Revisions to the Facility Safety Order and DOE-STD-1066
Document text
Text extracted from the attached file. Refer to the original document for the authoritative version.
Section 1
Proposed Revisions to DOE’s
Fire Protection Program
A Review of major changes to:
DOE Order 420, Facility Safety;
DOE-STD-1066 – Fire Protection Design Criteria
Manager - US DOE Fire Protection Program
Office of Health Safety and Security (HS-32)
Jim Bisker, PE
∗ DOE’s Fire Protection program is Regulated by the Department’s
Facility Safety Order (DOE O 420. B – 12/2005)
∗ The Office of Health Safety and Security (HS-32) is the Office of
Primary Interest (OPI) for the Order
∗ In April, 2011 Order 420.1 C entered the Directives Review Process
as a part of a major regulatory review process undertaken by HSS
∗ To date the Order revision (O 420.1 C) has received approval from
the Directives Review Board contingent on the publication of 2
DOE Technical Standards, DOE-STD-1066, Fire Protection and DOE-
STD-1020, Natural Phenomena Hazards
∗ On April 29, 2012 DOE-STD-1066 was approved for publication.
DOE-STD-1020 is nearing final concurrence
May 15, 2012 Fire Safety Workshop 2
Program’s Regulatory Status
Facility Safety Order
May 15, 2012 Fire Safety Workshop 3
Order 420.1 was originally developed in October of
1995 to soften the specifics that existed in past
regulations such as DOE 6430.1 A, General Design
Criteria and the 5480 series including Order 5480.7 A,
Fire Protection.
This Current revision (O 420.1 C) revisits the specify in
these past regulations; clarifies; and, in some cases –
relieves some of the regulatory burdens that existed
at the time - but may no longer be applicable to the
Department.
May 15, 2012 Fire Safety Workshop 3
Facility Safety Order
Revisions
May 15, 2012 Fire Safety Workshop 4
Front End –
• Removed all requirements that were not specific to DOE - Streamlined and
Clarified
• Clarified Authority Having Jurisdiction delegation requirements
• Added Safety System Oversight requirements (was in different DOE Directive)
Contract Requirements Document – Attachment 1
• Clarified requirements for exemptions
Contract Requirements Document – Attachment 2
Chapter 2: Fire Protection
• Reorganized requirements to better reflect topical areas of design, operations,
and emergency response
• More specifically invoked Standard 1066 (which was revised to incorporate
information from several related standards and guides to provide a single source,
and was further revised to address DNFSB Recommendation 2008-1 on safety
class/significant FP systems)
Order 420.1 C Specifics
May 15, 2012 Fire Safety Workshop 5
Order 420.1 B
Applicability: " …this Order applies to all
DOE elements with responsibility for DOE-
owned or - leased facilities… “
Order 420.1 C
Applicability: "This Order applies to all
DOE elements with responsibility for
design, construction, management,
operation, decontamination,
decommissioning, or demolition of
government-owned or government-
leased facilities and onsite contractor-
leased facilities used for DOE mission
purposes. .. "
Order 420.1 C continues to exclude nearly all of the types of facilities or
programs that were excluded in Order 420.1 B and added two more:
• Existing design projects (high level of maturity) at the time the Order
gets issued; and,
• Offsite Office facilities that are owned or leased by the GSA
Order 420.1 C Specifics
May 15, 2012 Fire Safety Workshop 6
Field Element Responsibilities have been expanded and
specified to include:
• Approval of the contractors fire protection program
• Fulfill the roles and responsibilities as the Building Code
Section 2
Official
• Perform responsibilities as the “owner” or other
equivalent term in the application of DOE technical
standards or industry codes and standards unless
delegated.
Order 420.1 C Specifics
May 15, 2012 Fire Safety Workshop 7
Facility Construction
All design and construction, at a minimum, must comply with
applicable national consensus industry codes and standards, the
International Building Code (IBC) and other requirements as
documented in this Order. If approved by the responsible Field
Element Manager, state, regional, and local building codes may be
used in lieu of the IBC upon contractor submission of a report that
demonstrates that implementation of the substituted code for the
specific application will meet or exceed the level of protection that
would have been provided by the IBC.
Order 420.1 C Specifics
May 15, 2012 Fire Safety Workshop 8
Chapter II of Attachment 2 includes the Department’s top tier fire
protection program requirements. These were initially written by a
task group of the DOE Fire Safety Committee - the intent to
structure existing requirements in a certain order; and, clarify some
of the ambiguity that existed in certain sections.
What we got from the field when we did this amounted to a majority
of the total comments that were received during the Directives
RevCom review phase. Through post comment negotiations we now
have an adequate set of criteria that we can move forward with.
May 15, 2012 Fire Safety Workshop 9
DOE O 420.1 C APPLICABILITY.
This chapter applies to organizations that
have responsibility for the design,
construction, maintenance, or operation of
government-owned or government-leased
facilities and onsite contractor-leased
facilities used for DOE mission purposes. For
leased facilities that are not nuclear hazard
category 1, 2, or 3 facilities, the design
requirements of this chapter (Section 3.c)
apply to the extent determined by the Field
Element.
DOE O 420.1 B APPLICABILITY.
This chapter applies to both
fire protection programs and
facility safety design for all
DOE elements that have
responsibility for DOE nuclear,
non-nuclear, and weapons
facilities.
Order 420.1 C Specifics
Chapter II
May 15, 2012 Fire Safety Workshop 10
Chapter II structure:
1. Objectives
2. Applicability
3. Requirements
a. General
b. Program Administration
c. Design
d. Operations
e. Emergency Response
f. Fire Hazard Analysis and building assessments
g. Wildland Fire
h. Specific Fire Protection Program Criteria
Order 420.1 C Specifics
Chapter II
May 15, 2012 Fire Safety Workshop 11
Some of the more notable actions of this Order revision include the following:
• Transferred the “Highly Protected Risk” language from the Order to DOE-STD-1066
• Refined and specified protection thresholds:
• Type I or Type II construction for all new facilities over 5,000 s.f.
• Sprinklers for all new facilities over 5,000 s.f. or with an $5 million dollar MPFL
• Sprinklers for any facility that:
• Is required via the Safety Basis Documentation
• Significant life safety hazard
• The potential for significant mission interruption
• Modifications exceed the dollar or area thresholds described
above.
• Property Protection – multiple approaches must be provided if the
MPFL exceeds $150 million. Fire areas must be established if the
MPFL exceeds $350 million.
Order 420.1 C Specifics
Chapter II
May 15, 2012 Fire Safety Workshop
Some of the more notable actions (continued):
Section 3
• The incorporation of wildland fire protection activities into Order
420.1C from Order 450.1, Environmental Protection Program.
• Reliance on more specific fire protection program criteria that is
contained within DOE-STD-1066 as an acceptable method for
implementing the requirements in Order 420.1 C. Other methods may
also be acceptable provided that any alternate approach must provide
an equivalent level of safety.
12
Order 420.1 C Specifics
Chapter II
May 15, 2012 Fire Safety Workshop
Chapter II of the Order relies on DOE-STD-
1066, Fire Protection for a significant amount
of technical detail that sites need to consider
within its fire protection program
13
Order 420.1 C Specifics
Chapter II
DOE-STD-1066
Fire Protection Program Specifics
May 15, 2012 Fire Safety Workshop
DOE-STD-1066-99, Fire
Protection Design Criteria
∗ Intent of the Standard was
to capture all the specifics
from 6430.1A and 5480.7a
that was not included in the
Order 420 and its
implementation guidance
∗ It also supplemented other
program guidance such as
DOE-STD-1088, Relocatable
Structures .
DOE-STD-1066-2012, Fire
Protection is intended to
capture all fire protection
program guidance that is
not addressed by DOE
Order 420.1C
14
DOE-STD-1066
Fire Protection Program Specifics
May 15, 2012 Fire Safety Workshop 15
DOE-STD-1066 replaces the following DOE regulations
• DOE-STD-1088-95, Fire Protection for Relocatable Structures
• DOE Guide (G) 420.1-3, Implementation Guide for DOE Fire Protection and
Emergency Services Programs for Use with DOE O 420.1B, Facility Safety; and,
• DOE G 450-1.4 Implementation Guide: Wildland Fire Management Program for Use
with DOE 450.1, Environmental Protection Program.
• DOE-STD-1066-99, Fire Protection Design Criteria
Additionally, Safety Significant and Safety Class fire protection design specifications
were included in response to DNFSB Recommendation 2008-1.
PLUS
The entire standard was updated and reformatted to align with standard engineering
requirements similar to that of other Federal agencies and consensus standards
organizations
DOE-STD-1066
Fire Protection Program Specifics
May 15, 2012 Fire Safety Workshop 16
Throughout this Standard, the word “shall” is used to denote a requirement; the
word “should” is used to denote a recommendation; and, the word “may” is used to
denote permission, but not a requirement or a recommendation. To satisfy this
Standard, all applicable “shall” statements need to be met. Alternate approaches
that demonstrate an equivalent level of safety are also acceptable, if approved by the
DOE field element.
Additionally
Nothing in this Standard is intended to limit the application of other fire protection
methods when unique situations or hazards warrant an alternate approach. Any
alternate approach should provide a level of safety equal to or greater than that
achieved by conformance with this Standard. Such alternate approaches should be
documented as required by the authority having jurisdiction (AHJ).
DOE-STD-1066
Fire Protection Program Specifics
May 15, 2012 Fire Safety Workshop 17
The Standard is structured to be consistent with the organization of
DOE O 420.1C
Section 2, General Fire Protection Requirements
Section 3, Fire Protection Program Administration
Section 4, Fire Protection Design
Section 5, Operations
Section 6, Emergency Response
Section 7, Facility Fire Protection Evaluations
Section 8, Wildland Fire Management
DOE-STD-1066
Fire Protection Program Specifics
Section 4
May 15, 2012 Fire Safety Workshop 18
There are also a number of appendices that address the following topics:
Appendix A, Safety Significant and Safety Class Fire Protection System Specifications
Appendix B, Fire Hazard Analysis
Appendix C, Relocatable Structures
Appendix D, Transitional Facilities
Appendix E, Sample Qualification Template for Lead Fire Protection Engineers
Appendix F is an endnote summary for explanatory materials that are numbered and
located throughout the document. Included with this Appendix is an MS word
automation feature such that the endnote text is made visible when the reader
positions the mouse cursor over the endnote number.
DOE-STD-1066
Fire Protection Program Specifics
May 15, 2012 Fire Safety Workshop 19
Facts and Opinions about DOE-STD-1066 (2012)
Fact – The update contains direction that may exceed or overlap or
conflict or augment those of the Building code. This direction is based
mainly on the guidance from past regulations that were developed to
address the unique hazards that exist within the Department. These
unique hazards are both nuclear and non-nuclear based
Opinion - This Standard will cost bags of dollars more to implement.
Fact – The update it took a long time to develop (upwards of 5 years)
Opinion - The OPI resists regulatory reform
DOE-STD-1066
Fire Protection Program Specifics
May 15, 2012 Fire Safety Workshop 20
Conclusions
• The Order and the Standard are ready for publication
• They may not be perfect, but they do provide clearer direction
to SME’s on what the Department’s expectations are
regarding our unique mission
• They also contain clauses to address situations where the
Department’s direction may not fit with the realities of these
unique structures.
• Future guidance needs to both refine and augment this
direction by dedicated engineers who have experience with
these unique hazards and structures.
• The Fire Safety Committee is the first step to achieving this
goal.
Proposed Revisions to DOE’s Fire Protection Program
Program’s Regulatory Status
Facility Safety Order
Facility Safety Order �Revisions
Order 420.1 C Specifics
Order 420.1 C Specifics
Order 420.1 C Specifics
Order 420.1 C Specifics
Order 420.1 C Specifics�Chapter II
Order 420.1 C Specifics�Chapter II
Order 420.1 C Specifics�Chapter II
Order 420.1 C Specifics�Chapter II
Order 420.1 C Specifics�Chapter II
DOE-STD-1066 �Fire Protection Program Specifics
DOE-STD-1066 �Fire Protection Program Specifics
DOE-STD-1066 �Fire Protection Program Specifics
DOE-STD-1066 �Fire Protection Program Specifics
DOE-STD-1066 �Fire Protection Program Specifics
DOE-STD-1066 �Fire Protection Program Specifics
DOE-STD-1066 �Fire Protection Program Specifics