W, X, Y, Z, of Figure 4.17.
6. Inspect the gasket sealing face or fluid seal knife-edge of the mounting frame and clean
if necessary. Place the replacement filter in position and secure the clamping devices.
Place the new medium efficiency filter in position and secure.
7. Remove the dirty filters and all debris from the glovebox and place the removed items in
a container for contaminated waste disposal.
8. Restore airflow through the glovebox and adjust the flow and negative pressure
throughout the system.
9. Before glovebox operations are resumed, test the newly installed HEPA filter with
challenge agent, using the permanent test connections on the housing. If the test result
is not satisfactory, stop the flow and inspect the filter for damage. If no damage is
apparent, reposition the filter, restore the flow, and retest the filter. If the second filter
challenge is unsatisfactory, the filter should be replaced and steps 3 through 9 should be
repeated. Continued leakage suggests a mounting frame failure, filter damage, or a
faulty test, and each possibility should be examined in detail until the fault is discovered
and corrected.
10. Decontaminate the area.
11. After successful filter replacement, notify the responsible operator.
DOE-HDBK-1169-2022
100
Figure 4.17: Filter Changing Process
4.2.17 Protection Against Fire and Explosion
The guidance in this subsection is offered to assist users in meeting the fire protection
requirements of DOE-STD-1066-2016 and DOE O 420.1C.
4.2.17.1 General Guidance
• Use nonflammable materials as much as possible in construction. Gloves and windows
are the most susceptible to fire due to their construction materials. Laminated or
tempered safety glass is the material of choice regarding fire.
• For applications where explosion, overpressure, or moving or rotating machinery are a
concern, impact-resistant, fire-retardant polycarbonate should be used to protect the
worker.
• Some material hazards may also dictate the use of high-impact material due to the
hazards to operating and maintenance personnel from a cracked or broken window.
Some applications resolve this problem by placing a layer of glass inside the glovebox.
• Strictly adhere to acceptable housekeeping practices. Spontaneous combustion of
certain materials can occur in a glovebox as well as in the secondary work area.
DOE-HDBK-1169-2022
101
• Avoid the use of flammable materials within the box wherever possible and limit the
amount of flammable material to the calculated air change when no suitable
nonhazardous substance can be substituted. Use containers for flammable substances
that are approved for the planned operation.
Section 90
• Maintain a current in-box material inventory. Gloveboxes should be used as designed.
They are inappropriate for long-term storage, especially for chemicals.
• For inoperative gloveboxes, establish a safer, glovebox configuration and periodically
check to ensure the gloveboxes are in a safe condition. Precautions include isolating
boxes by closing fire stops, checking through-flow, checking port covers, disconnecting
electrical equipment, and removing corrosives.
• Design the box with downdraft ventilation (high air inlet, low outlet) if possible, to
inhibit combustion while still purging the box. Generation of light flammable gases by
the process may dictate exhausting from the top.
• Provide a protective atmosphere. This measure is listed last because those preceding it
are applicable to all gloveboxes, whereas inerting is used only when there is too much
risk involved in operating without a protective atmosphere. Assessing the degree of risk
involved in an operation is often a subjective evaluation.
4.2.17.2 Detection
A glovebox fire detection system is recommended when there is a high risk of fire determined
by a Fire Hazard Analysis (FHA). If flammable solvents, coolants, and packaging materials need
to be present during operation, especially in unattended boxes, a heat detector should be
installed on the glovebox. Whenever a pyrophoric material (such as plutonium) is used in
gloveboxes, fire detectors are required.
4.2.17.3 Suppression
Since a fire within a glovebox may be of paper, chemical, electrical, or pyrophoric metal origin,
there is no single suppression method that is best for all gloveboxes. However, when designing
a glovebox, the designer should be aware of the materials, material quantities, process, and
interfacing equipment that will be involved in the installation. At this point, the FHA should
determine the proper suppression system for the installation. For further details, see Section
5.1 of this handbook, Section 4.4.2.3 of DOE-STD-1066-2016, and the American Glovebox
Society’s Standard of Practice for Glovebox Fire Protection (AGS-G010-2011).
There is no assurance that filters will remain functional during and following exposure to fire,
smoke, or burning debris. Variable destructive effects on medium efficiency filters and HEPA
filters include the temperature reached during a fire, the quantity and density of the smoke
released, the heat release rate, and the duration of the fire. After exposure to fire, smoke, or
burning debris, all components of the glovebox should be evaluated and tested prior to return
to service.
DOE-HDBK-1169-2022
102
4.2.17.4 Inert Environments
Inerting a glovebox environment is done when working with materials that are pyrophoric,
oxygen-sensitive, or moisture-sensitive, or when a process needs to be protected. Inert gases
such as helium, argon, and nitrogen are metered into a gas-tight glovebox to displace the “air”
volume. The characteristics of the gas (lighter than air, heavier than air) are applied using
proper sampling sensors to obtain a true inerted glovebox. In pyrophoric and high-fire-potential
applications, oxygen sensors are used to verify real-time concentrations. Inline filters should be
installed to protect the oxygen monitor, or any monitor, from contamination. Monitors and
sensors are available for many different types of gases and fumes. These should be selected
when fire, explosion, and any associated risk to the process would result in danger to personnel
and/or the facility. This should be determined by the facility risk and fire assessment groups. In
most of these instances, the facility fire department should be directly connected to any alarms
related to the event.
Section 91
Gas-tight systems require quality construction of all components including gloveboxes, filters,
and associated ducts. Any air ingress associated with the filter mounting or connecting duct will
adversely affect the quality of the inert atmosphere that can be maintained in the glovebox and
thus the cost of inert gas purification. Penetrations used to pass electrical input/output signals
and power into the glovebox should be hermetically sealed for this purpose.
In fire protection applications, the preventive step of inerting is safer, though more expensive,
than extinguishing a fire if it does occur. National Fire Protection Association (NFPA) 801
(Section 7.1.4.5.7) states that fixed inerting systems are not substitutes for fire suppression.
However, the oxygen level has to fall below 1 percent before it fails to support the burning of
some pyrophoric metal. The use of dry air (relative humidity less than 20 percent) reduces the
hazard of pyrophoric metal fires but does not eliminate it. Moisture in the presence of heated
pyrophoric or reactive metals (e.g., finely divided plutonium) increases the possibility of
explosion by generating hydrogen. The suitability and cost of an inert gas for the process are
significant factors when selecting this type of fire control. The gas flow rate in most inert gas
boxes is generally low. The flow should be consistent with required box-atmosphere purity
levels, the scrubber, or the inert gas purification system that supports it. The inert gas may be
purged on a once-through basis or recirculated through a purification unit protected with HEPA
filters. While gloveboxes usually have filters installed for this purpose, the designer should
assess the potential for equipment contamination and cleanup.
4.2.18 Control and Instrumentation
Glovebox instrumentation may range from simple indicators and alarms to sophisticated
control systems. The type of control or instrument used will depend on the characteristics to be
monitored, the relative hazards, and the method and time available to correct an upset
condition. Operational characteristics to be measured and alarmed should include the
differential pressure between box and surroundings, the filter resistance, the gas flow rate
through the box, and the box atmospheric temperature. An alarm should be available for any
activity that could lead to degradation of or loss of confinement; fire; or any other safety
DOE-HDBK-1169-2022
103
concerns. In addition to instruments and sensors on the box, it may be necessary to indicate
and provide for readouts and/or alarms at a central panel for oxygen content, liquid level,
neutron flux, gamma flux, fire, and explosive gas mixture inside the box.
When a monitored characteristic requires annunciation for safety when the level of a
monitored parameter passes some predetermined point, the alarm may be local. For example,
an alarm may alert the operator to an upset condition (e.g., when the glovebox pressure
differential becomes less negative than its design relative to the surroundings) or it may signal
an annunciator panel in an adjoining “cold” area (e.g., by the entry door to the glovebox room,
in a control room, or both). Standard operating procedures and sufficient information on the
current contents of each box should be available to assist evaluation of the hazard area when
an alarm sounds and to aid in planning corrective action.
Section 92
Minimum instrumentation for a glovebox ventilation system should include devices to indicate
the differential pressure between the box and its surroundings, exhaust filter resistance, total
exhaust flow rate, and exhaust air temperature. Figure 4.18 shows the arrangement of
indicating devices in a glovebox ventilation system. The items shown above the double-dashed
line indicate the types of instruments commonly used to supplement the minimum
instrumentation necessary to improve safety for a particular operation or circumstance.
For example, when box operators are not in full-time attendance for a continuous process, a
sensor can be provided to monitor abnormal pressure, temperature, or almost any other
critical process parameter and to actuate a remote alarm where an attendant is stationed.
Figure 4.19 shows an example of a local mounting for a differential pressure gauge (commonly
referred to as a differential pressure gauge) on top of a glovebox. The instrument should be
mounted near eye level, and the indicating face should be located so that the operator has a
clear view while manipulating the gloves.
The gauge display should make operating conditions easily discernible to the operator (e.g., a
differential pressure gauge with a range of 1 in. wg with “0” at the top). Sensing lines should be
short and should be sloped directly back to the glovebox so that moisture will not pocket in the
tube. Tubing should be at least 3/16 inch-diameter to allow the instrument to respond quickly
DOE-HDBK-1169-2022
104
Figure 4.18: Arrangement of Indicating Devices in Glovebox Ventilation System
DOE-HDBK-1169-2022
105
Figure 4.19: Typical Local Mounting for Differential Pressure Gauge
to rapid changes in pressure. Use of a three-way vent valve at the gauge permits easy
calibration (zeroing) without disconnecting the sensing tube. Calibration of glovebox differential
pressure gauges should be done routinely.
Selection of a differential pressure gauge, differential pressure gauge with switch, or transducer
should be determined by the application. One advantage of using a gauge is simplicity. A line is
connected across the upstream and downstream plenums of a filter where the pressure drop
can be measured. Most gauges and transducers install in this manner. A differential pressure
gauge with switch has the addition of an alarm function. A transducer allows multiple readouts
and greater accuracy and can be used to automate the exhaust system. It is costlier, however,
because it needs a power supply, readout, and transducer. The requirement for a gauge should
be based on the actual system pressure. Exhaust filter pressure drops, for example, can vary up
to 3 in. wg. If the inlet filter housing valve is closed, the device will see the full negative capacity
of the blower. The gauge or transducer needs to have a proof pressure greater than the
maximum system pressure (negative or positive) so that it will not be damaged by excessive
pressure.
Devices that measure pressure have a problem with “drift.” This occurs on most devices
because of continual pressure on the device. As a result, they need to be recalibrated on a
routine schedule. Liquid-filled devices (manometers) are not recommended for glovebox
pressure indicators; however, they have been used to check the calibration of an existing
device. Inlet filters on air-ventilated gloveboxes generally do not require differential pressure
gauges. The pressure drop across the inlet filter is approximately the same as the box pressure.
Section 93
A differential pressure gauge should be provided for each exhaust HEPA filter stage to indicate
filter resistance. Pressure-sensing connections can be provided to permit the use of portable
DOE-HDBK-1169-2022
106
instruments. Suitable alarms or controls that can function on small pressure differentials (equal
to 0.25 in. wg) are difficult to keep calibrated and are often expensive. Figure 4.19 shows a
method for indicating pressure drop through a filter.
Instruments used to measure airflow from gloveboxes include an orifice plate, venturi meter,
flow nozzle, and calibrated Pitot tube. The important point is to use a simple, trouble-free
device that gives reliable readings within an accuracy of ±15 percent. When free moisture is
absent, a Pitot tube is the least expensive and most adaptable device for the small volume flow
rates associated with glovebox ventilation. Immediately after installation and while filters are
still clean, the measured pressure drop across the HEPA filter can be used to check airflow to a
high degree of accuracy by proportioning the measured pressure drop to that stamped on the
filter case at the time of predelivery testing. The pressure drop across the filter is no longer a
dependable indication of gas flow rate after the filter has accumulated dust. After a filter has
been in service for a period of time, it is necessary to measure both the pressure drop across
the filter and the airflow through it to evaluate the filter’s status and relationship to the whole
ventilation system.
Written procedures for periodically testing each alarm, control, and emergency system serving
the glovebox and its ventilation system are essential.
4.2.19 Challenge Aerosol Testing of Glovebox Filters
The HEPA filters used in glovebox systems are often inconvenient to test because the challenge
aerosol has to be injected into the inlet duct or glovebox. The challenge aerosol cannot be fed
into the inlet of the box to test the exhaust-side filters if high-efficiency filters are used in the
inlet. Consideration is needed for safety, including contamination control and incompatible
materials. Testing of non-safety filters, such as medium efficiency filters, is not necessary in
contaminated gloveboxes. Methods A and B (Figure 4.20) require the challenge aerosol to be
drawn into the glovebox by the suction of the exhaust system. However, the challenge aerosol
should not be injected into gloveboxes housing apparatus with open or exposed optical lenses
or with highly polished surfaces, delicate balances, crystalline structures, sensitive conductors,
or similar equipment or products. In such cases, the filter should be installed in the duct
downstream of the glovebox so that the injected challenge aerosol will not back up into the
glovebox proper. Method C (Figure 4.21) may then be used for challenge aerosol testing of the
exhaust HEPA filter.
DOE-HDBK-1169-2022
107
Figure 4.20: Methods of Injecting Test Aerosol and Extracting Samples
DOE-HDBK-1169-2022
108
Figure 4.21: Methods of Injecting Test Aerosol and Extracting Samples
New or replacement exhaust filters are tested before restarting the ventilation system, and
Method D (Figure 4.21 above) may be used. Note that in this method the exhaust path from the
glovebox is closed and the challenge aerosol-air mixture for filter testing is drawn from a
separate valved path. The side path is closed and sealed after testing is completed.
Section 94
Methods A and B (Figure 4.20 above) require injection of the challenge aerosol-air mixtures
into the glovebox via some convenient opening. A gloveport can be used if confinement is not
critical during testing. Otherwise, a connection can be prepared (Figure 4.22), or an alternate
method can be devised. Methods C and D (Figure 4.21 above) do not require the introduction
of a challenge aerosol into the glovebox. The challenge aerosol inlet connection should be sized
to pass the challenge aerosol or challenge aerosol-air mixture. The connection for concentrated
challenge aerosol in Method C should admit 2 to 5 cfm, while the connection in Method D
should accommodate the total challenge aerosol-air mixture used for the test.
DOE-HDBK-1169-2022
109
Figure 4.22: Connection for Introducing Test Aerosol into Glovebox
4.2.20 Glovebox Shielding
Some gloveboxes may require gamma, beta, and neutron shielding because of the nuclides
used and the amounts of material involved. Boxes handling kilogram quantities of plutonium
can be shielded by providing lead-impregnated gloves, glovebox shielding (water or any other
similar mass), lead glass over the windows, and lead-hinged plugs or covers over the ports. The
operating, shielding, removal, and replacement requirements of the glovebox HEPA filter
should also be considered when glovebox shielding is required. The thickness of the shielding
affects the design of the filter housing used on this type of glovebox. The designer should
account for this by extending the service fittings (pressure measurement) and any other
glovebox pass-through used in the design. This practice is also mandated for bagging ports used
to remove the primary HEPA filters and the cover doors. Ergonomic operations inside shielded
gloveboxes should be given careful consideration because lead-lined gloves and dimensional
differences make manipulations very difficult.
4.2.21 Criticality Considerations
When criticality is a potential concern for glovebox design, geometry control and water use
restrictions become essential factors. Drains, in particular, need to be designed with great care.
DOE-HDBK-1169-2022
110
The buildup of fissile material on the HEPA filters should also be considered. Metal media and
ceramic filters should be considered by providing more rigid geometries to reduce criticality
concerns. Equipment wells or thermal wells in the floor of a glovebox should have a ridge or
raised boundary to prevent liquid or debris from accumulating in the wells. The size, shape, and
visibility of the interior of the wells should also be evaluated for material accumulation
concerns.
4.2.22 References
1. AGS (American Glovebox Society), 2007, Guidelines for Gloveboxes, AGS-G001 (Third
Edition), Santa Rosa, CA.
2. ASHRAE, 2016, HVAC Systems and Equipment, New York, NY.
3. ASME (American Society of Mechanical Engineers), 2019, Code on Nuclear Air and Gas
Treatment, ASME AG-1, New York, NY.
4. ASME, 2007, Testing of Nuclear Air Cleaning Systems, ASME N510, New York, NY.
5. DOE, 2018, Facility Safety, DOE O 420.1C.
6. DOE, Fire Protection, DOE-STD-1066-2016.
DOE-HDBK-1169-2022
111
4.3 Small Air Cleaning Units
4.3.1 Introduction
Section 95
This section discusses the installation of internal components, primarily HEPA filters, in systems
that require only a single filter per stage of each air cleaning unit. HEPA-Vac systems are not
considered small air cleaning units and should not be utilized as such. Single-filter (nonparallel)
installations are employed in the supply, exhaust, and recirculating air cleanup systems of
rooms, gloveboxes, hot cells, chemical fume hoods, and other contained spaces; in the off-gas
lines of process vessels and radiochemical operations; and in other applications in which the
airflow is 1,500 cfm or less. Although much of the discussion in this section focuses on
installation of HEPA filters, it also applies to adsorber cells and other components.
Single-filter installations can be grouped into three broad categories: (1) in-wall (filter mounted
in or to a wall penetration of a room, glovebox, hot cell, or other contained space); (2) in duct
(filter installed “in line” between two sections of duct, with or without transitions); and (3)
duct-entrance (filter installed at the opening of the duct leading from a room, glovebox, hot
cell, or other contained space). In-wall installations are generally employed to clean the air
entering a contained space, to prevent backflow of contamination in the event the contained
space becomes pressurized, or both. The filter may be installed bare (sides of case exposed) or
in a partial enclosure. As in other installations, a medium efficiency filter is recommended
upstream of the HEPA filter. Duct-entrance filters are strongly recommended to maintain the
cleanliness of contaminated exhaust and air cleanup ducts. These filters should be mounted in
or close to the entrance of the duct and, like the in-wall type installation, may be installed
either bare, as shown in Figure 4.23, or in a partial enclosure.
In-duct open-faced filters should be installed in totally enclosed housings or side-access
housings, as shown in Figure 4.24. Taping or clamping the filter between two sections of duct or
a pair of transitions with the case exposed is not recommended. Such installations provide no
secondary confinement in the event of a breach of the filter case, gaskets, or tape seals, and
(particularly for wood-cased filters) fail to meet the requirements of Underwriters Laboratory
(UL)-181A, Closure Systems for Use with Rigid Air Ducts and Air Connectors and NFPA 90A,
Standard for the Installation of Air Conditioning and Ventilating Systems.
DOE-HDBK-1169-2022
112
Figure 4.23: Mounting of Duct-Entrance Filters
Figure 4.24: Correct Mounting of In-Duct-HEPA Filter Housing
DOE-HDBK-1169-2022
113
4.3.2 Housings
Housings for in-duct installations may be as small as the side-access housing for a 25-cfm HEPA
filter or as large as the complete multistage air cleaning unit containing demister, medium
efficiency filter, two stages of HEPA filters, and adsorber. Probably the most common single-
component housing today is the bag-in/bag outside access type. Features that should be
checked carefully when purchasing standard commercial housings include the filter
(component) mounting frame and clamping device, the rigidity of the box and its cover, the
method of cover sealing and clamping, access to the installed component, the rigidity and
construction of duct connections, and the materials of construction of all parts, including the
component clamping mechanism. These same features are important in the design of one-of-a-
kind shop-built housings. Provisions for in place testing should be provided on all filter
housings.
Section 96
4.3.3 Component Installation
Requirements for installing components are basically the same as those for bank installations.
These include structural rigidity, flatness, and accuracy of the sealing surface construction;
positive, reliable sealing of the component to the frame; specification of and strict adherence to
close tolerances in fabrication; and leak tight welded construction. A minimum sheet-metal
thickness of 0.078 inch (No. 14 U.S. gauge) is recommended for the sealing surface of
commercially made and shop-fabricated housings. For gasket-sealed housings, the sealing
surface should be seal-welded into the housing such that no warping of the filter (component)
sealing surface will result. There should be a right-angle bend all around the seating surface to
provide reinforcement and to ensure flatness. Figure 4.25 shows a portion of the turned-angle
filter sealing surface of a commercial housing, and Figure 4.26 shows a schematic of the four-
bar-linkage gasket seal clamping mechanism that is operated by means of a wrench (shown in
Figure 4.27 from outside the housing. Other clamping systems are acceptable, so long as they
provide the required amount of clamping force on the gaskets.
The housing should be constructed to prevent leakage where the clamping mechanism
penetrates to the outside. The structural requirements of the mounting frame will be met if 14-
gauge steel is used, particularly if combined with the stiffening flange (right-angle bend).
Flat gasket-to-knife-edge seals are not recommended because they tend to leak excessively if
the knife-edge is nicked or if the knife-edge and the filter face are not parallel. The compression
set produced by a knife-edge in only a portion of the gasket also results in leakage if there is
any degree of relaxation of the clamping device. The gel seal design does not require special
tolerances and has been proven to create a very effective filter-to-sealing surface method.
A nonwelded mounting frame consists of a single 0.25-inch plate sealed by gaskets between the
flanges of the body and the transition of a field-assembled housing. The filter is clamped by
bolts and installed through a hatch in the side of the housing. A gasket compression of at least
80 percent is needed to create a reliable seal between high-efficiency devices such as a HEPA
filter or radioiodine adsorption cell and the housing. This requires a gasket loading of something
DOE-HDBK-1169-2022
114
over 20 psi of gasket area for a total loading of over 1,400 pounds for a 24- × 24-inch filter;
1,050 pounds for a 12- × 24-inch filter; or 700 pounds for a 12- × 12-inch filter. Such loadings
can be accomplished with the bolted clamping method. It is important for the designer to verify
that the clamping mechanism of the commercial housing being considered
Figure 4.25: Turned Angle, Gasket Sealing Filter Surface for a Commercial Housing
DOE-HDBK-1169-2022
115
Figure 4.26: Four-Bar-Linkage Gasket Seal Clamping Mechanism
Figure 4.27: Using Wrench to Operate Four-Bar-Linkage Gasket Seal Clamping Mechanism
can develop the loading required and is adjustable. All parts of the mechanism should be
stainless steel to prevent rusting and seizing under operational conditions (including springs,
which tend to break when rusted). The only exception to this rule is that, if nuts are used, they
should be brass, bronze, or another material that will not gall in contact with the stainless-steel
male-threaded part. Clamping mechanisms should be on the clean side of the filter, and
Section 97
DOE-HDBK-1169-2022
116
operator shafts, when required, should be sealed by O-rings or glands. A rest or guides, stops,
or some other means for aligning the filter prior to clamping should be provided within the
housing.
For gel seal housings, the knife-edge sealing surface should be seal-welded into the housing so
that warping of the filter (component) sealing surface will not result. There should be a right
angle all around the knife-edge sealing surface to provide reinforcement and ensure alignment.
Figure 4.28 shows a portion of the knife-edged filter sealing surface of a commercial housing.
The gel seal housing clamping mechanism is operated by hand from the side of the housing. All
parts of the mechanism should be 300 series stainless steel to prevent rusting and seizing under
operational conditions.
The clamping pressure required to properly seal a gasket-sealed HEPA filter or adsorber cell
needs to be both high and uniform. However, this requirement is substantially relaxed when gel
seal systems are used. As shown in Figure 4.29, the filter element has a groove filled with a
non-Newtonian (i.e., nonflowing) gel. The filter is pushed against the knife-edged flange of the
mounting frame so that the gel envelops the knife-edge, forming an airtight seal. The clamping
pressure only needs to be enough to prevent the filter from backing away from the knife-edge
(which would break the seal) under any foreseeable differential pressure across the filter in
either normal operating or system upset conditions. The gel, a silicone compound, has been
tested and found to be capable of maintaining an adequate seal under the fire and hot air
conditions of UL-586, Standard for High Efficiency, Particulate, Air Filter Units, and the radiation
exposure requirement of ASME AG-1, Code on Nuclear Air and Gas Treatment, Section FC.
Either the flat-gasket to flat-flange or the gel seal are recommended.
Figure 4.28: Gel Seal Commercial Housing Filter Sealing Surface
DOE-HDBK-1169-2022
117
Figure 4.29: Gel Seal System
4.3.4 Housing Construction
The walls of the housing should be sufficiently strong to prevent overstressing under an
alternating positive and negative pressure equal to at least 1.5 times the maximum gauge
pressure to which the housing will be subjected under the most severe conditions for which it is
intended. A minimum design pressure of 10 in. wg is generally recommended. In purchasing
commercial housings, the designer should check the details of construction to verify that the
design proposed is fully adequate for the intended application that stresses in the walls or
clamping mechanism will not exceed a value of 0.7 times the yield strength of the material from
which they are made under a housing pressure of 1.5 times the design pressure.
Many failures of commercial housings can be traced to corrosion. The filter housing is a
common point where corrosives tend to condense, collect, and concentrate. When the filter
housing is to be installed in a line that, under either normal or abnormal conditions, may
contain corrosive fumes or vapors, stainless steel construction should be employed. In any
event, all parts of the clamping device (including springs, but not nuts) should be stainless steel.
Whenever housings are painted, the coating should comply with American Society for Testing
and Materials D5144, Standard Guide for Use of Protective Coating Standards in Nuclear Power
Plants.
Section 98
Hand knobs of the type shown in Figure 4.30 should attach to the housing access door.
Attachment of covers with machine bolts or nuts may be cheaper but will be a constant
problem to the user. Nuts get lost and threaded bolts get damaged under service conditions.
The result is often an inability to seal the housing properly, and the need to remove and replace
a large number of nuts or bolts inhibits access and proper service. For access door clamping, the
door should have a 2-inch-deep lip or flange all around for stiffening (Figure 4.25 above). The
cover should also be stiff enough or sufficiently reinforced so that it will not collapse under the
DOE-HDBK-1169-2022
118
pressure variations to which it may be subjected. The cover and the cover-clamping mechanism
should be capable of sealing the cover opening whether or not a bag is in place.
4.3.5 Bagging
Most commercially manufactured and some one-of-a-kind shop-built housings are designed for
bag-in bag-out filter replacement. Figure 4.31 describes this procedure step-by-step. Shutoff
dampers are needed upstream and downstream of the filter (or other component being
replaced) to permit isolation of the housing during the change and to limit ballooning or
collapsing in of the bag when the access door is opened due to a pressure differential between
the inside and outside of the bag. A small, valve, breather vent can be specified on the clean
side of the filter to control pressure in the housing; a slight negative pressure (0.25- to 0.5-
in.wg) helps ensure inward leakage in case the housing becomes pressurized due to pumping of
the bag. When sealing change-out bags, two seals about 0.25-inch apart are usually made so
that, when the bag is cut between them, both the housing opening and the enclosed filter are
sealed from the room environment. The end user’s safety officer will determine the method of
sealing the change-out bag that best suits the facility.
Bags should be clear plastic, typically polyvinyl chloride (PVC), to permit the worker to see what
he is doing. In some housing designs, the worker has to manipulate the filter clamping
mechanism through the bag as shown in Figure 4.32. Radiation levels may limit the use of PVC.
Bags should be a minimum of 0.008-inch thick. Thinner bags could tear, particularly when used
with metal-cased filters or adsorbers. Care should be taken when carrying out the procedure
with larger (24- by 24- by 11.5-inch) items. Housings should be installed in a location that can
be isolated as a contamination or radiation zone in the event of a bag tear and resulting spill.
The excess bag material that remains after a new filter is placed into the housing is folded
carefully against the side of the filter element (shown in Figure 4.32 below) to prevent
DOE-HDBK-1169-2022
119
Figure 4.30: Access Door Hand Knobs
Figure 4.31: Bag-In Bag-Out Filter Replacement
DOE-HDBK-1169-2022
120
Figure 4.32: Use of Clear Bags
any portion from getting into the airstream or being pinched between the housing cover and
bagging ring.
After folding the bag within the filter housing, it should be isolated from system airflow on the
clean side of the filter because the plastic can be damaged from continued exposure to the
airstream. The covers of bag-out housings should be capable of sealing the housing with and
without the bag installed and should be kept closed when the system is in operation to protect
the bag that remains in the housing. Bagging should not be considered an automatic solution to
the contamination hazard, and the user is cautioned to take proper precautions during filter
changes.
Section 99
4.3.6 Housing Installation
Horizontal airflow with filter faces in a vertical position is recommended for large (24- by 24-
inch face dimensions) HEPA filters. This recommendation is not so important for smaller filters
designed with media support that is inherently sufficient to resist gravitational pull-on filter
core and collected dust. When vertical airflow (filter face in a horizontal position) is
unavoidable, up flow design is recommended over downflow design because filter media
sagging is offset to some extent by air pressure and because there is less chance of cross-
contamination from the dirty side to the clean side of the system. With the downflow design,
contaminated dust dislodged during a filter change can fall into the clean side of the system.
A downflow design should be avoided where there is a potential for liquid to collect in the
system. Liquid collected in the filter pleats of a downflow system will eventually seep through
the media and carry dissolved contaminants into the clean side of the system. On the other
hand, up flow systems may require withdrawal of contaminated filters into the clean zone.
When horizontal installations should be used, filters should be designed to seal on the upper
side of the mounting frame so that their weight will load rather than unload on the gasket or
DOE-HDBK-1169-2022
121
gel-sealing surface. Installation of the filter on the clean side (i.e., downstream) of the mounting
frame is always recommended for single-filter installations.
For multistage installation, components may be grouped as one assembly (Figure 4.33).
Although bolted, gasketed joints are recommended, flexible connections (see Figures 4.34 and
4.35) are suitable for housings connected directly to a fan. Duct-taped seals between housings
and ductwork are not acceptable. Multistage installations can create problems related to
periodic surveillance testing of HEPA filters and adsorber cells. Even though a flange-to-flange
installation (Figure 4.36) is undoubtedly the least expensive option when considering materials
and space occupancy, sufficient room should exist between components to introduce a well-
mixed test agent, to obtain a satisfactory upstream sample, or to probe for leaks on the
downstream faces of the components.
4.3.7 Cylindrical Filter Elements
Cylindrical filters may be either axial or radial flow. The cylindrical axial flow HEPA filter
configuration frequently offers an ideal solution to certain installation requirements. The core is
slipped into a molded or welded-seam cylinder (Figure 4.37) and sealed by catalyst-activated
plastic foam or urethane. Cylindrical flow HEPA filters can be obtained with or without flanges
on one or both ends. Radial flow filters as shown in Figure 4.38 are used in push-through (i.e.,
incessant) installations. The filters are sealed into a cylindrical opening with one or more half-
round circumferential gaskets (fixed to the filter) that make a slight interference fit with the
receiver. Flanged axial flow HEPA filters (Figure 4.39) can be installed in pipe openings by
bolting them to a flange on the pipe or by clamping the filter flange between mating pipe
flanges. Conventional neoprene sponge gaskets are used for sealing. Because filter flanges and
cases are characteristically made from light-gauge sheet metal with the flange seal-welded to
the cylinder, these filters often leak at the flange-to-case weld. The flange often becomes
deformed. Either condition results in an installation that is difficult to seal.
Section 100
There are two methods of installing cylindrical filters, one a duct-entrance design and the other
a hot-cell exhaust design. In the hot-cell exhaust design, the mounting is sloped to permit
runoff of any liquid accidentally spilled on the shield that protects the filter and to facilitate
handling by the cell electromechanical manipulators. Where cylindrical HEPA filters are used,
liberal clearance (at least 1/8-inch all around) between the case and receiver is necessary to
accommodate the characteristic out-of-roundness (see Figure 4.40). The advantage of
cylindrical filters is close conformance to round ducts and pipes, which can both permit the use
of smaller, cheaper duct transitions and require less space. For inline installations, however,
except where the filter has flanges on both faces and is installed as a spool piece, provision
should be made to extract the filter from the duct or pipe after the connection is broken, thus
risking loss of the space advantage over an equivalent open-faced rectangular filter. Spool-piece
filters should have flanges and withstand the forces imposed by the duct or piping system and
the flange bolting.
DOE-HDBK-1169-2022
122
Cylindrical filters are often used in radioactive vacuum cleaners and portable air purifiers. The
air purifier shown in Figure 4.41 is a single-use device that is discarded when the contamination
level or pressure drop of the collectors becomes greater than the pre-established design level.
Figure 4.33: Four Individual Housing Units Grouped as One Assembly
Figure 4.34: Flexible Connection
DOE-HDBK-1169-2022
123
Figure 4.35: Flexible Connection
Figure 4.36: In-Place Filter Test Section
DOE-HDBK-1169-2022
124
Figure 4.37: Open-Faced Axial Flow Cylindrical HEPA Filter
Figure 4.38: Radial Flow HEPA Filter
DOE-HDBK-1169-2022
125
Figure 4.39: Open-Faced Axial Flow Cycloidal HEPA Filter with Flange
Figure 4.40: Clearance Between Radial Flow Filter and Housing
DOE-HDBK-1169-2022
126
Figure 4.41: Cylindrical Filter Air Purifier
4.3.8 Installation and Human Factors
When practicable, single-filter installations should be located where they can be reached for
service and testing without workers having to climb ladders or scaffolding. This requires
consideration of human engineering factors. Analysis of the recommended weight limits
indicates that handling a 1,000-cfm HEPA filter in the body positions often encountered in filter-
change operations is at the upper range of personnel capability, and that handling of adsorber
cells is well beyond the limits for one person.
Consideration should be given to the positions that a worker should assume to perform the
required task. If the worker should hold his hands overhead for any length of time, fatigue may
result. If crouching, bending, or squatting is required, the worker will soon become stiff, which
will contribute to loss of efficiency. If a worker has to hold a heavy weight while performing a
precision operation, such as supporting the weight of a filter or adsorber cell while trying to fit
it between duct transitions or into a restricted opening, the stress of the combined task will
become fatiguing and a mistake could occur. All of these factors are compounded when the
worker should wear protective clothing and respiratory protection. In addition, protective
clothing adds to the worker’s spatial requirements and limits mobility. For HEPA filter and
adsorber cell installations, location of the filter or housing at an elevation between knee and
shoulder height is recommended.
Section 101
DOE-HDBK-1169-2022
127
4.3.9 Fume Hoods
The wide, often unpredictable variety of chemical operations conducted in laboratory fume
hoods makes selection and installation of HEPA filters difficult and uncertain. Corrosive fumes
may damage the filter and its mounting, and moisture and heat from hood operations may
accelerate that damage.
Some facilities install fume hood filters in the attic, usually directly above the hood served.
Where this design is employed, the attic space should be designed as a confinement zone for
easy cleanup in the event of a spill and should not be used for extraneous purposes such as
storage and experimental work when radioactive materials are handled in the hood.
Hood installations in which perchloric acid and certain other chemicals are handled should be
provided with washdown facilities to permit periodic decontamination of the hood and
ductwork (perchloric acid hoods should not be used for handling other materials because of the
explosion hazard. Off gas scrubbers are often provided in hoods. Both washdown facilities and
scrubbers generate substantial quantities of water droplets. Demisters should be considered to
protect the filters and their mountings. Moisture collected in the demister should be conducted
to a hood drain rather than permitted to fall into the workspace of the hood. Demisters should
have adequate handling space and be easily accessible for cleaning, inspection, and
replacement. Where incandescent particles or flaming trash can be released to the hood
exhaust stream, a spark arrester should be installed to protect the HEPA filter. This arrester can
be either a commercial flame arrester, a metal-mesh graded-density demister, or at minimum,
a piece of 40-mesh metal cloth. In any event, it is recommended that the arrester be located at
least one foot ahead of the HEPA filter and should have easily accessible for cleaning,
inspection, and replacement.
Heat sources such as heating mantles, furnaces, and Bunsen burners are common equipment in
laboratory fume hoods and should be planned for in the initial hood and exhaust system design.
Designers should control heat-producing operations by limiting the size of heat sources such as
furnaces or using air cooling methods.
4.3.10 Portable Air Cleaning Units
The use of portable HEPA filtration systems has become quite prevalent within the nuclear
industry. Radiation protection standards stress the use of engineered controls, principal
localized ventilation, and confinement as the primary means of controlling occupational
exposure to airborne contaminants. Decontamination and decommissioning activities utilize
supplemental ventilation to control the large amounts of dust generated by demolition
activities, especially as existing facility ventilation systems are decommissioned. Portable air
filtration systems pose their own unique challenges to both the designer and the end user. As
with commercial side-access housing, well-designed portable filtration systems (shown in
Figure 4.42) are much more than “black boxes.” Careful evaluation of system requirements,
selection and integration of components, and attention to construction methods are all
required to ensure a functional, effective, user-friendly system. This process has been made
DOE-HDBK-1169-2022
128
somewhat more difficult, however, due to a lack of industry standards that specifically address
portable HEPA filtration units.
Section 102
Procurement specifications for portable HEPA filtration systems should be developed by using
ASME AG-1. These standards address the in-place safety systems for nuclear facility ventilation.
While many aspects of these standards are applicable to portable systems, wholesale
application without consideration of the unique features and functionality of portable systems
may result in unrealistic specifications that are difficult, costly, or impossible to meet.
Compromises need to be made, but without sacrificing the overall functionality and safety of
the equipment.
Figure 4.42: Portable Filter Unit
4.3.10.1 Operational Considerations
Certain operational considerations should be addressed when selecting or specifying portable
HEPA ventilation units for use in environments where nuclear or another hazardous
contaminant is present. Like any other ventilation system, a portable HEPA filtration system
should be designed to move and effectively clean the appropriate amount of air, required to
maintain adequate environmental conditions within the workspace. Unlike permanently
installed facility systems, however, the ultimate applications of portable systems are rarely
known. They may be used for ventilating confined spaces, providing general area air
exchanging, or providing high, localized, capture velocity in support of cutting, burning,
grinding, or other mechanical and maintenance processes. Unless the system is intended for
“one time, one application” use, it should be designed and constructed with sufficient flexibility
to perform well under a variety of operating conditions. Thought should be given to the
anticipated use of the equipment, and some basic operational questions should be asked to
better define the required features. Examples include:
• Is particulate the only contaminate of concern, or will gas adsorption also be required?
• Is the expected operating environment or contaminant corrosive, or does it contain
other contaminants that might affect the construction materials?
• Will the unit be used indoors or outdoors?
DOE-HDBK-1169-2022
129
• What will be the ambient and process air temperature extremes?
• Will the unit be used in areas where there is high relative humidity or entrained water?
• Will the unit be used in areas where potentially explosive concentrations of gases or
dust will be present, requiring special hazard class electrical components?
• Does the process or contaminant warrant redundant (series) HEPA filtration for added
protection?
• Will the unit be subjected to high system losses due to using long lengths of temporary,
flexible ducting and/or multiple filtration stages?
• Is heavy dirt loading expected that might require larger, more robust prefiltration
capacity?
• Does the relative hazard of the contaminant require the added protection of bag-in/bag-
out filter changing?
• What power is available to run the equipment? (Low voltage and amperage as well as
single-phase power supplies can severely limit the capacity of the ventilation system.)
• How much space is available to stage the equipment? Is a single larger unit supporting
multiple exhaust points more workable, or are smaller units placed local to the work
more appropriate?
• What is the duration of the project or operation that will be supported by the portable
system? Is the unit intended for reuse many times over years, or is it a one-time
application? (Durability and ruggedness of construction can be greatly affected.)
Section 103
• What sampling is expected from the unit?
4.3.10.2 Component Considerations
Fan Assemblies
Portable systems typically use centrifugal fans. Cast aluminum housing and wheels are
common, as well as fabricated steel. Fiberglass, PVC, and other nonmetallic fans are available
for processing air with corrosive contaminants. Regardless of the type of fan used, it’s
performance should be matched with the intended application. A fan with high static
capabilities at the required flow rate is needed for a portable system that will be expected to
operate with high system losses (e.g., large amounts of flexible ducting on the inlet or
discharge; periods of high filter loading). Likewise, if the unit is only intended to provide local
recirculation without high system losses, a fan with lower static pressure capabilities is
acceptable. Fan performance should be developed using Standard 5110 published by the Air
Movement and Control Association (AMCA) and ASHRAE.
Fans are typically direct-drive systems. Motors with appropriate hazard class ratings should be
specified to protect them from internal contamination. If frequent washdown with high-
pressure water is expected, appropriate duty motors should be specified. Likewise, motors with
appropriate hazard class ratings should be used in hazardous locations in accordance with
NFPA-70, the National Electrical Code.
Motor starters should be mounted on the unit. National Electrical Manufacturers Association
(NEMA) enclosures should be selected for the intended service, and NEMA enclosures and
DOE-HDBK-1169-2022
130
liquid-tight conduit should be specified for units intended for outdoor application or where
direct water wash of the unit is expected. Reference NEMA Publication 250, Enclosures for
Electrical Equipment (1000 Volts Maximum), for electrical enclosure testing requirements.
Alternate enclosure testing standards such as International Electrotechnical Commission (IEC)
Publication 60529, Degrees of Protection Provided by Enclosures, are equally acceptable. The
important point is that the electrical enclosures and wiring should be suitable for the intended
operating environment, including any special NEC19 hazard class requirements. Overload
protection is suggested for all electrical starters. Special attention should be paid to using
three-phase motors and starters. Due to differences in wiring methods between the power
supply and the portable systems, starter fan rotation can be easily reversed with three-phase
motors.
Fan and motor assemblies should not be rigidly mounted to the system’s cart or the filter
housing/transitions. Vibration isolation should be used for the motor, and a flexible boot or
other vibration-isolating connection should be placed between the filter bank and the fan.
Vibration isolation will reduce noise significantly. The fan always should be mounted on the
downstream side of the filters to ensure the filters and ductwork are at negative pressure with
respect to the environment. All motor fan assemblies should have appropriate safety guards,
including the fan inlet and outlet (if normally accessible), the shaft, the pulley, and the belts (if
used).
Filters and Filter Housings
Any single, standard-sized, HEPA filter can be readily incorporated into a portable filtration
system rated 1,500 cfm or less. Gasketed and gel seal filters can both be used in portable
systems, provided the clamping/holding mechanism stays engaged as the unit is moved.
Section 104
The fan curve will indicate the system’s maximum potential flow rate. The free airflow, or the
flow at zero in. wg static pressure, is the maximum flow that most fans can develop. Since the
fan is connected to a filter bank, some system losses are present, so the free air rate is not a
good indication of maximum flow. The flow rate at the expected operating pressure is a better
indication of the maximum flow that the fan/filter system can be expected to deliver.
A housing with bag-in/bag-out features provides added protection from high-risk contaminants
or for units used outside. Figure 4.43 depicts several portable system arrangements. Whichever
method is used, the filter frame and clamping method should meet the recommendations in
this handbook. Since portable systems are designed to be moved, the chosen clamping or
housing method should adequately protect the filters and prevent unclamping or dislodging of
the filter due to cart movement. The system’s cart should be sufficiently rigid in construction to
limit the amount of flexing seen in and by the filter frame and housing. When the filter is
exposed, only metal-cased HEPA filters should be used.
19 National Electrical Code
DOE-HDBK-1169-2022
131
Prefiltration should be integral to the portable system. Prefilters should be accessible
independent of the HEPA filter and should not require unclamping of the HEPA filter during
change-out. Additional inline prefiltration may be needed for heavy dirt loading applications
such as concrete-cutting and abrasive blasting. A spark arrester should be added to the medium
efficiency filter for plasma arc cutting or any other type of spark producing activity. Moisture
separation also may be required. This can be addressed using either demisting pads that are
integral to the portable system or supplemental dehumidifiers in line.
Adsorber beds can be configured on portable carts as well. The carbon cells can be adapted as
part of the portable filter system or as a separate stand-alone assembly that is interconnected
with the filter unit on an as-needed basis.
Figure 4.43: Portable Systems
4.3.10.3 Construction
Portable equipment used in an industrial setting is subject to abuse. As such, construction of a
portable filtration system needs to be rugged and suitable to a harsh industrial environment.
Transitions and housing pressure boundaries should be fully welded. Properly designed
gasketed and bolted connections, especially on transition to and from the filter, are necessary
to avoid loosening over time. Assembly should allow access for decontamination purposes.
Construction materials should be compatible with the operating environment. Stainless steel is
highly recommended, especially for those components that come directly in contact with the
contaminated airstream.
DOE-HDBK-1169-2022
132
Quality wheels and casters should be used on wheeled equipment. At least one set should have
a brake or some other means of securing the cart in place. Wheels should be compatible with
the surface where the equipment will be used. Hard wheels are suitable for indoor use and are
more readily decontaminated, while large pneumatic wheels may be more appropriate for
outdoor applications. Wheel design should allow replacement if the wheel becomes
contaminated or damaged. On larger units, channels for fork truck lifting or lifting eyes will
facilitate handling. Lifting points should be conspicuously marked. A stout push handle is a
desirable feature. Tow bars can be used for larger skids, allowing the cart to be pulled like a
trailer.
Section 105
Flow control dampers should be incorporated into the unit, especially on systems with multiple
connection points. Dampers located in the ductwork close to the work area may be
advantageous if frequent flow adjustments are necessary. Dampers should include a positive
lock to ensure that the damper will not move once the desired flow balance is achieved. Blast
gates, quadrant control, and butterfly styles are all suitable for flow control dampers on
portable systems. If possible, dampers should be installed so that in the event of a failure, they
fail in place or open, thus preventing a sudden loss of flow in the event of damper failure.
Tapered transitions add considerable length to a portable system, so abrupt transitions are
frequently used on portable systems where size is a concern. If abrupt transitions (i.e., no
taper) are used, a plenum space of at least 4 inches should be left in front of and behind the
HEPA filter. This space will allow for airflow expansion, thereby reducing air velocity prior to
entering the filter.
Duct connection points should be undersized to allow connection of flexible ducting. Allow 1/8
inch less than the nominal size of the flex ducting used. A roll bead, round bar, or other
protrusion fabricated into the duct connection point will help secure the duct when a hose
clamp is installed behind it.
Differential pressure (DP) gauges should be installed to monitor dirt loading on the HEPA and
medium efficiency filter. Individual gauges for both stages of filtration are desirable. Since the
flow rate through a portable system can change significantly depending on ductwork routing
and damper adjustments, observed changes on the DP gauge may not be due to dirt only but
may instead reflect a change in the air velocity through the filter element. For this reason, it is
necessary to ensure that, when assessing dirt loading on the filters over time, DP readings are
taken under the same flow conditions. Alarms that indicate high filter DP, as well of loss of
airflow (which can be indicated by a very low filter DP), are also good features. The same
general caution about the effect of air velocity on filter DP would apply to these alarms as well.
4.3.10.4 Testing and Inspection
Portable air cleaning units require a periodic inspection and in-place leak testing. The rough
handling and shock they can be expected to experience during transport makes careful
inspections and functional tests, including in-place leak testing, mandatory prior to each use at
installation. Also, anytime these units are moved or jarred after they are put into service,
careful inspections and functional tests including in-place leak testing should again be
DOE-HDBK-1169-2022
133
performed. Temporary, portable ductwork is fragile and may be subject to degradation,
especially if exposed to sunlight, chemical vapors, or heat. It should be inspected and checked
for leakage frequently, depending on the application, a daily or weekly schedule may be
appropriate.
4.3.10.5 Vacuum Cleaning Systems
HEPA-Vacs are most commonly used to control friable particulate before it becomes airborne.
They are also used to control airborne particles and liquids in and around work areas and to
locally control loose debris when work operations could potentially spread contamination.
When used in the nuclear industry, HEPA-Vacs are commonly referred to as nuclear or
radiological vacuum cleaners.
Additional information on radiological vacuum cleaners is contained in Section 4.1.14 of this
Handbook.
Section 106
4.3.11 References
1. ANSI/AMCA Standard 210-16/ASHRAE 51-16, Laboratory Methods of Testing Fans for
Certified Aerodynamic Performance Rating, Atlanta, GA.
2. ASME, 2018, Quality Assurance Program Requirements for Nuclear Facilities, ASME NQA-1
New York, NY.
3. ASME, 2019, Code on Nuclear Air and Gas Treatment, ASME AG-1, New York, NY.
4. ASTM, 2018, Standard Guide for Use of Protective Coating Standards in Nuclear Power
Plants, Standard D5144, West Conshohocken, PA.
5. DOE, 2007, Quality Assurance Inspection and Testing of HEPA Filters, DOE-STD-3025.
6. DOE, 2015, Specification for HEPA Filters used by DOE Contractors, DOE-STD-3020.
7. IEC (International Electrotechnical Commission), 2013, Degrees of Protection Provided by
Enclosures, IEC 60529 ED2.2 B:2013, Geneva, Switzerland.
8. IEST (Institute of Environmental Sciences & Technology), 2016, HEPA and ULPA Filters, IEST-
RP-CC001, Mt. Prospect, IL.
9. NEMA (National Electrical Manufacturers Association), 2014, Enclosures for Electrical
Equipment (1000 volts Maximum), Publication 250-2014, Rosslyn, VA.
10. NFPA, 2018, Standard for the Installation of Air Conditioning and Ventilating Systems, NFPA
90A, Boston, MA.
11. NFPA, 2020, National Electrical Code, NFPA-70, Boston, MA.
12. UL, 2013, Standard for Closure Systems for Use with Flexible Air Ducts and Air Connectors,
UL-181B, Northbrook, IL.
DOE-HDBK-1169-2022
134
13. UL, 2013, Standard for Closure Systems for Use with Rigid Air Ducts and Air Connectors, UL-
181A, Northbrook, IL.
14. UL, 2017, Standard for High Efficiency, Particulate, Air Filter Units, UL-586, Northbrook, IL.
DOE-HDBK-1169-2022
135
4.4 Housing Design and System Layout
4.4.1 Introduction
The two basic housing designs are man-entry and side-access (Figures 4.47 and 4.48). Two side-
access housing types are square filters and the other radial flow/round filters (Figure 4.49).
Both side-access designs are for housings with two or more filters and for system capacities
greater than 2,000 cfm.
4.4.2 Housing System Design
Large-volume air supply and exhaust requirements may be met by side-access or man-entry
filter housing installations operating in parallel, or in a single central system. Parallel housings
have the advantages of: (1) greater flexibility for system modification; (2) minimum
interference with operations during filter replacement because individual units can be shut
down without affecting the remaining systems; (3) good overall ventilation control in the event
of malfunction, fire, or accident to one or a few individual units; and (4) easy system testing and
balancing.
Figure 4.47: Model of Man-Entry Plenum
DOE-HDBK-1169-2022
136
Figure 4.48: Side-Access Design (Square)
Figure 4.49: Side-Access Design (Cylindrical)
4.4.2.1 Man-entry Housing System Design
The man-entry filter housing consists of a fabricated steel confinement room with one or more
walls seal-welded in place. The walls have holes and hardware to mount HEPA filters or
absorbers. The room has access doors providing entry. Air is ducted into one end of the room,
passed through the filters/absorbers mounted on the wall, and exhausted from the other end
of the room. A wall with filters/absorbers mounted on it is considered a “stage” or “bank.” The
man-entry design is best used for housings with stages of 15 filters (5 across, 3 high) or more.
DOE-HDBK-1169-2022
137
Section 107
As the number of filters/absorbers increases, consideration should be given to the ability to test
the filters/absorbers and to the distribution of airflow. Isolation valves, recommended on each
housing, result in convenient system control, isolation of individual units during an emergency,
and maintenance or testing activities.
4.4.2.2 Arrangement and Location
Maintainability is a major consideration when laying out filter housings. Although some systems
may have only a single bank of HEPA filters, most will have at least one additional bank of
medium efficiency filters, and many will have multiple banks of HEPA filters. Those systems in
which contaminated gaseous and aerosol releases should be controlled will also require one or
more banks of adsorbers. Often a bank of moisture separators is required, resulting in as many
as six or more banks of components in a single housing. There should be sufficient clear
corridor space adjacent to the housing for handling filters during filter changes, as well as an
adequate number of corridors to and from the housing. Dollies are often used to transport
filters to and from the housing area. This practice results in safer operations that reduce the risk
of both injury to personnel and spread of contamination from dropped filters. When dollies are
used, space is required to move the dollies in and out, and for loading and unloading. Additional
space is desirable for stacking new filters adjacent to the work area during the filter change-out
process. Recommended clearances for housings and adjacent aisles or airlocks are given in
Figure 4.50.
Proper access to the filter housing is sometimes overlooked. Too frequently, housings are
situated among machinery, equipment, and ductwork where workmen are required to climb
between, over, or under obstructions to get to the housing door, where they still have
inadequate workspace. In some installations, it is necessary to carry filters one at a time over
ductwork and then rely on rope slings to transfer them up to the floor above where the air
cleaning system is located. It is essential to preplan the route for getting filters and adsorbers to
and from the housing, and to provide elevators or cranes when hoisting to an upper level in
required. Gallery stairways are also recommended in lieu of ladders.
DOE-HDBK-1169-2022
138
Figure 4.50: Recommended Clearances
High-risk operations often require segmented systems with two or more housings ducted in
parallel that exhaust from the same area and vent to the same stack. Housings with inlet and
outlet isolation dampers permit one housing to be held in standby or, when both are normally
operated simultaneously, to allow one housing to be shut down for maintenance, testing, and
emergencies.
Another important consideration in housing layout is uniformity of airflow through the installed
components. This is especially important for adsorbers, since flow through those components
should achieve the gas residence time required for efficient adsorption of gaseous
contaminants. For large, multiple-filter housings that should operate in parallel, equalizing
screens may be required in each filter unit to ensure uniform flow in housings. Long transitions
are difficult, particularly in large housings. Nevertheless, every effort should be made to locate
and design inlets and outlets to avoid stratification and to enhance the uniformity of airflow
through components.
Section 108
Special care should be taken in designing side-access housings to ensure uniform flow through
all filter elements. It is recommended that manufacturers performance-test prototype side-
access filter units in accordance with ASME AG-1, Section TA, to document uniformity of flow
through side-access filter units before fabrication of production units. When high-activity alpha-
emitters such as plutonium or transuranic elements are handled, it may also be desirable to
compartmentalize the system, both in series, with separate housings for medium efficiency
filters and HEPA filters, and in parallel for extra safety.
DOE-HDBK-1169-2022
139
4.4.3 Component Installation
4.4.3.1 General
Proper installation of HEPA filters, adsorber cells, and demisters is critical to the reliable
operation of a high-efficiency air cleaning system. HEPA filter and adsorber frames should be
designed in accordance with the requirements of ASME AG-1, Section FG. Considerations
include:
• Structural rigidity of mounting frames;
• Rigid and positive clamping of components to the mounting frame;
• Careful specification of and strict adherence to close tolerances on alignment, flatness,
and the surface condition of component seating surfaces;
• Welded-frame construction and the welded seal between the mounting frame and
housing;
• Ability to inspect the interface between components and the mounting frame during
installation (man-entry);
• Adequate spacing between components in the bank (man-entry); and
• Adequate spacing in the housing for men to work (man-entry).
4.4.3.2 Housing Construction
The components and mounting frame should form a continuous barrier between the
contaminated and clean zones of the system. Any hole, crack, or defect in the mounting frame
or in the seal between components and the frame that permits bypassing will result in leakage
of contaminated air into the clean zone and reduced system effectiveness. A mounting frame
that is not sufficiently rigid can flex so much during operation, particularly under abnormal
conditions, that leaks may develop in the HEPA filters clamped to the frame (due to differential
flexing of the filter case relative to the mounting frame). Cracks may also open between the
filters and the frame, between frame members (due to weld cracking or fatigue), or between
the frame and the housing. Insufficient attention to maintenance provisions in the original
design can increase operating costs and reduce reliability of the system.
Once the system is installed, defects are difficult to locate, costly to repair, and may even
require rebuilding the system. Mounting frames for HEPA filters and other critical components
should be all-welded structures of carbon or stainless-steel structural shapes. Carbon steel
frames should be painted or coated for corrosion resistance. Galvanized steel is not
recommended because of welding difficulties and because the zinc coating does not give
adequate protection in the environments that may be encountered in a contaminated exhaust
system. Aluminum is not recommended because of the high cost of surface preparation.
Stainless steel is often the best and most economic choice for radiochemical plant applications.
DOE-HDBK-1169-2022
140
ASME AG-1 Section HA contains information on suitable housing and mounting frame materials
and on fabrication.
4.4.3.3 Potential Housing Leakage
Section 109
The design of nuclear air cleaning system housings should consider the potential for leakage to
prevent contamination of adjacent service and operating areas. By locating the filter unit in an
appropriate plant location and locating the fan relative to the filter housing, leakage amounts
(especially leakage of contaminated air) can be minimized.
A once-through contaminated exhaust filter housing may be designed with the exhaust fan
located after the filter housing and the housing located in a space that is “cleaner” than the air
entering the housing. The benefit of this system configuration is that the air cleaning system up
to the fan is under a negative pressure. Leakage is into the housing, thereby minimizing the
potential impact of contaminated leakage on plant personnel during system operation. This
system configuration does not mean leakage should not be considered. It means that the
leakage potential can be reduced by component location and that further reductions in
personnel dose to levels ALARA are possible via housing construction.
If the space where an air cleaning system housing is located is more contaminated than the air
entering the housing, it would be better to locate the fan on the inlet side of the housing. This
arrangement would eliminate in-leakage of more contaminated air downstream of the filters.
For a habitability system where the housing is located within a protected space, the fan should
be located downstream of the filter unit to ensure any potential in-leakage is “cleaner” air. If
the housing in a habitability system is located in an area outside the protected space, then the
fan should be located upstream of the filter unit to ensure potentially contaminated air does
not bypass the filter unit.
The first step in determining housing leak-tightness is to assess the relative contamination
potential between the air entering the housing and the space where the housing is situated.
Locate the fan accordingly, then determine the allowable leak rate to maintain: (1) the
personnel dose within the requirements of 10 CFR Part 835 for in-plant personnel, (2) the
offsite dose per the Documented Safety Analysis, and (3) the ability of the system to maintain
performance [e.g., direction of airflow, required pressure differential, air exchange (dilution)
rates]. The latter item depends on the system design and margin. ASME AG-1, Section HA,
“Housings,” provides guidance on determining allowable leakage. The allowable leakage should
be considered when determining construction requirements. However, for filter housings, the
structural design requirements for pressure and dynamic forces dictate that the housing
fabricated of heavy platework (10-gauge to 3/16-inch-thick) can be seal-welded to join the
transverse and longitudinal joints, instead of using bolts, without significantly increasing cost.
This will result in a low-leakage installation.
4.4.3.4 Paints and Protective Coatings
Coatings and paint requirements should be consistent with the corrosion expected in a
particular application. Corrosion and radiation-resistant paints and coatings should, at a
DOE-HDBK-1169-2022
141
minimum, meet the requirements of ASTM D5144, Standard Guide for Use of Protective
Coatings in Nuclear Power Plants.
Section 110
Carbon steel housing interiors and mounting frames should be painted to protect against
corrosion and to facilitate cleaning and decontamination. Surfaces should be properly
prepared, and primer and topcoats should be applied in strict accordance with the coating
manufacturer’s instructions in order to obtain the necessary wet-film and dry-film thicknesses.
Film thicknesses should be tested during and after application. Surfaces to be coated should be
abrasive blasted to a profile of 1 to 2 mils in accordance with the Society of Protective Coating
(SPC) SSPC-SP-5/NACE No. 1, Near White Metal Blast Cleaning. The prime coat should be
applied within 2 to 3 hours, but in no case more than 8 hours, after surface preparation.
For exterior carbon steel surfaces, either hand or power tool cleaning (SSPC-SP-2 or SSPC-SP-3)
is usually sufficient. For certain conditions, such as humid atmospheres, exterior carbon steel
surfaces should be prepared in accordance with SSPC-SP-5/NACE No. 1 instead. Both ambient
and metal surface temperatures should be 10 to 20 degrees Fahrenheit (6.6 to 12.2 degrees
Celsius) above the dew point before starting to paint and there should be adequate drying time
(recommended by the coating manufacturer) between coats.
QA for nuclear grade coatings is discussed in ASME AG-1, Section AA and ASTM D3843, Practice
for Quality Assurance for Protective Coatings Applied to Nuclear Facilities. Other standards
applicable to painting of nuclear facilities include ASTM D3911, Standard Test Method for
Evaluating Coatings Used in Light Water Nuclear Power Plants at Simulated Design Basis
Accident (DBA) Conditions and ASTM D3912-95, Standard Test Method for Chemical Resistance
of Coatings Used in Light Water Nuclear Power Plants.
Because the difficulty in applying nuclear grade coatings to carbon steel surfaces often results
in unsatisfactory performance of the coatings in service, designers should seriously consider use
of stainless steel for mounting frames and housings in corrosive environments or where
frequent decontamination is required. While there are some special handling and fabrication
rules associated in working with stainless steel (particularly the highly polished surface finishes
that should be protected from scratches during fabrication), the overall costs of painted carbon
steel versus stainless are similar.
4.4.4 Man Entry Housing
4.4.4.1 General
Steel man-entry housings may be shop built or field fabricated. Stainless steel is the most
common material of construction; however, carbon steel also may be used. Aluminum and
galvanized steel are not suitable.
4.4.4.2 Structural
The mounting frame is a statically indeterminate lattice that generally consists of a set of full-
length members spanning the height or width of the bank (whichever is shorter), connected by
cross members that are slightly shorter than the width of individual filter (adsorber) units. For
DOE-HDBK-1169-2022
142
design purposes, the frame may be considered as an array of simply supported, uniformly
loaded beams. Experience has shown that, to obtain adequate frame rigidity, these beams
(frame members) should deflect no more than 0.1 percent of their length under a loading
equivalent to 1.5 times the maximum dirty filter pressure drop across the bank.
4.4.4.3 Structural Design
Section 111
Structural design of housings for both ESF air cleaning units and non-ESF units should consider
the service conditions the housing may experience during normal, abnormal, and accident plant
conditions. The design requirements for determining housing plate thickness, stiffness, spacing,
and size are presented in ASME AG-1, Section AA. Housing design should consider the following
load criteria. Key considerations for proper installation include:
• Additional dynamic loads,
• Constraint of free end displacement loads,
• Dead weight,
• Design pressure differential,
• Design wind speed,
• External loads,
• Fluid momentum loads,
• Live load,
• Normal loads,
• Normal operating pressure differential,
• Seismic load, and
• System operational pressure transient.
Stress criteria limits are given in ASME AG-1, Section AA. The maximum deflection for panels,
flanges, and stiffeners for the load combination should be the lesser of the two values derived
as shown below.
Criterion 1
• Plate or sheet: 1/8 inch per foot of the maximum unsupported panel span in direction of
airflow, but not more than 3/4 inch;
• Stiffeners and flange connections: not to exceed 1/8 inch per foot of span, but not more
than 3/4 inch; or
• Flange connection to dampers and fans: 1/360th of the span, but not to exceed 1/8
inch.
Criterion 2
Deflections are limited to values that will not cause:
• Distortion of the airflow path cross-section, resulting in unacceptable increase in system
pressure;
DOE-HDBK-1169-2022
143
• Damage to safety-related items such as instrumentation or other safety-related
equipment or accessories;
• Impingement of deflected elements on adjacent services such as equipment, pipe,
cables, tubing;
• Loss of leak-tightness (in excess of leakage limit);
• Buckling (refer to ASME AG-1, Section AA-4000); or
• Functional failure of components attached to ductwork (e.g., instrument lines).
4.4.4.4 Mounting Frame Configuration
The basic type of mounting frame construction is face-sealed (i.e., the filter seals to the
outermost surfaces of the frame members by means of gaskets glued to the front surface or to
the flange around the face of the filter unit) as shown in Figure 4.51.
A minimum face width of 4 inches is recommended for major and cross members of face-sealed
HEPA filter frames. This allows 1-inch-wide filter-seating surfaces to compensate for any
misalignment of the filter during installation and a 2-inch space between filters, horizontally
and vertically. It also provides adequate room for handling (personnel replacing contaminated
filters will probably have to wear double gloves), using power tools or torque wrenches during
filter change, and manipulating a test probe between units.
Face widths of frame members for installing Type I (pleated-bed) adsorber cells are the same as
those for HEPA filters. Face widths of frame members for installing Type II (tray-type) adsorber
cells may be narrower since handles are provided on the front of the trays to facilitate
installation. Satisfactory mounting frames may be made from rolled structural shapes or
rectangular structural tubing. Figure 4.52 shows a HEPA filter frame made from 4 × 4 inch
structural tubing that meets all structural requirements. Rolled structural shapes for building
mounting frames are given in Table 4.10. Square structural tubing frames for HEPA filters
should be made from rectangular tubing with a face width of at least 4 inches; structural tubing
frames for Type II adsorber cells may have narrower face widths.
Section 112
DOE-HDBK-1169-2022
144
Figure 4.51: Adsorber Gasket Seals Against Mounting Frame Face Plate
Figure 4.52: Filter Mount
DOE-HDBK-1169-2022
145
Table 4.10: Minimum-Cost Structural Members for 24-by-24 HEPA Filter
and Type I Adsorber Mounting Frames (maximum pressure drop to 12 in. wg)
Number of
1,000 cfm Units
High
Principal Member I-beam a Cross Member Channel (span = 22)
Span b Size (in.) lb./ft. Size (in.) lb./ft.
2 4 ft. 8 in. 4 X 4 M 13 4 x 13/4 5.4
3 6 ft. 10 in. 4 x 4 M 13 4 x 13/4 5.4
4 9 ft. 0 in. 4 x 4 M 13 4 x 13/4 5.4
6 13 ft. 4 in. 6 X 4 B 16 4 x 13/4 5.4
8 17 ft. 8 in. 8 X 4 B 10 4 x 13/4 5.4
10 22 ft. 0 in. 10 X 4 5/8 25.4 4 x 13/4 5.4
a Principal members should span the shortest dimension of the bank.
b Span = (number of filters X 26) + 4 (inches).
4.4.4.5 Frame Fabrication
Filter mounting frames should be shop-fabricated if practicable because it is nearly impossible
to avoid misalignment, warping, and distortion in field fabrication. Shop fabrication is less costly
than field fabrication and permits better control over assembly, welding, and dimensional
tolerances. Care should be taken to avoid twisting or bending the completed frame during
handling, shipping, and field installation. For proper performance and maintenance of installed
filters, dimensional and surface-finish tolerances should be tight and rigidly enforced. Welds on
the filter-seating side of the frame should be ground flat, smooth, and flush.
Only welders qualified in accordance with the American Welding Society (AWS) D1.1, Structural
Welding Code-Steel or Section IX of the ASME Boiler and Pressure Vessel Code should be
permitted to make welds on HEPA filter and adsorber mounting frames. Both seal and strength
welds should be visually inspected by a qualified inspector under a light level of at least 100-
foot candles on the surface being inspected. In addition, liquid penetrant (ASTM E165) or
magnetic particle inspection (whichever is applicable for the base material being inspected) of
the seal welds between frame members is recommended.
4.4.4.6 Clamping and Sealing
HEPA filters and adsorber cells should be carefully sealed to the mounting frame (Figures 4.53
and 4.54) to achieve the required low penetration leakage rates and to allow easy replacement.
Except for the fluid-seal design described at the end of this section, sealants are not a
satisfactory substitute for gaskets. Experience in clean rooms and contaminated exhaust and air
cleanup applications has shown that flat, closed-cell, neoprene gaskets, ASTM D1056 grade
2C3, give the most satisfactory seal for high-efficiency filters, adsorbers, and moisture
separators.
DOE-HDBK-1169-2022
146
Figure 4.53: HEPA Filter Mounting Frame (Showing Two Clamp Designs)
Figure 4.54: Absorber Mounting Frame with Test Section Manifold
DOE-HDBK-1169-2022
147
Gaskets that are too soft (i.e., are less than grade 2C3) take an excessive compression set that
may permit leakage when there is relaxation of the clamping bolts. Gaskets that are too hard
(i.e., harder than grade 2C4) require such high clamping loads to effect proper scaling that the
filter itself can be distorted or damaged. As little as 20 percent gasket compression is needed to
affect a reliable seal when the thickness of the gasket is uniform to within ±0.01 inches and the
seating surface of the mounting frame is plane to within ±0.01 inches.
Section 113
However, these tolerances are much too restrictive for economical construction, and
experience has shown that it is usually necessary to compress a 2C3 gasket at least 80 percent
to affect a reliable seal over long periods. Eighty-percent compression requires a loading of
approximately 20 psi of gasket area, or a total clamping load of about 1,400 pounds for a 24- by
24-inch filter unit. The recommended procedure for installing filters under nonhazardous
conditions is to initially torque the clamping bolts to produce 50 percent gasket compression
and then retorque them 1 or 2 weeks later to a total compression of about 80 percent. In a
radioactively contaminated filter system, replacement can be a hazard to personnel and to the
filters and/or adsorbers installed in the system. Under such conditions, one entry is advised.
One option is to manually compress the filter gasket to an estimated 50 to 80 percent. A spring-
loaded hold-down (Figure 4.55) is another option used at some DOE sites. Torsion bar clamps
designed to exert the proper clamping forces are a third option.
Figure 4.55: Filter Hold-Down (Spring Design)
Gaskets that are too thin may not give a reliable seal, whereas those that are too thick may be
unstable and tend to roll or pull off the flange of the filter case as they are compressed, perhaps
to the extent that sections may be extruded between the case and mounting frame and
produce a serious air leak. Recommended gasket sizes are 1/4 to 3/8 inch thick by 3/4 inch wide
and 1/4 to 3/8 inch thick by 5/8 inch wide. Gaskets should be glued to the filter element rather
than to the mounting frame because they should be replaced with each filter change. A sealant
such as silicone could be applied lightly to the filter gasket. Residue should be removed before
DOE-HDBK-1169-2022
148
installing new filters as the sealant may be contaminated, making disposal more difficult.
Gaskets should have cut surfaces on both faces because the “natural skin” produced by molding
sometimes tends to bridge discontinuities or defects in the seating surface, and because the
silicone mold-release compounds used in the manufacture of sheet neoprene prevent proper
adhesion of the gasket to the filter case.
Clamping devices should function easily and reliably after long exposure to hostile
environments. In addition, they should be capable of easy operation by personnel dressed in
bulky protective clothing, gloves, and respirators (or full-face gas masks) while working in close
quarters. Experience has shown that a simple nut-and-bolt system gives satisfactory service
under these conditions. Nut-and-bolt clamping, however, entails removal and handling of a
large number of nuts, and this procedure can be a problem during a filter change in a highly
radioactive system. However, clamping systems that provide the required torque and gasket
compression without loose parts are highly recommended. Any system that achieves the
desired clamping torque is acceptable. Figure 4.56 shows four pressure clamping points as
recommended for HEPA filters and provides an example of clamping a blanking plate for filter
change.
Eccentric, cam-operated, over-center, or spring-loaded latches, and other quick-opening
latches, such as the window latch design, are not recommended for clamping high-integrity
components such as HEPA filters and adsorber cells. Because of their weight, eight pressure
points are desirable for clamping Type I (pleated-bed) adsorber cells. For clamping Type II (tray-
type) cells, two pressure points on the top and two on the bottom edges of the front plate are
needed for proper sealing, with individual clamping.
Section 114
The minimum bolt size recommended for individually clamped filters is 3/8-16-UNC, but 1/2-11-
UNC or 5/8-11-UNC bolts are less prone to damage. For Type I adsorbers, 5/8-11-UNC bolts are
necessary. The nuts and bolts of the clamping system should be made of dissimilar materials to
prevent galling and seizing. Bolting materials and clips should be corrosion resistant. Stainless
steel (300 series) bolts with brass nuts are frequently used. Springs, if used, should also be
made from a PPH grade of stainless steel if they are to resist corrosion and relaxation over a
period of service.
DOE-HDBK-1169-2022
149
Figure 4.56: HEPA Filters Mounting Frame with Blanking Plate Installed for Filter Change
4.4.4.7 Filter Support
A cradle or other support for the filter element as it is moved into position on the frame is a
desirable feature from a maintenance standpoint. The cradle should not obscure any more of
the filter-to-frame interface than necessary to avoid interference with inspection as the filter is
installed. The support shown in Figure 4.57 is a good choice because it obscures less of the
gasket-frame interface. In some installations, filters have been supported on the bottom
clamping bolts, a practice that risks damage to the threads of the clamping bolts and is not
recommended.
DOE-HDBK-1169-2022
150
Figure 4.57: HEPA Filter Mounting Using Pressure Distribution Frame Design Filter Hold Down
4.4.4.8 Size and Arrangement of Filter and Adsorber Banks
The size (nominal airflow capacity) and orientation of filter banks (vertical or horizontal), the
location of filters on the bank (upstream or downstream side), and the floor plan and height of
the bank all affect the reliability, performance, maintainability, and testability of the air
cleaning system. Savings gained by designing for minimum space and materials can be wiped
out many times over by the higher operational, maintenance, and testing costs that will result
from higher pressure drop and cramped working space in the filter housing. See Section
4.4.4.11 for additional guidance on the size of filter banks and system capacity.
4.4.4.9 Vertical Filter Banks
Vertical banks with horizontal airflow are preferred in contaminated exhaust systems because
the filters are more favorably oriented with respect to ease of handling, mechanical strength of
the filters, and collection of condensate. The pleats of Type I adsorber cells and the beds of
Type II cells should be installed horizontally to avoid adsorbent settling in the cells. Before
designing a horizontal filter bank with vertical airflow, filter/adsorber components should be
validated for performance in this application/design. In addition, the design should include
provisions for filter installation and removal.
DOE-HDBK-1169-2022
151
4.4.4.10 Location of Filters on Mounting Frame
No clear-cut preference can be justified for mounting filters on either the upstream or the
downstream side of the mounting frame. Both methods have been used successfully and the
advantages and disadvantages of each are listed below.
Upstream Mounting
Advantages:
• The filters are withdrawn into and handled within the contaminated side of the system
during a filter change.
• No contaminated materials are brought into the clean side of the system, so there is
more complete separation of the clean and dirty sides of the system.
Disadvantages:
• Personnel have to work within a potentially contaminated zone during a filter change.
Section 115
• It is possible that contamination can be tracked or carried out of the contaminated zone
by workmen, unless the filter change is carefully planned and executed.
• The filter clamping devices are located in the dirty side of the system where they are
most exposed to corrosion and dirt.
• Contaminated material may accumulate on the horizontal surfaces of the filter case and
may dislodge during removal.
Downstream Mounting
Advantages:
• Filters are withdrawn into and handled within the clean side of the system, thereby
reducing the likelihood of tracking or carrying contamination into the building during a
filter change.
• Filter clamping devices are located on the clean side of the system where they are less
subject to corrosion.
• Leak-scanning of installed filters is more sensitive: if there are gasket or casing leaks, the
driving force of air entering the filter forces the test aerosol through the leak, and they
are readily detected.
• With upstream mounting, on the other hand, any test aerosol that goes through a leak
in a gasket or filter case mixes with the air and test aerosol passing through the opening
in the mounting frame, thus obscuring the leaks. Although the existence of a leak may
be disclosed by a test, the location of the leak cannot be easily determined by probing.
• Only the upstream face of the filter is contaminated during operation. The outer
surfaces of the filter case and the downstream face of the filter pack are not usually
contaminated.
DOE-HDBK-1169-2022
152
Disadvantages:
• The contaminated filters should be withdrawn into the clean side of the system in a
filter change. This disadvantage can be offset by “fixing” (locking down) the
contaminated dust by spraying the upstream side of the filter pack with paint or acrylic
spray or by taping cardboard over the upstream face of the filter. However, this
procedure requires personnel to enter the contaminated chamber of the housing, and
the possibility still exists of dislodging contaminated dust into the clean side of the
system, either from the filter itself or from the edges of the frame opening (which is
exposed to contaminated air during operation).
• Filters have been mounted on both sides of a mounting frame in some installations. This
is not recommended. A cardinal rule in contaminated exhaust systems is that no credit
is granted for untested and untestable filters. Such mounting precludes testing of both
filters. Therefore, although double mounting may provide two sets of filters, the
operator cannot take credit for two-stage filtration or series redundancy. This design
has been shown to fail in a fire. The upstream filter blows out when plugged with smoke
particles and impacts the filter downstream, causing it to blow out also.
4.4.4.11 Size of Banks
Previously, a nominal system capacity of 30,000 cfm has been recommended by DOE and NRC
for any filter or adsorber bank. This recommendation has been modified to account for the
larger capacity components now in use. Thus, the maximum size of a safety class or safety
significant filtration housing not exceeding 30 filtration components (e.g., medium efficiency
filter, moisture separator, HEPA filter or adsorber cell) per stage, allows for meaningful in place
testing. When significantly greater air flow than this is needed, multiple systems can be
installed in parallel. The purpose of this requirement is to facilitate maintenance and in-place
testing, to improve control in the event of a system upset, and to enhance the reliability of the
total system.
Section 116
By breaking the system into two or more air cleaning units, testing and filter replacement can
be conducted in one unit while the other unit remains online. NRC RG 1.52 recommends such
redundancy for ESF air cleaning systems in reactors. The designer may also choose to segment a
system into units of substantially less than 30,000 cfm or 30 filtration components when
redundancy is desired to achieve advantages of control, maintainability, and testability. The use
of 1,500-cfm filters allows higher-capacity systems without increasing the physical size of the
bank. In-place testing and maintenance is the determining factor.
4.4.4.12 Arrangement of Banks
Arrangement of filters on a mounting frame influences operating performance and
maintenance. Where possible, banks should be laid out in an array of three filters high or nine
Type II adsorber cells high. When floor space is at a premium, the bank may be arranged with
one 3-high array above another, with a service gallery between. Thus, an 18,000-cfm bank
might be arranged in an array 6-wide by 3-high or 3-wide by 6-high, with a service gallery
DOE-HDBK-1169-2022
153
between the third and fourth tiers. The arrangement of a 24,000-cfm bank in a 6-wide by 4-high
array would be undesirable. A better arrangement is an array 8-wide by 3-high or, if floor space
is at a premium, two 4-wide by 3-high arrays, one above the other, separated by a service
gallery. In no case should filter changing require the use of temporary ladders or scaffolding.
Based on the 95th-percentile man, the maximum height at which a man can operate hand tools
effectively is 78 inches, and the maximum load he can handle at a height of 5 feet or more is 40
pounds, which is the approximate weight of a clean HEPA filter. Therefore, provision for access
to the higher tiers of filters is necessary. In fact, ASME AG-1, Subsection HA, requires that a
permanent platform be installed to access filters above 6 feet.
Filter banks should be rectangular. The use of odd-shaped banks to limit installed filter capacity
to calculated system airflow requirements increases construction costs significantly. Operating
costs may also be reduced because the additional filters permit operation at a lower flow rate
per unit resulting in longer filter life and reduced filter-change frequency. For the purposes of
laying out adsorber banks, three Type II (tray) adsorbers will fit vertically into the space
occupied by one 24- by 24-inch HEPA filter.
4.4.4.13 Floor Plan of Filter Banks
The plenum floor plan of a vertical filter bank varies with the application of the system.
Judicious configuration of banks can often reduce pressure losses in the system and bring about
more uniform dust loading of filters, thereby equalizing the utilization of the filters installed in
the banks.
The procedures required for construction and operational maintenance should be considered
early in the planning stages. Adequate clearances for access should be maintained at turning
points and between the bank and the nearest obstruction. Passageways both between the
banks and between the banks and the housing wall should be wide enough for welders to
operate effectively and for workmen, dressed in bulky clothing, to get in to change filters (see
Figures 4.58 and 4.59). Both welders and workmen will have to kneel or stoop to get to the
bottom tier. A 95th-percentile man in a kneeling position requires a minimum clearance of 36
inches from the face of the filters to the nearest obstruction, excluding withdrawal space for
the filter unit itself. A minimum clearance of 40 inches is therefore recommended between the
face of one bank and the nearest obstruction.
Section 117
4.4.4.14 Steel Housings
Design practices used for conventional air conditioning and ventilation system ductwork and
equipment casings are not adequate for high-reliability, high-efficiency contaminated exhaust
and air cleanup systems. Experience has shown that, under system upset and shutdown
conditions, housing leaks can result in the escape of contamination to clean areas. Even with
fans operating, reverse leakage of particles from the low-pressure side of a system (i.e., the
interior of the housing or duct) to the high-pressure side (i.e., the occupied area of the building)
can sometimes occur because of dynamic and aspiration effects. Out-leakage may also occur
when the system is shut down. Filter housings for contaminated exhaust service should be able
DOE-HDBK-1169-2022
154
to withstand negative pressures without damage or permanent deformation at least up to fan
cutoff, which may be equal to 20 in. wg. in many systems. A pressure differential of 2 in. wg.
between the inside and outside of a housing produces a load of more than 1,000 pounds over
every 10 square feet of the housing wall. If the filters are operated to economical pressure
drops, the housing may have to withstand 10 or more times this load without appreciable
deflection. Pulsation and vibration may aggravate the condition. In addition, the housing should
be able to withstand design shock loads without damage.
Figure 4.58: HEPA Filter Mounted on Upstream Side of Mounting Frame Filter Replacement
DOE-HDBK-1169-2022
155
Figure 4.59: Blanking Plate Being Installed on Downstream Side of Mounting Frame
Housings should be of all-welded construction, with bolted flange or welded inlet and outlet
connections to the ducts and fans. Table 4.11 gives minimum sheet metal thicknesses for sheet
steel housings, and Table 4.12 gives minimum moments of inertia for steel reinforcing
members. Sheet metal thicknesses in Table 4.11 are based on a maximum deflection of 1/4
inch per linear foot at a pressure differential between the interior of the housing and
atmosphere equivalent to 1.5 times the maximum pressure at fan cutoff. The moments of
inertia for reinforcing members listed in Table 4.12 were selected to avoid exceeding the
allowable stress of the steel. Members up to 20 inches long were considered to be uniformly
loaded beams with fixed ends, whereas members longer than 20 inches were considered to be
uniformly loaded beams with simply supported ends. The sheet-metal thicknesses in Table 4.11
are given in U.S. gauge numbers for sheet and fractional inches for plate.
DOE-HDBK-1169-2022
156
Table 4.11 – Minimum Sheet-Metal Thicknesses a for Welded Steel b Filter Housings under
Negative Pressure
Dimensions of Largest
Unsupported Panel (in.)
Thickness c (U.S. gauge for sheet, fractional in. for plate) for negative
pressure
Long Side d Short Side 4 in. wg. 8 in. wg. 12 in. wg. 20 in. wg. 1 psi 2 psi
54 (2) 12 18 18 14 16 14 11
24 18 14 11 12 8 1/4
36 16 12 8 11 1/4 3/8
48 14 12 6 8 1/4 3/8
80 (3) 12 18 16 14 16 14 11
24 18 14 11 12 8 1/4
36 16 12 6 11 1/4 3/8
48 14 12 6 8 1/4 3/8
106 (4) 12 18 16 16 14 14 11
24 18 14 12 11 8 1/4
36 16 12 8 6 1/4 3/8
48 16 10 6 1/4 3/8 3/8
a Based on flat plate edges held but not fixed (Roark’s Formulas for Stress and Strain), and maximum deflection of
0.25 inch per foot between reinforcements.
b 30,000 to 38,000 psi yield strength.
c Metal thickness less than No. 18 U.S. gauge are not recommended because of welding problems.
d Length based on 2-inch spacing between 24- × 24-inch filter units; the numbers within parentheses denote
number of filter units. The metal thicknesses are adequate for panel lengths within ±10 inches of the length
shown.
Section 118
DOE-HDBK-1169-2022
157
Table 4.12– Recommended Minimum Moments of Inertia for Selecting Reinforcing Members
for Steel Filter Housings under Negative Pressure a, b
Reinforcement Moment of inertia (in.) c for negative pressure (relative to outside)
Length d
(in.)
Spacing
(in.) 4 in. wg. 8 in. wg. 12 in. wg. 20 in. wg. 1 psi 2 psi
54 (2) 12 0.04 0.04 0.04 0.04 0.04 0.08
24 0.04 0.04 0.04 0.06 0.08 0.16
36 0.04 0.04 0.05 0.09 0.12 0.24
48 0.04 0.05 0.07 0.12 0.16 0.32
80 (3) 12 0.04 0.04 0.05 0.08 0.11 0.21
24 0.04 0.06 0.09 0.16 0.21 0.43
36 0.05 0.10 0.14 0.24 0.32 0.63
48 0.06 0.13 0.19 0.32 0.42 0.86
106 (4) 12 0.04 0.09 0.13 0.22 0.30 0.60
24 0.09 0.18 0.26 0.44 0.60 1.19
36 0.13 0.27 0.39 0.66 0.90 1.79
48 0.18 0.36 0.52 0.88 1.19 2.38
132 (5) 12 0.09 0.17 0.26 0.51 0.69 1.39
24 0.18 0.34 0.52 1.02 1.39 2.78
36 0.27 0.51 0.78 1.53 2.08 4.17
48 0.36 0.68 1.04 2.04 2.76 5.55
158 (6) 12 0.15 0.29 0.44 0.73 1.0 2.0
24 0.29 0.59 0.88 1.46 2.0 4.0
36 0.44 0.87 1.32 2.19 3.0 6.0
48 0.58 1.16 1.76 2.19 4.0 8.0
a Based on permissible deflection of 1/8 inch per foot.
b Uniformly loaded beam, 50 percent simply supported and 50 percent fixed end assumed.
c Structural angles can be chosen from the tables given in the AISC Manual of Steel Construction.
d Length based on 2-inch spacing between 24- x 24-inch filter units; the numbers within parentheses denote
number of filter units. The metal thicknesses are adequate for panel lengths within ±10 inches of the length
shown.
Housings installed inside a reactor confinement may experience a pressure lag during rapid
pressurization of the confinement following a major accident. Unless the housings are equipped
with pressure-relief dampers, this lag could result in a pressure differential between the
housing and confinement substantial enough to collapse the housing.
Reinforcing members should be spaced to minimize vibration and audible drumming of the
housing walls, which can be transmitted through the system. Reinforcements should be
installed on the outside of the housing, when possible, to eliminate interior ledges and
projections that collect dust and constitute hazards to personnel working in the housing (Figure
4.60).
DOE-HDBK-1169-2022
158
Figure 4.60: Filter Plenum Floor Plan
All sharp corners, welds, weld spatter, and projections inside the housing should be ground
smooth. The housing design should minimize cracks and crevices that are difficult to clean and
that may collect moisture that can cause corrosion.
Mastics and caulking compounds, including silicone-based, room-temperature vulcanizing (RTV)
sealants, deteriorate in service and should not be used for sealing between panels and sections
of a contaminated exhaust housing. Lock seams, rivets, and bolts used in conventional
construction for joining panels do not produce leak-tight joints. When bolted flange joints are
used between the housing and ducts, 1.5- × 1.5- × 0.25-inch-angle flanges with ASTM D1056,
grade 2C5 or 30-40 Shore-A durometer neoprene gaskets are minimum requirements. A
maximum bolt spacing of 4 inches is recommended for flanges.
4.4.4.15 Masonry and Concrete Housings
Filter housings for low-gamma-activity systems and vaults for high- (or potentially high-)
gamma-activity systems sometimes have been built as an integral part of the building structure
utilizing the same concrete building walls for HEPA housing walls. This construction is not
recommended.
4.4.4.16 Housing Floor
Section 119
Steel housings should have steel floors welded continuously to the walls of the housing.
Housings should not be installed on a wood floor or on a floor having less than a 3-hour fire
rating. A steel curb, welded to the floor, is recommended to raise the filter-mounting frame off
DOE-HDBK-1169-2022
159
the floor. The section of flooring between two banks of components should be considered a
separate floor to be drained independently. Floors should be free of obstructions or raised
items that could be hazardous to workmen.
4.4.4.17 Housing Doors
Easily opened doors are essential on large housings, and more than one door is generally
needed. A door should be provided to each compartment (space between banks) where
maintenance, testing, or inspection may take place. The use of bolted-on removable panels for
access to filter compartments should be avoided for even the smallest filter housings when
human entry is required. Sliding doors are not recommended for filter housings, because they
cannot be sealed and because they jam after any distortion of the housing.
Sturdy double-pin-hinged doors with rigid, close-fitting casings and positive latches should be
provided on man-entry housings, particularly those for ESF and other high-hazard service.
Doors and gaskets should be designed to maintain a hermetic seal under positive and negative
pressures equal to at least the fan cut-off pressure. Doors of negative pressure systems should
open outward and, since they may have to be opened against the negative pressure, a means
for breaking the vacuum or for mechanically assisted opening is desirable. Doors should have
heavy-duty hinges and positive-latching devices that are operable from inside and outside.
Means for locking, such as a padlock, may be provided to prevent unauthorized entry. Door
stiffness is important because flexible doors can be sprung when opened against negative
pressure or allowed to slam shut under load. An airlock at the entry to the housing will
eliminate problems with opening doors against negative pressure and slamming, and, if large
enough, will provide an intermediate work area for personnel during a filter change.
Housing doors of the type shown in Figure 4.61 require a minimum of two latching dogs on
each side. Lighter-construction doors require additional latches to achieve a satisfactory seal.
Latching dogs should be operable from inside and outside the housing, and shafts should be
fitted with O-rings, glands, or stuffing boxes to prevent leakage. Door hinges should be of the
double-pin, loose-pin, or other type that will permit the full plane of the door to move
perpendicular to the plane of the doorframe during the last fraction of an inch of closure.
Single-pin hinges, which result in angular motion throughout the door closing arc, do not permit
the door to seal properly and may cause the gasket to be rolled out of its groove after a period
of use, thus resulting in the loss of housing leak-tightness. If door gaskets are too hard, they will
be incompressible, and the door cannot be sealed properly even with lever-and-wedge latching
dogs. If too soft, the gasket will rapidly take a compression set and lose its ability to seal. Solid
neoprene or silicone rubber of about 30 to 40 Shore-A durometer hardness is recommended.
DOE-HDBK-1169-2022
160
Figure 4.61: Filter Plenum Entry Door (No Airlock Type-Test Manifold with Valves Shown)
Section 120
The door should be large enough for easy access to personnel dressed in bulky protective
clothing, wearing gas masks or respirators, and carrying (a) 24x24x11.5-inch filters weighing up
to 40 pounds, or (b) 26x6x30 inch adsorber cells weighing up to 130 pounds. However, the
larger the door, the more difficult it is to seal and the more likely that it or its frame can be
damaged if allowed to slam under load. The door should be as large as possible for easy access,
but in no event should it be any less than 26 inches wide and 48 inches high. A coaming (2-inch-
high minimum to 6-inch-high maximum) should be provided at all doors to prevent the outflow
of contaminated water should the housing become flooded.
4.4.4.18 Housing Drains
Floor drains are essential in contaminated-exhaust filter housings, particularly when sprinkler
protection is provided. Even if moisture or condensation is not expected under normal
conditions, occasional wash-down may be required for decontamination and water will be
needed in the event of a fire. When the housing is above grade, the minimum provision for
DOE-HDBK-1169-2022
161
drainage is a Chicago half-coupling that is sealed with a bronze pipe plug using
tetrafluoroethylene (Teflon®) plastic “ribbon dope” so the plug can be easily removed when
needed.20 When the filter is at or below grade, drains should be piped to an underground
contaminated waste system during initial construction, since later drainage system installation
is likely to be costly. Drains from contaminated systems should be piped to the radioactive
waste system. In cold climates, water seats, traps, and drain lines should be protected against
freezing if they are above the frost line. In hot climates, water seats/seals may dry out. When
fire sprinklers are installed in the filter house, the drains should be sized to carry away the
maximum sprinkler flow without water backup in the housing. Design of housing drains and the
loop seals need to consider that the negative pressure within the system, caused by the
vacuum created by the downstream fans, may impact the ability of the housing to drain water.
If a separate drain is needed for each chamber of the filter house, then each drain should have
its own water/loop seal or trap (Figure 4.62). The raised drain (shown) takes into consideration
criticality concerns while minimizing wastewater. The spaces between two banks of
components in series are considered separate chambers. When piped to a common drain
system, drain lines from the individual chambers of the housing should have a valve or be
sealed, or otherwise protected to prevent bypassing of contaminated air around filters or
adsorbers through the drain system. The drain system should be tested for leakage as part of
the housing leak test, as well as part of system bypass testing of the HEPA and adsorbent filters.
Provision should be made for those seals or traps to ensure they are filled with water during
the plant life (Figure 4.63). Water seals should be periodically checked to ensure they do not
dry out. If the seal does dry out, there is a possibility that air from the contaminated drain
system will be drawn into the filters. A manual or automatic fill system may be utilized to
ensure water seals do not evaporate for systems that do not experience moisture conditions
continuously. Figure 4.64 shows alternate methods of drain connection.
20 Use of Teflon in radiation areas needs to be specifically considered for radiolytic decomposition on a case-by-
case basis.
Section 121
DOE-HDBK-1169-2022
162
Figure 4.62: Plenum Drain Detail
Figure 4.63: Filter Plenum Drain P-Trap Fill Tube
DOE-HDBK-1169-2022
163
Figure 4.64: Plenum Drain Designs
4.4.4.19 Other Housing Requirements
Figures 4.65 and 4.66 illustrate features that are desirable in an air cleaning housing. The
housing is all-welded construction. This housing consists of the moisture separator, medium
efficiency filter, HEPA filter, carbon adsorber, and downstream HEPA filter. The housing is a
9,000-cfm capacity system and includes the following features.
• Shop fabrication.
• Wired-glass viewports on each side of the filter bank for visual inspection without
entering the housing (Figure 4.67).
• Permanently installed lights in vapor-tight globes that are replaceable from outside of
the housing.
• Wiring installed on the outside of the housing (penetrations for wiring are a common
source of leakage).
• Shock-mounted instruments with a pressure-drop manometer across each bank of
filters and inlet and outlet temperature indicators (Figures 4.68 and 4.69).
DOE-HDBK-1169-2022
164
• A large marine bulkhead door that is operable from both inside and outside the housing
(Figure 4.70).
• Ample space (approximately 4 × 7 feet) inside the housing to allow personnel to work
during a filter change.
• All reinforcements located on the outside of the housing.
• A housing opening on the aisle that can be controlled and that serves as a workspace
during filter change-out.
• All-welded construction to eliminate leaks to occupied areas.
• All penetrations sealed by either continuous seal welding or adjustable compression-
gland-type seals rated and qualified for the environmental conditions.
• Housing drains located in each compartment.
• Permanently installed test aerosol and Freon injection and sample ports (highly
recommended).
Figure 4.65: Desirable Air Cleaning Housing Features (a)
DOE-HDBK-1169-2022
165
Figure 4.66: Desirable Air Cleaning Housing Features (b)
Figure 4.67: Viewport
DOE-HDBK-1169-2022
166
Figure 4.68: Manual Control and Instrument Panel
Figure 4.69: Air Monitor in Exhaust Duct from Plenum
DOE-HDBK-1169-2022
167
Figure 4.70: Plenum Door (Wheel-Type Inside Plenum Access)
4.4.5 Design of Side-Access Housings
The recommended capacity range for side-access housings is 2 filters (24 × 24 × 11 1/2 inches)
per stage to 12 filters per stage (4 across × 3 high). Single filter units are also available. Units
may be stacked 3 high or higher if platforms are provided. Housings may be provided with or
without bag-in/bag-out features. Bag-in/bag-out side-access housings feature a ribbed bagging
ring inside the side-access door. A specially designed polyvinyl chloride change-out bag is
secured around the bagging ring after initial filter loading. All subsequent filter changes are
accomplished through change-out bags. Contaminants are isolated to the inside of the bag to
protect site personnel and permit safe handling and disposal of spent filters. A self-adjusting
filter seal mechanism prevents filter bypass and maintains a positive seal during normal system
operation. The housing can also be utilized without the use of change-out bags, which may be
specified where future hazardous contaminants are unknown.
4.4.6 Recommended Design Features
Housing Material: Standard 14-gauge stainless steel.
Unit Construction:
• All pressure boundary joints and seams seal welded,
• Surfaces free of burrs and sharp edges, and
DOE-HDBK-1169-2022
Section 122
168
• Reinforced to withstand up to 30 in. wg.
Access Panel:
• Completely hand-removable,
• Handles retained in access panel after removal, and
• Protected panel gasket seal covers entire inner panel surface.
Bagging Ring:
• Two continuous ribs for optimum bag seal,
• Ring depth designed to contain bag during operations, and
• Smooth outer surface and hammed outer edge.
Filter Clamping Mechanism:
• Spring-loaded pressure bars exert uniform clamping force on filed frame;
• Spring loading compensated for any loss of filter gasket memory;
• Positive displacement screw-drive clamping mechanism;
• Leak-tight connection for clamping mechanism on outside of housing;
• Stainless steel clamping mechanism; and
• Over 1/2-inch travel to prevent filter binding.
Filter-to-Housing Seal
• Standard full perimeter flat mounting frame mates to filter gasket; and
• Full seal weld around filter frame.
Filter Removal Rod
• Standard mechanical assist on all multiple wide housings; and
• Operated through bagging ring.
Pressure Taps
• Welded in housing, upstream and downstream of filter,
• 1/2-inch National Pipe Thread half-coupling with plug.
Seals and Gaskets
Seals and gaskets should be installed on panels, and a “knife-edge” gasket sealing surface
should be provided. The gasket should be installed in as few pieces as possible to minimize the
number of joints and designed to prevent leakage due to miss fitting butt joints. Side-access,
bag-out access panels often use gaskets that accommodate the panel to the housing seals.
Latches or bolts should be of sufficient quantity and strength to compress the gasket and
DOE-HDBK-1169-2022
169
ensure that the housing leakage criteria are met. Panels should allow access for testing and
component inspection. The drawings for each type and size panel should be submitted to the
owner for review before fabrication. Panel drawings should show the location and details
concerning the hinges, latching lugs, and gaskets.
4.4.7 Differences Between Nuclear Filtration Systems and Commercial/Industrial Filtration
Systems
1. The standard design pressure for nuclear systems is 10 to 15 in. wg. compared to 3 in.
wg. or less for commercial/industrial systems. In addition, confinement systems can be
built to higher pressures, such as 30 to 40 in. wg. without significant cost increases.
2. Nuclear systems are designed, manufactured, and tested to a higher level of QA, such as
ASME NQA-1. This includes certified welders, in-process inspections, and material
traceability. Several factory tests are standard, such as filter fit, operability of filter
locking mechanisms, flatness of filter sealing surfaces or alignment of knife edges and
leak testing of each filter sealing surface and overall pressure boundary of each housing
and/or system. Test reports are available to the customer for their files.
3. Nuclear systems are designed and built with all-weld construction. All pressure-
boundary welds are continuously welded. These systems are built for long life, and RTV
sealants are not allowed.
4. Stainless steel is the material of construction for confinement systems versus galvanized
construction for commercial/industrial systems.
5. Most nuclear systems incorporate the bag-in/bag-out feature which allows the user to
protect their maintenance personnel and the surrounding environment during filter
change-out.
Section 123
6. Nuclear filter housings incorporate filter locking mechanisms that are designed to
achieve a filter-to-frame seal that will last throughout the life of the filter, not just when
the filter gasket is new.
7. Nuclear systems are designed so that each tier of filters has its own access door. This is
needed when the bag-in/bag-out feature is used and is desirable even without the bag-
in/bag-out feature.
8. Nuclear systems offer optional in-place test sections.
9. Nuclear systems offer optional separate access panels for medium efficiency filters,
which allows the seal of the HEPA filters to be on the upstream side.
10. Nuclear systems now incorporate isolation dampers in many cases. These dampers are
now readily available in both “bubble-tight” and “low-leakage” designs.
11. These dampers are designed, manufactured, and tested in the same manner as the filter
housings.
DOE-HDBK-1169-2022
170
4.4.8 Advantages of Stainless Steel Over Heavy Carbon Steel Construction
• Nuclear filtration systems are usually constructed of 14- and 11-gauge stainless steel
reinforced externally. The cost of this design is very nearly the same as manufacturing
from heavy steel plates and priming/painting for corrosion protection.
• Stainless steel offers much better corrosion protection during installation and use than
painted steel.
• Decontamination and cleaning of systems is much easier with stainless steel.
• Modification of systems in the field is much easier with stainless steel. Changes,
including welding, can be made without ruining the corrosion protection of the system.
• Stainless steel systems typically weigh less than carbon steel systems.
4.4.9 Side-Access Housings For Radial Flow Cylindrical HEPA Filters
Side-access housings for radial flow cylindrical filters have been designed for the installation of
up to 12 plug-in, 2000-cfm filters, for a total of 24000 cfm. Larger installations are possible
(Figures 4.71 through 4.73). A ring is provided around the filter access to facilitate fitting of the
change bag (Figure 4.74). An access cover is positioned over the filter. A locator fitted in the
cover ensures correct positioning of the filter in the module.
DOE-HDBK-1169-2022
171
Figure 4.71: Side-Access Housing
Figure 4.72: Side Access Housing
DOE-HDBK-1169-2022
172
Figure 4.73: Side Access Housing
Figure 4.74: Radial Flow Filter Bag-Out
DOE-HDBK-1169-2022
173
4.4.10 References
1. Adley, F. E., 1966, “Factors Influencing High Efficiency Gasket Leakage,” 9th Air Cleaning
Conference, U.S. Atomic Energy Commission Report CONF-660904, National Technical
Information Service, Springfield, VA, September.
2. AISC (American Institute of Steel Construction, 2015, Steel Construction Manual, 15th
Edition, Chicago, IL.
3. American Iron and Steel Institute, 2017, Cold Formed Steel Design Manual, Washington, DC.
4. ASME (American Society of Mechanical Engineers), 2002, Nuclear Power Plant Air Cleaning
Units and Components, ASME N509, New York, NY.
5. ASME, 2018, Quality Assurance Requirements for Nuclear Facilities, ASME NQA-1, New
York, NY.
6. ASME, 2019, Boiler and Pressure Vessel Code, “Welder Qualification,” New York, NY.
7. ASME, 2019, Code on Nuclear Air and Gas Treatment, ASME AG-1, New York, NY.
8. ASTM, 2015, Standard Specification for Steel Bars and Shapes, Carbon-Rolled from “T” Rails,
ASTM A499, West Conshohocken, PA.
Section 124
9. ASTM, 2016, Standard Test Method for Evaluating Coatings Used in Light-Water Nuclear
Power Plants at Simulated Design Basis Accident (DBA) Conditions, ASTM D3911-16, West
Conshohocken, PA.
10. ASTM, 2017, Standard Test Method for Chemical Resistance of Coatings and Linings for Use
in Nuclear Power Plants, ASTM D3912-10(2017), West Conshohocken, PA.
11. ASTM, 2018, Standard Guide for Use of Protective Coatings in Nuclear Power Plants, D5144,
West Conshohocken, PA.
12. ASTM, 2018, Standard Specification for Cold-formed Welded and Seamless Carbon Steel
Structural Tubing in Rounds and Shapes, ASTM A500/A500M-18, West Conshohocken, PA.
13. ASTM, 2018, Standard Specification for Flexible Cellular Materials-Sponge or Expanded
Rubber, ASTM D1056-18, West Conshohocken, PA.
14. ASTM, 2018, Standard Specification for Steel, Sheet and Strip, Hot-Rolled, Carbon, Structural,
High-Strength Low-Alloy and High-Strength Low-Alloy with Improved Formability, and Ultra-
High Strength, A1011/A1011M-18a, West Conshohocken, PA.
15. ASTM, 2019, Standard Specification for Chromium and Chromium-Nickel Steel Plate, Sheet,
and Strip for Pressure Vessels and for General Applications, ASTM A240/A240M-19, West
Conshohocken, PA.
16. ASTM, 2019, Standard Specification for Cold-Formed Carbon Structural Steel, ASTM
A36/A36M-19, West Conshohocken, PA.
17. ASTM, 2019, Standard Specification for Stainless and Steel Bars and Shapes for Use in Boilers
and Other Pressure Vessels, ASTM A479/A479M-19, West Conshohocken, PA.
DOE-HDBK-1169-2022
174
18. ASTM, Standard Practice for Quality Assurance for Protective Coatings Applied to Nuclear
Facilities, ASTM D3843-16, West Conshohocken, PA.
19. ASTM,2018, Standard Practice for Liquid Penetration Testing for General Industry, ASTM
E165/E165M-18, West Conshohocken, PA.
20. AWS (American Welding Society), 2015, Structural Welding Code-Steel, AWS D1.1/D1.1M-
2015, Miami, FL.
21. IEST (Institute of Environmental Sciences and Technology), 2007, High Efficiency Gas-Phase
Adsorber Cells, IEST-RP-CC008, Mt. Prospect, IL.
22. NRC, 10 CFR Part 100, Reactor Site Criteria.
23. NRC, 10 CFR Part 20, Standards for Protection Against Radiation.
24. NRC, 2012, Design, Inspection, and Testing Criteria for Air Filtration and Adsorption Units of
Post-Accident Engineered-Safety-Feature Atmospheric Cleanup Systems in Light-Water-
Cooled Nuclear Power Plants, Regulatory Guide 1.52, Revision 4.
25. Sims, L. L., 1969, “Molded HEPA Filter Gasket Leakage,” Hanford Environmental Health
Foundation Report HOHF-11, Richland, WA, September.
26. SPC (Society of Protective Coating), “White Metal Blast Cleaning,” Steel Structures Painting
Manual, Surface Preparation Specification 5, SPC-SP5/NACE No. 1, Pittsburgh, PA.
27. Young, W. and R. Budynas, 2011, Roark’s Formulas for Stress and Strain, 8th Edition,
McGraw-Hill, New York, NY.
4.5 External Components
4.5.1 Introduction
External components of an air cleaning system include fans, ductwork, dampers, louvers,
stacks, instruments, and other miscellaneous accessories that are associated with the
movement, control, conveying, and monitoring of the air or gas flow. This section contains
information on the design, fabrication, materials, and codes and standards requirements/
considerations for air cleaning system external components for nuclear facilities.
4.5.2 Ductwork
This section will address the functional design, mechanical design, materials, coatings, supports,
acoustic considerations, leakage, vibration considerations, and applicable codes and standards
for ductwork for nuclear facilities.
Section 125
4.5.2.1 Functional Design
The sizing and layout of ductwork to provide desired air distribution, ventilation rates, transport
velocities, and other functional requirements of the ventilation system are covered by the
standard Z9.2-2018, Fundamentals Governing the Design and Operation of Local Exhaust
Ventilation (LEV) Systems, published by ASHRAE, ACGIH, and ANSI. The least expensive first-cost
duct layout may not be the most economical when the total annual cost of operating the
DOE-HDBK-1169-2022
175
system is considered. Short-radius elbows and other shortcuts in ductwork may seriously
increase system resistance, which could require, for example, the use of a larger fan and/or fan
motor with resulting higher operating costs, or conversely, they could make it impossible for
the system, as installed, to operate at the desired level of performance.
The physical layout of ductwork in a building is often compromised to conform to the confines
of a building structure or design. This may be unavoidable when installing new ducts in an
existing building. In new construction, consideration should be given to providing adequate
space and optimizing the duct layout configuration in the earliest phases of building layout,
long before the building design has been finalized. Adequate access to filter housings, fans,
dampers, and other components is vital to maintainability and testability. Allowance of
adequate space is necessary to achieve well-designed elbows, transitions, and fan inlets.
4.5.2.2 Mechanical Design
The mechanical design of the ventilation system is influenced by the size and quantities of
ductwork, construction materials, coatings used for protection against corrosion, construction
methods (seams, joints), air-tightness requirements, erection sequence (including consideration
of space limitations, post-erection cleaning requirements), and the number and type of field
connections and supports (hangers, anchors) required. Consideration should be given to future
modification, dismantling, and disposal of contaminated ductwork, particularly in the design of
systems for DOE facilities, nuclear power plants, laboratories, experimental facilities, and other
operations where change-out of the ductwork or removal for maintenance can be expected.
Provision for adding on or changing ductwork is a consideration that is often overlooked in
initial design.
Where space permits, a round duct is generally preferred to a rectangular duct because it is
stronger (particularly under negative or collapsing pressure); is more economical for the high-
pressure construction often required for nuclear applications; provides more uniform airflow;
and is easier to join and seal than a rectangular duct. The principal disadvantages of round duct
are that it makes less efficient use of building space, and it is sometimes difficult to make
satisfactory branch connections. Specific requirements for the performance, design, structural
load combinations, construction, inspection, and shop and field fabrication acceptance testing
for ductwork, ductwork accessories, and ductwork supports can be found in ASME AG-1,
Sections SA and TA.
It is sometimes assumed that all leakage in negative pressure ductwork will be in-leakage, this is
not necessarily true. In the event of fire or explosion in a contained space (room, enclosure, hot
cell, glovebox, or confinement structure) served by the system, ductwork can become positively
pressured, resulting in out-leakage. Out-leakage can also be caused by a rapidly closing damper
or by dynamic effects (in a poorly laid-out system) under normal operating conditions.
Section 126
Under system shutdown conditions or during maintenance, the possibility of out-leakage from
normally negative-pressure ductwork also exists. The engineer should consider these
possibilities in the design and specification of permissible leak rates for negative-pressure
portions of systems.
DOE-HDBK-1169-2022
176
Ducts should be sized for the transport velocities needed to convey all particulate contaminants
without settling. Recommended transport velocities are given in Section 5 of Industrial
Ventilation. Ducts for most nuclear exhaust and post-accident air cleanup systems should be
sized for a minimum duct velocity of 2,500 feet per minute (fpm). ASME AG-1, Section SA,
contains requirements for ductwork construction standards. Article SA-4000 contains specific
details for the design requirements and methods for calculating ductwork specifications and
acceptance criteria. SMACNA and ACGIH provide guidance for duct fittings. Pressure loss due
to duct fittings is a design consideration and can be determined by laboratory testing. A
uniform velocity profile is important to maintain and can be established by using straight duct 3
to 10 diameters in length both upstream and downstream of the duct fitting in the laboratory.
If fittings are closely spaced, the total pressure loss will be higher than the sum of the losses of
the individual fittings, due to the nonuniform velocity entering the fittings combined with the
loss of any static pressure that may be regained due to the preceding fitting.
For ducts that are fabricated by welding, a minimum of No. 16 U.S. gauge sheet metal is
recommended because of the difficulty of making reliable welds in thinner material. Because a
nuclear facility may contain spaces of widely differing potential hazard levels, the type of duct
construction required may vary from one part of the plant to another. The following questions,
as a minimum, should be answered to establish the type of duct construction needed for a
particular application.
• Is the system nuclear safety related?
• If the system is nuclear safety related, is the level of radiation that exists in the duct, or
the level that could exist in the duct in the event of a system upset, low, intermediate, or
high?
• Should the air cleaning system remain operable in the event of a system upset (power
outage, accident, malfunction) or can it be shut down?
• Where will the ductwork be located in relation to: (1) the contained space served by the
system, and (2) the occupied spaces of the building?21
• Is the system once-through or recirculating?
• Is it a safety-related feature system that is intended to mitigate the consequences of an
accident?
• What are the environmental considerations (e.g., pressure, temperature, corrosion)?
Depending on the answers to these questions, the duct should be constructed to conform to
one of the several grades outlined in Table 4.13. Recommended construction requirements are
categorized as described below.
21 Building spaces that are not normally occupied but are occasionally entered for repair or service of equipment,
are considered “occupied.”
DOE-HDBK-1169-2022
177
Level 1. In accordance with SMACNA’s “HVAC – Systems-Duct Design,” (with the exceptions
that button-punch and snap-lock seam and joint construction are not permitted), these
constructions are considered unsuitable even for low-pressure construction. Companion-angle
or bolted (or screwed) standing-seam transverse joints are recommended. Standing edges of
seams or joints and reinforcement should be on the outside of the duct (Figure 4.75). Use of
Level 1 ductwork is limited to systems serving administrative areas and other non-safety-
related applications in which maximum static pressure does not exceed 2 in. wg.
Section 127
Level 2. In accordance with SMACNA’s “HVAC Systems-Duct Design,” the use of Level 2
ductwork is limited to systems serving administrative areas, as well as Secondary and Tertiary
Confinement Zones in which the radiotoxicity of materials that are handled or could be
released to the ductwork does not exceed hazard class 2 (see Tables 3.3 through 3.5), and in
which negative pressure does not exceed 10 in. wg. The following exceptions apply: (1) button-
punch and snap-lock construction are not permitted; (2) only bolted flanged joints, companion-
angle flanged joints, welded-flanged joints, or welded joints are permitted for transverse
connections; (3) tie rods and cross-braking are not permitted on negative-pressure ducts; (4)
standing edges and reinforcement of seams and joints should be on the outside of ducts only;
(5) sheet-metal thickness and reinforcement of negative-pressure ducts should be in
accordance with ASME AG-1, Section SA-4000, and (6) radiation-resistant sealants (e.g., silicone
room-temperature vulcanizing) are used as required in the makeup of nonwelded seams and in
penetrations of safety-related ductwork.
DOE-HDBK-1169-2022
178
Table 4.13: Guide for Selecting Recommended Duct Construction Levels for Various Applications in Nuclear Facilities
Contamination Level
and/or Function b
Operating
Mode c
System Type, Duct Location
Outside Contained Space, All
Systems, Duct Located in–
Zo n e I
H VAC, d Supply, e
R e c i r c u l a ti n g
Portion within
Contained Space Zo n e IV Zo n e III Zo n e II
None, supply, HVAC A 1 1 2 2 2
B 1 1 1 1 1
Low (class 4) A 3 2 2 2 2
B 1 1 2 2 1
Moderate (class 3) A 4 3 2 2 2
B 4 2 2 2 1
High (class 2) A 4 4 4 4 2
B 4 4 4 4 2
Very high (class 1) A 4 4 4 4 2
B 4 4 4 4 2
Process off-gas A 5 5 5 4 2
B 5 5 4 4 2
Controlled atmosphere I A 5 5 5 5 5
B 5 5 5 5 5
a Duct construction level: 1, SMACNA low velocity; 2, SMACNA, high velocity; 3, SMACNA high velocity; 4, welded; 5, pipe or welded duct, zero leak.
b Contamination levels from Tables 2.3 for classes 2, 3, and 4.
c Operating mode: (A) system to operate following upset or accident; (B) system shutdown in event of upset or accident.
d HVAC, building enclosure zones from Section 2.2.9.
e Contained space: The building area or enclosure served by the system.
f Inert gas, desiccated air, or other controlled medium.
DOE-HDBK-1169-2022
179
Figure 4.75: Leakage Class 1 Duct Seams
Level 3. This is the same as Level 2, with the exception that: (1) transverse joints are required to
have a full-flanged face width and use 1/4-in.-thick gaskets made of ASTM D1056 grade 2C2 or
2C3 cellular neoprene; grade 2C3 or 2C4, 30 to 40 durometer, Shore-A, solid neoprene; or an
equivalent silicone elastomer with interlocking notched corners; and (2) nonwelded
longitudinal seams, transverse joints, or the entire exterior may have hard-cast treatment
(polyvinyl acetate and gypsum tape system) or comparable fire-resistant, corrosion-resistant,
radiation-resistant, non-peeling, leak-tight treatment.
Level 4. This level requires all-welded construction with sufficient mechanical transverse joints
to facilitate coating (painting), erection, and future modification and/or dismantling.
Mechanical transverse joints should conform to Figure 4.76. For sheet-metal thickness and
reinforcement, see ASME AG-1, Section SA. Specific guidance is provided in nonmandatory
Appendix SA-C, Section C-1300.
Section 128
Level 5. Level 5 ductwork meets requirements for leak-tightness as determined in ASME AG-1,
Section SA, Nonmandatory Appendix SA-B or the requirements of the American National
Standard for Pressure Piping, ASME B31.1, or the ASME Boiler and Pressure Vessel Code.
Methodologies to calculate leak tightness are provided in ASME AG-1 Section SA. Table 4.14
specifies the recommended leakage criteria for each of the duct classes defined in Table 4.13.
See Figures 4.77 and 4.78 for examples of seams, joints, gaskets, and sealing of companion
angle joint corners.
DOE-HDBK-1169-2022
180
Table 4.14: Recommended Maximum Permissible
Duct Leak Rates a at 2 in. wg Negative (by methods of ASME N510)
Duct Class M a x i m u m P e rm i s si b le L e a k R a te
Level 1 5 percent of system airflow per minute
Level 2 1 percent of system airflow per minute
Level 3 0.2 percent of volume per minute b
Level 4 0.1 percent of volume per minute b
Level 5 Zero detectable leak at any test pressure up to 20 in. wg
Recirculating Leak test not required if totally within contained space served by air cleaning system
a Maximum permissible leak rate at pressure greater than 2 in. wg is found from the equation.
Lp× L2 √ (P ' / 2)
wh e re
Lp = permissible leak at higher
pressure,
L2 = permissible leak at 2 in.wg from
table,
P' = higher pressure.
b Based on volume of portion of system under test.
Figure 4.76: Acceptable Transverse Joints
DOE-HDBK-1169-2022
181
Figure 4.77: Acceptable Formed Flange
Figure 4.78: Control Dampers
4.5.2.3 Engineering Analysis
When sheet-metal thickness and reinforcements are established from engineering analysis, a
design pressure of at least 1.25 times the normal operating pressure is necessary for level 1, 2,
and 3 construction. A design pressure of 1.5 times the maximum negative pressure that can
exist in the particular run of duct, under the most adverse conditions to which it can be
subjected under any conceivable conditions, including the DBA and safe shutdown earthquake,
is recommended. The maximum negative pressure is generally the fan shutoff pressure. In the
engineering analysis, the following loadings should be considered as applicable to the particular
system under consideration:
1. DP across the duct wall, as affected by maximum internal and external pressures that could
prevail during testing and under normal and abnormal operating conditions, and any increase
or decrease in the pressure due to inadvertent closure of a damper or plugging of an internal
component. For ductwork located within the containment vessel of a reactor, the external
DOE-HDBK-1169-2022
182
pressure under DBA conditions, due to the lag of pressure rise within the ductwork during
the pressure transient in the containment vessel, should also be considered (such
overpressures may be alleviated through the use of pressure-relief dampers that discharge
to the containment space).
2. Effects of extreme natural phenomena on safety class-ductwork.
3. Thermal expansion.
4. Weight of the ductwork, including all attachments.
5. Weight of personnel walking on large ductwork only. Where this situation is likely to occur,
duct sections with exposed top surfaces should be capable of supporting a 250-pound weight
concentrated midway between the hangers or reinforcement, without permanent
deformation. The out-of-roundness produced by such loading could lead to a sudden collapse
of round duct when operating under negative pressure.
Section 129
A maximum allowable stress of 0.7 times the elastic limit is recommended for the design of
ductwork maximum deflections under normal operating conditions and should be:
Rectangular duct: 0.125 inch per foot of maximum unsupported panel span in the direction of
airflow, but not greater than 0.75 inches. Defection of reinforcement -0.125 inch per foot of
span, but not more than 0.75 inches across total span.
Round duct: 0.025 inch per foot of diameter, but not more than 0.5 inch at any point.
4.5.2.4 Engineered Ductwork
When sheet metal or piping thicknesses and reinforcement are established from analysis other
than as required by ASME AG-1 for safety systems and nuclear applications, SMACNA standards
for commercial grade applications, or other referenced documents, the design should be in
accordance with the criterion found in ASME AG-1, Sections AA and SA. In the engineering
analysis, the following are examples of loads that should be considered potentially applicable to
the system under consideration:
• Additional Dynamic Loads. These loads result from system excitation caused by structural
motion such as relief valve actuation and hydrodynamic loads due to DBAs.
• Constraint of Free End Displacement Loads. These loads are caused by the constraint of free-
end displacement and are caused by thermal or other displacements.
• Dead Weight. These loads are the weight of equipment and ductwork, including supports,
stiffeners, insulation, internally mounted components, externally mounted components and
accessories, and any contained fluids.
• Design Pressure Differential. These loads are dynamic pressures caused by the DBAs, and
intermediate or small break accidents.
• Design Wind Speed. These loads are produced by design extreme straight-line winds,
hurricanes, tornadoes, or other abnormal, infrequently occurring meteorological conditions.
• External Loads. These are applied loads caused by piping, accessories, or other equipment.
DOE-HDBK-1169-2022
183
• Fluid Momentum Loads. These are loads other than those previously listed, such as the
momentum and pressure loads caused by fluid flow.
- Live Load (L). Such loads occur during construction and maintenance and other loads
due to snow, ponded water, and ice.
- Normal Loads (N). These loads include normal operating pressure differential, system
operating pressure transients, dead weight, external loads, and inertia loads.
- Normal Operating Pressure Differential. This is the maximum positive or negative
pressure differential that may occur during normal system operation, including startup
and testing. These include the pressures resulting from normal airflow and damper or
valve closure.
- Seismic Load. These loads result from the operating basis earthquake or the safe
shutdown earthquake (SSE). These seismic forces are applied in the direction that
produces the worst-case stresses and deflections.
- System Operating Pressure Transient. These overpressure transient loads are caused
by events such as rapid damper or valve closure, rapid plenum or housing door closure,
or other loads of this type that result in a short duration pressure differential (spike).
Additional information concerning the structural design and supports for ductwork and
supports can be found in ASME AG-1, Section AA.
4.5.2.5 Materials of Construction
Section 130
Ductwork may be constructed from painted or coated carbon steel, galvanized steel, aluminum,
stainless steel, or any combination of these materials as required to resist corrosion in the
service environment. Glass-fiber reinforced plastic (GFRP) and epoxy ducts have been used in
corrosive environments where fire and safety requirements permit, and may be less expensive
than stainless steel, lined carbon steel, or epoxy- or vinyl-coated carbon steel. Although the
GFRP duct has been approved by the NFPA and UL for commercial and industrial use, even
high-temperature resins will soften under brief exposure to temperatures of 350 to 450 o F.
Softening of the GFRP duct can lead to rapid collapse or distortion, followed by loss of air
cleaning function. GFRP and other plastic ductwork should not be used for Level 3, 4, or 5
construction and should be used with caution for Levels 1 and 2.
4.5.2.6 Paints and Protective Coatings
Coating and paint criteria for ductwork are required to be consistent with the corrosion that
can be expected in the particular application and with the size of the duct. Corrosion- and
radiation-resistant paints and coatings should, as a minimum, meet the requirements of ASME
AG-1, and ASTM D5144, Standard Guide for Use of Protective Coating Standards in Nuclear
Power Plants. Unless special spray heads are used, spray coating of the interior of ducts smaller
than 12 inches in diameter is often unreliable because it is difficult to obtain satisfactory
coating and to inspect for defects. The interior of a duct sized 8 inches and smaller cannot be
satisfactorily brush-painted; therefore, dip coating is recommended. Ducts to be brush-painted
should be no longer than 5 or 6 feet to ensure proper coverage.
DOE-HDBK-1169-2022
184
When special coatings such as high-build vinyls and epoxies are specified, the designer should
keep in mind that difficulties in surface preparation, application, and inspection may increase
the cost of coated carbon steel to the point that stainless or galvanized steel may be more
economical. In addition, stainless or galvanized steel may provide better protection. Note that
high-build coatings and paints can be damaged during handling and shipping (as well as during
construction, maintenance, repair, and testing/surveillance). Corrosion can begin under such
damaged areas without the user’s knowledge. Painted and coated ductwork should be
inspected carefully during the painting (coating) operation, as well as on receipt. Galvanized
coatings and plates should also be carefully inspected, particularly on sheared edges and welds.
4.5.2.7 Supports
Non-safety class ductwork can be hung, supported, and anchored in accordance with the
recommendations of Chapter 5 of the SMACNA’s HVAC—Duct Design, with the following
exception: anchors and attachments which rely on an interference-fit between, or deformation
of, the base material (concrete roof deck, beam) and the attachment device (as is the case for
power-actuated drive bolts and studs and for concrete anchors) should not be used for safety-
related ductwork. Support requirements for safety class ducts and other ductwork that should
remain in place in the event of an earthquake or major accident should be established by
modeling or engineering analysis. Such analysis should be based on the inputs (forces,
accelerations) to the building element to which the duct is fastened or from which it is hung
(floor, wall, roof deck) that will be produced by the DBA or SSE, or both. Non-Engineered
Safeguard Feature ductwork located above or adjacent to other safety class equipment of the
facility, which could damage such equipment if it fell, is also subject to this restriction.
Section 131
4.5.2.8 Thermal Insulation and Acoustic Considerations
Acoustic linings and silencers are not permitted in safety-related ducts or ducts which carry, or
may carry, moisture. Acoustic treatment, if required, should be attached to the exterior of the
duct.
Thermal insulation, acoustic linings, and duct silencers are not permitted in ducts that carry or
may carry moisture, corrosive fumes, or radioactive air or gas. Thermal insulation and acoustic
treatment, if required, should be attached to the exterior of the duct and secured in such a
manner that it cannot fall off during applicable DBAs.
4.5.2.9 Ductwork Leakage
The leaktightness of ductwork is extremely important, particularly in systems that carry or
could potentially carry radioactive material. Duct leakage wastes power and thermal energy
(the energy required to heat, cool, or dehumidify air), causes noise, prevents correct airflow to
outlets from inlets, makes system balancing and temperature and humidity control difficult,
and produces dirt collections and radioactive contamination at leakage sites. Guidance on
ductwork leakage is defined in ASME AG-1 Non-Mandatory Appendix SA-B.
Even one percent is excessive for systems that carry or could potentially carry intermediate- to
high-level radioactivity. Duct tightness is generally tested by sealing off sections of the system
and individually testing them by either the direct-measurement or pressure decay method of
DOE-HDBK-1169-2022
185
ASME AG-1. With such procedures, a leakage criterion based simply on percentage of airflow
can produce anomalous results. By such a criterion, two duct systems build to the same
construction standards and having the same volume and surface area, but different airflow
could have widely differing permissible leakages. Conversely, if the airflow is the same but the
volumes differ, they could have widely differing permissible leakages. For this reason, a
permissible leakage based on duct volume or a permissible leakage based on the surface area
of the pressure boundary of the section under test is recommended.
Vibration and Flexible Connections
Vibration and pulsation can be produced in an air or gas cleaning installation by turbulence
generated in poorly designed ducts, transitions, dampers, and fan inlets, and by improperly
installed or balanced fans and motors. Apart from discomfort to personnel, excessive vibration
or pulsation can result in eventual mechanical damage to system components when vibrational
forces become high or when acceleration forces (e.g., from an earthquake or tornado) coincide
with the resonant frequencies of those components. Weld cracks in ducts, fan housings, and
component mounting frames may be produced by even low-level local vibration if sustained,
and vibrations or pulsations that produce no apparent short-term effects may cause serious
damage after long duration.
Vibration produces noise that can range from unpleasant to intolerable. An important factor in
preventing excessive vibration and noise is planning at the stage of initial building layout and
space allocation to ensure adequate space is provided for good aerodynamic design of
ductwork and fan connections. Spatial conflicts with the process and with piping, electrical, and
architectural requirements should also be resolved during early design so that the compromises
that are so often made during construction, which often lead to poor duct layout and resulting
noise and vibration, can be avoided. Ducts should be sized to avoid excessive velocities while
maintaining the necessary transport velocities to prevent the settling out of particulate matter
during operation.
Fan vibration can be minimized via vibration isolators and inertial mountings. It should be noted
that use of these devices should be carefully coordinated with the structural designers because
seismic design requirements sometimes prohibit their use. Some structural designers require
hard-mounting of fans where continued operation during and after an earthquake should be
considered.
Section 132
To minimize transmission of vibration from fans, flexible connections between fans and
ductwork may be employed. These should be designed to resist the high static pressures often
incurred in HVAC systems, particularly in those parts of the system under negative pressure,
e.g., near the inlet of large exhaust fans. In addition, consideration should be given to the
leakage and potential failure that can occur with flexible connections. Commercial applications
commonly use heavy-duty canvas. Canvas is not suitable for nuclear facility applications.
Consideration should be given to using at least two layers of a leak-proof material (e.g., rubber
or neoprene). Finally, the ductwork system should be balanced after installation, not only to
ensure the desired airflows and resistances, but also to “tune out” any objectionable noise or
vibration that may be inadvertently introduced during construction.
DOE-HDBK-1169-2022
186
4.5.3 Dampers and Louvers
4.5.3.1 Damper Descriptions
By definition, a damper22 is a device used to control pressure, flow, or flow direction in an air or
gas system. (See ASME N509 and AG-1, Section DA) Different types of dampers can be used,
depending on specific functional requirements. Table 4.15 lists the types of dampers and their
functions, and Table 4.16 lists the damper configurations. Figures 4.79 through 4.81 are
examples of industrial-quality dampers. Selection of the proper damper type and blade
configuration is important to achieve the required damper performance. The type and
configuration of damper can significantly impact pressure drop, leakage rates, and
controllability.
22 For more information on dampers, see reference document ERDA 76-21, pages 118=120.
DOE-HDBK-1169-2022
187
Table 4.15 – Classification of Dampers by Function
Designation Function
Flow control damper A damper that can be continuously modulated to vary or maintain a
given level of airflow in the system in response to a feedback signal
from the system, or from a signal fed to the damper operator via a
manually actuated control or switch.
Pressure control damper A damper that can be continuously modulated to vary or maintain a
given pressure or pressure differential in the air cleaning system or
in a building space served by the system in response to a pressure
signal.
Balancing damper A damper set (usually manually) in a fixed position to establish a
baseline flow or pressure relationship in the air cleaning system or
in building spaces served by the system.
Shutoff damper A damper that can be completely closed to stop airflow through
some portion of the system or opened partially or fully to permit
airflow (the flow control damper may also serve this function).
Isolation damper A high-integrity shutoff damper used to completely isolate a portion
of a system from a contained space, or from the remainder of the
system with a leaktight seal. In the case of confinement isolation,
butterfly valves are used in lieu of dampers.
Back-draft or check
damper
A damper that closes automatically or in response to a signal to
prevent flow reversal.
Pressure-relief damper A damper that is normally closed but will open in response to
overpressure in the system or in the contained space served by the
system to prevent damage to the system.
Fire and smoke damper A damper that interrupts airflow automatically in the event of fire or
smoke so as to restrict the passage of flame or smoke through the
air system, in order to maintain the integrity of the fire-rated
partition or other fire-rated separation.
Section 133
Tornado damper A damper that controls airflow automatically to prevent the
transmission of wind-generated pressure surges.
DOE-HDBK-1169-2022
188
Table 4.16 – Classification of Dampers by Configuration
Designation Configuration
Parallel blade damper A multi-blade damper with blades that rotate in the
same direction (AMCA 500).a
Opposed blade damper A multi-blade damper having adjacent blades that
rotate in opposite directions (AMCA 500).a
Butterfly damper A heavily constructed damper, often a valve, that is
used in piping or duct systems and is usually round in
cross-section and designed for high-pressure service
(25 psi minimum pressure rating), with one centrally
pivoted blade that can be sealed.
Single-blade balanced damper A damper, usually round in cross-section, with one
centrally pivoted blade.
Single-blade unbalanced damper An accurately fabricated, often counterbalanced
damper, usually rectangular in cross-section, with
one eccentrically pivoted or edge-pivoted blade.
Folding blade, wing blade, or check
damper
A damper with two blades pivoted from opposite
sides of a central post that open in the direction of
airflow.
Poppet damper A weight or spring-loaded poppet device that opens
when the pressure differential across it exceeds a
predetermined value.
Slide or gate damper A damper similar to a gate valve, with a single blade
that can be retracted into a housing at the side of
the damper to partially or fully open the damper.
a AMCA 500-D-1998, Laboratory Methods of Testing Dampers for Rating, Air Moving and Conditioning Association,
Arlington Heights, IL, 1998. Also, AMCA 500-L-1999, Laboratory Methods of Testing Louvers for Rating, Air Moving
and Conditioning Association, Arlington Heights, IL., Figures 4.80 through 4.82/5.5 through 5.7.
DOE-HDBK-1169-2022
189
Figure 4.79: Bubbletight Dampers
Figure 4.80: Backdraft Dampers
Figure 4.81: Tornado Dampers
DOE-HDBK-1169-2022
190
The following factors should be considered in the selection or design of dampers for nuclear
applications:
• Damper function.
• Construction type.
• Dimensions and space limitations.
• Pressure drop for open position and across closed damper.
• Normal blade operating position.
• Method of mounting damper.
• Blade orientation relative to damper frame.
• Operator type and power source.
• Seismic requirements.
• Requirements for position indicator.
• Limit switches and other appurtenances.
• Damper configuration.
• Permissible leakage through closed damper.
• Space required for service.
• Airstream environmental parameters (temperature pressure relative humidity).
• Damper orientation in duct.
• Airflow direction and velocity.
• Failure of mode and blade position.
• Maximum closing and opening times.
• Shaft sealing method.
4.5.3.2 Design and Fabrication
In conventional air conditioning and ventilating applications, damper procurement has been
generally accomplished by specifying little more than the manufacturer's make and model
number or “approved equal.” This is inadequate for nuclear and other potentially high-risk
applications. Dampers for nuclear applications should be designed and constructed in
accordance with ASME AG-1, Section DA.
Section 134
Clear, concise specifications should be established for mechanical strength, for leakage rate at
maximum (DBA) operating conditions, and for performance under required operational and
emergency conditions. The operability of linkages should be assured through specification of,
and requirement for, cycling at minimum torque requirements under full load. Static testing of
the closed damper should be required, where applicable, for those to be used in critical
applications to verify strength and leaktightness. All features important to proper operation
should be stipulated in detail, including construction materials, permissible lubricants, bearings,
blade design and edgings (if permitted), indicating and locking quadrants, supports, operator
type and capability, and the accessibility of operators, linkages, blades, and bearings for
maintenance. A checklist of the minimum requirements that should be included in a damper
design specification is given in ASME AG-1, Section DA.
DOE-HDBK-1169-2022
191
4.5.3.3 Structural Design
The structural design of dampers should be in accordance with Sections AA and DA of ASME
AG-1 for the loading combinations and the service levels specified in the design specifications.
The design should be verified by analysis, testing, or a combination of both for those dampers
that should remain functional or retain their structural integrity during a DBE.
4.5.3.4 Design and Construction Considerations
A very important part of damper design is determination of damper torque and sizing and
selection of damper actuator for the maximum torque. Actuator torque should be selected for
a minimum of 1.5 times the damper maximum torque to provide margin and allow for
degradation over the life of the damper. Actuators should be evaluated for damper blade
movement in both directions, at the beginning of blade movement, and while stroking blades
through the full cycle of movement.
The linkage mechanism is required to transmit actuator torque for the blades in order to
achieve required leakage performance. Ganging of more than two damper sections for
operation by one actuator is not recommended because of the potential problems in
transmitting the torque equally to each section and blade. Experience has shown that ganging
multiple damper sections has led to twisting of drive shafts and over-torquing of the blades
closest to the actuator.
Conversely, ganging two or more actuators per damper can also cause operating problems if
the actuators are not synchronized. Some blades may close tighter than others, since not all of
the blades are linked together. Damper actuators should be factory-mounted whenever
possible. Wherever actuators should be installed in the field or removed for maintenance,
manufacturer's installation instructions should identify the necessary amount of retorquing
required to achieve design leakage. The actuator shaft, coupling, and blade shaft should be
“match-marked” for easy installation.
Seals are another important component of damper design. Dampers designed for low leakage
rely heavily on blade and jamb seals to limit leakage. Seals typically are either metal (e.g.,
stainless steel) or elastomer. Design of seals should consider the required life of the damper
assembly to minimize maintenance. For this reason, stainless steel seals are recommended for
low leakage dampers in contaminated airstreams whenever possible (see Section DA of ASME
AG-1). To control frame leakage, either stuffing boxes or frame cover plates are required.
Section 135
4.5.3.5 Damper Operators
Damper operators can be one of three types: pneumatic, electric, or electrohydraulic, as
described below.
Pneumatic. These damper operators are used whenever controls rely primarily on compressed
air (pneumatic) for moving operators or transmitting control signals. Most nuclear facilities only
use pneumatic control systems and operators for nonsafety-related applications, as the control
air is not usually an assured source during DBAs.
Electric. These damper operators are used whenever controls rely primarily on low voltage
electric circuits to transmit control signals and are usually two-position. That is, they are either
DOE-HDBK-1169-2022
192
open or shut and cannot modulate. Most nuclear facilities use electric control systems and
operators for safety-related applications because power can be obtained from the emergency
electric power and control system.
Electrohydraulic. These damper operators are the same as the electric type described above,
except for capacity to modulate. Experience has shown that these operators require significant
maintenance to keep them functional. They use an electric control signal to position a hydraulic
system that, in turn, positions the damper.
4.5.3.6 Limit Switches
Limit switches are usually provided directly on the damper to detect the open and closed
position of the damper blade. The switches are housed in enclosures defined by NEMA 250. The
contact rating should be properly selected for the electrical load. The force required to operate
the limit switches should be considered to properly size the damper actuator.
4.5.3.7 Performance Requirements
The dampers for nuclear air cleaning systems are required to meet the following performance
criteria:
• Seat leakage.
• Frame leakage.
• Pressure drop.
• Closure (or opening) time.
• Fire rating and closure.
Seat and frame leakage is required to meet ASME AG-1, Section DA, for Leakage Class I (low
leakage), II (moderate leakage), III (normal leakage), and IV (applications where leakage is of no
consideration). Leakage class 0 (zero leakage or bubble tight dampers are typically used at
filtration housing inlets and outlets. Seat leakage class should be determined by the engineer
based on radiological and health physics analysis and known or estimated airborne
concentrations within the duct system. Frame leakage is also based on radiological assessments
of the effect of airborne concentrations inside and outside the ductwork, as well as the system
configuration. For further guidance on leak class determination, refer to ASME AG-1 Code,
Section DA.
Pressure drop of the damper has an important impact on proper system operation. Dampers
with high-pressure drop, especially for counterbalanced pressure relief dampers, may restrict
airflow and affect space pressurization. The pressure drop characteristics of dampers as a
function of airflow rate or velocity indicates the ability of each particular type of damper to
control airflow. Preferably, the pressure drop/airflow characteristic should be as close to linear
as possible to achieve controllability. Opposed blade damper pressure drop characteristics
make this type of damper well suited for flow or pressure control compared to parallel blade or
butterfly dampers.
DOE-HDBK-1169-2022
193
Section 136
For fire dampers installed within duct systems where the airflow normally flows continuously
and the damper is expected to isolate portions of the duct system in case of fire, the damper is
required to close under airflow. This requirement has caused difficulties with past damper
construction. Different manufacturers’ dampers react differently based on their particular
design. Some dampers are sensitive to air velocity, such as the shutoff dampers shown in Figure
4.82. Figure 4.83 shows dampers with actuator options. These dampers are more sensitive to
duct pressure upstream of the damper when they are closing.
Figure 4.82: Shutoff Dampers
Figure 4.83: Actuator Options
4.5.3.8 Qualification Testing
Qualification consists of performing prototype or preproduction-model tests to verify the
design, performance, and operational characteristics of the dampers. In the case of the
AMCA-rated dampers, these tests essentially consist of pressure drop and airflow
determinations at various degrees of blade opening. The AMCA rating is generally considered
sufficient evidence that suitable qualification tests have been performed. For dampers not
listed by AMCA, the manufacturer should be required to provide performance data obtained
under conditions equivalent to those used in the AMCA 500-D test standard. One particularly
important piece of information that can be obtained by qualification testing is the resistance of
the fully open damper and the resistance versus blade-position curve from full open to full
DOE-HDBK-1169-2022
194
closed. Resistance should be included in the air cleaning system design calculations in the same
manner as other system resistance. Qualification tests are required to be performed prior to
fabrication and, if possible, prior to award of a contract.
Production units should be subjected to acceptance tests to verify that the units are in good
operating condition and to document their ability to meet performance requirements such as
leakage and closure time. Repetition of other qualification tests to demonstrate operational
characteristics is generally unnecessary and unwarranted. Dampers should be cycled through
the full range at least 10 times, with all accessories attached, to verify the free and correct
operation of all parts and the correct adjustment, positioning, and seating of the blades.
Maximum time for operation of any of the cycles should be not more than the specified cycle
time. Limit switches, if used, should be checked for proper operation. Adjustments should be
made as necessary during the test to correct deficiencies. Shop leakage tests for seat and frame
leakage should be performed when applicable. Seat leakage testing should be performed after
cycle testing is completed. Tests should be performed in accordance with ASME AG-1, Section
DA. Because damper operators are generally furnished to the damper manufacturer as a
purchased item, a test to verify the torque characteristics of the operator is desirable after
installation of the damper in its service position, particularly for control, shutoff, and isolation
dampers for all safety-related dampers.
Fire dampers should be qualified for closure under airflow by testing in accordance with AMCA
500-D for both plenum-mounted and duct-mounted configurations. The damper should close
completely at maximum airflow rate for various sizes of dampers and for maximum static
pressure. Fire and smoke dampers are required to be tested in accordance with UL-555 and UL-
555S, respectively, when dampers are required in fire- or smoke-rated barriers.
Section 137
4.5.3.9 Louvers
The function of louvers is to keep rain, snow, and trash from being drawn into outside air
intakes of air handling systems. They can be either fixed-blade or movable-blade design. The
vast majority of louvers are of the fixed-blade type. If shutoff or modulation of the airstream is
necessary, dampers can be used downstream of the louvers. If operable louvers are used and
shutoff or modulation is required, then an operator is required. Architects usually are consulted
when specifying louvers because the louvers are located on outside walls or roofs and should
blend in with the architectural features of the structure.
It is important to account for the size of the area that the louver blades take up when sizing the
louvers. Blades typically take up 50 percent or more of the free area that affects the velocity of
the air entering the intake. The usual maximum velocity to prevent water and snow
entrainment in the airstream is less than 500 fpm. For louvers on exhaust openings, the velocity
is not usually a primary concern, with the exception that the higher the velocity, the higher the
pressure drop that has to be accounted for in the system pressure drop calculations.
Finally, louvers are required to meet the same structural requirements as the rest of the air
cleaning system. That is, they should meet the seismic loading requirements if they are
required to function during and after a DBA. Louver testing should conform to AMCA 500-L.
DOE-HDBK-1169-2022
195
4.5.4 Fans and Motors
The selection of fans and motors for air treatment systems is a very important part of the
design of the systems. An air cleaning unit may be properly designed and arranged, the duct
system may be nearly leak-free, dampers may be properly constructed, and controls may be
functioning correctly, but if the fan is not sized and selected properly, then the system will not
perform its design function. For example, the system resistance should be correctly calculated,
the effect of parallel or series fans should not result in surging, and the fan should be selected
for the applicable range of airflow and pressure. ASME AG-1, Section BA, contains a list of the
design parameters necessary to properly specify and/or select a fan and motor.
4.5.4.1 Fan Types and Applications
Fan types can be classified as centrifugal, vane-axial, and high-pressure blowers. Centrifugal
fans can be further classified by blade type as airfoil, forward curve, radial, and backward
inclined/backward curved. Vane-axial fans can be classified as either fixed or adjustable pitch.
All fans can be furnished as either direct or belt drive. Note that, for nuclear power plant
applications, fans located inside the confinement are usually direct drive to minimize the
maintenance and adjustments associated with belt drives (because confinement entry is
limited).
High-pressure blowers may be required when airflow rates are low (10,000 cfm or less) and
pressure is high (10 to 15 in. wg). This may dictate a radial-bladed centrifugal fan selection.
Vane-axial fans are typically used in larger built-up systems when the fan is located as part of
the duct system rather than part of the filter housing. Vane--axial fans are best suited for
airflow rates greater than 30,000 cfm and pressures less than 10 in. wg. Whenever possible,
vane-axial fans should be located downstream of filter units because the fan motor is in the
airstream.
Section 138
Fans should be selected such that fan power requirements are non-overloading (the fan brake
horsepower does not increase with increasing airflow) unless provisions are made to prevent
overloading the motor (e.g., airflow control and high limit trip). Radial-bladed and forward-
curved centrifugal fan power increases with increasing airflow.
Belt drives should be used only in areas that are accessible for maintenance during normal and
accident conditions. Multiple belts should be provided so that loss of one belt does not impair
system function. For constant flow systems, variable pitch sheaves should be changed to fixed
pitch sheaves after air balancing. Belt driven fans that should operate during and after dynamic
events (e.g., seismic events) should be qualified for operation by testing.
Fans for general heating, ventilating, and air conditioning (HVAC) duty (e.g., air supply systems
and small exhaust systems), are selected using the guidance for such systems found in sources
such as the ASHRAE HVAC Applications Handbook, and the ASHRAE Systems and Equipment
Handbook. These systems can range in size from a few hundred cfm to over 100,000 cfm and
are usually low-pressure systems (less than 5 in. wg).
DOE-HDBK-1169-2022
196
4.5.4.2 Fan Performance
The previous use of information in the ASHRAE Handbook of Fundamentals covered methods
for designing industrial exhaust systems and balancing branch duct resistance either by utilizing
balancing dampers or by sizing ductwork. For systems handling highly radioactive particulate,
self-balancing is recommended to eliminate particulate accumulation in the duct system. This
recommendation should be considered against the potential for changes to duct runs during
installation. The development of computer aided design tools has replaced the preparation of
design documents such as a total pressure grade line, summarizing the branch and main duct
pressure drop for each fan system. Published guidance by ASHRAE and SMACNA provides
guidance on how to determine system resistance and fan pressure requirements, such as
Chapter 21, “Duct Design,” in the ASHRAE Handbook.
System Effect Factors
Figure 4.84 shows the effects of various inlet conditions on fan performance and the resulting
increase in fan capability (fan static pressure) to compensate for these effects. Too often, these
effects are not considered when calculating fan requirements, with the result that neither the
fan nor the filters can perform to the desired design levels. Outlet connections also affect fan
performance, as indicated in Figure 4.85. Drastic transitions such as elbows should be avoided
directly upstream and downstream of fans. Simply adding an evase (flow diffuser that converts
kinetic energy into pressure energy) downstream of the fan can have significant impacts in terms
of fan static pressure and energy efficiency over time.
DOE-HDBK-1169-2022
197
Figure 4.84: Effect of Fan Inlet on Performance
DOE-HDBK-1169-2022
198
Figure 4.85: Effect of Fan Outlet Connection on Fan Performance
Figure 4.85 illustrates inlet and outlet conditions that will affect fan performance and are
important factors in initial fan selection. System effects are the losses in fan performance that
result in the fan being installed in a less than ideal configuration. These effects should be
considered by the designer to obtain a realistic estimate of fan performance under actual
operating conditions in the field. Publication 201, “Fans and Systems,” contained in the AMCA
Fans and Air Systems Application Manual,” provides information on system effect factors that
should be considered in the design calculations.
Section 139
Figure 4.86 illustrates a deficient fan-system interaction resulting from one or more undesirable
design conditions. It is assumed that pressure losses in the duct system were accurately
estimated (point 1, curve A), and a suitable fan, based on published ratings, was selected for
operation at that point. However, no allowance was made for the effect of the fan connections
on fan performance (the interaction between the fan and the system as designed). To
compensate for the system effect (capacity loss resulting from unfavorable interaction between
the fan and its connections), a system effect factor should be added to the calculated system
pressure losses to determine the actual system characteristic curve. It will then be possible to
select the fan required to produce the required operating characteristics.
Testing to establish the capability of the fan in a nuclear air cleaning system, as originally
installed, is recommended by ASME AG-1, Section TA. Planes of measurement, measurements
DOE-HDBK-1169-2022
199
to be made, average test readings, calculation of test results, and corrections to overcome
deficiencies disclosed by the tests are all covered in detail. It is preferable to apply such system
Figure 4.86: Deficient Fan-System Interaction
effect factors before selection, purchase, and installation of a fan to prevent the incorporation
of unfavorable features into the system design. In applying system effect factors, it should be
recognized that those factors given in the AMCA manual are only guidelines and general
approximations, although many have been obtained from research studies. Fans of different
types and fans of the same type that are made by different manufacturers will not necessarily
interact with the system in the same way. It is necessary, therefore, to apply judgment based
on experience using system effect factors.
Fans play an important role in establishing a well-mixed sampling location so that
representative samples according to ANSI/HPS N31.1-2011 are obtained for qualification, in-
place testing and in-service testing of the fans and ventilation systems.
Fan and System Curves
A major requirement for a fan operating in a high-efficiency air cleaning system is its ability to
perform safely and efficiently over a much larger variation of resistance than more
conventional ventilation systems. This variation of resistance is caused by dust loading of the
HEPA filters and may double from the time of filter installation to the time of filter change or
may increase as much as five times in some systems. The increase in resistance across the HEPA
DOE-HDBK-1169-2022
200
filters is usually the major factor influencing the pressure flow relationships of high- resistance
versus airflow are represented by characteristic curves such as curves A, B, and C of Figure 4.86.
The volume of air that can be delivered by the fan is determined by the intersection of the fan
and system characteristic curves. The flow represented by this point of intersection is the only
flow that can be delivered by the fan under the given operating conditions. In most cases, a fan
with a steeply rising characteristic (curve A, Figure 4.86) is desirable to maintain reasonably
constant airflow in the system over the entire life of the HEPA filters. If a fan with a broad, flat
characteristic is chosen, it will be less capable of delivering the required airflow as the filters
become dust-loaded (curve 1 to curve 2), and either system performance (airflow) or filter life
will have to be sacrificed. Any decrease in filter life will, of course, be accompanied by higher
change frequency and corresponding increases in operating and maintenance costs. If a
pressure-equalizing device (damper) is installed to balance system pressure against filter
pressure drop in order to maintain a constant pressure-airflow relationship in the system, a
penalty in operating (power) costs will result.
Section 140
4.5.4.3 Fan Leakage Flexible Connection Leakage
Vibration created by fans, motors, and drives can be isolated by using flexible connections
between the fan and ductwork on both the fan discharge and suction. Where such connections
are used, a frequent problem has been tearing and pulling-out of the fabric (from which the
flexible connection is made) at the connector clamp and an associated increase in leakage. The
flexible connection design shown in Figure 4.87 can overcome these problems. The fabric
shown consists of two layers of 30-ounce neoprene-impregnated fiberglass cloth, lapped so
that the ends are displaced from one another, and glued. Flexible materials reinforced with
fiberglass or other products are also available. Flexible connections should be periodically
inspected (visually) to ensure the connection is intact (no tears or holes). Eliminating leakage at
the flexible connection is important to the effective operation of the unit. With the fan located
properly with respect to the contamination concentration, the leakage on the suction side
should not impact personnel dose but could impact system effectiveness by reducing the flow
rate of the discharge leakage through the connection at the point of contamination. This could
affect the local derived air concentration (DAC) levels, depending on the relative concentration
between the space and the duct.
Flexible connections should be qualified for the temperature, pressure, relative humidity, and
contaminants that will be encountered. However, since the flexible connections are exposed to
continuous stresses due to airflow turbulence and fan vibration, the flex connections should be
replaced frequently throughout the life of the plant. A maintenance frequency should be
planned based on the results of the periodic surveillance inspections for each specific fan.
DOE-HDBK-1169-2022
201
Figure 4.87: Flexible Connection Design
Shaft Leakage
Fan shaft penetration of fan housings should be designed to minimize leakage. When the fan is
located properly so that leakage does not impose a contamination burden on the space, or the
fan is located in the space supplied by air from the fan, then no special sealing is required.
However, if there is a potential for a significant increase of DAC levels or a significant impact on
airflow rate from the space the air is being induced from, then shaft seals should be installed.
Shaft seals should limit leakage to 0.01 percent of design airflow rate per inch of fan operating
pressure or 0.5 cfm, whichever is greater. The safety analyses should be consulted for allowable
leakage for safety class designs, especially for systems with multiple HEPA filter banks. If the
fans are located downstream of the HEPA banks, or if in a potentially contaminated area,
extremely small levels of fan shaft in-leakage (< 0.001 cfm) may be unacceptable for
maintaining the desired level of removal.
Multiple Fan Installation
Installation of two fans in series is sometimes desirable where a steeply rising pressure-airflow
characteristic is needed. However, caution should be exercised in such a design. In theory, the
combined pressure-volume characteristic of two fans operating in series is obtained by adding
the fan pressures at the same volumetric airflow, as shown in Figure 4.88. Care should be taken
in designing the connection between the fans, because a significant loss of efficiency can occur
in the second-stage fan due to nonuniform airflow into its inlet, particularly if the two fans are
closely coupled. Manufacturers may be able to install two fan wheels in series within a single
housing, which is longer than a single-wheel fan. Fan manufacturers should provide certified
fan performance curves for these multistage fans.
Section 141
For fans installed in series and not in a common plenum, a bypass duct is recommended so that
a failed fan can be isolated from the system for repair and to avoid additional system resistance
due to the failed fan wheel. Two or more fans are often operated in parallel to move large
DOE-HDBK-1169-2022
202
volumes of air, to enhance the control of segmented air cleaning facilities, or to limit the
installed capacity (filters, adsorbers) of any one unit of the air cleaning system. The combined
volume-pressure curve in this case is obtained by adding the volumetric capacity of each fan at
the same pressure (Figure 4.89).
One concern in parallel fan installations is that some fans have a positive slope in their
characteristic curves to the left of the peak pressure point (Figure 4.90). If the fans are
operated in the pressure-volume regime of this positive slope, unstable operation may result.
This is shown by the closed loop to the left of the peak pressure point in Figure 4.90 (this loop is
obtained by plotting all of the possible combinations of flow at each pressure). If the system’s
characteristic curve intersects the fan characteristic in the area of this loop, more than one
point of operation is possible; this may cause one of the fans to handle more of the system
airflow than the other and result in a motor overload. The unbalanced flow conditions tend to
shift rapidly so that the fans intermittently load and unload. The pulsing that results from such
loading and unloading generates noise and vibration and may cause damage to the fans,
motors, and ductwork. In addition, if more than two fans are operated in parallel, the designer
and/or fan manufacturer should review the fan performance curves and system curves for
possible combinations of fans, assuming one or more are out of operation for maintenance,
Figure 4.89: Typical Characteristic Curve of Two Fans Operating in Series
DOE-HDBK-1169-2022
203
Figure 4.90: Parallel Fan Operation
filter change-out, or repair. Fans should be selected for stable flow throughout the service
conditions (clean to dirty filter pressure drop) and combinations of fans.
Mounting
Mounting of the fan and motor on a common base designed for isolation of vibration is
recommended. The fan and motor are mounted on a concrete base that acts as an inertial pad
to limit the amplitude of vibration and to dissipate vibrational energy. The pad is mounted on
spring isolators, which will provide a high degree (99 percent or more) of vibrational damping.
For some systems, positive amplitude limiters may be required to restrain the base from
excessive movement under extreme conditions (such as the accelerations imposed by a DBE).
Some designers require hard-mounting of fans where seismic requirements and continued
operation during and after an earthquake should be considered. Infiltration may be reduced by
designing a tighter building structure. Careful balancing of the fan shaft and impeller to minimize
vibrations that cannot be isolated via installation design is particularly important in this latter
design.
DOE-HDBK-1169-2022
204
Building Pressure Effects
Sizing of supply and exhaust fans should recognize the interaction of these fans with each other
in order for nuclear air-cleaning systems to maintain proper space pressure relative to
surrounding areas.
Section 142
In push-pull systems (systems containing both supply and exhaust fans that operate at the
same time), the space pressure depends on the relative capacity of the fans. If supply flow
exceeds exhaust, the space is positive. If exhaust exceeds supply, the space pressure will be
negative. When space pressure is required to be negative, the exhaust fan capacity should
compensate for infiltration, pressure surges, high wind effects (pressure variations in the
building and ductwork due to variable wind conditions exterior to the building), as well as
temperature variations between supply and exhaust air, to eliminate any possibility of over
pressurizing the building via the supply fans. The pressure effects of other building ventilation
systems serving adjacent spaces should also be considered.
Improper fan operation can be avoided by carefully evaluating system pressure drops and
interactions under all predictable operating conditions, and by specifying the type and size of
fan that matches the demands of the duct system as installed. Control should be exercised over
the installation of ducts and fans to prevent field compromises that can reduce the ability of the
system to perform as intended.
4.5.4.4 Fan Construction
AMCA has developed standards for fan construction. In general, these standards are applicable
to the construction of fans for nuclear air cleaning systems. In addition, fans for nuclear air
cleaning systems should be constructed in accordance with ASME AG-1, Section BA, which
defines additional specific features that are required for nuclear applications.
4.5.4.5 Qualification and Testing
Fans for nuclear air cleaning systems should be qualified, rated, and tested for the following
factors:
• Performance.
• Structural capability.
• Vibration.
• Sound.
• Leakage.
• Environmental conditions.
ASME AG-1 Code, Section BA, provides inspection and testing requirements for fans and
motors. AMCA 210 defines the methods for testing fans for rating purposes. ASME AG-1 Section
TA provides field testing requirements, and ASME/ANSI N511 provides guidance for in-service
testing. Environmental qualification and testing of electrical components should be in
accordance with IEEE-323, Standard for Qualifying Class 1E Equipment for Nuclear Power
Generating Stations. Standard motor tests that include “First Unit of a Design” and “Routine
Motor Tests” (all motors) should be performed in accordance with IEEE 112 and ASME AG-1,
DOE-HDBK-1169-2022
205
Section BA. Documentation of test results should be prepared in accordance with the above
references.
4.5.4.6 Fan Reliability and Maintenance
Operational reliability is an important consideration in selecting fans for nuclear applications.
Even when the system is planned for part-time or intermittent operation, continuous operation
may be required after the system goes into service. This should be a consideration in the design
and procurement process.
Adequate access for maintenance and service is imperative, and fans installed above floor level
should have sufficient clear space around and below for personnel to get to them with the aid
of ladders and/or scaffolding. Permanently installed ladders and galleries are recommended to
ensure ease of access for maintenance and repair. Procedures should be developed for
periodic, preventative maintenance based on the fan manufacturer’s recommendations and
actual field operational experience. These procedures are critical for the reliability of the fan
and its operational readiness in the event of a DBA.
Section 143
4.5.4.7 Special Duty Considerations Temperature, Pressure, and Humidity
Fans are constant-volume machines whose airflow rate can be impacted by variables such as
temperature, pressure, and relative humidity because they affect the mass flow rate of air
being moved. It is necessary to identify and specify these variables for normal and abnormal
conditions so the fan manufacturer can make proper fan and drive selections. In addition,
temperature, pressure, and humidity can affect fan components such as the bearings and
bearing lubricant. Therefore, the fan manufacturer should know these properties to make
proper material selections for fan components.
Material Moving
Fans that are required to move particulate matter require identification and specification of the
properties of the airstream. Particulates can be abrasive, require high transport velocities, or be
composed of corrosive, explosive chemicals. These materials can affect the fan wheel, casing,
shaft, bearings, bearing lubricant, and the fan manufacturer should know these properties to
make the proper material selections for the fan components.
Contaminated Air Moving
Fans that are required to move contaminated air (primarily radioactive particles in nuclear
facilities) also need to have these properties identified and specified. Radioactive contaminants
can affect some of the materials used in fan construction (primarily bearing lubricants) or in
ductwork components that are attached to the fan (flexible connections and gaskets). Another
primary concern is contaminated leakage into or out of the fan. The fan manufacturer should
know the properties of the contaminated air so that proper material selections and leakage
provisions can be provided.
DOE-HDBK-1169-2022
206
4.5.5 Air Intakes and Stacks
4.5.5.1 Locating Intakes and Stacks
The design and location of exhaust stacks and air intakes have an important bearing on system
performance. If air intakes are too close to the ground, blowing sand, dust, grass clippings, and
other particulate matter may be drawn into the building, plugging the supply-air filters and/or
reducing their life. Exhaust fumes from vehicles passing nearby or standing close to the building
may also be drawn into the building. Intakes should be sited to protect them from snow, ice,
and freezing rain during the winter, and baffles or louvers should be provided to give protection
from driving rain and to minimize the effect of wind. Architectural louvers should be designed
and tested in accordance with AMCA 500-L for pressure drop and water penetration. Wind
pressure can have an appreciable effect on flow rates in a low-head ventilation system and can
cause pulsations that may disrupt or reverse differential pressure conditions between the zones
of the building.
Average wind direction and weather conditions that are likely to cause stack discharges to areas
close to the ground (known as looping and fumigation) should be analyzed when establishing
the location of stacks and intakes. This analysis is necessary to ensure that stack effluents
cannot be drawn back into the building or into an adjacent building. Intakes should be located
upwind of stacks (based on the prevailing wind for the site). Intakes downwind of shipping
docks may be prone to drawing vehicle exhaust fumes into the building. Intakes located close to
a roof or in a roof penthouse may have the same problems as those located too close to the
ground due to aerodynamic building downwash.
Section 144
Considerable guidance on the location of intakes and exhaust stacks is given in Chapter 16
(“Airflow Around Buildings”) of the 2017 ASHRAE Handbook of Fundamentals. The flow around
adjacent structures is complex and is affected not only by a building’s dimensions, but also by
the topography surrounding a building. Additional guidance can be found in Section 6.8.3 of
DOE-HDBK-1224-2018, Aerodynamic Effects of Buildings. Proper consideration should be given
to wind (speed/direction) and stack flow patterns for a single rectangular building. Air intakes
located within the recirculation zone or contaminated region will re-entrain the effluent.
Computational fluid dynamics models could be developed to determine flow patterns around
the building.
Intakes located on the sides of buildings may also be affected by the pressure (positive or
negative) at those points. Ventilation systems should be designed and sized to account for this
pressure, especially if a negative pressure is possible for a supply system or a positive pressure
may exist for an exhaust system. A static pressure at least equivalent to the surface pressure
associated with the design wind velocity for the specific location should be included in system
pressure calculations. Pressure controls also should be used to regulate flow fluctuations
occurring due to the wind velocity and surface pressure.
In northern climates, intakes should be designed to minimize snow entrainment. Even at low
velocity through louvers, snowflakes can clog medium efficiency filters located close to the
louvers. In addition, hoarfrost can form on operable louvers and prevent their operation.
Hoarfrost can also block louver screens. To prevent such potential problems, it may be
DOE-HDBK-1169-2022
207
advisable to heat the areas adjacent to the louvers. If snow is blown or otherwise induced into
the ventilation system and no provision is made for settling or dropping out snow or ice
particles, the filters can become clogged.
The following factors should be considered when locating stacks:
• High stack velocity is a poor substitute for proper stack location. A stack velocity to wind
velocity ratio of 4:1 is required to discharge effluent out of the recirculation cavity
boundary for a stack located flush to a roof.
• If an enclosure is needed around the stack, the stack should extend above the building
zone of the enclosure and should not be flush to the enclosure.
• A circular stack shape is recommended. Nozzles may be used at the tip of the stack to
increase exit velocity.
• Stack caps that deflect effluent downward are not recommended. High exit velocities
will prevent rain from entering. Some drainage provision is recommended instead of
rain caps.
• For both stacks and intakes, provision should be made for drainage of water or melted
snow that may be induced into the system.
• Stacks should be located where they cannot damage the facility they serve or other
important nearby structures.
4.5.5.2 Sizing Intakes and Stacks
Air intakes should be sized to minimize pressure drop and maintain air velocity through the free
area below the velocity at which water droplets may be entrained (usually less than 500 fpm).
Manufacturers should be requested to provide pressure drop and water penetration test
results for louvers tested in accordance with AMCA 500-L.
Section 145
Sizing of stacks is even more important to prevent re-entrainment of the release due to the
aerodynamic effects of the facility and ensure proper dispersion. Additional guidance is
contained in Section 6.8.3 of DOE-HDBK-1224-2018, Hazard and Accident Analysis Handbook.
Dispersion calculations should be performed to determine whether elevated, ground-level or
mixed mode effluent release is required to maintain offsite personnel exposures within the
plant environmental permit, Technical Safety Requirements (TSR), and applicable Federal,
State, and local regulations. The term “elevated release” typically refers to stacks that are
situated well above the tallest building. Ground level releases are typically exhaust points
located on the building wall or roof. “Mixed mode” refers to stacks that are marginally higher
than the tallest building. Additional guidance on mixed mode releases can be found in USNRC
Regulatory Guide 1.111, Methods for Estimating Atmospheric Transport and Dispersion of
Gaseous Effluents in Routine Releases from Light-Water-Cooled Reactors. When calculating
atmospheric pressure change and missiles from a hurricane and tornado, and other missile
barrier needs, the need to prevent access by unauthorized personnel should be considered.
(See DOE-STD-1020-2016 and DOE-HDBK-1220-2017.)
DOE-HDBK-1169-2022
208
The exit velocity of the stack should be at least 1.5 times the wind velocity to minimize
downwash. Stacks may need to be partitioned or sectioned if multiple systems discharge into
the stack and individual system operations do not occur at the same time or frequency. A
minimum stack exit velocity of 3,000 fpm is recommended to prevent downwash from winds up
to 22 mph, to keep rain out, and to prevent condensation from draining down the stack. If
condensation may be corrosive, a stack velocity of 1,000 fpm is recommended with a drain at
the bottom to remove condensation and a nozzle at the top of the stack to maintain high exit
velocity. However, high stack exit velocity does not remove the need for a stack meeting GEP
height requirements. The structural design of stacks for wind gusts up to 115 mph should be
considered based on the climatology of the particular site as identified in ASCE 7.
4.5.5.3 Structural Design Aspects
Louvers designed for conventional ventilation and air conditioning applications are usually
acceptable for use as air intakes for nuclear air cleaning systems. If louvers are required to
remain in place following DBAs (such as earthquake or tornado), they should be designed in
accordance with the requirements of ASME AG-1, Section DA.
Historically, stacks were designed in accordance with the requirements of ASME AG-1, Section
AA, and ASME STS-1-2000, Steel Stacks. Most stacks today are lined Fiberglass-Reinforced
Plastic (FRP) stacks. Guidance can be found in ASCE/SEI 52-10, Design of Fiberglass-Reinforced
Plastic (FRP) stacks. Loading due to design basis winds, tornadoes, hurricanes, and other
abnormal meteorological conditions should be included in the structural analysis, as well as
dynamic loads due to seismic excitation whenever applicable. Even if not required to remain
functional, stacks should be designed so they do not collapse and cause unacceptable damage
to surrounding structures, systems, or components. Stiffeners for stacks should be located on
the outside to avoid providing ledges for potential “buildup” of radioactive material, even
though the air has been “cleaned.” The structural design of stacks should be qualified by
analysis in accordance with AG-1, Section AA. Care should also be exercised in the structural
design so that stacks do not “crimp” or bend and cut off the effluent flow if they are subject to
a strike by wind-generated missiles.
Section 146
Openings in nuclear-safety-related structures for either air intakes or exhaust stacks should be
protected from the effects of high wind or tornado missiles if such a missile could damage a
nuclear-safety-related component and prevent it from functioning. Missile protection typically
involves utilizing staggered building wall structures or a lattice of steel bars to prevent a
straight-through missile path. Sufficient space should be allocated for these intake structures.
Free-area reduction caused by using staggered walls or steel bars in the openings should be
considered when sizing the openings, particularly intakes, so that velocity requirements are not
exceeded.
For metal exhaust ducts, see the American Conference of Governmental Hygienists, Industrial
Ventilation, A Manual of Recommended Practice (2013), Chapter 5, “Exhaust System Design
Procedure.”
DOE-HDBK-1169-2022
209
4.5.6 Instrumentation and Control
4.5.6.1 Codes and Standards Requirements
Instrumentation and control systems, components, and equipment should meet the
requirements of ASME AG-1, Section IA. In addition, they should be qualified according to the
requirements of IEEE 336, 383, and 384.
4.5.6.2 Functional Requirements
The function of the instrumentation and control systems associated with nuclear ventilation
and nuclear air cleaning systems is to control the environment of the space served within the
limits of the controlled variable and to monitor the performance of the system and its
components to ensure safe, efficient, reliable operation. The design of instrumentation and
control systems should consider the consequences of single failure as well as environmental
conditions.
The primary variables by which nuclear air cleaning systems are controlled are temperature,
airflow rate, and pressure. Temperature, pressure, flow, and radioactivity levels are monitored
to indicate system performance and alarm abnormal conditions.
Effluent air cleaning systems typically are controlled to maintain a minimum negative pressure
or building pressure around a preselected flow rate. Habitability systems are usually controlled
to maintain a constant airflow rate that is selected to maintain a positive pressure in the space
served. Temperature is also usually controlled for habitability systems.
Instrumentation should be provided to monitor the radioactivity levels of effluent discharged
into the atmosphere. Each discharge point that could potentially have concentrations
exceeding TSR limits should be monitored. Monitoring of emission airflow rates and
concentrations is also required. Values in excess of established high limits should be alarmed in
the control room. In addition, airflow rates and radioactivity levels for habitability systems
should be monitored and alarmed.
The best indicator of system performance for continually operating systems is the level of
radioactivity. Monitoring flow rates and concentrations both before and after air cleaning units
could indicate trends in filter degradation. The controls recommended in ASME AG-1, Section
IA, should be provided to assist the operators in monitoring system performance.
4.5.6.3 Airflow Control
Airflow control is one of the most important control variables for nuclear air cleaning systems.
Nuclear air cleaning system pressure could vary by as much as 25 to 30 percent, depending on
system components, clean filter pressure drop, and the change-out pressure drop. It is
recommended that airflow rates be maintained within + 10 percent of design to maintain
proper fan performance. The airflow rate is usually required to be automatically controlled by:
(1) discharge or inlet control dampers, (2) variable inlet vanes, or (3) variable speed control.
Section 147
To control the airflow rate, the flow first should be accurately measured. Flow should be
measured where the air velocity profile is uniform. AMCA 210 and 203, as well as ACGIH
Industrial Ventilation provide guidance on the proper location of airflow sensing devices.
DOE-HDBK-1169-2022
210
Several manufacturers produce airflow measuring devices that can provide accurate averaged
velocity pressures, as well as the instrumentation to convert velocity pressures to airflow rates.
An alternative method of controlling the airflow rate within + 10 percent of design is to select a
fan that has a steep performance curve such that a 25 percent change in pressure will not result
in more than a 10 percent change in flow rate. This is difficult to achieve, however, due to
system margins, system effect factors, and the ability to accurately calculate system pressures.
The choice of control dampers or inlet vanes will depend on fan type, required pressure
reduction, and airflow uniformity. Control dampers should be sized to provide controllability.
Flow stability should be maintained to avoid a controller “hunting” (control instability).
AMCA 210 recommends the use of variable vane inlet dampers when the fan is to be operated
for long periods at reduced flow. The effectiveness of this damper stems from the fact that the
inlet vanes generate a forced inlet vortex that rotates in the same direction as the fan impeller;
similarly, any restriction of the fan inlet reduces the fan performance. Inlet vane dampers are of
two types: integral (built-in) and add-on. The resistance and system effect of inlet vane
dampers in the wide-open position should be considered in the original fan selection and
system functional design. System effects of inlet vane dampers should be available from the fan
manufacturer; if not, the system effect curves of AMCA 210 should be applied to account for
pressure losses due to the use of these dampers.
Although variable vane inlet dampers generally provide smooth airflow control down to less
than 30 percent of operating-point flow, there have been instances of severe vibration on large
fans when the vanes were positioned between 30 and 60 percent opening. Because vibration is
aggravated by system turbulence, consideration should be given to ways of ensuring smooth
airflow patterns in the duct entering the damper and leaving the fan when inlet vane dampers
are employed in high-velocity systems. Variable-pitch vane-axial fans may also be used to
maintain system flow under varying pressure conditions. Variable pitch fans, however, may not
qualify for safety-related seismic applications that require environmentally qualified
components.
With the increase in variable air volume air conditioning systems, much has been done to
improve variable speed controls for fans. Variable frequency controls, eddy current clutch
motors, and mechanical adjustable speed drives are various methods of speed controls for fans.
For variable air volume air conditioning systems, the airflow rate is varied to maintain a
constant system pressure. For nuclear air cleaning systems, the speed of the fan is varied to
maintain a constant airflow under varying system pressures.
Adjustable frequency drives are becoming more economical due to lower-cost solid state
electronic components. The speed of the fan motor is directly proportionate to the frequency
of the motor. Since the horsepower of the fan is a function of the cube of the speed, there can
be significant secondary benefits of saving energy by using frequency drives, as well as better
matching of fan performance to changing system pressure requirements.
Section 148
DOE-HDBK-1169-2022
211
4.5.6.4 Pressure Control
Effluent air cleaning systems are typically controlled to vary the system flow rate to maintain
building (or space) pressure. This is accomplished by maintaining constant supply airflow and
varying exhaust flow by adjusting control dampers and inlet vanes, and through speed control.
Accurately sensing building pressure and outside air pressure are important for achieving a
stable operating system. The sensing system should incorporate a “dead leg” to dampen the
system reaction to wind gusts. Multiple outdoor and, if necessary, indoor sensors should be
provided to obtain an average outside air pressure. To maintain a building at a negative
pressure with respect to the lowest outside air pressure, the outdoor sensors should be located
on each exposure. The system should then be designed to control flow based on the highest
positive pressure sensed (the one that would result in the most infiltration).
Sensors should be located with due consideration given to local pressure fluctuations, eddy
currents, and the turbulence that can be experienced at building corners and roof edges. The
ASHRAE Handbook of Fundamentals provides guidance on determining turbulent zones due to
airflow around buildings. This information should be considered in locating the sensors.
4.5.6.5 Qualification and Testing
All instruments used in safety-related nuclear air cleaning systems are required to be qualified
for environmental and seismic conditions in accordance with ASME AG-1, Section IA, IEEE 323,
and IEEE 344. All instruments and devices should be calibrated and tested in accordance with
the manufacturer's test procedures. In addition, all power wiring internal to control panels,
except control or shielded cable, should be subjected to a high-potential test to demonstrate
freedom from ground and correct wiring connections.
It is recommended that extensive onsite pre-operational testing be performed on all
instrumentation and control systems associated with nuclear air cleaning systems prior to
placing the systems in service. Preoperational testing should be performed to confirm correct
installation and design and to ensure correct operability of the control system and operated
equipment.
4.5.7 References
1. ACGIH (American Conference of Governmental Industrial Hygienists), 2015, Industrial
Ventilation: A Manual of Recommended Practice, 28th Edition, Cincinnati, OH.
2. AMCA (Air Moving and Conditioning Association), 2011, Fan Application Manual of Fan
Systems, AMCA 203-90 (R2011), Arlington Heights, IL.
3. AMCA (Air Moving and Conditioning Association), 2015, Laboratory Methods for Testing
Louvers for Rating, AMCA 500-L-12, Arlington Heights, IL.
4. AMCA (Air Moving and Conditioning Association), 2018, Laboratory Methods of Testing
Dampers for Rating, AMCA 500-D-D-18, Arlington Heights, IL.
5. AMCA (American Air and Conditioning Association), 2011, Fans and Systems, AMCA 201-
02 (R2011), Arlington Heights, IL
DOE-HDBK-1169-2022
212
6. ANSI, 2018, Fundamentals Governing the Design and Operation of Local Exhaust
Ventilation (LEV) Systems, ANSI Z9.2-2018, New York, NY.
7. ANSI/AMCA Standard 210-16/ASHRAE 51-16, Laboratory Methods of Testing Fans for
Certified Aerodynamic Performance Rating, 2016, Atlanta, GA.
8. ASHRAE (American Society of Heating, Refrigerating, and Air Conditioning Engineers,
Inc.), 2016, HVAC Systems and Equipment Handbook, Atlanta, GA.
Section 149
9. ASHRAE (American Society of Heating, Refrigerating, and Air Conditioning Engineers,
Inc.), Fundamentals Handbook, Atlanta, GA.
10. ASHRAE, 2017, Duct Fitting Database, Atlanta, GA.
11. ASHRAE, 2019. HVAC Applications, Atlanta, GA.
12. ASME (American Society of Mechanical Engineers), 2002, Nuclear Power Plant Units and
Components, ASME N509, New York, NY.
13. ASME (American Society of Mechanical Engineers), 2007, Testing of Nuclear Air Cleaning
Systems, ASME N510, New York, NY.
14. ASME (American Society of Mechanical Engineers), 2017, Steel Stacks, ASME STS-1,
2016, Three Park Avenue, New York, NY.
15. ASCE/SEI (American Society of Civil Engineers/Structural Engineering Institute 52-10
Design of Fiberglass-Reinforced Plastic (FRP) Stacks, 2010, Reston, VA.
16. ASME (American Society of Mechanical Engineers), 2018, Power Piping, ASME B31.1-
2018, New York, NY.
17. ASME (American Society of Mechanical Engineers), 2019, Boiler and Pressure Vessel
Code, New York, NY.
18. ASME, 2019, Code on Nuclear Air and Gas Treatment, ASME AG-1, New York, NY.
19. ASTM, 2018, Standard Guide for Use of Protective Coating Standards in Nuclear Power
Plants, Standard D5144-18, West Conshohocken, PA.
20. ASTM, 2018, Standard Specification for Flexible Cellular Material- Sponge or Expanded
Rubbers, ASTM D1056-18, West Conshohocken, PA.
21. DOE, 2011, Maintenance Management Program for DOE Nuclear Facilities, DOE O
433.1B, Washington DC.
22. IEEE (Institute of Electrical and Electronic Engineers), 2003, IEEE Standard for Qualifying
Class IE Equipment for Nuclear Power Generating Stations, IEEE 323-2003, New York, NY.
23. IEEE (Institute of Electrical and Electronic Engineers), 2003, IEEE Standard Criteria for
Qualifying Class IE Electric Cables, and Field Splices for Nuclear Power Generating
Stations, IEEE 383-2003, New York, NY.
24. IEEE (Institute of Electrical and Electronic Engineers), 2010, IEEE Recommended Practice
for Installation, Inspection, and Testing Requirements for Class IE Power,
DOE-HDBK-1169-2022
213
Instrumentation, and Control Equipment at Nuclear Facilities, IEEE 336-2010, New York,
NY.
25. IEEE (Institute of Electrical and Electronic Engineers), 2017, IEEE Standard Test
Procedure for Polyphase Induction Motors and Generators, IEEE 112-2017, New York,
NY.
26. IEEE (Institute of Electrical and Electronic Engineers), 2018, IEEE Standard Criteria for
Independence of Class IE Equipment and Circuits, IEEE 384-2018, New York, NY.
27. IEEE (Institute of Electrical and Electronic Engineers), 2018, IEEE Standard For Seismic
Qualification of Equipment for Nuclear Power Generating Stations, IEEE 344-2018, New
York, NY.
28. NEMA (National Electrical Manufacturers Association), 2014, Enclosures for Electrical
Equipment (1000 Volts Maximum), NEMA-250, Rosslyn, VA.
29. SMACNA (Sheet Metal and Air Conditioning Contractors’ National Association), 2006,
HVAC Systems - Duct Design, 4th Edition, Chantilly, VA.
30. UL (Underwriters Laboratories), 2012, Standard for Fire Dampers, UL-555, Northbrook,
IL.
31. UL (Underwriters Laboratories), 2014, Standard for Smoke Dampers, UL-555S,
Northbrook, IL.
32. Young, Warren and Richard Budynas, 2011, J. R. Roark’s Formulas for Stress and Strain,
8th Edition, McGraw Hill, New York, NY.
DOE-HDBK-1169-2022
214
5.0 SPECIAL TOPICS
5.1 Fire Protection of Air Cleaning Systems23
5.1.1 DOE Fires Affecting Air Cleaning Systems
Section 150
Fires in nuclear facilities have been caused by a variety of energy sources, including electrical
energy and spontaneous combustion of pyrophoric metals. While fixed fire suppression systems
or operator intervention have limited the size and consequences of most of these fires, some
did propagate and cause significant damage and material release. There have been numerous
occurrences of fire in nuclear facilities since the beginning of the Manhattan Project and many
lessons learned from those fires. Some lessons have been learned at great expense. A brief
history is discussed in the 2003 Nuclear Air Cleaning Handbook (DOE-HDBK-1169-2003) in the
hope that the lessons will not be forgotten or ignored by facility designers and operators.
The most significant fires involving the HEPA filters of confinement ventilation systems have
occurred at the Rocky Flats Plant. In 1957, pyrophoric ignition of plutonium in a production line,
spread within the glovebox system and eventually ignited combustible cellulose filters in the
production box and spread from there via laminated plexiglass window materials and other
unknown combustible materials in the ventilation system to involve and destroy combustible
HEPA filters in the final filter stage. Delays in fighting this fire were due to radiation safety
concerns and delays in using water due to criticality concerns allowed it grow. It was
extinguished soon after water was used, but a buildup of combustible vapors and dusts in the
ventilation ductwork and the final filter stage ignited and resulted in a small explosion. This
severely damaged the HEPA filters in the final filter stage and allowed the second-highest
known plutonium release at Rocky Flats to occur. A significant portion of the plutonium
released from this fire was deposited offsite. As a result of this event, fire-resistant glass fiber
HEPA filters were researched, developed, and put into service in the nuclear industry. The
release could have been more severe, but much of the plutonium was at the bottom of the
stack due to the weight of the material, thus reducing the amount lofted out of the exhaust
stack.
Another fire occurred at Rocky Flats in 1969 in a production line glovebox. The exact cause of
this fire is unknown, but the area of origin included a storage cabinet that housed small, open
metal containers filled with plutonium machine turnings. It is speculated that these plutonium
briquettes self-ignited. The cabinets, which were constructed of high-density pressed wood
shielding material and plastic, were included in the production line to reduce neutron exposure
to workers. Heat detectors originally installed in the glovebox were removed to the underside
of the glovebox floor to accommodate the cabinet. A fire detector alarm alerted the fire
department. When the firefighters arrived, the building was smoke-filled, indicating the fire had
escaped the confinement system (likely initially through the glovebox gloves). While localized
23 This guidance is drawn (in somewhat condensed form) from Chapter 10 of NACH (2003). It should be viewed as
supplementary to guidance and information offered in DOE-STD-1066-2016. Where the guidance here and that of
DOE-STD-1066-2016 are not consistent, DOE-STD-1066-2016 should be followed.
DOE-HDBK-1169-2022
215
contamination was detected outside the building, no measurable contamination escaped the
site.
5.1.2 Fire Phenomena
Section 151
Fire is a complex phenomenon that involves the initiation of an event and subsequent actions
that can mitigate or exacerbate the event’s effects. The matrix in Table 5.1 covers: (1) the
initiation and generation of harmful products from a fire; (2) the means by which these harmful
effects are transported throughout the confinement ventilation system; and (3) the impacts of
these harmful effects on the main components of the confinement ventilation system.
Table 5.1 – Fire Phenomena
Heat Smoke Related Effects
Generation Fire growth Initial aerosol makeup Water vapor, chemical
releases, deflagrations
Transport Temperature in ducts
(less heat transfer and
dilution)
Change in aerosol with time
and temperature
Change with movement
through ducts
Effects on
filters Media failure Filter media plugging Filter media plugging and
failure due to delta P
Fires occurring outside a confinement ventilation system, e.g., within a room, generate heat
that exposes the outside of ducting as well as produce combustion products that are drawn into
the confinement ventilation system while operating as intended. These combustion products
will impact the components of the confinement ventilation system. Hot gases from such a fire
will be entrained within the system and will be conveyed via the duct system to the filter banks.
While a certain amount of heat dissipation (heat transfer to the duct) and dilution will occur,
over time the gases may cause steady deterioration of the filter medium and may ignite
combustible framing. HEPA filters with fire retardant wooden frames will delay ignition, but
they are still considered combustible.
5.1.2.1 Smoke Generation
Smoke contains particulates of combustion that can pose a significant plugging threat to HEPA
filters. Smoke is a suspension of solid and/or liquid particles and gases resulting from
combustion and pyrolysis. Soot is an intrinsic part of smoke. However, the term “soot” can be
further refined to mean finely divided particles, mainly carbon, produced and/or deposited
during incomplete combustion of organic materials. Moreover, the amount of smoke generated
from any material is strongly influenced by the same conditions that effect combustion
efficiency.
In general, smoke is a heterogeneous combination of solid and liquid particles of varying size
and composition. Their instantaneous character depends on the material of origin, combustion
conditions, environment, and flow dynamics. The sizes of particulates vary from 0.002 to 0.5
DOE-HDBK-1169-2022
216
µm, depending on the experience described above. Conditions related to incomplete
combustion generally result in an aerosol distribution of larger mean particulate size. However,
if the smoke concentration is high, particle agglomeration (smoke aging) proceeds rapidly, as
does fallout and surface deposition.
Agglomerated smoke aerosols can attain diameters as large as 10 µm in plumes from fires;
however, visibility is most influenced by particulates with diameters of >1.0 µm. Collections of
data on smoke production rates (g of soot/g of material burned) are available and can be used
to estimate visible obscuration and smoke detector response time.
5.1.2.2 Water Generation
The quantity of water generated in the fire is as important as the soot and other particulates.
Water vapor can condense on the particulates in smoke, both increasing their average
diameters and leading to increased agglomeration resulting in generally larger particulates.
Larger particulates lead to more rapid HEPA filter plugging.
Section 152
5.1.2.3 Heat Loss in Ducts
Hot gas from fires may enter the exhaust duct system and lead to excessive temperatures at
the HEPA filters if not mitigated. The two primary tools for analyzing the cooling of hot exhaust
gas are: (1) dilution analysis with additional exhaust streams, and (2) duct cooling by convective
and radiative heat transport.
As the combustion products from a fire travel through the length of a duct, losses occur.
Thermal energy is added or lost through the walls of the duct according to the temperature
differential between the products of combustion gases in the duct and the atmosphere external
to the duct. Solid and liquid particulates are deposited along the duct interior surfaces
according to a number of factors.
Because confinement systems are part of the enclosures that support operations with nuclear
materials, computer codes have been developed to predict the results of accidents on the
internal conditions within the system. For fire events, the room fire models discussed above can
serve as the source term for codes that treat the response of components within the
confinement ventilation system. Modeling tools are available (such as CFAST24) to help analyze
heat transport in the ducts. In some cases, these models will not account for loss of heat from
the heat transfer for conservatism.
5.1.2.4 Smoke and Water Loss in Ducts
A significant quantity of smoke and water may settle out in the ventilation ducts. In one
configuration where the duct was located outside the fire area, it was observed that about 60
percent of the aerosol mass (including water) was lost between the duct entrance and the
HEPA inlet (about 19 feet for a 2-foot × 2-foot cross-section duct).
Transport of related combustion products such as smoke particulates can be modeled using
available techniques. Analysis methods for the entrainment and transport of these products in
24 Consolidated Fire and Smoke Transport
DOE-HDBK-1169-2022
217
confined situations such as ducts are generally well understood. The form and dispersion
characteristics of the combustion products in question also should be studied. Once this is
done, the effects on the HEPA filters can be shown over time.
5.1.2.5 Effects on Filters of Heat, Smoke, and Related Products
The impact of fires on the integrity of the HEPA filters can be determined through a sequence of
analyses to establish: (1) the dynamics of the design basis fire; (2) the generation of smoke,
water, and heat (temperature) that enters the confinement ventilation system; (3) the
mitigation of smoke, water, and heat through the ducting to the HEPA filters; and (4) the
response of the HEPA filters to the smoke, water, and heat that reach them. The interaction of
smoke, water, and heat play a major role in the plugging of HEPA filters, as well as the
consequent rise in filter pressure drop and possible reduction in exhaust flow. This sequence of
analysis will determine the potential of the design basis fire for causing structural damage to
the HEPA filters and thereby increasing the filter penetration. Finally, the effect of the smoke
and water loading and the air temperature on the HEPA filters needs to be determined.
5.1.2.6 HEPA Filter Response to Temperature
Section 153
Section 5.1.4.3 of DOE-STD-1269-2022 requires that fire-resistant HEPA filters meet the
requirements of Underwriters Laboratory (UL)-586, High-Efficiency, Particulate, Air Filter Units,
while medium efficiency filters meet the requirements of UL-900, Performance of Air Filter
Units. These UL test methods qualify the construction materials for the filter, frame, and
gaskets. To be listed by UL under UL-58613 as a HEPA filter unit, HEPA filters are required to
pass the following three criteria:
• Withstand 750 ± 50 degrees Fahrenheit heated airflow for 5 minutes at not less than 40
percent of rated capacity.
• Have a greater than 97 percent test aerosol efficiency after exposure to the hot air test
and cooling.
• Withstand a spot-flame test in which a Bunsen burner flame at 1,750 ± 50 degrees
Fahrenheit is placed on the filter with no after-burning when the flame is removed.
For the spot flame test, a horizontal Bunsen burner is touched to the filter at three locations for
5 minutes at each site. Afterwards, the burner flame is moved to touch the filter frame, filter
pack, and sealing materials. To pass the test, flaming on the downstream side of the filter is
required to cease within 2 minutes after removal of the burner flame. Although this test
indicates the fire performance of the filter, it is a small-scale test with a limited, controlled heat
source that does not replicate the temperatures experienced during actual exposure of the
entire filter to a more severe, full-scale fire. Many fires can reach higher temperatures and
more severe conditions than this test fire.
Extended exposure to temperatures above 800 degrees Fahrenheit will cause destruction of the
casing of wood-cased filters and warping of the casing of steel-cased filters, allowing unfiltered
air to bypass the filter. The medium of HEPA filters is thin (0.015 inch) and can be destroyed by
incandescent sparks, flaming trash, or burning dust on its surface.
DOE-HDBK-1169-2022
218
Although HEPA filters can withstand a temperature of 750 degrees Fahrenheit for an extremely
limited time, they should not be subjected to continuous exposure to temperatures higher than
250 degrees Fahrenheit. Longer filter life and more reliable service, as well as a greater
operational safety factor, can be obtained when normal operating temperatures are below 200
degrees Fahrenheit and higher temperature extremes are avoided.
5.1.2.7 HEPA Filter Response to Smoke and Water Loading
Water from combustion plays a major role in potential HEPA filter clogging with smoke
aerosols. The temperature at the HEPA filter is important for determining the extent of water
condensation from the fire exhaust. The HEPA filter-plugging studies suggest using the
following approach to analyze the potential of fires to plug HEPA filters.
With the design basis fire and its combustion products previously established, transport of the
hot gases, smoke particulates, and water vapor through the duct system should be established.
The characteristics of the combustion products penetrating the medium efficiency filter or
demister should be determined next. This process will yield a mass of smoke aerosols for
comparison to a reference mass holding capacity for HEPA filters. The amount of water
condensing on the smoke deposits is determined from the temperature at the HEPA filters and
from the combustion water loading.
Section 154
The nature of the aerosols has a major effect on plugging of all filters, including DBS filters,
medium efficiency filters, and HEPA filters. Previous studies have shown that, in addition to the
mass of the smoke aerosols, the particle size and the state of the aerosol (liquid or solid)
significantly affect HEPA filter clogging. In related tests using rolling medium efficiency filters
(the media roll advances through the test duct as it plugs), Bergman et al., showed that, once a
fire and the ventilation system have reached the point where the smoke generated can plug a
HEPA filter, plugging can occur within one minute.25
Depending on circumstances and the specific design, the effects of aerosols on various type of
filters will vary. Although very large DBS may not plug up as fast as a small HEPA assembly, all
filters including DBS filters will eventually plug under enough soot exposure.
5.1.2.8 Filter Exposure to Water
Water is an effective method for reducing temperature, but HEPA filters are not designed to
operate when wet and will suffer structural damage. The HEPA filter medium is treated with
water-repellent chemicals. Tests have shown a reduction in water repellency effectiveness with
each wetting of the medium. The tensile strength of the filter medium can be reduced to failure
levels with as little as one wetting. HEPA filters exposed to water should be replaced
immediately.
25 See Bergman, W., W. D. Kuhl, W. L. Russel, R. D. Taylor, H. D. Hebard, A. H. Bierman, N. J. Alvares, D. G. Beason,
and B. Y. Lum, 1980, Electrofibrous Prefilters for Use in Nuclear Ventilation Systems, Lawrence Livermore National
Laboratory, Livermore, CA.
DOE-HDBK-1169-2022
219
5.1.2.9 Effects on Physical Integrity of the Confinement Ventilation System Components
Fires external to the confinement ventilation system may not only damage the HEPA filters
inside the confinement ventilation system, they also may damage the integrity of the
confinement ventilation system ductwork and enclosures. If the confinement ventilation
system ductwork or enclosures are breached, some or all of the functionality of the
confinement ventilation system will be impaired. This should be considered in the design of the
physical components and the fire suppression systems provided in the facility.
5.1.2.10 Effects of Wildland Fires
Wildland fire experience such as at the Cerro Grande fire in Los Alamos in 2001 demonstrated
the potential for smoke to adversely affect confinement ventilation systems. Facilities in areas
where this type of event may occur are required to analyze the hazard in their authorization
basis documents. During the 2001 Cerro Grande fire, some confinement ventilation systems in
facilities at the Los Alamos National Laboratory were shut down to prevent the rupture of HEPA
filters due to clogging from smoke. Other external situations (such as volcanic eruptions or the
dust from denuded landscapes) can also create abnormally dusty conditions that cause clogging
of medium efficiency filters and HEPA filters and present serious threats to confinement
ventilation systems. System designers and operators should implement features that minimize
the probability of having to shut down confinement ventilation systems in other than extreme
emergency situations. During emergency situations, if the Incident Commander determines that
a confinement ventilation system has been breached and radioactive material is being released,
a decision should be made whether to shut the confinement ventilation system down
completely or operate it in a manner that would minimize the impact. Additional prefilter
change outs may also need to be considered near facilities subjected to wildfire exposures
during and immediately after emergency periods of such events.
Section 155
These hazards may reveal the need for additional safeguards, including but not limited to,
administrative controls of the removal of natural vegetation and other combustibles near filter
inlets, installing smoke removal systems such as an ESP medium efficiency filter or installing
additional filtration to preclude ingress of particulate into the building. NFPA Standard 1144,
Protection of Life and Property from Wildfire, provides guidance on minimum defensible spaces
around all buildings. High-hazard facilities would be expected to have defensible spaces
exceeding these minimum values.
5.1.2.11 Fires Occurring within Confinement Ventilation Systems
Fire may originate from sources within the confinement ventilation system (e.g., glovebox-sized
operations and small hot-cells). The effects of fires occurring within confinement ventilation
systems, although similar to those resulting from fires external to the confinement ventilation
system, may be different and thus require different controls.
5.1.2.12 Generation of Heat, Smoke, and Related Products
Fire events occurring inside a confinement ventilation system may appear in a number of
physical forms. Fire may occur in ordinary combustible material. The amount of combustible
DOE-HDBK-1169-2022
220
material within a confinement ventilation system generally would not be as much as in a larger
room, so the fire growth characteristics may be somewhat altered.
Fire may occur in the radioactive materials in a confinement ventilation system, or a fire
involving ordinary combustibles may subsequently involve radioactive materials. A fire involving
a flammable liquid or gas used inside a confinement ventilation system also may occur. These
events may take the form of a flame front moving rapidly through a flammable vapor, a flame
front moving rapidly enough to deflagrate and produce some overpressure, or even a
detonation if the conditions for such phenomena exist.
Filter fires can occur due to either decomposition of combustible dust deposits within the filter,
organic decomposition of chemical residue carried by the airstream from upstream processes,
or spark/ember introduction from an upstream source. While introducing a water spray within
or prior to the duct inlet can prevent the latter condition, fires originating at the filter itself
cannot be satisfactorily mitigated by automatic suppression methods. Consequently, reliance is
placed on the manual deluge system and fire department response.
Industrial and institutional loss experience has shown that over a period of time even “office
dust” accumulations can form highly combustible residues on filters that are sufficient to cause
damage if ignited. It also has been established that the concentration of these fuels need not be
high to cause severe damage due to the fragility of the media. Fire-retardant chemical
preparations for the filter media may initially make ignition difficult, particularly on clean
media. However, this retardant material tends to become less effective over time and does
nothing to retard or reduce the combustibility of dust or residue deposits from the airstream
itself.
Administrative controls and alarm interlocks are designed to alert operators about impending
change-out intervals that have been established to maintain dust or residue inventories below
radiological actions points. It is not feasible, however, to eliminate the potential for direct filter
fires or to practically reduce residue levels below those that may damage the filter itself.
Section 156
5.1.2.13 Transport of Heat, Smoke, and Related Products
The transport of hot gases, smoke, water vapor, and chemicals from an internal fire through a
confinement ventilation system can be modeled in much the same way as is done for an
external fire. A fire occurring within the confinement ventilation system may affect the
transport mechanism by altering the airflow through the system more than an external fire.
The transport mechanism also may be affected if the actual structural confinement barrier of
the confinement ventilation system is involved in the fire and is contributing to its spread. The
accumulation of dust and debris inside the air cleaning system ductwork over long periods of
operation provides a mechanism for transporting flames from an ignition source to the filters,
and also can produce soot that can clog filters in a fire.
5.1.2.14 Effects on Filters of Heat, Smoke, and Related Products
The effects of the products of combustion reaching the HEPA filters are the same for internal
and external fires. The same physical parameters affect the manner in which the filters are
threatened.
DOE-HDBK-1169-2022
221
5.1.3 Fire Hazard Controls and Design Features
5.1.3.1 Objectives and Requirements
There are three major objectives for fire protection of confinement ventilation system:
• To prevent fires from affecting the operation of the ventilation system;
• To protect the filtration function; and
• To prevent the release of material that has accumulated on filters.
General Requirements
Special hazards may cause exposure of the filters to the following: highly combustible dust
loading; pyrophoric materials; chemically reactive, explosive, or corrosive vapors; or high-
moisture conditions that may cause rapid degradation of HEPA filters. These should be
evaluated on a case-by-case basis by a fire protection engineer who understands the process
sufficiently to determine the protection warranted.
A comprehensive fire protection scheme for filter housings should include the following
principles:
• The ventilation system filter housing construction materials should be noncombustible.
• Process hazards inside and outside the ventilation filter housings should be controlled.
• General area sprinklers should be provided within all process areas, in accordance with
the facility Fire Hazards Analysis.
• The final filter housing should be separated from the general building area by fire-rated
construction.
• Automatic water spray should be installed upstream (before) the demister filter and
before the first-stage filters.
• Manual water spray should be installed and directed at the first-stage HEPA filter.
• Automatic fire detection should be provided in the inlet ductwork, prior to the HEPA
filtration plenum, and within the plenum where there is the possibility of combustible
materials within the plenum.
• Automatic flammable gas detection should be provided in filter housings where
flammable or combustible processes are performed.
The FHA for a confinement ventilation system may indicate the need for further fire protection
measures.
5.1.3.2 Fuel Control
The flammability/combustibility of materials should be considered in designing the
confinement ventilation system. This is a first line of defense against fire, without which any
ignition will lead to a dangerous situation. NFPA standards and DOE fire protection criteria
DOE-HDBK-1169-2022
222
Section 157
provide requirements and guidance on how to accomplish fuel control. The FHA should address
the issue of materials flammability/combustibility as it pertains to the facility under analysis.
If the process involves the presence of flammable or combustible vapors or liquids, the
allowable concentration of flammable vapors inside the filter enclosure should be limited and
controlled. The maximum permissible concentration of flammable vapors is normally taken to
be 25 percent of the lower flammable limit.
5.1.3.3 Control of Energy Sources
Ignition sources inside the filter enclosures should be limited to those necessary for operating
the system. Electrical systems should be installed in accordance with NFPA 70, the National
Electrical Code. The presence of flammable gases or vapors in the operation of the confinement
ventilation system will require specialized electrical equipment to prevent their ignition, e.g.,
NFPA 70, Article 500.
5.1.3.4 Passive Design Features
The design of the duct runs can greatly influence the effect of a fire in the facility or within the
ductwork on the ability of the confinement ventilation system to perform its required safety
function. This section will address the physical configuration aspects of the ducts and filter
housings. Ductwork and related equipment are required to comply with the criteria of NFPA
90A, Installation of Air Conditioning and Ventilation Systems and NFPA 91, Standard for Exhaust
Systems for Air Conveying of Vapors, Gases, Mists, and Noncombustible Particulate Solids. These
standards provide explicit requirements for integrating the ventilation system with the building
construction, as well as operational guidance for systems inspection, cleaning, and
maintenance. Other sections address the active fire protection or cooling systems that may be
required to maintain confinement ventilation system functionality.
Another significant consideration in the design and layout of an air cleaning system is provision
of separate systems for each building fire area. Buildings are subdivided into discrete fire areas
to limit fire damage to only one area. Fire areas are established to limit the maximum possible
fire loss and in accordance with the building codes. If fire area boundaries are penetrated to
allow passage of the air cleaning ducts, the possibility of fire spreading to multiple fire areas is
introduced, potentially resulting in much more extensive fire damage.
5.1.3.5 Duct Response to Fire
There may be situations where fire dampers cannot be installed at firewall duct penetrations
because of the critical safety requirement to maintain confinement ventilation. In some cases,
ducting may traverse other fire areas before reaching the filter banks. The quality of the duct
construction and installation are the most important factors in maintaining the integrity of the
ducting. A number of factors need to be considered:
• Where the duct penetrates a firewall, distortion during a fire may permit flames to pass
through the wall around the perimeter of the duct. Investigators have performed full-
scale fire testing that provided insight into the performance of reinforced ducting under
limited fire exposures. One investigation concluded that a reinforced duct could
withstand a design basis fire without collapse or deformation.
DOE-HDBK-1169-2022
223
• Conductive heat transfer through the duct may ignite combustible materials in adjacent
fire areas. This can be mitigated by insulating or enclosing the duct as determined by the
FHA (generally 10 feet).
Section 158
• Duct collapse can occur due to weakening of the duct or the hangers when heated.
Additional hangers and/or reinforcement of the duct at the penetration point will
mitigate this potential problem.
• Where there are duct openings in a non-fire space, the FHA should consider the
potential for fire spread and the need for additional safeguards.
5.1.3.6 Air Supply and Extraction
The method of air supply and extraction profoundly influences the efficiency with which a fire
burns. Most gloveboxes are designed so that the air supply enters at the bottom on one side of
the box and exits at the top on the other side. This design ensures that a vigorous fire will
persist so long as fuel and air are available. If, the ventilation pattern is reversed and air enters
at the top of the box and exits at the bottom, however, combustion products will mix with the
supply air to weaken and ultimately extinguish the fire. This tactic is effective for all but very
large enclosures.
5.1.3.7 Entrance Filters
Because the duct-intake filter is the major dust collector, it is also the primary component in
which a fire could occur. Protection of the HEPA filter downstream from sparks and burning
fragments from the duct-intake filter may be needed if the distance between them is not great.
If it is less than 20 to 30 feet, a fine (20 to 30 mesh) screen may be installed downstream of the
duct-entrance filter (such screens should be located where they are convenient for periodic
cleaning). Because lint tends to bridge the openings, screens, and coarse filters (e.g., furnace
filters), installation of fine-mesh screens on the face of the duct-entrance filter is not
recommended; however, this does not preclude installation of a mesh screen for physical
protection of the filter. For glovebox and hot cell applications, the duct-intake filter should be
designed for ease of removal and replacement from the contained space. The filter should also
be afforded maximum protection against the effects of or ignition by a fire in the contained
space.
5.1.3.8 Medium Efficiency Filters
Medium efficiency filters are usually provided in the central filter housing in addition to or in-
lieu of duct-intake filters. Again, fire is more likely to occur in the medium efficiency filter rather
than in the HEPA filter downstream. Medium efficiency filters should never be mounted directly
on the face of the HEPA filter or on the opposite side of a common mounting frame with the
HEPA filter (i.e., back-to-back). A spacing of at least 36 inches between the downstream face of
the medium efficiency filter and the upstream face of the HEPA filter is recommended—not
only for maintainability, but also to provide space where burning fragments and sparks can
burn out or settle to the floor of the filter housing.
DOE-HDBK-1169-2022
224
5.1.3.9 Filter Housings
HEPA filter housings/plenums should be protected from facility fires by fire-rated construction
(generally 2-hour). High temperatures in exhaust filter housings can be minimized by long runs
of duct preceding the housings/plenums, by
• Intake of dilution air from air streams from other contained or occupied spaces of the
building,
• Cooling of the exterior of the duct with water spray, and
• Cooling via water spray installed inside the duct (has been employed in some
applications).
The overall intent is to locate the HEPA filters where they are least likely to be exposed to
elevated temperatures, hot sparks, and burning embers from a potential fire in the process line.
Section 159
5.1.3.10 Fire Screens
A fire screen is a noncombustible sheet of meshed metal similar to a roughing filter that is
intended to reduce the potential for transporting glowing embers/burning brands through the
airstream from the fire source to the filter banks. The screen should be installed upstream from
the medium efficiency filter(s) and ahead of the filter housings/plenums. Specific design criteria
for fire screens can be found in DOE-STD-1066-99.
5.1.3.11 Materials
Ideally, all construction materials used in confinement ventilation system enclosures should be
noncombustible. Use of noncombustible materials for the enclosure will help limit the total
amount of fuel available to burn if a fire occurs, and also ensure integrity during a fire event. If
suitable noncombustible materials cannot be used because of process, shielding, corrosion-
resistance, or other special purpose requirements, attempts should be made to minimize the
quantity and surface area of the installed combustible materials should be minimized. If a
combustible duct material is utilized, installation of automatic sprinklers within the duct may be
required according to DOE, NFPA, or FM Global requirements. Additionally, an approved or
listed duct material may be required, e.g., fire retardant FRPs.
The preferred construction materials for ductwork are steel, stainless steel, or galvanized steel.
If FRP ductwork is required because of corrosion issues, special ductwork that meets the flame-
spread criteria in NFPA 90A is required. Acoustic linings or duct silencing materials are
combustible and are not permitted inside air cleaning system ductwork.
5.1.3.12 Wood Filter Frames
If wood is used for HEPA filter frames, a fire-retardant treatment is used that results in (a) a
flame spread of 25 or less and (b) a smoke-developed rating of 50 or less when tested to ASTM
Standard E-84. This test measures the speed at which flames will travel across the surface of
the material being tested. As a comparison, the flame spread of red oak boards is 100, while the
flame spread of concrete or unpainted steel is zero. Thus, even with the fire-retardant
treatment, wooden filter frames will combust in a sufficiently severe exposure fire.
DOE-HDBK-1169-2022
225
5.1.3.13 Fire Barriers
HEPA filter housings/plenums located within nuclear or hazardous process buildings are
required to be separated from the remainder of the building by a minimum of 2-hour-rated fire
barriers. This requirement is intended to ensure HEPA filters are protected from fires occurring
in the process building. One common type of 2-hour-rated barrier is constructed of 8-inch-thick
concrete block walls and a poured concrete ceiling. Another method is to provide this level of
required separation is to locate the filter housing external to the process building. If the filter
housing is located in a separate building, no specialized fire barriers are required, provided the
housing is located at least 20 feet from the process buildings and the exterior walls of both
buildings have no unprotected openings, and are of non-combustible construction. If the filter
housing is located less than 20 feet but more than 5 feet from the process building, the filter
housing is required to be constructed as a 1-hour-rated fire barrier. Filter housings are required
to be installed in 2-hour-rated firewalls if they are less than 5 feet from the process buildings.
Section 160
Small filter housings, which have a leading-edge surface area of 16 square feet or less, are not
required to be separated from the rest of the building, provided the building has area-wide
automatic sprinklers.
Penetrations through the air cleaning system enclosure fire barriers are only permitted for
services necessary to the operation of the filtering system. Where penetrations cannot be
avoided, the openings created through the fire barrier are required to be properly sealed with a
listed or approved, penetration seal method. Penetration seals are tested and approved under
the requirements of ASTM E-814, Fire Tests of Through Penetration Fire Stops. The penetration
seals should also be compatible with and capable of continued exposure to the types of
materials and atmospheres present inside the filter enclosure. Doors in 2-hour-rated enclosures
are required to be Class B (90-minute) fire door assemblies. Doors in 1-hour-rated enclosures
are required to be Class C (45-minute) fire door assemblies. The requirements for construction
and installation of fire doors are found in NFPA 80, Fire Doors and Other Opening Protectives.
HVAC ducts that penetrate 2-hour-rated enclosures should be protected with UL-listed or FM
Approved fire dampers. HVAC ducts that penetrate 1-hour-rated enclosures are not required to
have fire dampers.
In some cases, it is necessary for ductwork that is part of the nuclear air cleaning system to
penetrate fire-rated barriers. Fire dampers cannot be installed in these ducts because their
operation during a fire would cause the dampers to close causing the isolation of ventilation
flow. Because the air cleaning system is required to be functional at all times, an alternative
method of fire protection should be provided. It is recommended that a qualified fire
protection engineer be consulted to evaluate such configurations on a case-by-case basis. In
some cases, it may be possible to obtain an exemption on the use of fire dampers where
building alterations would involve working in highly contaminated areas. During the evaluation,
the qualified fire protection engineer will determine a technically justified approach providing
the level of protection required without causing unwarranted impacts to the overall system’s
operational capabilities.
DOE-HDBK-1169-2022
226
5.1.3.14 Active Design Features and Fire Hazard Controls
One of the goals of the nuclear industry has been to provide gloveboxes, caves, canyons, hot
cells, fume hoods, and other radiological confinement areas with practical ventilation exhaust
systems that can remain in service during a fire that can capture all of the airborne radioactive
contamination from the fire. It has been established by both consensus standards and
industry/government regulations that ventilation components in nuclear air cleaning systems
should continue to perform their safety functions effectively under all conditions by confining
radioactive or other potentially dangerous materials. To realize this for fire protection
purposes, it is necessary to protect the filter housing in the exhaust system from heat, smoke,
and burning material that would be generated during a fire scenario. In the event of fire, the
release of contaminated smoke through a ruptured or damaged filter housing may have more
serious consequences than any potential casualty losses from the fire itself.
5.1.3.15 Fire Dampers
Section 161
Fire dampers should not be provided in ductwork penetrating fire-rated construction when the
ductwork is part of the nuclear ventilation system and is required to continuously operate. In
lieu of fire dampers, a performance-based approach is performed by a qualified fire protection
engineer. This evaluation may require (for example) one of the following:
• Duct wrapping utilizing a listed or approved duct wrap,
• A sprayed-on material,
• Enclosure of the duct in fire-rated construction,
• Structural enhancements to the duct at the duct penetration.
5.1.3.16 Fire Detection and Suppression Systems
Detection Systems
Detection equipment for early warning of fire conditions should be provided in all HEPA filter
housings/plenums. Rate anticipation heat detectors are most commonly used because of their
good stability, low maintenance requirements, and relatively quick response to heat. Linear
heat detection is also acceptable and may be preferable due to ease of installation, resistance
to varied chemicals, and especially ease of testing.
Sampling types of smoke detection systems has been suggested as a means of providing early
warning, however, precautions should be taken to ensure they do not provide a leak path that
bypasses the filters. Such systems are utilized strictly in accordance with their listing/approval.
Alternative fire detection methods are possible depending on the specific design of the filter
enclosure. If flammable liquids or gases are used and the possibility of explosion exists, rapid
detection using flame detection devices may be needed.
NFPA Standard 72 provides the requirements for the installation of fire detection devices and
systems.
Automatic Fire Suppression Systems
Prior to the Brown’s Ferry nuclear power plant fire in 1975, the use of water on electrical fires
was not considered a safe practice by the nuclear power industry. Following the Brown’s Ferry
DOE-HDBK-1169-2022
227
fire (see NRC NUREG-0050, Recommendations Related to the Brown’s Ferry Fire), Factory
Mutual (now FM Global) and other organizations performed studies to test the use of water in
electrical spaces (see Electric Power Research Institute (EPRI) NP-188131 and EPRI NP-2660). In
addition, Sandia National Laboratories (SNL) performed tests on cable tray protection schemes
(see NRC NUREG/CR-2377,33 NUREG/CR-2607,34 and NUREG/CR-3656). These studies by
Factory Mutual and other organizations proved that fighting fires in grouped cables could be
accomplished efficiently using water (these tests were done on unenergized electrical cables,
however, the conclusions on the use of water as an efficient extinguishing agent were
confirmed).
Following the Brown’s Ferry fire and the tests performed by Factory Mutual, SNL, and others,
the inhibition against using water to extinguish fires in all spaces with electrical equipment
began to subside, and fire protection engineers made more deliberate assessments of the type
of electrical occupancy when considering use of water as a fire suppressant. Automatic fire
suppression systems throughout a facility will control a fire in its early stages of growth, thus
mitigating fire effects that could impact the functionality of the confinement ventilation system.
Wet pipe sprinkler systems are the most common type of automatic fire suppression system
and have a proven record of fire extinguishment. Other types of systems exist and are
described further in this section. Activation of a suppression system will control and/or
extinguish an incipient fire and automatically alert first responders or the fire department.
Section 162
Consideration should be given during the design phase on the testing and maintenance of fire
suppression and fire detection systems throughout the life of the system/facility. Consideration
also should be given to avoiding interference with or inhibition of the safety function of other
safety features (i.e., water addition/criticality controls, HEPA filters).
5.1.3.17 Wet Pipe Sprinkler Systems
Wet pipe sprinkler systems are used to control the fire potential in the facilities where there is a
confinement ventilation system. Such systems will control and/or extinguish the fire and thus
limit the threat to the facility, the HEPA filters. These systems will also limit physical fire
damage to the ductwork of the confinement ventilation system.
The need for wet pipe sprinkler protection is established by the FHA. The design and installation
requirements for these systems are contained in NFPA Standard 13, Standard for the
Installation of Automatic Sprinkler Systems.
5.1.3.18 Deluge and Water Spray Systems
A deluge sprinkler system is one in which the sprinklers are normally open and water flow is
controlled by a valve in the piping leading to the open sprinklers. When this valve is opened,
water is discharged from all the open sprinklers at the same time.
Two types of deluge systems are required for protection of HEPA filter housings. The first type
is automatic with the water-spray sprinklers being located upstream of the demister filters. This
type of system is generically referred to as a water curtain, as it consists of closely spaced, open
deluge nozzles connected to sprinkler piping located in front of and above the demisters. When
the system is activated, all of the nozzles spray water simultaneously downward, forming a wall
DOE-HDBK-1169-2022
228
of water. This system is intended to cool incoming air, hot sparks, and flames before the
medium efficiency filters are threatened. The water curtain is located upstream of the
demisters so the water spray carryover can be diverted (i.e., knocked down) to prevent
moisture from reaching the downstream HEPA filters.
Operation of an automatic deluge spray system is initiated by a fire detection system (generally
heat detectors) located in the ducting, just prior to the filter plenum. The detection system
opens a deluge valve, allowing water flow to the nozzles. The spray nozzles are open sprinklers
listed/approved for their intended use. The automatic system is also equipped with a locked
bypass valve that can be manually opened if the detection system or the deluge valve fail to
operate. Closed-head pilot sprinklers are sometimes used in place of an electrically-operated
heat detection system to open the deluge valve. In this case, the pilot sprinklers serve only as
temperature sensors and do not spray water. The use of pilot sprinklers has an advantage for
safety class systems since they do not require energy to activate.
Fires produce smoke and soot that will cause rapid clogging of filters. Because the automatic
spray deluge system functions much like the scrubbers that are used to clean stack exhaust,
there is an expectation that the automatic system may also reduce smoke clogging. However,
the nozzles are not optimized for smoke reduction due to their larger droplet size. In limited
research with spray nozzles, it was found that smoke clogging decreased in some cases but
increased in others.26 Therefore, premature manual activation of the spray deluge system to
reduce smoke is not recommended without further research to quantify results for specific
arrangements and combustible contents. Operational procedures such as shutting down or
throttling back the blowers to prevent rupture of clogged filters during a fire should be
addressed in the authorization basis documents. The generic operational procedures provided
here resulted from studies at a DOE site and are applicable to the procedures at most sites. Use
of these procedures should be preceded by a thorough design review to ensure their specific
applicability.
Section 163
Demisters should be installed between the automatic spray nozzles and the HEPA filters.
Demisters are specially configured metal panels that redirect the water droplet trajectory
toward the floor of the enclosure. Performance criteria for demisters are contained elsewhere
in this handbook. The demisters should be positioned at least 3 feet upstream of the HEPA
filters, and approximately 6 inches downstream of the automatic deluge nozzles.
The second type of deluge system is a manually activated deluge spray system. This system is
operated only if the filters begin to combust because it discharges water directly onto the first
stage filter system. Combustion cannot only breach the filters but may also release particulate
that has accumulated on the filters over time. Facilities without this manual system should rely
on firefighters to attack HEPA filter fires with hose streams. The manual deluge system is
intended to avoid unnecessary exposure of firefighters who would otherwise need to enter the
hazardous environment within the housing/plenum. The manual system also has a much more
26 PNNL-18894 (WTP-RPT-197, Rev 0), Pretreatment Engineering Platform Phase-1 Final Test Report, Dec. 2009,
Pacific Northwest National Laboratory, Richland, WA; PNNL-22415 (WTP-RPT-221, Rev 0), Large Scale Spray
Releases: Additional Aerosol Test Results, August 2013, Pacific Northwest National Laboratory, Richland, WA.
DOE-HDBK-1169-2022
229
efficient flow pattern and utilizes less flow than a fully charged fire hose. The manual control
valve for the manual deluge spray system is normally locked in the closed position and only
accessible to firefighters. Fire department training programs should address operating
procedures for these valves.
The potential for nozzle plugging or corrosion in housing deluge systems should be considered
during design. Potential remedies include, but are not limited to, strainers, blow-off caps, and
corrosion control measures such as use of special corrosion-resistant materials or coatings.
Some sites have utilized stainless steel nozzles to avoid the potential for corrosion. These sites
felt that the increased cost upfront was well worth the investment.
The automatic extinguishing systems should be designed to comply with the requirements of
NFPA 13 and NFPA 15, Standard for Water Spray Fixed Systems for Fire Protection. These
standards provide the requirements for designing and installation of the system its
components, as well as associated installation requirements. Research conducted by Dow
Chemical Company following the 1969 filter housing fire at Rocky Flats determined that the
minimum water supply for the system should be hydraulically calculated to provide at least
0.25 gpm/ft2 over the entire face area of the filters, or one gpm per 500 cfm of airflow,
whichever is greater.
The automatic deluge system uses standard deluge-type sprinklers installed on the piping at a
minimum spacing of 4-feet. The system should be activated by the rate-compensated heat
detection system, linear heat detection or by pilot-operated sprinklers. A manually operated
release is also provided on the deluge valve in the event a malfunction in the releasing system
occurs. The use of corrosion-resistant deluge sprinklers and piping should be considered for all
installations.
5.1.3.19 Water Mist Systems
Section 164
Water mist technologies have been developed that use fine water sprays to efficiently control,
suppress, or extinguish fire using limited volumes of water. Their use in a specific confinement
ventilation system should be carefully analyzed in the FHA. See NFPA 750, Standard on Water
Mist Fire Protection Systems. The challenge with this type of system are the effects of the
facility ventilation on the ability of the mist to extinguish the fire via heat absorption and/or
smothering.
5.1.3.20 Sprinklers within Ductwork
Provision of wet-pipe or deluge sprinkler systems within ducts or filter housings is the exception
rather than the rule, however, deluge sprinkler systems are routinely provided on carbon-filled
adsorption systems in nuclear power reactors. On deluge systems for adsorption filters, fog
nozzles with as fine a droplet-size distribution as possible are recommended for maximum
cooling and smoke particulate capture. To limit the volume of water discharged, consideration
should be given to an automatic recycling (re-setting) deluge system.
5.1.3.21 Demisters and HEPA Filters
Water protection for HEPA filters has been controversial due to concerns about water plugging
of the filters. The research that led to this concern was based on conditions that are not
DOE-HDBK-1169-2022
230
reflected in an actual filter installation. Specifically, the research involved soaking filters in pans
of water. However, in a properly designed confinement ventilation system, demisters
significantly reduce the amount of water from the automatic deluge system reaching the filters.
Manual deluge systems are only operated after the filters begin to combust. Consequently,
water damage is no longer an issue. This topic is further discussed in DOE-STD-1066-99.
5.1.3.22 Fire Department Standpipe Systems
Because the possibility of a fire affecting the filters cannot be entirely eliminated; some
provision for manual firefighting via a standpipe system (meeting the requirements of NFPA 14,
Standard for the Installation of Standpipe and Hose Systems, is necessary. The fire department
will almost always use its own hose packs.
The use of a hose stream can only be considered when all other automatic and manual
safeguards have been determined to have failed. At this point, the filters cannot be saved,
however, hose streams may prevent fire spread to subsequent stages of filters and avoid failure
of the final filter stage that could release contamination. In addition, a hose stream can serve to
prevent further damage to the filter mounting frames and housing, the duct, or the building.
Similar observations can be made for the common types of sprinkler systems, both automatic
and manually actuated, if they are installed inside the filter housing.
5.1.3.23 Water Runoff Collection
Facilities protected by sprinklers or deluge systems should have a provision to collect and
dispose of water used for fire extinguishing. In addition, design of the water drainage system
has to be consistent with the characteristic of water as a neutron moderator. In some cases,
water collection for filter plenums may consist of a criticality-safe water collection tank. Also,
the plenum drains may have a 2-inch lip that will permit up to two inches of water to collect in
the plenum prior to being discharged to the collection tank. This permits short duration flows to
be captured within the plenum and allowed to evaporate.
5.1.3.24 Gaseous Agent Systems
Section 165
Some spaces external to the ductwork are protected with gaseous fire suppression systems.
There are NFPA standards for the design of these systems that include Halon alternatives and
carbon dioxide systems. Competent technical persons should be consulted to design these
systems.27 The same challenges exist for these systems in nuclear facilities where the
ventilation from the space has a significant impact on maintaining the concentration of the gas
within the space. Typical industrial occupancies the ventilation system is isolated prior to the
activation of the system. For nuclear facilities, isolation of the ventilation system is nearly
always not advisable (or permitted).
5.1.3.25 Flammable Gas Detection
If flammable gases are used, the FHA may require flammable gas detection equipment in the
ductwork or filter housings. The installed gas detectors should be connected to an alarm system
located at a continuously attended position to ensure immediate corrective actions are taken
27 Because CO2 is an asphyxiant, its use is discouraged in the DOE complex.
DOE-HDBK-1169-2022
231
when elevated flammable vapor concentrations are detected. The effective design of systems
to detect flammable gases depends on the gases themselves, the airflow characteristics within
the confinement ventilation system, the actions that should be taken in response to
unacceptable concentrations of flammable gases, and many others. Systems that do not
adequately address such issues will either not work or will provide false alarms on a frequent
basis which can be an equally unacceptable situation. Competent technical persons who are
knowledgeable of the hazards present and the design of such systems should be consulted to
design these systems.
5.1.3.26 Protection of Carbon-Filled Adsorption Systems
To prevent loss of confinement for radioactive iodine and iodine compounds, carbon-bed
filtration temperatures should be maintained at a level where impregnants and trapped
radioiodine cannot desorb. This requires the bed(s) to be large enough that specific loadings of
iodine cannot exceed 2.5 mg/g of carbon, and that airflow through the bed can be maintained
at some level in excess of 6 (preferably 10) linear fpm. If bed temperatures can be maintained
below the level where desorption of impregnants and trapped radioiodine takes place, carbon
ignition is unlikely. If a fire should initiate, however, total flooding or dumping of the carbon
into a container of water is currently the only effective means of extinguishing a carbon bed
fire. Carbon dioxide and gaseous nitrogen are ineffective against activated carbon fires because
the fire feeds on the oxygen adsorbed in the pores of the carbon, and the quantity of liquid
nitrogen required to provide effective cooling would be unavailable in most cases.
Combustible Metal Fires
Metal fires, particularly fires in water-reactive metals such as sodium, present unique
challenges. Water and extinguishing agents such as the Halon alternatives cannot be used, and
inert atmospheres such as nitrogen and carbon dioxide require the total exclusion of oxygen to
be effective. Combustible metal fires should be addressed in the operating space before it can
reach the ducts or filters. However, most of the fire-extinguishing agents that are effective
against such fires produce copious clouds of dust that, when released, rapidly threaten to plug
the duct entrance filter. This in turn threatens over pressurization of the glovebox or hot cell,
resulting in blowback of contamination to occupied spaces of the building. Carbon
microspheres and magnesium oxide (sand) have been shown to be extremely effective against
plutonium, sodium, uranium, sodium-potassium, magnesium, aluminum, lithium, and other
types of fire that produce intense heat. The material can be dispensed automatically or
manually and produces essentially no dust when dispensed. In addition, it has negligible
chloride content (and so poses no threat to stainless steel equipment and cells), is very easy to
cleanup, is inexpensive, and is readily available.
Section 166
When metals such as aluminum are being processed that have the potential to produce
explosive dust, the potential presence of such dust in both the airstream and inside the filter
enclosure should be documented in the FHA. Appropriate hazard controls should be provided
as necessary—duct-entrance filters alone will not prevent dust from entering the ducting.
DOE-HDBK-1169-2022
232
5.1.3.27 Filter Assemblies in Plywood Enclosures
Some smaller HEPA filter assemblies are purchased as a single package. These are often self-
contained in assemblies constructed of plywood or other wooden composite material. These
assemblies have male duct connections on their inlet and discharge sides and are easily
dropped into place by clamping existing ducts onto them. Given the lack of fire resistive
properties of these filter assemblies, it is not recommended that they be used in new
construction.
5.1.3.28 High-Efficiency Metal Fiber Filter Systems
High-efficiency metal fiber (HEMF) filter systems have been commercially available in the U.S.
since the mid-1980s. They are made of sintered stainless-steel fibers that are welded into steel
housings and steel frames. ASME AG-1 Sections FM, High-Strength HEPA Filters, and Section FI,
Metal Media Filters, contain information and guidance on these types of filters. Future editions
of ASME AG-1 will contain additional information on emerging technologies, such as Section F,
Ceramic Filters.
In contrast to HEPA filters, HEMF filters are not weakened by moisture impingement. They can
also operate for longer time periods and in hotter conditions than HEPA filters because the
metal filters contain no flammable components and are inherently resistant to high
temperatures. However, the finely divided filter media in a metal filter will not resist a direct
flame impingement. The resistance of the metal filter to moisture and heat makes this filter
attractive for fire protection purposes. Because the use of HEMF filters is relatively new to the
DOE community, only limited experiential data on the behavior of these filters in actual fires is
available. They are also very expensive to purchase and operate.
5.1.3.29 Radioiodine Absorber Air Cleaning Systems
Although much discussion in the nuclear community has been generated in the past 40 years
regarding fire protection of absorbers, little consensus and few conclusions have been reached
about the proper method of extinguishing fires in absorbers with combustible material.
Available methods include: (1) using a combination of manual and automatic water spray
systems, (2) limiting airflow to the absorbers, and (3) using alternative noncombustible
absorber media (e.g., silver zeolite). Absorber air cleaning systems are often used in nuclear
reactor emergency ventilation confinement systems where they are frequently referred to as
charcoal- or carbon-type filters. Other inorganic absorber materials are available for absorber
media, including silver oxide, silver nitrate, aluminum silicate, and silver zeolite. It is generally
accepted that, as a minimum, absorbers should be provided with fire detection.
For carbon-type filters, American Nuclear Insurers, an insurance carrier for nuclear power
plants, recommends the following fire protection:
• Charcoal filters should have a hydraulically designed, automatic water spray system that
uses directional, solid-cone spray nozzles controlled by an approved deluge valve. The
system should be capable of being manually actuated from a suitably remote location.
Section 167
DOE-HDBK-1169-2022
233
• Spray nozzles for horizontal beds or drawers should be oriented above each bed or
drawer and should be designed to distribute water evenly across the top of each bed or
drawer at a minimum density of 0.25 gpm/ft2.
• Spray nozzles for vertical beds should be oriented at the top of the bed and should be
designed to distribute water evenly across the top of the bed at the rate of 3.2 gpm/ft2
of charcoal bed.
• A supervised, fixed-temperature detection system should be provided and connected to
an annunciator in the control room. The detectors should be located on the
downstream side of the charcoal bed to facilitate timely, automatic operation of the
spray systems. The spray system should be equipped with a local alarm and should be
connected to an annunciator in the control room. The airflow should terminate (with
fan isolation) upon water activation.
• For the pressure vessel-type charcoal filter, where a shut-off bypass arrangement is
employed around each tank, an automatic water spray system is not required. A hose
connection should be available on the side of the tank to allow the introduction of
water.
Once carbon in adsorber beds becomes wet, either by actuation of the water sprays, moisture
in the air stream, or by any other means, it is extremely important to remove all of the carbon
and wash the trays of any residual carbon, as corrosion of the trays will begin to occur and will
be accelerated with time.
5.1.3.30 Deep-Bed Fiberglass Filter Systems
Early designs of deep-bed, fiberglass filters did not address filter media replacement. Fiberglass
filters plug over time, resulting in combustible deposits that may contribute to fire risk. It is
generally accepted that water applied to this type of filter media will extinguish the fire.
Precautions should be taken when water is applied to filter media containing radioactive
material to prevent the water from being released to the environment.
5.1.3.31 Deep-Bed Sand Filter Systems
For the most part, DBS filters are fire-resistant, chemically inert, and require no special fire
protection systems. HEPAs have been traditionally installed prior to the sand filters for fear of
sand fires carrying over and plugging the HEPAs.
Since plugging is a “worst case” scenario for both HEPA and DBS filter arrangements, both
require mitigation measures. It has been largely accepted that DBS filters, while expensive to
construct, decontaminate, and demolish, offer improved performance in their ability to operate
in the presence of high temperature, heat, and fire products.28
28 Some tests have been conducted on DBS smoke and soot loading. See Schurr, G. A., D. B. Zippier, and D. C.
Guyton, 1972, “Deep-Bed Filter Tests,” 12th Atomic Energy Commission Air Cleaning Conference, USAEC Report
CONF-720828. Access at http://isnatt.org/Conferences/12/session10a.pdf.
DOE-HDBK-1169-2022
234
5.1.3.32 Self-Cleaning Viscous Liquid Filters
This type of filter uses a viscous liquid for cleaning purposes. These filters should be avoided
where radioactive materials are handled because they produce radioactive sludge that requires
disposal. They also require special fire protection systems because of the combustible nature of
the liquid.
5.1.3.33 Electrostatic Precipitator Prefilter
Section 168
Another type of medium efficiency filter used at DOE facilities is the ESP medium efficiency
filter. This medium efficiency filter imparts an electrical charge to particles in the airflow
stream, causing them to adhere to collector plates. The ESP medium efficiency filter has been
used to extend the life of HEPA filters when processes involve larger-diameter airflow particles.
An ESP medium efficiency filter provides some fire protection, as long as the particles resulting
from the combustion products of a fire can be properly collected on the filter throughout the
fire. Most commercially available ESP medium efficiency filters cannot catch the smaller
airborne particles and smoke particles associated with a burning fire. However, more work
needs to be done to understand which particle sizes associated with fire can be effectively
filtered by an ESP medium efficiency filter. When ESP medium efficiency filters are used, they
should be made of noncombustible materials and, as with any medium efficiency filter, the user
should pay careful attention to preventing dust loading on the medium efficiency filter during
use. In addition, ESP medium efficiency filters should not be used where explosive
concentrations of gases or dusts are present.
5.1.3.34 Ceramic HEPA Filters
A ceramic HEPA filter is designed to be noncombustible, corrosion resistant, and compatible
with high temperatures and moisture. These filters have the ability to significantly increase
filter life span, increase storage life and reduce life cycle costs. These filters are currently under
development at the LLNL, the Idaho National Laboratory, and at other DOE sites.
5.1.4 Fire Protection Concepts for Gloveboxes
Fire protection and prevention in gloveboxes is mainly accomplished via the following methods:
• Using noncombustible construction materials. (For information on gloves and windows,
which are more vulnerable to fire damage, refer to DOE Standard 1066-99.1, and AGS
GO10-2011, Standard of Practice for Glovebox Fire Protection.)
• Adhering to acceptable housekeeping policies and procedures.
• Avoiding the use of flammable materials within the box wherever possible. (When no
suitable nonhazardous substance can be substituted, the amount of flammables is
limited to the minimum required for immediate use. The containers used for flammable
substances are safest available for the planned operation.) A Fire Hazards Analysis
should be performed by a qualified fire protection engineer establishing the maximum
amount of flammable liquid permitted such that the glovebox atmosphere is kept at less
than 25% of the lower explosive limit.
DOE-HDBK-1169-2022
235
• Maintaining a current in-box material inventory. (The box is not used for storage. Boxes
usually are inappropriate for storage, especially for chemicals.)
• Establishing a safer, nonoperative box configuration and periodically checking it to
ensure that nonoperating boxes are in a safe condition. (Precautions include isolating
boxes by closing fire stops, checking through-flow, checking port covers, disconnecting
electrical equipment, and removing corrosives.)
• Designing the box with down-draft ventilation (high air inlet, low outlet) to inhibit
combustion while still purging the box.
• Providing a protective (inert) atmosphere. (This measure is listed last because those
preceding it apply to all gloveboxes, whereas inerting is used only when there is too
much risk involved in operating without a protective atmosphere. Assessing the degree
of risk involved in an operation is often a subjective evaluation.)
Section 169
Other methods may be used if analyzed and supported in the FHA. Useful references include
the 1999 edition of DOE-STD-1066 and AGS GO10-2011, Standard of Practice for Glovebox Fire
Protection.
5.1.4.1 Protective Atmospheres
The inerting atmosphere system is designed for continuous operation, whereas the
extinguishing system usually has a one- or two-shot, single-incident application before
reservicing is required to return the system to the ready state.
Inerting with smothering agents may require that less than one percent oxygen be present in
the glovebox atmosphere. Process and product-purity considerations may require as little as
100 ppm29 of total atmospheric impurities within the glovebox for successful operation. Since
many of the detailed considerations are similar for high-purity and fire protection inerting, and
because of the widespread application of high-purity inerting, most of this discussion will
involve high-purity systems.
Inert-atmosphere gloveboxes that contain radioactive material may be operated at pressure
differentials ranging from 0.3 up to 1.5 in.wg negative pressure relative to the surroundings.
The gas flow rate is usually determined by the atmospheric purity required and the purity of the
incoming gas. The box atmosphere purity can be compromised by air leakage into the box or
into service connections, as well as leakage from process equipment in the box.
Filter installation requirements in inert atmosphere gloveboxes can be more stringent than
those for air-ventilated boxes because acceptable box air leakage rates can be justified by
Helium Mass Spectrometer Detector Leak Analysis with low helium leakage concentrations and
maintaining very low PPM oxygen and moisture levels inside the gloveboxes. Joints and
fastenings between items of equipment and materials (gaskets and seals) should have
extremely low gas permeability. Full-welded joints are recommended for all permanent
29 Parts per million
DOE-HDBK-1169-2022
236
fixtures. Gasketed joints may deteriorate in service, imposing continuing costs for periodic
testing and repair.
Low-leak systems require quality construction for all components including boxes, filters, and
associated ducts. Any in-leakage associated with the filter mounting or connecting duct will
adversely affect the quality of the inert atmosphere that can be maintained in the box, and thus
the cost of inert gas purification. Penetrations should be minimized in both number and size.
The use of smaller HEPA filters allows smaller ports for maintenance. Filter changes should be
planned for times when other maintenance operations (routine or special) are taking place
inside the box to reduce interruptions to operations, to reduce the loss of inert gas, and to
minimize the time required to recondition box spaces.
For fire protection, the preventive step of inerting is more satisfactory, albeit more expensive,
though much less than the cost of extinguishing a fire if it were to occur. For normal
combustibles an oxygen level of 10% or less is recommended. However, oxygen should be
reduced below one percent before it fails to support the oxidation of some pyrophoric metals.
The use of dry air (relative humidity less than 20 percent) reduces the hazard of pyrophoric
metal fires but does not eliminate it. Moisture in the presence of heated pyrophoric or reactive
metals, such as finely divided plutonium, increases the possibility of explosion by generating
hydrogen.
Section 170
The suitability and cost of an inert gas for the process are significant factors when selecting this
type of fire control. The gas flow rate in most inert gas boxes is kept as low as possible to be
consistent with required box-atmosphere purity levels; low-capacity filters are frequently used.
The inert gas may be purged on a once-through basis or recirculated through a purification unit.
A word of caution concerning commercially available (off-the-shelf) recirculating gloveboxes: on
one occasion at a DOE installation, there was a problem with oil mists developing in the
recirculating pumps and being circulated along with the inert gas. Off-the-shelf items cannot be
used in a confinement-type ventilation system without evaluation, nor can they be applied as
“black boxes” by those responsible for operational safety.
5.1.5 Operations and Maintenance Practices for Fire Protection of Confinement Ventilation
Systems
5.1.5.1 Essential Elements
The success of a confinement ventilation system to continue to provide its intended function
during a fire situation depends on the reliable operability of the procedures, systems, and
barriers as they were designed. To retain that design capability, it is critical that the inspection,
testing and maintenance of these systems be accomplished by qualified personnel on an
established schedule. Procedures should be practiced, and systems should be regularly
inspected to identify procedural issues that may require revision of the maintenance practices
and operational procedures.
DOE-HDBK-1169-2022
237
5.1.5.2 Fire Prevention
The most critical aspect of fire prevention is fuel/combustible control. The storage of any
extraneous combustible materials in filter enclosures or areas where radioactive materials are
being handled should be strictly prohibited.
Procedures for the use of flammable liquids and gases should be in place and adhered to.
Quantities of flammable liquids and gases should be limited to only those required to perform
the task.
Accumulation of dust and debris inside the confinement ventilation system ductwork over long
periods of operation increases the consequences of any fires that might occur. Periodic cleaning
is required to eliminate the presence of undesired fuel.
Appropriate procedures and controls should be implemented to prevent the rapid oxidation of
pyrophoric radioactive materials. Much experience exists on the initiation of fires in nuclear
facilities that involve or affect the confinement ventilation system. The lessons of the past
should be applied to prevent fire from occurring in or affecting confinement ventilation
systems.
5.1.5.3 Procedures
All hazards and necessary controls should be delineated in existing operational procedures. Fire
protection procedures should complement a facility’s safety documentation required by law or
contractual obligations.
5.1.5.4 Inspection, Testing, and Maintenance
Inspection, testing, and maintenance requirements for fire detection and suppression systems
are contained in the NFPA standards. Proper implementation demands a program that either
complies with the NFPA standards or employs a fully justified alternative approach that
provides an equivalent degree of reliability.
Section 171
Establishing and implementing an effective inspection, testing and maintenance program is
critical to ensure all fire protection systems associated with the nuclear confinement system
will operate as intended. The NFPA Codes and Standards establish the inspection, testing, and
maintenance criteria and schedules. In most cases adherence to these codes and standards is
required by statute, regulation, or Order. The established schedules can be reduced or
extended based on mathematical analysis acceptable to the Authority Having Jurisdiction.
Limited life materials should be identified and replaced according to an established plan, and in
the accordance to its listing and or approval.
It is important that water-based fire suppression systems be designed such that they do not
have to discharge water on HEPA filter media. Any exposure to water will significantly weaken
the filter media and can result in an undesired loss of filtration due to the filter media physically
failing. Systems should be designed such that they can be discharge tested without having to
actually spray water on the filter media. The design may include covering the filters with plastic,
which may also require the isolation of the ventilation flow.
DOE-HDBK-1169-2022
238
5.1.5.5 Impairment Planning
A program should exist to handle situations where fire detection and suppression systems are
impaired. Plans should be developed and instituted to guide facility operations when these
systems are not functioning as they should. Impairment plans also should exist for other critical
facility systems. The occurrence of an impairment is not the time to develop such plans.
All impairment plans should be analyzed to identify and control to the greatest possible extent
the hazards that may exist under a given condition. Impairment programs also identify
required compensatory measures such as fire watches and temporary water feeds.
5.1.5.6 Modifications
Modifications in a nuclear facility should follow the protocols for Unreviewed Safety Question
determination in accordance with the work control process. This is a somewhat roundabout
means of identifying the impact to the established safety basis and all that goes with that, but it
is what the current culture understands and accepts. Configuration control should be
maintained when modifications are made so that all changes are tracked across all affected
documentation and all impacts are identified and understood.
5.1.5.7 Emergency Planning
The successful mitigation of a fire in a nuclear facility containing a confinement ventilation
system requires emergency planning and exercises involving all entities that may be called on
to mitigate a fire situation. Post-fire recovery plans should exist to aid in the resumption of
work in the facility after a fire.
5.1.5.8 Technical Safety Requirements Tie-in
Maintenance and operational procedures may be formalized in the nuclear facility’s TSR.
Generally, TSRs that apply to fire protection systems will define the operability of the particular
system. Operability of the system is nearly always based on the inspection, test, and
maintenance criteria within the NFPA Codes and Standards (for example, NFPA 25, 72, 80, 750
and 2001). Also, within the TSR there are compensatory measures dealing with inoperability of
a fire protection system. Compensatory measures might include a fire watch, termination of
operations, and stopping of hot work.
5.1.5.9 Quality Assurance
Section 172
All aspects of operations should be clearly linked to the facility’s QA Program.
5.1.5.10 Assessments
Periodic management and independent assessment are necessary to ensure that established
requirements are adequate and are properly implemented. Refer to Attachment 2 of DOE
420.1C for the required frequencies of such assessments.
5.1.6 Generic Firefighting Procedures
The following recommendations apply to firefighting procedures and instructions. They provide
a strategy that minimizes the likelihood of losing filtered, forced ventilation during a fire. These
procedures were derived from extensive work at Rocky Flats and are included here because
DOE-HDBK-1169-2022
239
they are generically applicable to all DOE facilities where active fire protection measures are
installed for filter housing protection.
A special need for nuclear facilities with confinement ventilation systems is smoke venting.
Although smoke cannot be vented to the exterior of a building, there are methods of moving
smoke concentrations from one place to another to enable more rapid application of manual
suppression.
5.1.6.1 Control Ventilation Configurations, Volumes, and Flow Rates in the Field
An individual who is responsible for ventilation control (and successors or alternates in case of
unavailability) should be established in the facility emergency planning documentation. This
individual should work in consultation with the fire department sector officer (or incident
commander) stationed at incident command, in the control room, or at the housing/plenum to
ensure a fire emergency will be successfully mitigated, with minimal impact to the nuclear
ventilation system.
DP changes in the initial filter stages should be continuously monitored, even if the DP gauge
readout is exceeded. Most gauges have a maximum capability of 4 to 6 in.wg, but a rapid drop
from an off-scale high reading to a lower reading will confirm stage failure, as will a significant
rise in DP for the next downstream stage. Attention should be focused on the first stage and
the next downstream stage until a first stage failure is indicated. A rise in DP may be due to
progressive filter plugging from fire particulates or wetting of the filters from deluge spray.
Because the initial filter stages are usually (but not always) viewed as sacrificial, the DP may be
allowed to rise to the maximum achievable by the fan. If there is only one stage of filtration,
then this is not applicable.
For housings/plenums with four stages, the second- and third-stage DP should be monitored at
the first indication of a loss of first-stage filter integrity. The third and fourth stage DP should be
monitored if the second stage fails.
Ventilation on the affected housings/plenums should be throttled when DP across the final
filter stage reaches 2 to 4 in.wg (4 in.wg is the current filter change-out criterion for normal
operation).
Failure of initial stages and erosion of margin in the final filter stage is permitted if continued
ventilation is necessary to support effective firefighting in the facility. If the fire department
officer in charge or incident commander judges that the ventilation system is no longer
providing a substantial advantage in controlling or containing the fire, and the emergency
commander (generic term) validates that position, action should be taken to protect the
ventilation (for example, ventilation should be discontinued at 2 in.wg DP on the final filter
stage). Throttling, if selected, should be performed in a manner that maintains the actual DP
reading on scale within the 2- to 4-in.wg readings at all times. In no case should ventilation be
continued when the differential pressure threatens failure of the final filter stage.
Section 173
At the first indication of an explosion, the first-stage DP should be monitored for a rapid or
complete loss of DP as an indication of failure. The second-stage DP should be immediately
monitored under such conditions and the filters should be visually inspected if possible. If the
DOE-HDBK-1169-2022
240
second-stage DP is less than 0.5 in.wg, or greater than 4 in.wg, or if there is visible damage to
the second stage, ventilation on the affected housing/plenum should be discontinued. The
decision to isolate ventilation should be clearly preplanned and well thought out. Explosive
conditions that could clearly impact multiple stages are judged to present too great a risk to any
remaining stage to warrant any attempts to maintain active ventilation.
Ventilation should be restored to an affected housing only by the decision of the Emergency
Commander or an approved Recovery Plan. Restoration of ventilation should be considered
likely to result in a forced convection release from the facility unless other recovery efforts have
confirmed no airborne contamination is present in the facility. The decision to restore
ventilation also should be preplanned and well thought out.
5.1.6.2 Activation of the Manual Deluge System
The manual deluge system provides an important emergency capability should the first-stage
filters be in danger of being consumed by fire. However, manual deluge system activation will
likely result in loss of the first stage of filters either through plugging or media failure.
Consideration may be given to intermittently flowing the deluge systems with the fans shut
down when doing so for short time periods. Before actuating the manual deluge system, the
following recommendations should be followed:
• Direct impingement of flame or embers on the first stage filters should be visually
confirmed, if possible.
• The manual deluge system should be activated only when it is clearly required, because
activation is likely to damage the filters, could cause plugging, and could isolate
ventilation. Early activation of manual deluge as a precautionary measure is considered
imprudent. If the viewing ports are accessible, they should be used to facilitate
confirmation of filter integrity (i.e., visible flaming or smoldering of filter media). Where
viewing ports are inaccessible, the inner access doors to the airlocks should be used as
an alternative to viewing ports.
• The manual deluge system should be activated only when the fire department officer in
charge decides it is necessary, based on a determination from the available evidence
that flame is present in the first stage of filters.
• The person in charge of ventilation control at the facility should be authorized to initiate
the manual deluge system as necessary prior to fire department arrival. Possible filter
plugging and shutdown of ventilation should be anticipated once manual deluge is
activated.
• The initial filter stages should be monitored for evidence of plugging or blowout of the
first-stage filter (DP changes) and for evidence of either particulate buildup/wetting (DP
changes) or flame (visual) on the second and subsequent stages. If flame is confirmed on
any downstream stage, all fans connected to the affected housing should be secured
immediately.
DOE-HDBK-1169-2022
241
5.1.6.3 Deluge System Flow Times
The following recommendations address when the deluge system flow should be terminated.
Section 174
• The housing deluge system flow should be discontinued upon visual verification by the
fire department incident commander or other authorized personnel if:
- (automatic system) there is no visible smoke in the housing upstream of the spray
nozzles and temperatures in the filter housings have dropped to or are dropping to
safe levels; or
- (manual system) the fire involving the first stage is extinguished and the spray
duration is judged to have sufficiently cooled the filter media and frame.
• Only the fire department incident commander or other authorized personnel should
terminate the flow prior to meeting these criteria. Ventilation should only be restored
to the affected housing following a decision by Emergency Commander or in accordance
with an approved Recovery Plan.
• If filter plugging is preventing effective ventilation, removal of the plugged media should
restore ventilation. However, restoration of ventilation is likely to result in a forced
convection release from the facility unless other recovery efforts have confirmed there
is no airborne contamination in the facility.
The removal of plugged filter media in a confinement ventilation system during a fire situation
is fraught with hazards, of course, and should only be done in extreme circumstances.
5.1.6.4 Manual Activation of the Automatic Deluge System
Early activation of the automatic deluge system could increase the potential for the first filter
stage to survive. For this reason, the automatic deluge system may be activated manually
rather than waiting for high-temperature actuation where early activation provides an
advantage. The decision to activate the system should be made by the fire department incident
commander and/or the authorized person in charge of ventilation control at the facility based
on initial assessment of the fire condition.
Small fires that are under control and expected to be quickly extinguished would not challenge
the HEPA filters sufficiently to warrant activation of the system. In addition, the limited
available data indicate that early activation is not beneficial in reducing the potential for smoke-
induced plugging for those housings equipped with fog jet nozzles for automatic deluge, and
the procedures should not call for early activation of the automatic deluge system for those
housings. Extensive preplanning should be conducted to define as much as possible the
situations in which the automatic deluge system would be manually actuated.
5.1.7 References
1. Alvares, N. J., 1986, “Assessment of Thermal Damage to Polymeric Materials by
Hydrogen Deflagration in the Reactor Building,” ACS Symposium Series 293 (the Three
Mile Island Accident).
DOE-HDBK-1169-2022
242
2. Bergman, W., W. D. Kuhl, W. L. Russel, R. D. Taylor, H. D. Hebard, A. H. Bierman, N. J.
Alvares, D. G. Beason, and B. Y. Lum, 1980, “Electrofibrous Prefilters for Use in Nuclear
Ventilation Systems,” Lawrence Livermore National Laboratory, Livermore, CA.
3. ChemRisk®, 1992, Health Studies on Rocky Flats, Phase I: Historical Public Exposures,
Reconstruction of Historical Rocky Flats Operations & Identification of Release Points,
Project Tasks 3 & 4, McLaren/Hart, Alameda, CA, August.
4. ChemRisk®, 1992, Health Studies on Rocky Flats, Phase I: Historical Public Exposures,
Draft Report, Estimating Historical Emissions from Rocky Flats, Project 5, McLaren/Hart,
Alameda, CA, November.
5. DOE, 1994, Primer on Spontaneous Heating and Pyrophoricity, DOE-HDBK-1081-94,
Washington, DC, December.
Section 175
6. EPRI (Electric Power Research Institute), 1982, Categorization of Cable Flammability:
Intermediate-Scale Fire Tests of Cable Tray Installations, EPRI NP-1881, Factory Mutual
Research Corp., Norwood, MA, August.
7. EPRI (Electric Power Research Institute), Hill, J. P., 1982, Fire Tests in Ventilated Rooms,
Extinguishment of Fire in Grouped Cable Trays, EPRI NP-2660, Factory Mutual Research
Corp., Norwood, MA, December.
8. Gewain, R., B. Campbell, J. Shanley Jr., J. Scheffey, “Protection of Duct Openings in Two-
hour Fire Resistant Walls and Partitions,” ASHRAE Journal, 1990, Vol 32, Num 5; 16-26;
American Society of Heating, Refrigerating and Air Conditioning Engineers, Inc., Atlanta,
GA.
9. Gewain, R., J. Shanley Jr., P. DiNenno, J. Scheffey, and B. Campbell, “Evaluation of Duct
Opening Protection in Two-hour Fire Walls and Partitions,” Fire Technology, Vol. 27,
pages 204–218 (1991), National Fire Protection Association, Quincy, MA.
10. Gottuk, D. T. and R. J. Roby, 1995, “Effect of Combustion Conditions on Species
Production,” Section 2, Chapter 7, SFPE Handbook of Fire Protection Engineering, 2nd
Edition, National Fire Protection Association, Quincy, MA.
11. Kovach, J. L., 1987, “Review of Fires and Fire Control Methods for Nuclear Air Cleaning
Systems,” 19th DOE/NRC Nuclear Air Cleaning Conference, Seattle, WA.
12. NRC, Chavez, J. M. and D. Lambert, 1986, Evaluation of Suppression Methods for
Electrical Cable Fires, SAND 83-2664, NUREG/CR-3656, NRC, Washington, DC, October.
13. NRC, Dube, D. A., 1987, Fire Protection Research Program for the Nuclear Regulatory
Commission, 1975-1981, SAND 82-0431, NUREG/CR-2607, NRC, Washington, DC, April.
14. NRC, Recommendations Related to Brown’s Ferry Fire, NUREG-0050, Washington, DC.
15. NRC, Williamson, R. B. and F. L. Fisher, 1981, Tests and Criteria for Fire Protection of
Cable Penetrations, SAND 81-7160, NUREG/CR-2377, NRC, Washington, DC, October.
16. Pryor, Andrew J., “Brown’s Ferry Revisited,” 1977, Fire Journal, Vol. 71 #3, May.
DOE-HDBK-1169-2022
243
17. Ricketts, C. I., V. Rüdinger, and J. Wilhelm, 1990, “Aspects of the Increase in Pressure
Drop of High-efficiency Particulate Filters under Fog Conditions,” Nuclear Technology,
Vol. 92, November/October.
18. Sawyer, et al., “Cable Fire at Brown’s Ferry Nuclear Plant,” Fire Journal, Vol. 70 #4, July
1976.
19. White, P. A. F. and S. E. Smith, 1962, Inert Atmospheres in the Chemical, Metallurgical
and Atomic Energy Industries, Washington: Butterworths.
DOE-HDBK-1169-2022
244
5.2 Natural Phenomena Hazards
5.2.1 Introduction
This section of the Handbook provides guidance for meeting requirements found in Section 5.2
of DOE-STD-1269-2022, Air Cleaning Systems in DOE Nuclear Facilities.
5.2.2 DOE Order 420.1C and DOE Guide 420.1-1A
Safety class and safety significant air cleaning systems are required to meet the applicable
Natural Phenomena Hazards (NPH) requirements of Chapter IV of Attachment 2 to the Order,
Natural Phenomena Hazards Mitigation. Guidance on applying these Order requirements to
ventilation systems is provided in DOE Guide (G) 420.1-1A, Section 5.4.12, Design of Ventilation
Systems, and Table A-1, Confinement Ventilation Systems Design and Performance Criteria. 30
5.2.3 DOE-STD-1020-2016 and DOE-HDBK-1220-2017
Guidance and best practices for applying the NPH requirements of DOE-STD-1020-2016 can be
found in DOE-HDBK-1220-2017, Natural Phenomena Hazards Analysis and Design Handbook for
DOE Facilities (the “NPH Handbook”). For example, the following guidance on mitigating the
hazards of volcanic ashfall with respect to ventilation systems is provided in Section 8.4 of the
NPH Handbook:
Section 176
Section 8.4.6 of the Standard lists some considerations in ventilation design; paramount
is filter loading. Designs to accommodate ashfall should account for the airborne
concentration, small particle size, and duration of an ashfall event. As noted above in
Section 8.3.1, airborne concentration estimates are likely to be imprecise, and a range
of values may need to be considered. The small size and abrasiveness of volcanic ash
particles may pose unique hazards that should be evaluated in ventilation system
design. Ash deposits can be easily re-suspended, so the effects of an ashfall event are
likely to linger in a region for days or weeks. In accordance with Section 8.4.6 of the
Standard, any effects of ashfall and volcanic gases on other mechanical and electrical
systems will also be evaluated.
Section 11 of the NPH Handbook contains an extensive list of technical references and national
consensus standards dealing with identifying, analyzing, and mitigating NPH hazards.
5.2.4 Additional References
1. Seismic Restraint Manual: Guidelines for Mechanical Systems, 3rd edition 2008,
ANSI/SMACNA 001-2008. This document consists of guidelines showing designers and
contractors how to determine the correct seismic restraints for sheet metal ducts,
piping and conduit used in ventilation systems.
2. ANSI/ASHRAE Standard 171-2008, Method of Testing Seismic Restraint Devices for
HVAC&R Equipment.
30 Note especially the table’s items under the headings “External Events” and “Other Natural Phenomena Events.”
DOE-HDBK-1169-2022
245
3. ASHRAE 2012, Practical Guide to Seismic Restraint, 2nd Edition.
4. IAEA, 1987, Design of Off-gas and Air Cleaning Systems at Nuclear Power Plants.
5. IAEA, 1993, Off-gas and Air Cleaning Systems for Accident Conditions in Nuclear Power
Plants.
6. Yow, Holloman and Algar, “Seismic Qualification of HEPA Filters by Test in an Actual
Operating Condition,” #16-1175, Proceedings of the 16th DOE/NRC Nuclear Air Cleaning
Conference, 1980.
(For a more extensive list of NPH references, see DOE-STD-1020-2016)
5.3 Occupational Safety and Health
5.3.1 Introduction
Workers operating and maintaining large ventilation systems in a nuclear facility are exposed to
a variety of health and safety risks. Some of these risks are:
• Confined space entry.
• Excessive noise.
• Excessive heat.
• Hazardous biological and chemical substances.
• Respiratory protection.
• Radiation exposure.
The contractor for every DOE nuclear facility is required to have a documented and DOE-
approved worker safety and health program that addresses these risks, among many others.31
This section of the handbook will identify these requirements, associated guidance, and best
practices for their application to nuclear air cleaning systems.
5.3.2 Confined Space Entry
Working on a ventilation system frequently involves entering into a confined space, thus
activating comprehensive Occupational Safety and Health Administration (OSHA) safety
requirements in 29 CFR §1910.32 Every DOE contractor will have OSHA-compliant confined
space entry policies and procedures.
When applying OSHA rules to servicing ventilation systems, these additional best practices
should be considered:
a) Specific procedures should be developed in advance for each major maintenance
operation. It is not advisable to create the confined space entry procedure as part of the
work permit or plan, because time pressures may result in hasty work.
Section 177
31 See 10 CFR Part 851, Worker Safety and Health Program. (2016)
32 Imposed on DOE contractors by 10 CFR Part 851. OSHA provides a summary of its confined space program at:
https://www.osha.gov/SLTC/confinedspaces/standards.html.
DOE-HDBK-1169-2022
246
b) Each confined space entry procedure should be walked down fully and adjusted when
practical problems are discovered.
c) Each entry procedure should cover all equipment needed to carry out maintenance
operations, including personal protective gear. This equipment should be procured,
checked, and stored well in advance of actual confined space operations.
d) After the conclusion of each confined space operation, lessons learned should be used
to correct and improve the procedure.
e) If a violation of OSHA confined space rules occurs, the cause of the violation should be
investigated and remedial actions taken.
5.3.3 Excessive Noise
The driving machinery of large ventilation systems (chiefly motors and fans) may create high
sound levels in confined spaces. Workers can be exposed to hazardous sound levels when
conducting in-operation repairs or maintenance checks.
OSHA safety requirements for noise hazards are contained in 29 CFR §1910.95, Occupational
Noise Exposure. Additional OSHA guidance and standards in this area can be found at:
https://www.osha.gov/SLTC/noisehearingconservation/. ASHRAE, Handbook of Fundamentals,
Chapter 8, “Sound and Vibration” (2017), provides useful guidelines and best practices.
When applying OSHA rules on the protection of workers from sound hazards, these additional
best practices should be considered:
a) The facility should compile a list of areas where excessive sound levels associated with
ventilation systems are present. Each such area should be surveyed to determine the
necessary level of hearing protection for workers entering the area for any reason.
b) Sound protection procedures for each designated area should specify the protective
equipment required for workers to enter the area, even if just momentarily. This
equipment should be procured, checked, and stored in the vicinity of the area for which
hearing protection is required.
c) Workers at all levels should be cautioned via prominent signs that entry into a high-
noise area without proper hearing protection is prohibited except for emergencies.
d) If a violation of OSHA noise rules occurs, the cause of the violation should be
investigated and remedial actions taken.
5.3.4 Excessive Heat
As in the case of excessive noise, the environment surrounding the machinery of a large
ventilation system in operation can be extremely hot. Moreover, when the machinery is shut
down for repairs or filter replacements, workers may have to work in a hot, stagnant
atmosphere, and may also be required to wear personnel protective clothing that makes heat
stress more likely.
Both OSHA and NIOSH (National Institute for Occupational Safety and Health, part of the
Centers for Disease Control and Prevention) have been active for many years in promoting
protection of workers from excess heat exposure. The most recent development is NIOSH’s
2016 document, “Criteria for a Recommended Standard Occupational Exposure to Heat and Hot
https://www.osha.gov/SLTC/noisehearingconservation/
DOE-HDBK-1169-2022
247
Environments.”33 NIOSH maintains a website dealing exclusively with heat stress.34 Applicable
OSHA requirements are stated on an OSHA web page.35
Finally, 10 CFR Part 851 requires the following:
Section 178
(a) With respect to a covered workplace for which a contractor is responsible, the
contractor must: (1) Provide a place of employment that is free from recognized
hazards that are causing or have the potential to cause death or serious physical harm
to workers …”
When applying OSHA rules on the protection of workers from heat stress, these additional best
practices should be considered:
a) The facility should compile a list of areas where excessive heat associated with
ventilation systems may be present either during operations or during maintenance
tasks. Each such area should be surveyed to determine the necessary level of heat stress
protection for workers entering the area for any reason.
b) Heat stress procedures for each designated area should specify the protective
equipment required for workers to enter the area, even if just for a brief time. This
equipment should be procured, checked, and stored in the vicinity of the area for which
heat stress protection is required.
c) Workers at all levels should be cautioned via prominent signs that entry into a high-heat
area without proper personal protection is prohibited except for emergency situations.
d) If a violation of OSHA heat stress rules occurs, the cause of the violation should be
investigated and remedial actions taken.
5.3.5 Hazardous Biological and Chemical Substances
A 2013 scientific paper authored by Polish researchers reached the following conclusions
concerning the biological and chemical hazards of ventilation systems:36
Regular checking on the cleanliness of the ventilation systems, as well as their periodic
cleaning and, if necessary, disinfection are for the proper maintenance of each system.
During maintenance operations (repairs, cleaning, filter replacement), workers are at
risks associated with exposure to hazardous chemicals and harmful biological agents.
In ventilation systems there are usually favorable conditions for the development of
microorganisms, mainly bacteria and fungi, due to surfaces contaminated with dust
particles or increased humidity caused by ventilation ducts, air filters, thermal
insulation, noise dampers, air coolers, etc. Workers who perform cleaning and
disinfection operations on ventilation systems are exposed to chemical agents through
contacts with contaminants released from sealing materials, adhesives, fireproof lining
33 Available at https://www.cdc.gov/niosh/docs/2016-106/default.html.
34 https://www.cdc.gov/niosh/topics/heatstress/default.html.
35 https://www.osha.gov/SLTC/heatstress.
36 Medycyna Pracy, 2012; 63(6):711-22, “Exposure of ventilation system cleaning workers to harmful biological and
chemical agents.”
DOE-HDBK-1169-2022
248
and insulating materials, volatile organic compounds present in air filters, noise
dampers and insulating materials, as well as with cleaning agents and disinfectants.
Exposure to harmful chemical and biological agents may induce adverse health effects
ranging from allergic reactions and irritation through infections to toxic reactions and
other non-specific symptoms. Due to lack of studies on the exposure of this group of
workers, employers face great difficulties in identifying hazards, which prevent them
from performing an occupational risk assessment.
Section 179
DOE has in place a set of general requirements to address biological and chemical hazards. The
primary requirements are imposed by 10 CFR Part 851, which mandates compliance with 29
CFR 1910, subpart H, “Hazardous Materials,” and with ACGIH, ‘‘Threshold Limit Values for
Chemical Substances and Physical Agents and Biological Exposure Indices,’’ (2016). Section 7 of
Appendix A to Part 851, “Biological Safety,” sets out a program for dealing with biological
hazards. Guidance on controlling chemical hazards may be found in DOE Handbook 1139,
Chemical Management, 2004.
Because addressing the chemical and biological hazards of ventilation systems is a complex
task, it is a best practice to prepare a complete occupational risk assessment that takes into
account the applicable OSHA requirements and the ACGIH standard. This assessment will serve
as the basis for establishing worker controls to protect all facility workers operating or
maintaining ventilation systems. The assessment should be revisited on a regular basis not to
exceed five years.
Ventilation systems should be designed to minimize the need for workers to use respiratory
protection. The goal is to remove the hazard or mitigate the hazard with engineering controls:
provide ventilation so that personal protective equipment is not needed, and administrative
controls to define safe operating conditions. Design considerations include generation rates,
maximum allowable concentrations, the presence of chemicals that can result in combined
impacts, and allowable stack release rates. These design considerations facilitate the calculation
of removal efficiencies, allowable leak rates of ductwork and equipment, required dilution
ventilation airflow in workspaces, and stack flows and concentrations.
5.3.6 Respiratory Protection
Both 10 CFR Part 851 and OSHA’s 29 CFR 1910 (§1910.134, “Respiratory Protection”) address
this topic extensively. Part 851’s citation of American National Standards Institute (ANSI) Z88.2,
‘‘American National Standard for Respiratory Protection,’’ (1992) now refers to a revised
standard, ANSI/ASSP Z88.2-2015, “Practices for Respiratory Protection.”
When applying OSHA rules and ANSI standards on respiratory protection, these additional best
practices should be considered:
a) The facility should compile a list of areas associated with ventilation systems where
respiratory protection for workers may be needed.
b) Respiratory protection procedures for each designated area should specify the
protective equipment required for workers to enter the area, even if just for a brief
DOE-HDBK-1169-2022
249
time. This equipment should be procured, checked, and stored in the vicinity of the area
for which respiratory protection is required.
c) Workers at all levels should be cautioned via prominent signs that entry into a
respiratory protection area without proper personal protection is prohibited except for
emergencies.
d) If a violation of OSHA respiratory protection rules occurs, the cause of the violation
should be investigated and remedial actions taken.
5.3.7 Radiation Exposure and the ALARA Principle
DOE’s requirements for protecting workers from radiation are set out in 10 CFR Part 835,
Occupational Radiation Protection. Relevant DOE technical standards include the following:
• DOE-STD-1098-2017, Radiological Control.
• DOE STD-1107-97, Knowledge, Skills, and Abilities for Key Radiation Protection Positions
Section 180
at DOE Facilities.
• DOE-STD-1121-2008, Internal Dosimetry.
• DOE-STD-1128-2013, Good Practices for Occupational Radiological Protection in
Plutonium Facilities.
• DOE-STD-1136-2017, Good Practices for Occupational Radiological Protection in
Uranium Facilities.
Guidance documents pertaining to radiation hazards include the following:
• DOE G 441.1-2, Occupational ALARA Program Guide.
• DOE-HDBK-1129-2015, Tritium Handling and Safe Storage.
Radiation safety training is addressed in the following documents:
• DOE-HDBK-1122-2009, Radiological Control Technician Training.
• DOE-HDBK-1130-2008, Radiological Worker Training Materials (Reaffirmed 2013).
• DOE-HDBK-1131-2007, General Employee Radiological Training (Reaffirmed 2013).
• DOE HDBK-1145-2013, Radiological Safety Training for Plutonium Facilities.
In nuclear facilities, the primary source of ventilation-related occupational radiation exposure is
to service and replace HEPA filters that have filtered radioactive materials. HEPA filter
replacement projects are required to apply all of DOE’s radiation safety and ALARA
requirements and guidance as set out above. The following best practices should be considered
for application during HEPA filter change out process:
(a) Because used HEPA filters have accumulated significant amounts of dust and particulate
matter, the weight of the filters should be considered when planning replacement.
(b) The sharp edges and corners of HEPA filters have the potential to cause personal injury.
Planning should account for this hazard.
(c) The fragility of HEPA media should be considered to ensure that the filters remain intact
during changeout and no particulate matter is released.
DOE-HDBK-1169-2022
250
(d) Changeout planning should cover space considerations: working space, areas for
placement of tools and new/used filters, and egress paths for discarded filters.
(e) Changeout planning should include specific methods for transporting new and used
filters to and from the filter housing.
(f) Briefings of all staff involved in the changeout process should be conducted prior to
commencement of the operation.
5.4 Deep-Bed Sand Filters
5.4.1 Introduction
This section of the Handbook provides guidance and best practices for meeting requirements
found in Section 5.4 of DOE-STD-1269-2022, Air Cleaning Systems in DOE Nuclear Facilities. The
content of this section has been drawn principally from the 2003 edition of the Nuclear Air
Cleaning Handbook, DOE-HDBK-1169 (archived).37
5.4.2 Overview of Deep-Bed Sand Filters
DBS filters have been used in the ventilation and process exhaust systems of radiochemical
processing facilities since 1948. The major attractions of DBS filters include large dust-holding
capacity, low maintenance requirements, inertness to chemical attack, high heat capacity, fire
resistance, and the ability to withstand shock loadings and large changes in airstream pressure
without becoming inoperative. The disadvantages of DBS filters include high capital cost, large
area, high pressure drop, high power costs, uncertainties in selection, availability, grading, and
handling of suitable sands, and disposal of the spent unit. In accordance with ASME AG-1, Non-
Mandatory Appendix FL-B, a large-scale DBS filter mock-up supports seismic calculations.
Testing of the mock-up will provide validation of the response of the DBS filter structure and
media to a design basis earthquake.
Section 181
DBS filters are deep (several feet thick) beds of rock, gravel, and sand, constructed in layers
graded with about two-to-one variation in granule size from layer to layer. Airflow direction is
upward, and granules decrease in size in the direction of airflow. A top layer of moderately
coarse sand is generally added to prevent fluidization of finer sand. The rock, gravel, and sand
layers are positioned and sized for structural strength, cleaning ability, dirt-holding capacity,
and long life. Figure 5.1 shows the cross-section of a typical DBS filter.
Ideally, the layers of larger granules, through which the gas stream passes first, remove most of
the larger particles and particulate mass, and the layers of finer sands provide high-efficiency
removal. Below the fixed bed of sand and gravel is a course of hollow tile or steel grating that
forms the air distribution passages.
The filter is enclosed in a concrete-lined pit. The superficial velocity is around 5-7 fpm, and the
pressure drop across multiple layers, sized from 3 1/2 inches to 50 mesh, is from 7 to 11 in.wg.
37 Some historical material has been omitted. All historical material is preserved in the archived version of NACH
2003.
DOE-HDBK-1169-2022
251
Collection efficiencies up to 99.98 percent [determined by in place test with polydispersed 0.7-
number mean diameter (NMD) test aerosol have been reported.
A removal efficiency approaching that of a single HEPA filter has been claimed for DBS filters if
the proper sands are used and the contact path is long enough. Efficiency tests of DBS filters
can only be made using polydispersed test aerosols with an NMD of about 0.7 µm. True
efficiency tests of HEPA filters, on the other hand, are made with a monodispersed test aerosol
with an NMD of 0.3 µm. In addition, tests of very large units, such as DBS filters, are often made
under conditions that sometimes yield results difficult to interpret. For these reasons, although
the efficiency of DBS filters approaches that of HEPA filters, it should not be assumed that the
efficiency of DBS filters for submicron particles is equivalent to that of HEPA filters.
Following initial installation of a DBS filter at DOE’s Hanford Site, nine others were installed at
Hanford, SRS, the Midwest Fuel Recovery Plant at Morris, Illinois, and the Zero Power Physics
Reactor at Idaho Falls. As of the date of publication, SRS has five functional DBS filters: two
servicing F Canyon and H Canyon, one servicing the Defense Waste Processing Facility, one
servicing a facility (235-F) that supported Pu238 RTG (Radioisotope Thermoelectric Generator)
production, and one servicing Savannah River National Laboratory. Details of existing and
former DBS filters are given in Table 5.2. Properties of sands and aggregates used as the
filtration media of these filters are given in Table 5.3.
Figure 5.1: Section through Typical Sand Filter
DOE-HDBK-1169-2022
252
Table 5.2 – Dimensions and Operating Data for U.S. Deep-Bed Sand Filters
DBS Filter
No. a
Plan
Dimensions b
(ft)
Design Flow
(cfm)
Design
Superficial
Velocity
(fpm)
Design
Pressure
Drop
(in.wg)
Year of
Initial
Operation
1 108×46 25,000 5.0 5.0 1948
2 108×46 25,000 5.0 7.0 1948
3 96×96 40,000 4.3 10.0 1950
4 85×85 40,000 5.5 12.0 1951
5 240×100 20,000-30,000 4.8 10.0 1954
6 240×100 20,000-30,000 4.8 9.2 1955
7 360×100 210,000 5.8 10.0 1975
8 360×100 210,000 5.8 10.0 1976
9 140×103 74,000 5.1 Not available 1974
10 72×78 32,000 5.7 Not available 1974
11 50 to 62.5
Section 182
Not available d Not available 1968
12 120 x 192 115,000 5.0 8.0 1995
13 99x83 30,500 3.9 Not available 1987
a Filter identification:
1. T Plant, Building 291-T, Hanford West Area, Richland, WA.
2. B Plant, Building 291-B, Hanford East Area, Richland, WA.
3. U Plant, Building 291-U, Hanford, Richland, WA.
4. Redox Facility, Building 291-S, Hanford, Richland, WA.
5. F Area, Building 294-F, Savannah River Site, Aiken, SC.
6. H Area, Building 294-H, Savannah River Site, Aiken, SC.
7. F Area, Building 294-1F (new), Savannah River Site, Aiken, SC.
8. H Area, Building 294-1H (new), Savannah River Site, Aiken, SC.
9. SRL, Building 794-A, Savannah River Laboratory, Aiken, SC.
10. Midwest Fuel Recovery Plant (MFRP), c Morris, IL.
11. Zero Power Plutonium Reactor Facility, Argonne National Laboratory, Idaho Falls, ID.
12. S Area, Defense Waste Processing Facility, Savannah River Site, Aiken, SC
13. F Area, Building 294-2F, Savannah River Site, Aiken, SC.
b Inlet side shown first, outlet side italicized.
c MFRP is not engaged in reprocessing, only storage; sand filter is active.
d This is an emergency relief system.
DOE-HDBK-1169-2022
253
Table 5.3 – Properties of Sands and Aggregates Used in U.S. Deep-Bed Sand Filters
Property Filter No. a
1 2 3 4 5 6 7 8 9, 12 10
Depth of bed, feet 9 8.5 8 8 8 8 7.5 7.5 7.5 8
Number of layers 9 8 7 7 7 7 6 6 6
Depth of layers (inches)
Granule size range, mesh (unless inches noted)
Layer A 2-3 inches 12
2 1/2-1 1/4
12
3-1 1/4 in 12 12 12 12 12
3-1 in 12 12 18
Layer B 1-2 in 12
1 3/4-5/8
12 12 12 12
1 1/2-5/8 in 12 12 12 12 12
Layer C 1-1/2 in 12
3/4 in ~ 6 12 12 12
5/8-1/4 in 12 12 12 12 12
Layer D 1/2 in -4 12
3/8 in -3 12
Layer E 4-8 12 6 6 6 6 6 6 6 6
1/4 in -8 6
Layer F 8-20 12 12 12 12 12 12 12 12 6
8-18 12
Layer G 20-40
30-50 36 b 36 36 36 36
20-50 36 36 b 36
a See Table 5.2 for locations corresponding to number.
b Removed 12 inches from G layer, July 1972, to reduce pressure drop.
5.4.3 Deep-Bed Sand Filter Design
A rough approximation of the collection efficiency of sand, on an activity basis, is given by the
following equation:
F = - exp (–KL1/2V-1/3D-4/3)
where:
F = fractional collection efficiency on a radioactivity or mass basis (dimensionless)
L = depth of fine sand, feet
V = superficial gas velocity, fpm
D = average sand grain diameter, inches
K = proportionality factor (dimensionless)
Note: The values of L, V, and D vary with sands from different sources of the same mesh size
and need to be determined experimentally for any given sand.
DOE-HDBK-1169-2022
254
Values for the proportionality constant, K, for several sands tested at Hanford are:
Type of Sand K
Hanford 0.053
AGS flint 0.045
Rounded grain sand (Ottawa, Eau Claire, Monterey) 0.035
Collection efficiency on a radioactivity basis gives a higher number than the collection efficiency
on a count basis, as reflected by the test aerosol test, because larger, more easily collected
particles may carry more radioactivity and bias the analysis to give greater value to larger
particles. The relationship between count and activity collection efficiency cannot be
determined without accurate information on aerosol size distribution and the relationship of
aerosol size to radioactivity.
Section 183
The approximate void fraction of a sand bed is generally about 0.4. Sand permeability tests
have shown that intense vibration can cause extreme compaction, resulting in near doubling of
the pressure drop. Factors that should be considered include the effects of compaction, steam
injection, relative humidity, and velocity change on efficiency and pressure drop. Besides
permeability and filtration requirements, the sand should be abrasion-resistant and fracture-
resistant and should resist corrosion from the fumes likely to be present in the exhaust
airstream. Additional properties of sandfilter media can be found in ASME AG-1, Section FL.
Filter life is determined by the increase in pressure drop and the decrease in gas flow caused by
the collection of solids within the sand bed. Filter life can be significantly reduced if solids
collection is concentrated in small fractions of the bed or on the finer sand. Uniform
concentration of coarse aggregate layers upstream of the fine sand layer tends to maximize
filter life.
Clogging of DBS filters is aggravated by local decreases in porosity at the interfaces between
graded layers. The mixing of aggregates (sand, gravel) at the interfaces usually results in a lower
void fraction at the interface than if no mixing is permitted. The extent of reduction in void
fraction depends on the characteristics of the aggregates and on the technique used to charge
them into the filter bed. The lowest layer may require hand placement for the first few inches
so that no rocks fall through the openings in the distribution blocks. Significant improvement in
filter life can be obtained by careful attention to loading. An isometric of this filter is shown in
Figure 5.2.
DOE-HDBK-1169-2022
255
Figure 5.2: Isometric View and Details, Sand Filter at Savannah River National Laboratory
5.4.4 Deep-Bed Sand Filter Plugging
Some filters have experienced plugging at low dust loadings. In one case, the plugging was
caused by moisture entering through cracks in the concrete sidewalls of the unit. In another
instance, plugging was caused by crystal growth in the filter media fines, probably due to a
reaction of nitric acid vapors from the process building with calcite, with dolomite present in
the original sand, and with cement dust generated by severe erosion and acid attack on the
concrete entry ducts and support structures.
5.4.5 Spent Media Disposal
Deactivation of existing filters is generally accomplished by sealing and abandoning the filter.
Spent media are stored in place within the unit. The total unit is replaced by a new filter located
close by. Present Government regulations for radioactive solid waste, though unclear, may rule
out such in-place disposal in the future. If the material were handled as high-level radioactive
waste, each 1,000-cfm capacity of filter would require about two hundred 55-gallon drums for
disposal.
DOE-HDBK-1169-2022
256
5.4.6 Burial in Place
Burial in place (or entombment) for DBS filters is feasible and could be economical if provisions
are applied during initial design of the filters to ensure that the walls, floors, and roof integrity
are sufficient to satisfy the requirements of 10 CFR Part 61, Licensing Requirements for Land
Disposal of Radioactive Waste, and the requirements of other regulatory bodies such as the
U.S. Environmental Protection Agency.
5.4.7 Decontamination
Section 184
Because of the irregular surface areas and porous nature of the clay tile, stones, gravel, and
sand filter media utilized in DBS filters, decontamination methods currently available would be
mostly ineffective. Ancillary materials such as concrete confinement walls and supports and
steel grating, if utilized, are potential candidates for decontamination, but make up a relatively
small percentage of the total mass of the DBS filter.
5.4.8 References
1. Juvinall, R. A., R. W. Kessic, and M. J. Steindler, 1968, “Sand-Bed Filtration of Aerosols: A
Review of Published Information on Their Use in Industrial and Atomic Energy Facilities,”
USAEC Report ANL-7683, Argonne National Laboratory, Chicago, IL, February.
2. Mover, R. A., J. H. Crawford, and R. E. Tatum, 1975, “Deep-Bed Sand Filter at Savannah River
Laboratory,” 13th Atomic Energy Commission Air Cleaning Conference, USAEC Report
CONF-740807.
3. Schurr, G. A., D. B. Zippier, and D. C. Guyton, 1972, “Deep-Bed Filter Tests,” 12th Atomic
Energy Commission Air Cleaning Conference, USAEC Report CONF-720828, August.
4. SAND FILTERS, 31st Nuclear Air Cleaning Conference Charlotte, NC 20 July 2010; Steve Kline,
Battelle Memorial Institute; Kevin Matthews, Savannah River Nuclear Solutions; Helen
Mearns, U.S. Army; Mahendra Patel, URS; Glen Petersen, URS; Jerome Roberts, retired.
1.0 Introduction
1.1 Purpose
1.2 Applicability
1.3 Organization
2.0 Terminology
2.1 Acronyms & Abbreviations
3.0 System Design
3.1 Introduction
3.2 Contaminants
3.3 Environmental Conditions
3.4 Backup Power
3.5 Work Area Ventilation
3.6 References
4.0 Component Level Guidance and Best Practices
4.1 Filtration Components and Filter Testing
4.1.1 Introduction: Filtration Components
4.1.1.1 Air Filter Types
4.1.1.2 Filtration
4.1.1.3 Particle Collection by Filters
4.1.1.4 Particle Retention in Filters
4.1.1.5 Airflow Resistance of Filters
4.1.1.6 HEPA Filters: Historical Background
4.1.1.7 Filter Medium
4.1.1.8 HEPA Filter Construction
4.1.1.9 Separators
4.1.1.10 Filter Case
4.1.1.11 Sealants
4.1.1.12 Gaskets
4.1.1.13 Faceguards
4.1.1.14 Separatorless HEPA Filters
4.1.1.15 Mini-Pleat HEPA Filters
4.1.2 HEPA Filter Classes and Sizes
4.1.2.1 Filter Construction Grades
4.1.2.2 Filter Performance Levels
4.1.2.3 Enclosed Filters
4.1.2.4 Cylindrical Filters
4.1.2.5 Filter Sizes
4.1.2.6 Filter Weight
4.1.3 HEPA Filter Performance Characteristics
4.1.3.1 Airflow Resistance
4.1.3.2 Dust-Holding Capacity
4.1.3.3 Shock and Blast Resistance
4.1.3.4 Heat from Fire and Explosion
4.1.3.5 Moisture and Corrosion Effects
4.1.3.6 Radiation Resistance
4.1.4 HEPA Filter Performance Testing for Nuclear Service
4.1.4.1 Airflow Resistance
4.1.4.2 Quality Control/Assurance Considerations
4.1.5 Effects of Aging, Wetting, and Environmental Upsets on HEPA Filter Performance
4.1.5.1 Aging
4.1.5.2 Upset Environmental Conditions
4.1.5.3 In-Place Testing of Filter Installations
4.1.5.4 Packaging, Storage, and Handling of HEPA Filters
4.1.6 Medium Efficiency Filters (Prefilters) for HEPA Filters
4.1.6.1 Filter Descriptions
4.1.6.2 Classes, Sizes, and Performance Characteristics of Medium Efficiency Filters
4.1.6.3 Commercial and Industrial Grade Filters Performing as Medium Efficiency Filters
4.1.6.4 Electrostatic and Electrified Filters
4.1.6.5 Operation and Maintenance of Medium Efficiency Filters (Prefilters)
Section 185
4.1.7 Deep-Bed Filters
4.1.7.1 Deep-Bed Sand Filters
4.1.7.2 Deep-Bed Glass Fiber Filters
4.1.7.3 Deep-Bed Metal Filters
4.1.7.4 Moisture Separators (Demisters)
4.1.8 Testing
4.1.8.1 Introduction
4.1.8.2 Proof of Design – HEPA Filter Design Qualification Testing for Nuclear Service
4.1.8.2.1 Penetration (Efficiency)
4.1.8.2.2 Airflow Resistance
4.1.8.2.3 Aerosol Test
4.1.8.2.4 Resistance to Rough Handling Qualification Test
4.1.8.2.5 Moisture and Overpressure Resistance Qualification Test
4.1.8.2.6 Fire and Hot Air Resistance Qualification Test
4.1.8.2.7 Spot Flame Resistance
4.1.8.2.8 Quality Control, Inspection and Testing of HEPA Filters
4.1.9 Filter Qualification, Quality Assurance Inspection, and Testing of HEPA Filters
4.1.9.1 Introduction
4.1.9.3 In-Place Component Tests and Criteria
4.1.9.4 Component Acceptance Testing
4.1.9.5 Duct and Housing Leak Test
4.1.9.6 Mounting Frame Pressure Leak Test
4.1.9.7 Airflow Capacity and Distribution Test
4.1.9.8 Air-Aerosol Mixing Uniformity Test
4.1.9.9 Duct Damper Bypass Test
4.1.9.10 System Bypass Test
4.1.9.11 Duct Heater Performance Test
4.1.10 Surveillance Testing
4.1.10.1 Introduction
4.1.10.2 In-Place System Leak Test, HEPA Filter Banks
4.1.10.3 In-Place Testing for Adsorbers
4.1.10.4 Nonradioactive Tracer Gas Test
4.1.10.5 Radioactive Iodine Tests
4.1.10.6 Test Sequence and Frequency
4.1.10.7 In-Place Testing for Multistage Systems
4.1.10.8 First-stage Downstream Sample
4.1.10.9 In-Place Testing for Multistage Adsorber Systems
4.1.10.10 Test Aerosol/Gas Injection, throughout Second-Stage Upstream Sample
4.1.11 Adsorbent Sampling and Laboratory Testing
4.1.11.1 Sampling
4.1.11.2 Laboratory Testing
4.1.11.3 Frequency of Testing
4.1.12 Testing of Deep Bed Sand Filters
4.1.13 Testing Portable HEPA Filtration Systems
4.1.13.1 General Testing and Periodic Maintenance Considerations
4.1.13.2 Portable Filtration Systems Testing Applications
4.1.13.3 Testing Problems and Special Considerations
4.1.14 Testing HEPA Filter Vacuum Cleaners
4.1.14.1 Description of Radiological Vacuum Cleaners
4.1.14.2 Operation
4.1.14.3 HEPA Filter Vacuum Cleaner Tests
4.1.15 References
4.2 Glovebox Filtration
4.2.1 Introduction: Filtration Components
4.2.2 Glovebox Types and Characteristics
4.2.3 Importance of Glovebox Ventilation and Filtration
4.2.4 Design of Glovebox Ventilation Systems
4.2.4.1 Introduction
4.2.4.2 Blowers
4.2.4.3 Filter Housings
4.2.5 Dilution of Evolved Gases
4.2.6 Heat Dissipation
4.2.7 Empirical Flow Rates
4.2.8 Exhaust Requirements
4.2.9 Vacuum-and Pressure-Surge Relief
4.2.10 Glovebox Exhaust Manifold
4.2.11 Exhaust Cleanup Criteria
4.2.12 HEPA Filters
4.2.12.1 HEPA Filter Selection Criteria
4.2.13 Medium Efficiency Filter (Prefilter) Selection
4.2.14 Inlet HEPA Filters
4.2.15 Roughing Filters
4.2.16 Filter Replacement
4.2.17 Protection Against Fire and Explosion
4.2.17.1 General Guidance
4.2.17.2 Detection
4.2.17.3 Suppression
4.2.17.4 Inert Environments
4.2.18 Control and Instrumentation
4.2.19 Challenge Aerosol Testing of Glovebox Filters
4.2.20 Glovebox Shielding
4.2.21 Criticality Considerations
4.2.22 References
Section 186
4.3 Small Air Cleaning Units
4.3.1 Introduction
4.3.2 Housings
4.3.3 Component Installation
4.3.4 Housing Construction
4.3.5 Bagging
4.3.6 Housing Installation
4.3.7 Cylindrical Filter Elements
4.3.8 Installation and Human Factors
4.3.9 Fume Hoods
4.3.10 Portable Air Cleaning Units
4.3.10.1 Operational Considerations
4.3.10.2 Component Considerations
4.3.10.3 Construction
4.3.10.4 Testing and Inspection
4.3.10.5 Vacuum Cleaning Systems
4.3.11 References
4.4 Housing Design and System Layout
4.4.1 Introduction
4.4.2 Housing System Design
4.4.2.1 Man-entry Housing System Design
4.4.2.2 Arrangement and Location
4.4.3 Component Installation
4.4.3.1 General
4.4.3.2 Housing Construction
4.4.3.3 Potential Housing Leakage
4.4.3.4 Paints and Protective Coatings
4.4.4 Man Entry Housing
4.4.4.1 General
4.4.4.2 Structural
4.4.4.3 Structural Design
4.4.4.4 Mounting Frame Configuration
4.4.4.5 Frame Fabrication
4.4.4.6 Clamping and Sealing
4.4.4.7 Filter Support
4.4.4.8 Size and Arrangement of Filter and Adsorber Banks
4.4.4.9 Vertical Filter Banks
4.4.4.10 Location of Filters on Mounting Frame
4.4.4.11 Size of Banks
4.4.4.12 Arrangement of Banks
4.4.4.13 Floor Plan of Filter Banks
4.4.4.14 Steel Housings
4.4.4.15 Masonry and Concrete Housings
4.4.4.16 Housing Floor
4.4.4.17 Housing Doors
4.4.4.18 Housing Drains
4.4.4.19 Other Housing Requirements
4.4.5 Design of Side-Access Housings
4.4.6 Recommended Design Features
4.4.7 Differences Between Nuclear Filtration Systems and Commercial/Industrial Filtration Systems
4.4.8 Advantages of Stainless Steel Over Heavy Carbon Steel Construction
4.4.9 Side-Access Housings For Radial Flow Cylindrical HEPA Filters
4.4.10 References
4.5 External Components
4.5.1 Introduction
4.5.2 Ductwork
4.5.2.1 Functional Design
4.5.2.2 Mechanical Design
4.5.2.3 Engineering Analysis
4.5.2.4 Engineered Ductwork
4.5.2.5 Materials of Construction
4.5.2.6 Paints and Protective Coatings
4.5.2.7 Supports
4.5.2.8 Thermal Insulation and Acoustic Considerations
4.5.2.9 Ductwork Leakage
4.5.3 Dampers and Louvers
4.5.3.1 Damper Descriptions
4.5.3.2 Design and Fabrication
4.5.3.3 Structural Design
4.5.3.4 Design and Construction Considerations
4.5.3.5 Damper Operators
4.5.3.6 Limit Switches
4.5.3.7 Performance Requirements
4.5.3.8 Qualification Testing
4.5.3.9 Louvers
4.5.4 Fans and Motors
4.5.4.1 Fan Types and Applications
4.5.4.2 Fan Performance
4.5.4.3 Fan Leakage Flexible Connection Leakage
4.5.4.4 Fan Construction
4.5.4.5 Qualification and Testing
4.5.4.6 Fan Reliability and Maintenance
4.5.4.7 Special Duty Considerations Temperature, Pressure, and Humidity
4.5.5 Air Intakes and Stacks
4.5.5.1 Locating Intakes and Stacks
4.5.5.2 Sizing Intakes and Stacks
4.5.5.3 Structural Design Aspects
4.5.6 Instrumentation and Control
4.5.6.1 Codes and Standards Requirements
4.5.6.2 Functional Requirements
4.5.6.3 Airflow Control
4.5.6.4 Pressure Control
4.5.6.5 Qualification and Testing
4.5.7 References
Section 187
5.0 SPECIAL TOPICS
5.1 Fire Protection of Air Cleaning Systems22F
5.1.1 DOE Fires Affecting Air Cleaning Systems
5.1.2 Fire Phenomena
5.1.2.1 Smoke Generation
5.1.2.2 Water Generation
5.1.2.3 Heat Loss in Ducts
5.1.2.4 Smoke and Water Loss in Ducts
5.1.2.5 Effects on Filters of Heat, Smoke, and Related Products
5.1.2.6 HEPA Filter Response to Temperature
5.1.2.7 HEPA Filter Response to Smoke and Water Loading
5.1.2.8 Filter Exposure to Water
5.1.2.9 Effects on Physical Integrity of the Confinement Ventilation System Components
5.1.2.10 Effects of Wildland Fires
5.1.2.11 Fires Occurring within Confinement Ventilation Systems
5.1.2.12 Generation of Heat, Smoke, and Related Products
5.1.2.13 Transport of Heat, Smoke, and Related Products
5.1.2.14 Effects on Filters of Heat, Smoke, and Related Products
5.1.3.1 Objectives and Requirements
5.1.3.2 Fuel Control
5.1.3.3 Control of Energy Sources
5.1.3.4 Passive Design Features
5.1.3.5 Duct Response to Fire
5.1.3.6 Air Supply and Extraction
5.1.3.7 Entrance Filters
5.1.3.8 Medium Efficiency Filters
5.1.3.9 Filter Housings
5.1.3.10 Fire Screens
5.1.3.11 Materials
5.1.3.12 Wood Filter Frames
5.1.3.13 Fire Barriers
5.1.3.14 Active Design Features and Fire Hazard Controls
5.1.3.15 Fire Dampers
5.1.3.16 Fire Detection and Suppression Systems
5.1.3.17 Wet Pipe Sprinkler Systems
5.1.3.18 Deluge and Water Spray Systems
5.1.3.19 Water Mist Systems
5.1.3.20 Sprinklers within Ductwork
5.1.3.21 Demisters and HEPA Filters
5.1.3.22 Fire Department Standpipe Systems
5.1.3.23 Water Runoff Collection
5.1.3.24 Gaseous Agent Systems
5.1.3.25 Flammable Gas Detection
5.1.3.26 Protection of Carbon-Filled Adsorption Systems
5.1.3.27 Filter Assemblies in Plywood Enclosures
5.1.3.28 High-Efficiency Metal Fiber Filter Systems
5.1.3.29 Radioiodine Absorber Air Cleaning Systems
5.1.3.30 Deep-Bed Fiberglass Filter Systems
5.1.3.31 Deep-Bed Sand Filter Systems
5.1.3.32 Self-Cleaning Viscous Liquid Filters
5.1.3.33 Electrostatic Precipitator Prefilter
5.1.3.34 Ceramic HEPA Filters
5.1.4 Fire Protection Concepts for Gloveboxes
5.1.4.1 Protective Atmospheres
5.1.5 Operations and Maintenance Practices for Fire Protection of Confinement Ventilation Systems
5.1.5.1 Essential Elements
5.1.5.2 Fire Prevention
5.1.5.3 Procedures
5.1.5.4 Inspection, Testing, and Maintenance
5.1.5.5 Impairment Planning
5.1.5.6 Modifications
5.1.5.7 Emergency Planning
5.1.5.8 Technical Safety Requirements Tie-in
5.1.5.9 Quality Assurance
5.1.5.10 Assessments
5.1.6 Generic Firefighting Procedures
5.1.6.1 Control Ventilation Configurations, Volumes, and Flow Rates in the Field
5.1.6.2 Activation of the Manual Deluge System
5.1.6.3 Deluge System Flow Times
5.1.6.4 Manual Activation of the Automatic Deluge System
5.1.7 References
5.2.1 Introduction
5.2.2 DOE Order 420.1C and DOE Guide 420.1-1A
5.2.3 DOE-STD-1020-2016 and DOE-HDBK-1220-2017
5.2.4 Additional References
5.3 Occupational Safety and Health
5.3.1 Introduction
5.3.2 Confined Space Entry
5.3.3 Excessive Noise
5.3.4 Excessive Heat
5.3.5 Hazardous Biological and Chemical Substances
5.3.6 Respiratory Protection
5.3.7 Radiation Exposure and the ALARA Principle
5.4 Deep-Bed Sand Filters
5.4.1 Introduction
5.4.2 Overview of Deep-Bed Sand Filters
5.4.3 Deep-Bed Sand Filter Design
5.4.4 Deep-Bed Sand Filter Plugging
5.4.5 Spent Media Disposal
5.4.6 Burial in Place
5.4.7 Decontamination
5.4.8 References