DOE-STD-1195-2011, Design of Safety Significant Safety Instrumented Systems Used at DOE Nonreactor Nuclear Facilities
Functional areas: Safety Instrumented Systems, Safety Significant Functions, Hazard Controls
This standard provides requirements and guidance for the design, procurement, installation, testing, maintenance, operation, and quality assurance of safety instrumented systems (SIS) that may be used at Department of Energy (DOE) nonreactor nuclear facilities for safety significant (SS) functions.
Version history and related documents
Document text
Text extracted from the attached file. Refer to the original document for the authoritative version.
Section 1
DOE-STD-1195-2011
April 2011
DOE STANDARD
DESIGN OF SAFETY SIGNIFICANT
SAFETY INSTRUMENTED SYSTEMS USED
AT DOE NONREACTOR NUCLEAR
FACILITIES
U.S. Department of Energy AREA SAFT
Washington, D.C. 20585
DISTRIBUTION STATEMENT. Approved for public release; distribution is unlimited.
This document is available on the
Department of Energy Technical Standards Program Web page at
http://www.hss.doe.gov/nuclearsafety/ns/techstds
i
FOREWORD
Safety instrumented systems (SIS) that include both analog and digital control systems are
widely used in many industries, including in commercial nuclear power plants, for safety-related
applications. SISs are also used in the U.S. Department of Energy’s (DOE) nonreactor nuclear
facilities for various safety controls, including safety class (SC) and safety significant (SS)
controls. Although use of the SIS technology and, more specifically, computer-based digital
controls, can improve performance and safety, it can also introduce complexities, such as failure
modes, that are not readily detectable.
DOE requirements and guidance for structures, systems, and components used in SC and SS
applications are contained in the following DOE Orders: DOE O 420.1B, Chg 1, Facility Safety,
along with its associated guide, DOE G 420.1-1, Nonreactor Nuclear Safety Design Criteria and
Explosives Safety Criteria Guide for Use with DOE 420.1, Facility Safety; and DOE O 414.1C,
Quality Assurance. This standard focuses on SISs utilized in SS applications and illustrates
how a widely-used process industry standard, American National Standards Institute
/International Society of Automation (ANSI/ISA) 84.00.01-2004, Functional Safety: Safety
Instrumented Systems for the Process Industry Sector, can be utilized to support reliable
designs. SISs utilized in SC applications are designed in accordance with nuclear industry
standards with additional guidance provided in DOE G 420.1-1. Beneficial comments
(recommendations, additions, deletions) and any pertinent data that may improve this document
shall be sent to:
U.S. Department of Energy
Office of Nuclear Safety Policy and Assistance (HS-21)
1000 Independence Avenue SW
Washington, DC 20585.
DOE technical standards, such as this, do not establish requirements. However, all or part of
the provisions within this DOE technical standard shall be implemented under the following
circumstances:
● The provisions are explicitly stated to be requirements in a DOE requirements
document; or
● The organization makes a commitment to meet a standard 1) in a contract, or 2) in an
implementation plan or program plan of a DOE requirements document.
Throughout this standard, the word “shall” is used to denote actions that must be performed if
the objectives of this standard are to be met. If the provisions in this standard are made
requirements through one of the two ways discussed above, then the “shall” statements become
requirements. It is not appropriate to consider that “should” statements would automatically be
converted to “shall” statements, as this action would violate the consensus process used to
approve this standard.
ii
Intentionally Blank
iii
TABLE OF CONTENTS
Section 2
1. INTRODUCTION .................................................................................................. 1
1.1 Scope ................................................................................................................ 1
1.2 Applicability ....................................................................................................... 1
1.3 Background ....................................................................................................... 1
1.4 Contents of Standard ........................................................................................ 2
1.5 Users ................................................................................................................ 3
2. REQUIREMENTS AND IMPLEMENTATION GUIDANCE ................................... 3
2.1 General Requirements ...................................................................................... 3
2.2 Quality Assurance for Safety Software used in SISs ........................................ 4
2.3 Commercial Grade Dedication .......................................................................... 4
2.4 Setpoint Development ....................................................................................... 5
2.5 Power ................................................................................................................ 5
2.6 SIS Life-Cycle Management Process ............................................................... 5
2.7 Human Factors Engineering ............................................................................. 6
2.8 Security ............................................................................................................. 6
2.9 Instrumented System Applications not Covered by ANSI/ISA 84.00.01-2004 .. 6
APPENDIX A. OVERVIEW OF ANSI/ISA 84.00.01-2004 .......................................... A-1
A.1 Purpose ......................................................................................................... A-1
A.2 Background .................................................................................................... A-1
A.3 ANSI/ISA 84.00.01-2004 Life-Cycle Approach ............................................... A-1
APPENDIX B. SAFETY INTEGRITY LEVEL DETERMINATION METHODOLOGY . B-1
B.1 Purpose ......................................................................................................... B-1
B.2 SIL Determination and Independent Protection Layers .................................. B-1
APPENDIX C. SAFETY INTEGRITY LEVEL VERIFICATION GUIDANCE ............... C-1
C.1 Purpose ........................................................................................................ C-1
C.2 SIL Verification Calculation Content .............................................................. C-1
C.3. SIL Verification Calculation Guidance ........................................................... C-2
C.4. Spurious Trips ............................................................................................... C-4
APPENDIX D. ILLUSTRATION OF A SAFETY INTEGRITY LEVEL DETERMINATION
AND SAFETY INTEGRITY LEVEL VERIFICATION CALCULATION ............. D-1
D.1 Purpose ........................................................................................................ D-1
D.2 SIL Determination of an Example SS SIS ..................................................... D-1
Section 3
APPENDIX E. FAILURE RATE DATA ........................................................................ E-1
E.1 Failure Rate Data ........................................................................................... E-1
APPENDIX F. QUALITY ASSURANCE FOR SAFETY SOFTWARE FOR SAFETY
INSTRUMENTED SYSTEMS ............................................................................ F-1
F.1 Safety Software .............................................................................................. F-1
F.2 Software and Hardware Integration ............................................................... F-1
iv
F.3 Safety Software Quality Assurance Work Activities ....................................... F-2
APPENDIX G. HUMAN FACTORS ENGINEERING .................................................. G-1
APPENDIX H. APPLICABLE DOCUMENTS ............................................................. H-1
H.1 Department of Energy Directives .................................................................. H-1
H.2 National and International Standards ............................................................ H-1
H.3 Nuclear Regulatory Commission (NRC) Guidance ....................................... H-3
H.4 Other Sources ............................................................................................... H-3
APPENDIX I. ABBREVIATIONS, ACRONYMS, AND DEFINITIONS ........................ I-1
I.1 Abbreviations and Acronyms .......................................................................... I-1
I.2 Definitions ....................................................................................................... I-2
DOE-STD-1195-2011
1
1. INTRODUCTION
This standard provides requirements and guidance for the design, procurement, installation,
testing, maintenance, operation, and quality assurance of safety instrumented systems (SIS)
that may be used at Department of Energy (DOE) nonreactor nuclear facilities for safety
significant (SS) functions.
The focus of this standard is on how the process industry standard, American National
Standards Institute/International Society of Automation (ANSI/ISA) 84.00.01-2004, Functional
Safety: Safety Instrumented Systems for the Process Industry Sector, can be utilized to support
design of reliable SS SISs.
1.1 Scope
This standard covers SS SISs that contain analog or digital components. Those analog or
digital components include: switches, electrical relays, analog transmitters, computer-based
systems consisting of embedded hardware and software components (such as programmable
logic controllers, smart transmitters with built-in logic functions, and microprocessor-based
monitoring systems), and final control devices. In essence, an SIS is composed of any
combination of sensors, logic solvers, and final elements.
This standard is not intended to be used as the sole source of information to develop design
requirements for specific applications. Other requirements and specifications, such as those
found in DOE Order (O) 420.1B, Chg 1, Facility Safety, and DOE O 414.1C, Quality Assurance
(and their associated guides) should also be consulted, as appropriate. In addition, recognized
national and international standards, as well as the Nuclear Regulatory Commission’s regulatory
guides, should also be consulted, as appropriate.
Section 4
This standard uses a set of hazard controls identified in a nuclear facility’s documented safety
analysis (DSA) to support identification of SIS reliability targets. The standard is not to be used
to evaluate the adequacy of the set of hazard controls established in the DSA.
1.2 Applicability
This standard is applicable to SS SISs identified in the safety basis documents (Conceptual
Safety Design Report [CSDR], Preliminary Safety Design Report [PSDR], and Preliminary
Documented Safety Analysis [PDSA]) for new nonreactor nuclear facilities and for major
modifications as defined in 10 CFR Part 830.3, Nuclear Safety Management, Definitions, for
existing Hazard Category 1, 2 and 3 nonreactor nuclear facilities.
This standard is not applicable to safety class (SC) SISs.
This standard may also be useful to support design of SISs for facilities other than Hazard
Category 1, 2 and 3 nonreactor nuclear facilities.
1.3 Background
SISs are widely used in many process industries and commercial nuclear power plants for
safety-related functions. SISs are also used in DOE nonreactor nuclear facilities for various
safety controls such as safety interlocks and process alarms.
DOE-STD-1195-2011
2
Some SISs utilize programmable electronic technology (i.e., computer-based control systems),
which has the capability of improving performance and safety, but also introduces complexity in
failure modes that are not as readily predicted or understood, and may cause common mode
failures that are difficult to detect. A primary concern is that a design that uses the same or
shared hardware, software (including embedded software), and data may be susceptible to a
common-cause or common-mode failure due to software errors, hardware failures, or
combinations thereof, thus defeating the defense-in-depth/layer-of-protection concept
implemented in the design. In addition, DOE did not have a standard method for determining
the safety integrity level (SIL) for SISs that would account for defense-in-depth/layer-of
protection concept in the design.
SS structures, systems, and components (SSC), whose preventive or mitigative function is a
major contributor to defense-in-depth and/or worker safety as determined by safety analyses,
should be designed to ensure that failures in one layer will not propagate to or affect other
protection layers. This standard for SS SISs emphasizes quality, independence, and SIS
reliability as protection against common-cause failures within and between protection layers.
Equally important in preventing the propagation of common-cause failures is the application of
sound software quality assurance practices throughout the software life cycle to ensure reliable
software.
DOE has evaluated the chemical industry’s approaches and practices, and this standard was
developed using (ANSI/ISA) 84.00.01-2004.
1.4 Contents of Standard
Section 2 provides requirements for SISs, with Section 2.1 providing general requirements and
identifying two industry standards options for SIS design, and Sections 2.2 through 2.9
identifying detailed requirements.
Appendices A through I provide the following guidance or requirements related to ANSI/ISA
84.00.01-2004 implementation.
• Appendix A provides a general overview of ANSI/ISA 84.00.01-2004.
• Appendix B provides requirements of the approved method for the determination of SILs.
• Appendix C provides guidance on SIL verification.
• Appendix D provides an example of SIL determination and verification.
Section 5
• Appendix E provides guidance for obtaining failure rate data.
• Appendix F provides guidance related to quality assurance for safety software used in
SISs.
• Appendix G provides guidance on human factors engineering.
• Appendices H and I provide references, abbreviations, acronyms, and definitions.
DOE-STD-1195-2011
3
1.5 Users
The users of this standard should include personnel from various organizations including project
management, engineering and design, procurement, and operations and maintenance.
2. REQUIREMENTS AND IMPLEMENTATION GUIDANCE
2.1 General Requirements
General requirements for SSCs, including SISs, used in SC and SS applications are contained
in DOE O 420.1B, Chg1, Facility Safety, with implementation guidance provided in the
associated guide, DOE G 420.1-1, Nonreactor Nuclear Safety Design Criteria and Explosives
Safety Criteria Guide for Use with DOE O 420.1, Facility Safety.
Additionally, DOE-STD-1189, Integration of Safety into the Design Process, provides certain
general requirements (e.g., seismic design). For SSCs associated with facilities/modifications
under the purview of DOE G 420.1-1 and/or DOE-STD-1189 should be used, if required, and as
applicable, for guidance on environmental and seismic qualification requirements.
DOE O 420.1B, Chg 1, Chapter I, states that the safety SSCs and safety software must be
designed, commensurate with the importance of the safety functions performed, to perform their
safety functions when called upon, and to meet the quality assurance program requirements of
10 CFR 830, Subpart A, Quality Assurance Requirements, and DOE O 414.1C or its successor
directives, as applicable. That statement supports a graded approach to design and reliability of
an SIS based on the importance of its safety function. Either of the following two approaches
for an SS SIS design should be utilized.
Use of Commercial Nuclear Standards (Used for SC SISs)
To achieve the required reliability, the design can utilize industry standards developed for
commercial nuclear power plant design for safety-related systems. These standards are listed
in DOE G 420.1-1 for SC instrumentation and control systems. However, the listed standards
include some design requirements that are unwarranted for the design of SS SISs used in DOE
nonreactor nuclear facilities (e.g., the application of nuclear power industry standards call for
single-failure-proof designs, when other options to achieve adequate reliability might be more
appropriate and cost effective).
Use of Process Industry Standards
An appropriate alternative means for meeting the reliability requirements for SS SISs is to utilize
the processes outlined in ANSI/ISA 84.00.01-2004 – Part 1, Functional Safety: Safety
Instrumented Systems for the Process Industry Sector – Part 1: Framework, Definitions,
System, Hardware and Software Requirements. ANSI/ISA 84.00.01-2004 is used by the
process industries for designing reliable SISs that are commensurate with the level of hazard
mitigation or prevention strategy.
Appendices A, C, and D of this standard provide specific information on the use of ANSI/ISA
84.00.01-2004, whereas Appendix B provides an approved method for SIL determination.
Appendices E through G provide additional information to support the design process. To
support implementation of ISA 84.00.01-2004, DOE Order requirements and practices for
DOE-STD-1195-2011
4
Section 6
performing hazards analysis, selection of hazard controls, quality assurance, qualification of
personnel, testing and maintenance shall be used.
2.2 Quality Assurance for Safety Software used in SISs
2.2.1 Introduction
This section provides guidance on an approach to meet the objectives of ISA 84.00.01-2004,
Part 1, Clause 12, Requirements for application software, including selection criteria for utility
software, for achieving an acceptable level of assurance that SS SIS components that use
software will execute the required safety functions within the system/application and operational
environment. This section draws on the requirements of DOE O 414.1C and guidance provided
in DOE G 414.1-4, Safety Software Guide for use with 10 CFR 830 Subpart A, Quality
Assurance Requirements, and DOE O 414.1C, Quality Assurance.
2.2.2 Background
Three major types of software are used in SISs:
• Embedded software (normally provided by a vendor of programmable electronic
systems);
• Utility software (i.e., software supplied by a vendor that is used to develop and verify
application software); and
• Application software developed for the specified safety functions (normally the
responsibility of the end-user or process system designers for the SIS).
An SS SIS may have any combination of software stated above. Each programmable electronic
system (e.g., the logic solver), may have hardware and software components that can be
divided into embedded software and application software.
2.2.3 Requirements and Guidance
Quality assurance (QA) requirements for software development shall be controlled in
accordance with the contractor’s QA process, which shall meet the DOE’s QA requirements (10
CFR 830, Subpart A and DOE O 414.1C, as appropriate).
Appendix F provides relevant details for software quality assurance activities, as discussed in
DOE G 414.1-4 and in ANSI/ISA 84.00.01-2004 and other industry practices.
2.3 Commercial Grade Dedication
2.3.1 Introduction
Commercial Grade Dedication (CGD) may be used to approve the selection of components and
subsystems in an SIS in lieu of the ANSI/ISA 84.00.01-2004, Part 1, Clause 11.5, methodology
of acceptance by qualification to IEC 61508, Functional Safety of Electrical/Electronic/
Programmable Electronic Safety-Related Systems and/or “prior use.”
ASME Nuclear Quality Assurance (NQA)-1, Quality Assurance Requirements for Nuclear
Facility Applications, provides details of the CGD process. The goal of CGD is to provide a
DOE-STD-1195-2011
5
reasonable assurance that an item procured will perform its intended safety function, as
specified by design requirements.
2.3.2 Critical Characteristics for Commercial Grade Dedication:
The following critical characteristics, as appropriate, should be addressed when assessing the
acceptability of an SIS that utilizes software for meeting the design attributes.
a. Failure rate of an item such as:
• unsafe/dangerous failure rate (detected and undetected); or,
• safe failure rate (spurious trip rate)
b. Safe failure state, and safe recovery
c. Environmental design constraints
d. Software critical characteristics (e.g., build date, release name, part or catalog number,
traceability matrix, etc.)
e. Diagnostic coverage
f. Response time
g. Accuracy
h. Isolation capability of component/system from non-safety interfaces (i.e., communication
inputs and outputs)
i. Unused and unintended or prohibited functions
j. Supplier catalog and part number
Section 7
k. Supplier technical manual and product specification
l. Conformance to national codes and standards
The above list is not all inclusive. Users should develop the list for specific SS SIS design
requirements.
2.4 Setpoint Development
SS SIS setpoint development, including indications and alarms, shall follow the requirements of
ANSI/ISA 67.04.01, Setpoints for Nuclear Safety-Related Instrumentation.
2.5 Power
Power sources (i.e., electric power or instrument air) shall be provided with backup power
sufficient to fulfill the requirements of the SIS safety function, except in cases where the design
is fail-safe on loss of power.
2.6 SIS Life-Cycle Management Process
A key aspect of the implementation of ANSI/ISA 84.00.01-2004 is effective control over each
stage of the SIS life cycle to ensure proper initial design, proper installation, effective operation
DOE-STD-1195-2011
6
and maintenance, and configuration control. The processes for performing the life-cycle
management for SIS should be defined, including identifying the organization(s) responsible for
implementing them. Appendix A provides additional details on the SIS life-cycle process. The
life-cycle stages outlined in ANSI/ISA 84.00.01-2004 can be fulfilled by conformance to the
ANSI/ISA 84.00.01-2004 requirements or by conformance to DOE orders, manuals, standards,
and guides that provide equivalent processes and methods for the life-cycle stages of the safety
instrumented functions.
2.7 Human Factors Engineering
ANSI/ISA 84.00.01-2004, Part I, Clause 11.2.6 requires that the design of SIS take into account
human-machine interfaces and their limitations, and follow good human factors engineering
(HFE) practices. HFE involves diverse areas (e.g., information display, user-system interaction,
alarm management, operator response, control room design, and system maintainability), which
affect all aspects of a system’s development and modification. Appendix G gives an overview of
how HFE should apply in the SIS life cycle. An HFE Plan should be developed for the SS SIS,
defining the required participants and human factors activities, including the documentation,
review, and approval of each activity.
Details of the HFE Plan should be developed in accordance with DOE G 420.1-1, guided or
supplemented by information in NUREG 0700, Human-System Interface Design Review
Guidelines, ANSI/ISA 18.2, Management of Alarm Systems for the Process Industries, and
other HFE references given in Table G-1.
The HFE process should follow applicable requirements of DOE O 414.1C for software and
hardware configuration controls.
2.8 Security
This standard does not provide details of security requirements for SIS design. The SS SISs
shall be secured from electronic vulnerabilities, including unauthorized and/or inappropriate
access that may harm system integrity and safety.
The SS SIS design development process should address the potential security vulnerabilities in
each phase of the system life cycle, and the requirements should be commensurate with risk
and magnitude of harm resulting from unauthorized and inappropriate access, use, disclosure,
disruption, or destruction of the system.
ANSI/ISA 84.00.01-2004, Clause 11.7.2.2, provides some basic access security protection
measures. Users should consult applicable DOE requirements and other industry standards to
ensure the design meets the security requirements.
2.9 Instrumented System Applications not Covered by ANSI/ISA 84.00.01-2004
Section 8
ANSI/ISA 84.00.01-2004, Part 1, design methodology should not be used for instrumented
systems in the following applications because they are more appropriately covered by other
industry standards such as National Fire Protection Association (NFPA) standards and
American Nuclear Society 8.3, Criticality Accident Alarm Systems. Users should judge whether
the SS SISs are more appropriately covered by any other industry standards. DOE G 420.1-1
identifies the standards that would be applied to systems such as:
DOE-STD-1195-2011
7
a. Evacuation alarms (e.g., nuclear incident monitors, fire alarms, and public address systems);
b. Fire protection/detection systems (covered by NFPA standards); and
c. Support systems (e.g., electrical power systems, instrument air systems).
DOE-STD-1195-2011
A-1
APPENDIX A. OVERVIEW OF ANSI/ISA 84.00.01-2004
A.1 Purpose
This appendix provides an overview of American National Standards Institute/International
Society of Automation (ANSI/ISA) 84.00.01-2004, Functional Safety: Safety Instrumented
Systems for the Process Industry Sector. It describes a life-cycle approach that is useful in the
implementation of this process industry standard at the Department of Energy (DOE).
A.2 Background
Several national and international bodies have developed and published standards and
guidelines to enable application of Electrical/Electronic/Programmable Electronic Systems
technology in safety systems. Efforts are continuing to further the understanding of the safety
application concepts, improve the standards and guidelines, and be responsive to new process
needs and technology developments. Examples of standards that are currently published and
widely used by the process industries for safety applications are listed below.
ANSI/ISA 84.00.01-2004, Functional Safety: Safety Instrumented Systems for the Process
Industry Sector - Parts 1, 2, and 3 and the Technical reports in the ISA TR84.00.xx series.
International Electrotechnical Commission 61511, Functional Safety: Safety Instrumented
Systems for the Process Industry Sector - Parts 1, 2, and 3. IEC 61508, Functional Safety of
Electrical/Electronic/Programmable Electronic Safety-Related Systems. (This standard is
primarily applicable to vendor-manufactured products.)
The ANSI/ISA 84.00.01-2004 approach provides coverage of the safety system full life cycle to
account for the many deficiencies identified in the evaluations of past industry methods and
approaches.
A.3 ANSI/ISA 84.00.01-2004 Life-Cycle Approach
The elements in the life cycle are hazards identification, safety requirements specification,
design, installation, startup testing, management of change, operational testing, maintenance,
operation, modification, and decommissioning of safety instrumented systems (SIS). The life
cycle also includes retention of the original documentation, including design criteria,
procurement specification, commercial grade dedication files, and other relevant information for
the life of the affected systems. Management of changes is applied in all steps of the life cycle.
This life-cycle approach is directed toward reducing the risks inherent in process facility
operations. The ANSI/ISA 84.00.01-2004 approach can be summarized into five steps as
depicted in Figure A.3-1: Life-Cycle Steps for Safety Instrumented Systems.
DOE-STD-1195-2011
A-2
Figure A.3-1: Life-Cycle Steps for Safety Instrumented Systems
Step 1: Develop overall safety requirements
Section 9
This initial phase focuses on how much risk reduction will be required throughout the life cycle
of the SIS. Some level of residual risk will always exist. The purpose of any safety system is to
reduce the identified risk to an acceptable level as defined in the safety basis documentation.
Following the establishment of the conceptual requirements and scope definition, ANSI/ISA
84.00.01-2004 begins with a requirement to perform a hazard analysis, identification of hazards
and associated risks. The safety functions that are required to reduce the identified risks to an
acceptable level are determined during this phase. (See Appendix B for application at DOE
facilities.)
Step 1 – Develop overall safety
requirements (concept, scope
definition, perform hazard and risk
assessment)
Step 2 – Allocate safety
requirements to safety instrumented
functions
Step 3 – Design safety instrumented systems
Design safety
instrumented
systems
Step 4 – Testing, installation,
commissioning and safety validation
of integrated safety instrumented
systems
Step 5 – Operation and maintenance,
modification and retrofit, decommissioning or
disposal phases of safety instrumented
systems
Design safety
instrumented system
software
DOE-STD-1195-2011
A-3
Step 2: Allocate safety requirements to safety instrumented functions
Acceptable risk is achieved by allocating safety requirements to various safety functions. The
safety functions are then allocated to different systems, such as safety class/safety significant
(SC/SS) mechanical or process systems, design features, SC or SS SISs, and other external
hazard controls. When a safety function is allocated to an SIS, it is called a safety instrumented
function (SIF). The allocation process also includes assigning a safety integrity level (SIL) to the
SS SIF, which corresponds to the amount of risk reduction determined to be necessary in the
hazard and risk analysis.
SILs can be expressed as either risk reduction factors (RRF) or as a probability of failure on
demand-average (PFDavg). SILs have four discrete performance ranges and two kinds of
controls; namely, those that respond “on demand” and those for “continuous demand.” The SIL
is related to the average probability of the SIS failing when demanded to perform its safety
function. In either case, ANSI/ISA 84.00.01-2004 applies. Since the majority of DOE safety
controls are of the “on demand” mode of operation, this is the focus of this standard. The SIL
performance requirements in terms of the PFDavg and RRF are listed in Table A.3-1: SIL Level
and Performance Ranges for On-Demand Mode below.
Table A.3-1: SIL Level and Performance Ranges for On-Demand Mode
SIL Level
Designation
Probability of Failure On
Demand-average (PFDavg) Risk Reduction Factor (RRF)
SIL-1 < 10-1 to ≥ 10-2 PFDavg > 10 to ≤ 100 RRF
SIL-2 < 10-2 to ≥ 10-3 PFDavg > 100 to ≤ 1000 RRF
SIL-3 < 10-3 to ≥ 10-4 PFDavg > 1000 to ≤ 10,000 RRF
SIL-4 < 10-4 to ≥ 10-5 PFDavg > 10,000 to ≤ 100,000 RRF
SIL-1 represents the lowest risk-reduction level of performance; SIL-4 represents the highest
risk-reduction level of performance. SIL-4 is not used in the process industry sector because it
requires elaborate systems and is difficult to support because of the high level of reliability
required of the hardware. SIL-4 systems are not expected to be used for SS controls in DOE
facilities.
Section 10
A number of methods (qualitative and quantitative) are available for assigning the SIL.
Qualitative methods may be appropriate when the risk, implementing design, and the hardware
are not well understood. Quantitative methods, such as fault tree or event tree analysis, should
be used when the design and hardware are well understood and supporting data are available.
Quantitative methods are required for verification that the final design and its installation meet
the assigned SIL. Assigning the SIL links the design integrity of the SIS to the required level of
risk reduction, and thereby closes the gap between the hazard analysis and safe process
operation.
ANSI/ISA 84.00.01-2004 provides several methods for determining SIL, such as Layer of
Protection Analysis, which uses frequency of the event as a basis, or Safety Layer Matrix, which
uses available information of independent protection layers (IPLs) as a basis for selection of SIL
for the SIS. For DOE’s application, the accepted methodology is a deterministic method using
the number of IPLs credited by hazard analysis (per DOE-STD-3009, Preparation Guide for
DOE-STD-1195-2011
A-4
U.S. Department of Energy Nonreactor Nuclear Facility Documented Safety Analysis and DOE-
STD-1189, Integration of Safety Into the Design Process). The DOE deterministic methodology
is discussed in Appendix B.
Step 3: Design the SIS and safety software
The SIL establishes a minimum required performance for the SIS, as measured by the PFDavg
or RRF. The factors that affect the PFDavg or RRF are:
a. Component failure rate;
b. Redundancy/diversity of systems and components;
c. Voting (e.g., one-out-of-two or two-out-of-four logic);
d. Testing frequency;
e. Diagnostic coverage (e.g., on-line testing, monitoring of component and system
performance, and monitoring of various failure modes);
f. Common cause failure (e.g., design, human factors, manufacturing, and software);
g. Human factors;
h. Technology (e.g., digital vs. analog); and
i. Software integrity (e.g., diversity, failure detection by on-line monitoring, etc.).
The user should design the SIS with hardware and software components considering the above
factors to achieve the PFDavg or RRF related to the target SIL. The target SIL is an objective of
design process decisions, component specification and procurement to ensure that the design
is consistent with the target SIL. The design is verified at the end of the detailed design process
to ensure that the design as installed and tested can achieve the assigned PFDavg or RRF.
Step 4: Testing, installation, commissioning, and safety validation of SIS
Testing is performed throughout the installation stages to enable validation and verification that
SIS requirements are met. This phase of the life cycle addresses the policy that will be applied
for the following:
a. Integration of software and hardware;
b. Types of testing to be performed and data required to demonstrate functional adequacy
and acceptance;
c. Environment necessary for conducting testing along with the configuration that exists for
testing;
d. Test criteria for which data will be collected and used to judge acceptability;
e. Physical locations (factory or site) for which the test will be performed;
f. Personnel requirements and qualifications required for performing the various activities
related to the validation and verification functions; and
g. Process for documenting and dispositioning non-conformances.
DOE-STD-1195-2011
Section 11
A-5
In Step 4, the SIS design is validated in its “as installed” configuration as achieving its assigned
SIL.
Step 5: Operation and maintenance, modification and retrofit, decommissioning or
disposal phases of SISs
Long-term preservation of an SIS through startup, operation, maintenance, and management of
change activities is as important as initial design and installation phases. The SIL is not just a
design parameter; it is also an operational parameter. The selection made during conceptual or
preliminary design phases, including design configuration, testing frequency, and so on, is
maintained throughout the life of the facility. Therefore, it is essential that management of
system change be maintained to ensure preservation of the SIS.
DOE-STD-1195-2011
B-1
APPENDIX B. SAFETY INTEGRITY LEVEL DETERMINATION METHODOLOGY
B.1 Purpose
This appendix establishes a method for determining the appropriate safety integrity level (SIL)
for safety significant (SS) safety instrumented function (SIF) for DOE nonreactor nuclear
facilities. The target SIL provides design input to an SS safety instrumented system (SIS) that is
credited with reducing the risk of a hazardous event by itself or in combination with other
features to an acceptable level, as defined in the safety basis documentation. The SIL
determination methodology defined in this appendix shall not be used as an input or
requirement to hazard/safety analysis, classification of Safety, Systems, and Components
(SSC) as safety class (SC) or SS, or crediting of SSCs, specific administrative controls (SAC),
or administrative controls (AC) to prevent or mitigate hazardous conditions.
ANSI/ISA 84.00.01-2004, Functional Safety: Safety Instrumented Systems for the Process
Industry Sector, leaves it up to the user to determine the level of performance (i.e., SIL) that is
needed to achieve the user’s process safety objectives. There are a number of recognized
methods, which include, but are not limited to, deterministic, Layers of Protection Analysis, and
Safety Layer Matrix (SLM). A deterministic methodology (a modified SLM methodology), is the
approved method for applying the ANSI/ISA 84.00.01-2004 approach in this standard. The
basis for this modified SLM methodology is that the safety classifications of SSCs are based on
documented safety analyses (DSAs), and, therefore, likelihoods and consequences do not have
any further role in SIL determination.
B.2 SIL Determination and Independent Protection Layers
The SIL Determination Methodology (Figure B.2-1) is a qualitative approach to determine the
SIL of the last SS SIS credited with preventing or mitigating a hazardous event by assessing the
total number of Independent Protection Layers (IPLs) credited with protecting the worker or
public from this event.
Figure B.2-1 is used solely to determine the SIL of an SS SIS after it has been classified as SS.
It is not to be used to determine whether an SSC is classified as SC or SS and should not be
used to determine the required number of IPLs.
N
um
be
r o
f I
P
Ls
3 SIL-1
2 SIL-2 (1)(2)
1 SIL-2 (1)(2)
Figure B.2-1: SIL Determination Methodology
Note 1: When an event may result in a prompt public fatality or multiple prompt
collocated worker fatalities (due to chemical releases; see Appendix B of
DOE-STD-1195-2011
B-2
DOE-STD-1189, Integration of Safety Into the Design Process), the design
authority should consider increasing the SIL number of the SIS by one or
credit an additional IPL.
Section 12
Note 2: When an event (non-criticality) is not expected to result in a facility worker or
collocated worker prompt fatality or serious injuries or significant radiological
or chemical exposures (see Appendices B and C of DOE-STD-1189), the
design authority may consider decreasing the SIL number of the SIS to SIL-1.
IPLs shall meet the following general requirements:
• The IPL shall be designed to prevent an event or to mitigate the consequences of an
event to a level that is supported by safety basis documents;
• The IPL safety function shall be identified and documented in the safety basis
documents of a facility;
• The IPL shall be designed to perform its safety function during normal, abnormal, and
design basis accident environmental conditions for which it is required to function; and
• The IPL shall be sufficiently independent so that the failure of one IPL, or of a
component or subsystem of an IPL, does not adversely affect the probability of failure of
another IPL credited for the same event.
An IPL shall be independent from the initiating cause of the SS event. A process system (e.g.,
ventilation, cooling water) that is not functionally classified as SS or SC should only be identified
as an IPL if its functions are implemented for the purposes of risk reduction, and if its
components and the basic process control system (BPCS) are independent from the initiating
event. This IPL should be maintained in a maintenance/surveillance program and should have
a limiting condition of operation (LCO).
If some combination of components or systems is required to function together to protect a
worker or the public, they shall be considered as one IPL. Thus, if two out of three components
are needed to complete the SS function of a series of components that must function together to
protect a worker, then the combination of components shall constitute one IPL.
Selection of IPLs and the justification for SIL determination for an SS SIS shall be documented
in the DSA.
B.2.1 Independent Protection Layer Identification
The identification of IPLs by the hazard analysis is used as input to SIL determination. As
shown in Figure B.2-1, the number of IPLs credited for a hazardous event will determine the SIL
of an SIS. Safety functions, controls, and programs that can be credited as IPLs are as follows:
• Credited passive safety design features: Each passive safety design feature may be
credited as two IPLs if it is controlled under a documented configuration management
program and subject to periodic surveillance, if required, that confirms and documents
that the SSC will perform its intended safety function.
DOE-STD-1195-2011
B-3
• Specific administrative control (SAC): SACs that can be directly credited with
preventing or mitigating an event to a level as defined in the safety basis documentation.
Only one SAC shall be credited in the SIL determination for a specific hazardous event.
• Administrative control programs (AC): AC programs should be credited in the SIL
determination only for the protection of in-facility workers or for protection against
criticality accidents. The AC shall be identified in the Technical Safety Requirements as
being important to risk reduction for specific accidents. Only one AC shall be credited in
the SIL determination for a specific hazardous event.
Section 13
• Safety Significant systems: Process systems classified as SS (e.g., ventilation
systems, cooling systems) can be credited when they provide protection against the
same set of hazards/accidents as the SIS being evaluated. They may be credited as
two IPLs if a calculation of their safety unavailability in terms of the average probability of
failure on demand (PFDavg) is less than 10-2 or the RRF is greater than 100.
• Safety Class systems: An SC system that is credited with providing protection against
the same set of hazards/accidents as the SIS being evaluated may be credited as two
IPLs. An associated defense-in-depth SS control for an SC control may be credited as a
separate IPL if it is independent of the SC system.
• The SIS whose SIL is being determined: An SIS whose SIL is being determined is
also credited as an IPL.
B.2.2 Application of the SIL Determination Methodology
This section describes how the SIL Determination Methodology shown in Figure B.2-1 can be
used to determine the SIL for an SIS for protection from an event impacting a collocated worker.
If only two IPLs are credited in the hazard analysis for this event, and one of them is a SS SIS,
the SS SIS target SIL is SIL-2. If three or more IPLs are credited for this scenario, the SS SIS
would have a target SIL of SIL-1.
In a situation in which two SS SISs are credited with preventing or mitigating the same event,
one of the SS SISs may be assigned as SIL-1. The second SS SIS shall have its SIL
determined by Figure B.2-1. Both SS SISs can be credited if they meet the requirements listed
in Sections B.2 and B.2.1.
If an instrumented system has been classified as SS during the hazard analysis and functional
classification process, then, regardless of the number of IPLs credited, it shall have a target SIL
of no less than SIL-1. The SIL determination methodology shall not be used by itself to reduce
the classification of an SS SIS to non-safety significant. A more detailed example utilizing a
specific SIS is provided in Appendix D.
DOE-STD-1195-2011
C-1
APPENDIX C. SAFETY INTEGRITY LEVEL VERIFICATION GUIDANCE
C.1 Purpose
This appendix provides guidance on safety integrity level (SIL) verification calculations that are
required in Section 11.9.1 of ANSI/ISA 84.00.01-2004, Functional Safety: Safety Instrumented
Systems for the Process Industry Sector. In particular, this appendix provides additional
clarification and information for some calculation techniques that are not addressed in ISA
TR84.00.02, Safety Instrumented Functions (SIF) ― Safety Integrity Level (SIL) Evaluation
Techniques.
C.2 SIL Verification Calculation Content
The SIL verification calculation should include details on input data, the safety significant (SS)
SIF, and the SS safety instrumented system (SIS) description that should be met. The
information described below for SIL verification calculations is necessary for developing or
reviewing the calculation, as well as for adequate understanding of the SS SIS and the risk
reduction that it provides.
C.2.1 Input Data
1. The source of failure rate data and the periodic surveillance and test frequencies for
components of the SS SIS should be documented.
2. Where facility documents, such as a Technical Safety Requirements (TSR) or
Documented Safety Analysis/safety basis documents, allow a grace period (e.g., test
frequencies may be extended up to 25 percent without prior approval) for calibration and
test frequencies, this grace period should be added to the test/calibration frequencies to
prevent unanalyzed conditions.
Section 14
3. Input data, such as periodic test frequencies and trip setpoints, should be in the safety
basis documents.
4. Components that are certified for process safety under the International Electrotechnical
Commission (IEC) 61508, Functional Safety of Electrical/Electronic/Programmable
Electronic Safety-Related Systems, are supplied with a vendor safety manual. The
vendor safety manual should be referenced. The vendor safety manual may list
restrictions on the operating conditions and configuration of components in order to
achieve a specific average probability of failure on demand (PFDavg) or SIL compliance.
The vendor safety manual should be reviewed in its entirety to ensure that a component
can be used in the selected design configuration and environment to achieve the target
SIL.
5. The failure modes on loss of motive force should be documented for each of the SS SIS
components.
6. When support systems (e.g., electrical power, instrument air) are required to complete
the SS SIS, their availability should be determined so that it can be included in the
verification calculation.
DOE-STD-1195-2011
C-2
7. Operator errors should be included in the SIL verification calculation when an operator
action is required to respond to an alarm or indication to accomplish the SS SIF. To
credit operator action either the alarm/indication should be in (1) a continuously-manned
control room, or (2) a remote area that has a mandated periodic surveillance. The
source of operator error data should be documented.
8. Components that do not have an assigned test or calibration frequency, but the
availability of which contributes to the overall functionality of the SS SIS, should be
assigned a test interval equivalent to the “mission time” of the process. The mission
time is the life of the process being performed or the period of time that a component will
be in service before it is replaced.
C.2.2 SS SIF Description
A complete description of the SS SIF addressed should be included in the SIL verification
calculation. The description should include the required SIL for the function, and the required
modes of operation for the SS SIF.
A description of any manual (operator) actions that are required to complete the safety function
should be identified. The performance requirements for the SS SIF (e.g., response times,
maximum valve leakage) should be identified. The required operating range and analytical
safety limit of the SS SIF should be identified. References to the safety documents that
describe the SS function and its performance requirements should be provided.
C.2.3 SS SIS Components Identification
All of the SS components (e.g., sensors, logic solvers, final control elements) of the system, a
description of their safety functions in the system, and a sketch and/or reference drawing(s)
(e.g., piping and instrumentation diagram, schematic, loop diagram, logic diagram, or
description) for the system should be identified. A description of SS SIS interfaces from/to
support systems and non-safety operator information systems should also be included.
C.3. SIL Verification Calculation Guidance
The ISA technical report, ISA TR84.00.02, provides guidance on SIL verification calculations. A
SIL verification calculation for a SS SIF is normally performed using simplified equations (ref.
ISA TR84.00.02-2002 – Part 2) or fault tree analysis (ref. ISA TR84.00.02-2002 – Part 3).
C.3.1 Common Cause Failure
Section 15
Common Cause Failures (CCF) can be either safe detected or undetected, or dangerous
detected or undetected. The SIL verification calculation is concerned only with dangerous
undetected failures. CCFs are influenced by physical and electrical separation, diversity, and
the robustness of design of the component (ability to withstand environmental stressors).
ANSI/ISA 84.00.01-2004 uses the beta factor method to model common cause failures (see ISA
TR84.00.02) in a single SS SIS with redundant components. The beta factor normally falls
within the range of 0 to 10 percent. When good engineering design is followed, the beta factor
will generally fall within the range of 0 to 5 percent (Ref. ISA TR84.00.04 –Part 1).
When physical and electrical separation is provided consistent with the intent of IEEE 384,
Standard Criteria for Independence of Class 1E Equipment and Circuits, for two or more diverse
DOE-STD-1195-2011
C-3
SS SISs that are IPLs for a specific hazardous event, they may be considered as independent,
and the addition of a CCF factor into the SIL verification calculation is not recommended.
A CCF factor should be included in the SIL verification calculation of an SS SIS when it is
credited with another SS SIS IPL to reduce the risk of a specific hazardous event to a level
defined in the safety basis documentation, and the SS SISs have identical or similarly
functioning components in any of the subparts of the systems (i.e., sensors, logic solvers, final
control elements), and when physical and electrical separation between SS SIS IPLs is not
maintained.
For example, if both SS SISs for a hazard event use identical valves as the final control element
to shut off flow, then a beta factor times the PFDavg of the valve should be added to the final
PFDavg value in at least one of the SS SIS SIL verification calculations. If an individual SS SIS
has redundant architecture within a subpart (e.g., 1oo2 valves or 2oo3 sensors) and has
included a beta factor to address this architecture, then no additional beta factor is
recommended for using identical components in similar SS SIS IPLs for a specific event
because a beta factor is already addressed in the SS SIS SIL verification calculation of one of
the IPLs.
The following CCF term should be added to the total PFDavg of the SIL verification calculation
for each component/subsystem that is identical between two or more SS SISs credited for a
single hazard.
CCF = β x λ x (TI/2)
β is the fraction of failures that impact more than one component/subsystem in a
redundant configuration.
λ is the undetected dangerous failure rate of the component/subsystem.
TI is the time interval between functional tests of the component/subsystem.
C.3.2 Systematic Failure
Systematic failures (e.g., human design errors, software failures, programmatic failures) are
generally not to be included in the verification calculation if they are adequately addressed by
procedures. For example, if software development meets the intent of ANSI/ISA 84.00.01-2004,
Part 1, Section 12, then software failures should not be included in the SIL verification
calculation.
C.3.3 Converting Per Demand Failures into Failure Rate
Section 16
Some mechanical components (valves/relays) have their failure described as “failures/demand”
versus a failure rate (λ) “failures/hour.” This failure/demand value may be used in the fault tree
or simplified equation as the PFDavg for that component. When it is desired to take credit for
the periodic testing of these components, the failure/demand can be converted to a failure rate.
The conversion from failure data given in failures/demand to a failure rate should only be done
for hardware failures. Human failure rates given in failures/demand cannot be converted into
failures/hour.
DOE-STD-1195-2011
C-4
A conversion example using a hardware failure of 5.0 E-03/demand for an anticipated hazard is
shown below. The demand rate in this equation is the quantitative or qualitative value for the
frequency of the hazard. When the hazard frequency has been qualitatively defined as
“Anticipated,” “Unlikely,” or “Extremely Unlikely,” the calculation should use a demand rate of
once per year. Conversion from a per demand value to a failure rate (λ) is not recommended
when the hazard rate is less than once per year.
λ = PFD x Demand Rate
λ = failure/demand x demand/hours
λ = (5.00E-03/demand) x (demand/8760 hours)
λ = 5.7 E-07/hour
C.3.4 Dangerous Detected Failures
Dangerous detected failures should be managed. If a dangerous failure is detected either
automatically (diagnostic alarm) or through periodic surveillance, some action should be taken
to either: (1) restore the device to full operability within the allowed mean time to repair (MTTR);
(2) place that device or system in a safe/tripped state; or, (3) provide compensatory measures.
If none of the actions described above is taken, the dangerous detected failure should be
treated as a dangerous undetected failure as far as the verification calculation is concerned.
C.4. Spurious Trips
ISA 84.00.01-2004 Part 1, Section 10.3.1, requires the identification of the maximum allowable
spurious trip rate for a SIF. This value in terms of a spurious trip rate or mean time to fail
spurious (MTTFspurious) is a key design feature which establishes the required reliability of the
SIF. A system that requires a high availability may require redundancy of field devices that are
voted in a 1 out of 2 (1oo2) or 2oo3 configuration regardless of the SIL value. Evaluation
techniques for MTTFspurious can be found in ISA TR84.00.02.
DOE-STD-1195-2011
D-1
APPENDIX D. ILLUSTRATION OF A SAFETY INTEGRITY LEVEL DETERMINATION AND
SAFETY INTEGRITY LEVEL VERIFICATION CALCULATION1
D.1 Purpose
This appendix is intended to provide an example of a safety significant (SS) safety instrumented
system (SIS) and to show the activities appropriate to two stages in the safety life cycle: safety
integrity level (SIL) determination and SIL verification calculation. The entire safety life cycle
consists of all of the activities involved in the implementation of safety instrumented function
(SIF), starting at project conception and ending with decommissioning. The example in this
appendix illustrates the determination of an SIL based on the hazard analysis and SIF
description. The example also includes the SIL verification calculation performed to confirm that
the design, operation, and testing of the SS SIS meets the designated SIL.
Note: The design, SIL determination, and verification are for illustrative purposes only.
The values (failure rates, test frequencies, beta factors) used in the SIL
verification calculation were developed for this example only and are not to be
construed as valid for any other calculation.
Section 17
D.2 SIL Determination of an Example SS SIS
D.2.1 Hazard Description (Example)
The liquid aqueous waste solutions from separations processes are concentrated in batch
evaporators. The solution is heated to the boiling point by condensing steam in the evaporator
coils. The steam pressure in the coils is maintained between 14 psig and 24 psig at saturated
conditions. In a typical batch process, the evaporator pot is filled with process waste solution to
a predetermined level to cover the heating coils. The solution is heated to boiling. As the
solution is heated, it begins to circulate through the evaporator pot draft tube from the bottom to
the top. This flow is created by natural heat convection and engineering design. As the solution
is boiled, the vapors flow upward to the condenser. Feed flow from the evaporator feed tank
must be started at this time to maintain the evaporator pot liquid level. The formation of an
organic layer above the aqueous layer is possible.
When tributyl phosphate (TBP) and nitric acid are mixed and heated, the TBP starts to
decompose. Although a heat source is required to initiate the rapid initial reactions, at some
point, the reaction generates enough heat and pressure to sustain the reaction without an
external heat source. This is the autocatalytic or runaway reaction initiation temperature. In this
example, a potential exists for an uncontrolled reaction between TBP and nitric acid that could
result in a significant release of radioactive material.
A hazard analysis was performed that identified the need for SS control(s). The hazard is
anticipated and has a consequence that exceeds evaluation guidelines to the collocated worker.
1 Appendix D is included for information only. All the conditions presented are representative and may need
modification to ensure their suitability to any specific application.
DOE-STD-1195-2011
D-2
D.2.2 SS SIF Description (Example)
An interlock is provided to close the steam shutoff valve to the evaporator coils prior to reaching
the autocatalytic temperature in the evaporator’s liquid aqueous waste solution. The steam
shutoff valve must close within (to be determined) seconds.
D.2.3 SIL Determination (Example)
The SIL determination is made by considering the type and number of independent protection
layers (IPL) that are provided to prevent or mitigate the hazardous event in question. Appendix
B of this standard provides details on the SIL determination methodology and how it is to be
applied.
The following describes the IPLs selected for the evaporator used as the example.
Two IPLs were considered to prevent a TBP-nitric acid reaction. These IPLs either limit the
temperature or prevent large accumulations of TBP in a single vessel. The methods used to
implement these basic approaches include the following:
1. Limit the mass of TBP (organics) present, and
2. Prevent mixtures of TBP and nitric acid from reaching high temperature by controlling
the heat sources.
The hazard analysis has determined that the event exceeds evaluation guidelines to collocated
workers. SS controls are required to prevent the event. The following controls (IPLs) were
selected:
IPL#1 — A specific administrative control (SAC) requires a periodic inspection (to be completed
annually) of the feed tank for a continuous layer of organic. If a continuous layer of organic is
detected, it shall be removed by flushing or skimming. This allows detection and removal of the
organic to limit the mass of TBP present; and,
Section 18
IPL#2 — A high temperature-steam flow interlock is credited as an SS feature to prevent
exceeding the autocatalytic reaction temperature. Two IPLs are credited for this event: the SAC
and the SS SIS temperature. With two IPLs credited, the SS SIS (temperature interlock) is
required to be SIL-2 per the Figure D.2.3-1: SIL Determination Methodology shown below.
DOE-STD-1195-2011
D-3
N
um
be
r o
f I
P
Ls
3 SIL-1
2 SIL-2(1)(2)
1 SIL-2(1)(2)
Figure D.2.3-1: SIL Determination Methodology
Note 1: When an event may result in a prompt public fatality, or multiple prompt
collocated worker fatalities (due to chemical releases; see Appendix B of
DOE-STD-1189, Integration of Safety Into the Design Process), the design
authority should consider increasing the SIL number of the SIS by one or
credit an additional IPL.
Note 2: When an event (non-criticality) is not expected to result in a facility worker or
collocated worker prompt fatality, or serious injuries, or significant radiological
or chemical exposures (see Appendices B and C of DOE-STD-1189), the
design authority may consider decreasing the SIL number of the SIS to SIL-1.
D.2.3.1 SS SIS Description
The high temperature steam flow interlock for the batch evaporator (see Figure D.2.3.1-1:
Evaporator Temperature Interlock) consists of sensors (two temperature elements/transmitters),
logic solver (safety programmable logic controller [PLC]), and final control elements (solenoid
and isolation valves). Temperature control is provided by temperature element, or TE-1, the
Digital Control System (DCS), and the flow control valve (FCV). When a high temperature is
sensed by one-out-of-two (1oo2) temperature devices (TE-2 and TE-3), the interlock prevents
the evaporator from reaching the runaway initiation temperature. The temperature interlock will
shut off the steam to the heating coils by deenergizing the solenoid valve (SV), thus closing the
steam isolation valve (FV). The isolation valve has no leakage classification requirements. The
shutoff capability of the isolation valve is tested periodically by verifying temperature drop after
the valve is shut.
DOE-STD-1195-2011
D-4
FCV FV
AS
~
~AS
TT-1 TT-2 TT-3
TE-1 TE-2 TE-3
FCV FV
AS
~
~AS
TT-1 TT-2 TT-3
TE-1 TE-2 TE-3
Figure D.2.3.1-1: Evaporator Temperature Interlock
The SV fails in the closed position (vents air from the FV on loss of signal or loss of instrument
air) (fail safe). The FV closes on loss of instrument air (fail safe). SS temperature transmitters
(TT-2 and TT-3) are reverse acting so that a low signal or loss of signal initiates the interlock.
The PLC is programmed to detect a “hi-hi” signal or loss of signal from the temperature
transmitters and initiate the temperature interlock.
Hardware Fault Tolerance
An SIL-2 design requires a minimum hardware fault tolerance of 1 for sensors and final
elements (See ANSI/ISA 84.00 -2004, Functional Safety: Safety Instrumented Systems
for the Process Industry Sector - Part 1, Section 11.4.4).
To meet this requirement for the sensors, the design employed redundant temperature
elements (TE-2, TE-3) and temperature transmitters (TT-2, TT-3).
The SS PLC uses an internal triple modular redundant configuration. It is certified as SIL-3
compliant in a non-redundant configuration that exceeds the requirements for SIL-2 design.
Section 19
The SV and the FV function together as the final element. The solenoid valve is certified as
SIL-2 compliant in a non-redundant configuration. Based on “prior use,” and other attributes
stated in ANSI/ISA 84.00.01-2004 – Part 1, Sections 11.4.4 and 11.5.3, the hardware fault
DOE-STD-1195-2011
D-5
tolerance for the steam isolation valve was reduced to zero. Therefore, a single isolation valve
is adequate for the SIL-2 design.
D.2.3.2 SIL Verification Calculation
The purpose of the SIL verification calculation is to demonstrate by analysis that the design of
an SS SIS meets the integrity requirement specified by its SIL determination.
Technical Safety Requirements (TSR) allow a grace period for loop and calibration testing to be
extended by 25 percent without an engineering review. To account for this allowance, all test
frequencies (τ) will be multiplied by a factor of 1.25.
SENSOR (S) FAILURES
Resistance Temperature Element (RTD) Failure (TE-2, TE-3)
Failure data was obtained from the facility owner’s database (λ = 1.0E-06/h). The temperature
elements are replaced on an 18-month cycle when the thermowells are replaced due to
corrosion concerns. The failure of an RTD would be corrected at the time the RTD is changed
out (18 months). TSRs allow the change-out period to be extended by 25 percent without an
engineering review.
τ = mission time or the periodic functional test period
τ = (1.5 yr) (8760 hours/yr) (1.25)
τ = 16,425 hours
PFDavg(TE) = 0.5λτ
PFDavg(TE)= (0.5)(1.0E-06)(16,425) = 8.2E-03
Temperature Transmitter Failure (TT-2, TT-3)
Failure data was provided by the vendor (λ = 9.8E-08/h). The test interval per TSR for the
instrument loop test of the interlock is once every 90 days (2160 hrs) 2160 hrs x 1.25 = 2700
hours (τ = 2700 hours).
PFDavg(TT) = 0.5λτ
PFDavg(TT) = (0.5)(9.8E-08)(2700) = 1.3E-04
The PFDavg of the temperature element and transmitter series combination is calculated below:
PFDavg(TE/TT) = PFDavg(TE) + PFDavg(TT)
PFDavg(TE/TT) = 8.2E-03 + 1.3E-04 = 8.3E-03
DOE-STD-1195-2011
D-6
Beta Factor
Since redundant temperature elements and temperature transmitters were used to meet the
hardware fault tolerance requirement for a SIL-2 system, a beta factor was included. A very
conservative beta factor of 10 percent was used in this example. A lesser beta factor would be
justifiable based on environmental stressors and the physical and electrical separation provided
by the design.
Sensor PFDavg(s)
The PFDavg(S) equation for the TE/TT sensor devices in a one-out-of-two (1oo2) arrangement
is:
PFDavg(S) = [PFDavg(TE/TT)]2 + β x PFDavg(TE/TT)
PFDavg(S) = 6.9E-05 + (0.1) x 8.3E-03
PFDavg(S) = 9.0E-04
LOGIC SOLVER (LS) FAILURES
PLC Failure
Probability of failure on demand is provided by the vendor as (PFD = 5.5E-05).
PFDavg(LS) = 5.5E-05
FINAL CONTROL ELEMENT (FE) FAILURES
Solenoid Valve (SV) Failure
The solenoid valve has been certified as SIL-2 compliant. Failure data was obtained from the
vendor (λ = 4.0 E-7/d). To convert a “per demand rate of failure” to a “per hour rate of failure,” a
demand rate (hazard event frequency) of once per year is used. Therefore:
λ = PFD * Demand Rate
λ = failure/demand * demand/hours
λ = (4.0E-07/demand) * (demand/8,760 hours)
λ = 4.6 E-11/hour
The test interval per TSR for the instrument loop test is once every 90 days (2160 hrs) x 1.25 =
2,700 hours (τ = 2,700 hours).
PFDavg(SV) = 0 .5λτ
PFDavg(SV) = (0.5) (4.6E-11/h) (2,700h) = 6.2E-08
Section 20
DOE-STD-1195-2011
D-7
Steam Valve (FV) Failure
Because no vendor-specific data are available, site generic failure data for a control valve failing
to close is used (λ = 3.0 E-6/h). The test interval per the TSR for the instrument loop test is
once every 90 days (2,160 hrs) x 1.25 = 2,700 hours (τ = 2,700 hours).
PFDavg(FV) = 0.5 λτ = (0.5) (3.0 E-6/h) (2700h) = 4.0E-03
Final Control Element (FE) PFDavg
PFDavg(FE) = PFDavg(SV) + PFDavg(FV)
PFDavg(FE) = 6.2E-08 + 4.0E-03 = 4.0E-03
SYSTEM (SIS) PFDavg
PFDavg (SIS) = PFDavg(S) + PFDavg(LS) + PFDavg(FE)
PFDavg (SIS) = 9.0E-04 + 5.5E-05 + 4.0E-03
PFDavg (SIS) = 5.0E-03
The required SIL for this example was SIL-2. The accepted PFDavg range for SIL-2 is
<10-2 to ≥10-3. The calculated PFDavg for the SS SIS is 5.0E-03.
RRF(SIS) = 1/PFDavg(SIS) = 200
DOE-STD-1195-2011
E-1
APPENDIX E. FAILURE RATE DATA2
E.1 Failure Rate Data
American National Standards Institute/International Society of Automation (ANSI/ISA) 84.00.01-
2004, Functional Safety: Safety Instrumented Systems for the Process Industry Sector, requires
the user to verify that the average probability of failure on demand (PFDavg) of the safety
significant (SS) safety instrumented system (SIS) as designed, operated, and tested meets its
safety integrity level (SIL). One of the key factors in the calculation of PFDavg is the failure rate
of the components comprising the SS SIS.
Failure rate database use is common in the process industry sector when complying with
ANSI/ISA 84.00.01-2004 – Part 1. The databases that provide a relative probability of failure for
component types (e.g., level transmitters, pressure transmitters, analyzers, relays, breakers,
pumps, motors, valves) are obtained from various industry sectors. In virtually all cases, these
industrial databases turn out to be more conservative than product-specific data or user-specific
data. Although some of the databases have not been updated recently, their data can be used
in SIL verification calculations based on the conservatism of their failure rate values and the
improved reliability, on average, of newer equipment.
The ANSI/ISA 84.00.01-2004 requirements for hardware fault tolerance (HFT) for SIL-2 and
SIL-3 systems will drive redundancy and guard against the underestimation of equipment failure
rates adversely affecting system-level safety unavailability (PFDavg). In addition, the ANSI/ISA
84.00.01-2004 requirement for performance monitoring will detect those cases in which the
failure rate of a device was underestimated, or it proved unsuitable in a particular process
application. HFT requirements and performance monitoring, in combination with failure rate
databases, provide assurance that the design and operation of the SIS will be in compliance
with the target SIL.
Failure rate data can be obtained from the sources listed below.
E.1.1 Industrial Databases
1. Offshore Reliability Data (OREDA)
2. Reliability Analysis Center
a. EPRD-CD, Electronic Parts Reliability Data
b. FMD-97, Failure Mode/Mechanism Distributions
c. NPRD-CD, Non-electronic Parts Reliability Data
3. Guidelines for Process Equipment Reliability Data, with Data Tables, 1989, Center for
Chemical Process Safety of American Institute of Chemical Engineers (AIChE)
2 Appendix E is included for information only. All the conditions presented are representative and may need
modification to ensure their suitability to any specific application.
DOE-STD-1195-2011
E-2
Section 21
4. ANSI/IEEE-Std-500, IEEE Guide to the Collection and Presentation of Electrical,
Electronic, Sensing Component, and Mechanical Equipment Reliability Data for Nuclear-
Power Generating Stations, 1984
5. Reliability Data for Control and Safety Systems, 1998, SINTEF Industrial Management
6. Process Equipment Reliability Database, Center for Chemical Process Safety (CCPS),
AIChE
Note 1: In addition to the above industrial databases, many consultant companies
working in the chemical process safety industry have developed their own
failure rate databases, combining the above data with company-specific and
product-specific data.
Note 2: The list of databases above is not all inclusive. There is no intent to endorse
or limit the use of comparable databases.
Industrial databases are not product-specific or application-specific; that is, they do not
distinguish between harsh or mild environments, process conditions, or levels of maintenance
and inspection. The data do provide a good, generally conservative estimation of equipment
failure rates. Users should evaluate the expected environmental stressors on their safety
devices, and, if they are expected to be above the norm, the SIS design should consider
increased diagnostics and/or a factor increase in the failure rates. The source of the industrial
data is an indicator of the environment in which the equipment was performing. For example,
the OREDA data are primarily from the rather severe conditions of the North Sea oil rigs, and
the ANSI/IEEE-Std-500 data are from the less severe environmental conditions for electrical
devices in commercial nuclear power plants.
In using failure rate data, whether it is from industrial databases, product-specific data, or user-
specific data, the conditions (both environmental and other stressors) in which the equipment
identified in the database was required to perform should be ascertained and understood.
These conditions should then be compared to the performance conditions of the equipment to
be analyzed. The first choice of failure rate data should be that which comes from applications
that are as near as possible to the application to be analyzed. The best practice is to consult
more than one database in determining or confirming the appropriate failure rate value to be
used. For any differences between the application to be analyzed and the database
applications, data adjustment would be in order and may be necessary.
E.1.2 Product-Specific Data
Suppliers of components (e.g., instrumentation, programmable logic controllers, valves) used in
process safety applications perform detailed analysis of their products to determine their specific
probabilistic failure rate. The vendors providing equipment to the process industry sector must,
by U.S. and international requirements, meet process safety requirements that are generally
met by adhering to IEC 61508, Functional Safety of Electrical/Electronic/Programmable
Electronic Safety-Related Systems. This standard establishes recommendations for the design
and manufacture of components and discrete systems, including quality assurance, testing, and
performance. The product-specific failure rates should be determined either by the
manufacturer or a third-party certification organization. Product-specific failure rates can be
determined by performing a failure modes and effects analysis (FMEA), which provides a
specific failure rate for each component. In addition, the analysis should provide a
Section 22
DOE-STD-1195-2011
E-3
determination of safe versus dangerous failures and, where applicable, the diagnostic
capabilities of the device to detect unsafe failures. Product-specific data end at the boundary of
vendor equipment. Product-specific failure data do not consider process conditions or
environmental factors. When using product-specific data in SIL verification calculations, the
user is cautioned to include failures of process interfaces (e.g., sensor impulse line plugging).
Vendors of process safety equipment generally monitor the failures of devices after they have
gone to market through contact with their users and returns of failed devices. On average, the
FMEAs of a device designed for safety applications in the process industry have been found to
have a lower failure rate versus the industrial databases identified in Section E.1.1.
E.1.3 User-Specific Data
Many chemical and process industry companies have developed their own failure rate
databases based on their usage and applications. These data can be generic (e.g., level
transmitters or control valves) or product-specific (i.e., Company ABC Model No. XYZ). When
sufficient operational data exists, a user-specific database can be the most accurate because it
reflects all stressors that impact a device. This includes environmental (e.g., temperature,
vibration, process conditions) and operational (e.g., maintenance, testing, inspection)
considerations. Caution should be taken when using data that come from multiple facilities on
one site to ensure that the stressors and environmental conditions are applicable to the
application to be analyzed.
E.1.4 Performance Monitoring
ANSI/ISA 84.00.01-2004 – Part 1, Section 5.2.5.3, requires the user to assess whether the
observed fail-dangerous failure rates are in accordance with those used in the SIL verification
calculation. To fulfill this requirement, the user should have a procedure to monitor the
performance of safety devices and should periodically assess the observed failure data for
comparison to that used in the SIL verification calculation.
ANSI/ISA 84.00.01-2004 – Part 1, Section 11.5, allows for the selection of safety components
and subsystems based on “prior use.” Essentially, when users have experience with a device in
either a safety or non-safety application, they may use that knowledge of failure modes and
rates to justify application of that device in an SS SIS. In order to have the necessary data
available to support “prior use,” the user should have systems/procedures in place to capture
operational experience (Performance Monitoring) for devices that may be used in the future for
safety applications.
DOE-STD-1195-2011
F-1
APPENDIX F. QUALITY ASSURANCE FOR SAFETY SOFTWARE FOR SAFETY
INSTRUMENTED SYSTEMS
This appendix provides a general discussion of the types of safety software and applicable
quality assurance requirements.
F.1 Safety Software
The following types of software are used in safety instrumented systems (SIS).
Embedded software, normally provided by the vendor, is developed by a vendor and contained
within the assembly of a programmable electronic device that is configured for performing a
specific functional need and is not accessible for modification by the end-user. Embedded
software is also referred to as firmware or system software.
Utility software, supplied by the vendor, is used to develop and verify application software.
Utility software, like embedded software, is also developed by a vendor.
Section 23
Application software, normally programmed by the end users, is developed for a specific
application. In general, it contains logic sequences, permissives, limits, and expressions that
control the appropriate input, output, calculations, and decisions necessary to meet the Safety
Instrumented Function requirements. For application software, the vendor generally provides
Fixed Program Language (FPL), Limited Variability Language (LVL), or Full Variability
Language (FVL) programming software.
FPL is designed to limit the user to the adjustment of a few parameters; for example, range of
the pressure transmitter, alarm levels, and network addresses.
LVL is designed to be comprehensible to process sector users, and provides high-level
configurable program instructions, such as ladder logic or function blocks, to allow the end-user
to configure the application within a strictly controlled framework or environment. LVL is widely
used by the end-user for Programmable Logic Controller (PLC) application programming.
FVL is designed to be comprehensible to computer programmers and provides the capability to
implement a wide variety of functions and applications.
F.2 Software and Hardware Integration
Three elements of safety software applications are as follows:
• the sensor (may have internal logic; the primary function is to sense and transmit data
or some form of aggregated data);
• the logic device (the purpose is to process information variables to determine their
condition relative to a trip point, calculating transfer functions, or other process specific
tasks); and
• the control element (an actuator, for example, performs a desired function based on the
output results from the sensor or logic device).
DOE-STD-1195-2011
F-2
The above elements are normally integrated using a network system with software of some
type, such as an embedded program. Fieldbuses are also used for communication to field
devices. Software development management control principles and software life-cycle
elements apply to each of the above elements to the extent that the safety case can be verified
for all safety subsystems and the overall safety system.
Prior to development of application software, an SIS software requirements specification should
be developed (in accordance with guidance provided in DOE G 414.1-4, Safety Software Guide
for Use with 10 CFR 830 Subpart A, Quality Assurance Requirements, and DOE O 414.1C,
Quality Assurance) that describes overall system operating requirements and functions,
including applicable safety functions and safety requirements that form the safety basis for the
system design. Safety software is designed to support one of the following or a combination of
them.
• Isolation — Critical components are separated from each other in a manner to preclude
undefined interactions. When applied to software design, the emphasis is on
encapsulation, information hiding, and formal interfaces that preclude (i.e., isolate) SIS
failure due to unintended software execution or malfunction.
• Independence — The stimuli for actions originate from, and are handled by, separate
components. This is generally implemented by redundant components often with
different designs that support a safety-related task. As applied to software, independent
hardware inputs are directed to independent software modules.
Section 24
• Inoperability — Abnormal conditions cause a component to become inoperable in a safe,
predictable manner and before any isolation features are compromised. As applied to
software design, these criteria may be implemented through comprehensive exception
handling and fail-safe designs in critical components.
• Incompatibility — Components in different parts of the system cannot operate together in
a satisfactory manner. To avoid incompatibility, consider that sensors, a logic device
(such as a processor), and control devices may have embedded software that needs to
be integrated into a networked system. The acceptability of the integration needs to be
validated.
Embedded software is generally used for software/hardware integration, and fieldbus is used for
networking and communication purposes. Fieldbuses used to implement safety functions
should follow the design considerations listed in ISA TR84.00.06.
F.3 Safety Software Quality Assurance Work Activities
DOE G 414.1-4, Safety Software Guide for Use with 10 CFR 830 Subpart A, Quality Assurance
Requirements, and DOE O 414.1C, Quality Assurance, identifies 10 software quality assurance
(SQA) activities applicable to software development and acquisition. Table F.3-1: Crosswalk of
SQA Work Processes with Acceptable Industry Implementation Guidance Standards identifies
industry guidance standards available to fulfill requirements of the DOE Guide. The industry
guidance standards listed in Table F.3-1 are not intended to be an exhaustive list. Other
standards may be applied so long as the basis for their selection for the application is
documented and is shown to be equivalent level of quality assurance as to DOE O 414.1C,
Quality Assurance.
DOE-STD-1195-2011
F-3
Table F.3-1: Crosswalk of SQA Work Processes with Acceptable Industry and Other
Implementation Guidance Standards
Item SQA Work Processes
DOE G 414.1-4
Acceptable Industry
Implementation Guidance
Standards
1 Sec. 5.2.1, Software Project Management and
Quality Planning
Software project management and quality
planning should involve identifying all tasks
associated with the software development and
procurement, including procurement of
services, as described for safety software in
Section 5.2.1.
• ANSI/ISA 84.00-01-2004-Part 1
(Clause 12)
• ASME NQA-1-2000 and Subpart
2.7
• ANSI/IEEE STD 730, Standard for
Software Quality Assurance Plans
2 Sec. 5.2.2, Software Risk Management
The risk associated with safety software
applications needs to be understood and
documented. As discussed in Section 5.2.2,
all apparent risks known at the time, whether
large or small, should be identified, analyzed
for impact and probability of occurrence,
prioritized, and resolved to a level as defined
in the safety basis documentation of risk to
enable establishing a historical record for the
life of the safety software.
• ANSI/ISA 84.00-01-2004-Part 1
(Clause 12)
• ASME NQA-1-2000 and Subpart
2.7
• ANSI/IEEE STD 730, Standard for
Software Quality Assurance Plans
3 Sec. 5.2.3, Software Configuration
Management (SCM)
SCM activities identify all functions and tasks
required to manage the configuration of the
software system, including software
engineering requirements, establishing the
configuration baselines to be controlled, and
software configuration change control
process. SCM includes (1) configuration
identification, (2) configuration control,
(3) configuration status accounting, and (4)
configuration audits and reviews.
• ANSI/ISA 84.00-01-2004-Part 1
(Clause 12)
Section 25
• ASME NQA-1-2000 and Subpart
2.7
• ANSI/IEEE STD 730, Standard for
Software Quality Assurance Plans
4 5.2.4, Software Procurement and Supplier
Management
This section provides essential attributes for
safety software procurement that are
applicable to SIS embedded software and
utility software, as well as any services
provided for application software
development.
• ANSI/ISA 84.00-01-2004-Parts 1
(Clause 12)
• ASME NQA-1-2000 and Subpart
2.7
• ANSI/IEEE-Std-730, Standard for
Software Quality Assurance Plans
DOE-STD-1195-2011
F-4
Item SQA Work Processes
DOE G 414.1-4
Acceptable Industry
Implementation Guidance
Standards
5 Sec. 5.2.5, Software Requirements
Identification and Management
SIS design basis requirements provide the
foundation for the identification and
management of software requirements that
include functional, performance, safety
requirements, design constraints, interface,
installation considerations, and access
control, as appropriate. The software design
requirements should identify the applicable
operating system, functions, interfaces,
performance requirements, installation
considerations, design inputs, and constraints.
The requirements shall be traceable, verifiable
(including acceptance criteria), consistent,
and clear (unambiguous).
• ANSI/ISA 84.00-01-2004-Part 1
(Clause 12)
• ASME NQA-1-2000, and Subpart
2.7
• IEEE-STD-7-4.3.2-2003, IEEE
Standard Criteria for Digital
Computers in Safety Systems of
Nuclear Power Generating
Stations
• ANSI/IEEE-STD-830-1998, IEEE
Recommended Practice for
Software Requirements
Specification
• ANSI/IEEE-STD-730, Standard for
Software Quality Assurance Plans
6 Sec. 5.2.6, Software Design and
Implementation
For application software, the design should be
documented and include, as applicable,
numerical methods, mathematical models,
physical models, control and logic flow, data
flow, process flow, data structures, applicable
relationships between data structures and
process structures, and traceability
requirements. The software design shall be
translated into computer program(s) using the
programming or design organization’s
programming standards and conventions.
• ANSI/ISA 84.00-01-2004–Part 1
(Clause 12)
• ASME NQA-1-2000, and Subpart
2.7
• IEEE-STD-7-4.3.2-2003; Standard
Criteria for Digital Computers in
Safety Systems of Nuclear Power
Generating Stations
• ANSI/IEEE-STD-830-1998,
Recommended Practice for
Software Requirements
Specification
• ANSI/IEEE-STD-730, Standard for
Software Quality Assurance Plans
7 Sec. 5.2.7, Software Safety
The development of software applications
requires identification of hazards that have the
potential for defeating a safety function and
the implementation of design strategies to
eliminate or mitigate those hazards. Methods
to mitigate the consequences of software
failures should then be an integral part of the
software design.
• ANSI/ISA 84.00-01-2004-Part 1
(Clause 12)
• IEEE-STD-7-4.3.2-2003, Standard
Criteria for Digital Computers in
Safety Systems of Nuclear Power
Generating Stations
DOE-STD-1195-2011
F-5
Item SQA Work Processes
DOE G 414.1-4
Acceptable Industry
Implementation Guidance
Standards
8 Sec. 5.2.8, Verification and Validation
Verification is performed throughout the life
cycle of the safety software. Validation
activities are performed at the end of the
software development or acquisition
processes to ensure the software meets the
intended requirements.
• ANSI/ISA 84.00-01-2004-Part 1
(Clause 12)
Section 26
• ASME NQA-1-2000 and Subpart
2.7
• ANSI/IEEE-STD-1012, Standard
for Software Verification and
Validation
9 Sec. 5.2.9, Software Problem Reporting and
Corrective Management
The reporting and corrective action system
will cover (1) methods for documenting,
evaluating, and correcting software problems;
(2) an evaluation process for determining
whether a reported problem is indeed a defect
or an error; and (3) the roles and
responsibilities for disposition of the problem
reports. Procurement documents should
identify the requirements for suppliers to
report problems and any required responses
and the method for the purchasers to report
problems to the supplier.
• ANSI/ISA 84.00-01-2004-Part 1
(Clause 12)
• ASME NQA-1-2000 and Subpart
2.7
• ANSI/IEEE-STD-730, Standard
for Software Quality Assurance
Plans
10 Sec. 5.2.10, Training of personnel in the
design, development, use, and evaluation of
safety software
Training should be commensurate with the
scope, complexity, and importance of the
tasks and the education, experience, and
proficiency of the individual.
• ANSI/ISA 84.00.01-2004, Section
5, “Management of Functional
Safety”
• ASME NQA-1-2000 and Subpart
2.7
• ANSI/IEEE-STD-730, Standard
for Software Quality Assurance
Plans
DOE-STD-1195-2011
G-1
APPENDIX G. HUMAN FACTORS ENGINEERING
See Section 2.7 of this standard for details regarding Human Factors Engineering (HFE).
Figure G-1: Application of HFE Throughout the SIS Life Cycle shows how HFE is applied
throughout the safety system life cycle. Table G-1: Human Factors Standards and Guidance
Documents provides information on HFE standards and guidance documents.
Figure G-1: Application of HFE Throughout the SIS Life Cycle
DOE-STD-1195-2011
G-2
Table G-1: Human Factors Standards and Guidance Documents
HFE Phase Standard/Document HFE Guidance Provided
Planning DOE-HDBK-1140-2001, Human
Factors Ergonomics Handbook
for Ease of Maintenance
Provides guidelines for ease of
maintenance.
NUREG-0711, Human Factors
Engineering Program Review
Model
Defines an approach for
ensuring that the HFE aspects
of a facility are developed,
designed, and evaluated on the
basis of a structured analysis
using accepted HFE principles.
EPRI 1008122, Human Factors
Guidance for Control Room and
Digital Human-System Interface
Design and Modification:
Guidelines for Planning,
Specification, Design, Licensing,
Implementation, Training,
Operation and Maintenance
Provides a general analytical
tool for considering system
design and required operator
actions. It includes a
comparison of how control
room operators perform control
room tasks and or respond to
alarm conditions in traditional
analog control rooms versus a
modernized control room that
incorporates digital instrument
and control systems.
IEEE-STD-845, IEEE Guide to
Evaluation of Man-Machine
Performance in Nuclear Power
Generation Station Control Room
and Other Peripheries
Provides guidance for the
selection and application of
human factors techniques to
carry out the following tasks:
Evaluation of a given man-
machine design in control
rooms and other control
areas to ascertain the
degree of design
adequacy;
Determination, as needed,
of changes to increase
acceptability of a man-
machine design; and
Determination of the
relative adequacy of
alternative designs.
DOE-STD-1195-2011
G-3
HFE Phase Standard/Document HFE Guidance Provided
Section 27
• ANSI/IEEE-STD-1023,
Recommended Practice for
the Application of Human
Factors Engineering to
Systems, Equipment and
Facilities of Nuclear Power
Generating Stations and
Other Nuclear Facilities
Provides help in evaluating the
effect that automated system
actions have on the operator’s
understanding of process
operations and the potential for
operator confusion. Also, it
provides general guidance to
address human error and the
implementation of design
features to mitigate undesirable
consequences associated with
anticipated human errors.
HFE Analysis
(Requirements,
Guidelines,
Conventions) and
Requirements &
Design
ANSI/ANS 58.8, Time Response
Design Criteria for Safety-
Related Operator Actions
Provides guidelines to be
applied in determining time
requirements for safety-related
operator response.
DOE-HDBK-1140-2001 (same as
Planning)
(See Planning)
DOE-STD-3009-94, Preparation
Guide for U.S. Department of
Energy Nonreactor Nuclear
Facility Safety Reports
Provides guidance in identifying
the human-machine interfaces
required for ensuring safety
function during normal,
abnormal, and emergency
operations. This guide also
identifies interfaces for
surveillance and maintenance
of safety systems, structures,
and components during normal
operations.
EPRI 1008122 (same as
Planning)
(See Planning)
ANSI/ISA 18.2, Management of
Alarm Systems for the Process
Industries
Covers all aspects of alarm
management.
MIL-STD-1472, Department of
Defense Design Criteria
Standard – Human Engineering
Presents human engineering
design criteria, principles and
practices to be applied in the
design of systems, equipment
and facilities.
DOE-STD-1195-2011
G-4
HFE Phase Standard/Document HFE Guidance Provided
NUREG-0700, Human-System
Interface Design Review
Guidelines, Rev. 2
Provides a comprehensive
review for HFE principles and
design guidelines, regardless of
the platform.
Implementation ANSI/ANS 3.5, Nuclear Power
Plant Simulators for Use in
Operator Training and
Examination
Provides guidance for simulator
model requirements.
Testing NUREG-0711, Human Factors
Engineering Program Review
Model, Rev. 2
Defines an approach to ensure
that the HFE aspects of the
facility are developed,
designed, and evaluated on the
bases of a structured analysis
using accepted HFE principles.
Continuous
Improvement
NUREG-0711 (same as Testing) (See Testing)
DOE-STD-1195-2011
H-1
APPENDIX H. APPLICABLE DOCUMENTS
H.1 Department of Energy Directives
The following DOE Directives provide high-level requirements and guidance that are the basis
for the Safety Instrumented Systems (SIS) criteria and guidance in this standard. The DOE
Directives (or their successor directives) should be referred to in support of effective
implementation of this standard.
• DOE O 414.1C, Quality Assurance
• DOE O 420.1B, Change Notice No. 1, Facility Safety
• DOE O 426.1, Federal Technical Capability
• DOE O 426.2, Personnel Selection, Training, Qualification, and Certification
Requirements for DOE Nuclear Facilities
• DOE G 414.1-4, Safety Software Guide for Use with 10 CFR 830 Subpart A, Quality
Assurance Requirements, and DOE O 414.1C, Quality Assurance
• DOE G 420.1-1, Nonreactor Nuclear Safety Design Criteria and Explosives Safety
Criteria Guide For Use With DOE O 420.1, Facility Safety
• DOE-HDBK-1140-2001, Human Factor/Ergonomics Handbook for the Design for Ease
of Maintenance
• DOE-STD-1186-2004, Specific Administrative Controls
Section 28
• DOE-STD-1189-2008, Integration of Safety into the Design Process
• DOE-STD-3007-2007, Guidelines for Preparing Criticality Safety Evaluations at
Department of Energy Nonreactor Nuclear Facilities
• DOE-STD-3009-94, Change Notice No. 3, Preparation Guide for U.S. Department of
Energy Nonreactor Nuclear Facility Safety Analyses
H.2 National and International Standards
These national and international standards should be referred to in support of effective
implementation of this standard. Some of these are specifically identified for use within this
standard.
• ASME NQA-1, Quality Assurance Requirements for Nuclear Facility Applications
(Version 2000, and all subsequent editions)
• ANSI/ANS 3.5, Nuclear Power Plant Simulators for Use in Operator Training and
Examination
• ANSI/ANS 8.3, Criticality Accident Alarm Systems
• ANSI/ANS 58.8, Time Response Design Criteria for Safety-Related Operator Actions
DOE-STD-1195-2011
H-2
• ANSI/IEEE- Std -500, IEEE Guide to the Collection and Presentation of Electrical,
Electronic, Sensing Component, and Mechanical Equipment Reliability Data for Nuclear
Power Generating Stations
• ANSI/IEEE- Std -730, Standard for Software Quality Assurance Plans
• ANSI/IEEE- Std -828, Standard for Software Configuration Management Plans
• ANSI/IEEE- Std -829, Standard for Software Test Documentation
• ANSI/IEEE- Std -830, Recommended Practice for Software Requirements Specifications
• ANSI/IEEE-Std-1012, Standard for Software Verification and Validation
• ANSI/IEEE-Std-1023, Recommended Practice for the Application of Human Factors
Engineering to Systems, Equipment, and Facilities of Nuclear Power Generating
Stations and Other Nuclear Facilities
• ANSI/IEEE-Std-1028, Standard for Software Reviews and Audits
• ANSI/IEEE-Std-1074, Standard for Developing Software Life-Cycle Processes
• ANSI/IEEE-Std-1219, Standard for Software Maintenance
• ANSI/IEEE-Std-1228, Standard for Software Safety Plans
• IEEE-Std-845, IEEE Guide to Evaluation of Man-Machine Performance in Nuclear
Power Generation Station Control Room and Other Peripheries
• IEEE-Std 7-4.3.2, Standard Criteria for Digital Computers in Safety Systems of Nuclear
Power Generating Stations
• ANSI/ISA 18.2, Management of Alarm Systems for the Process Industries
• ANSI/ISA 67.01.01, Transducer/Transmitter Installation for Nuclear Safety Applications
• ANSI/ISA 67.04.01, Setpoints for Nuclear Safety-Related Instrumentation
• ANSI/ISA 84.00.01-2004 Part 1 (IEC61511-1 Mod), Functional Safety: Safety
Instrumented Systems for the Process Industry Sector – Part 1: Framework, Definitions,
System, Hardware and Software Requirements
• ANSI/ISA 84.00.01-2004 Part 2 (IEC 61511-2 Mod), Functional Safety: Safety
Instrumented Systems for the Process Industry Sector – Part 2: Guidelines for the
Application of ANSI/ISA-84.00.01-2004 Part 1 (IEC 61511-1 Mod) – Informative
• ANSI/ISA 84.00.01-2004 Part 3 (IEC 61511-3 Mod), Functional Safety: Safety
Instrumented Systems for the Process Industry Sector – Part 3: Guidance for the
Determination of the Required Safety Integrity Levels – Informative
• ISA TR84.00.02, Safety Instrumented Functions (SIF) – Safety Integrity Level (SIL)
Evaluation Techniques
DOE-STD-1195-2011
H-3
• ISA TR84.00.03, Guidance for Testing of Process Sector Safety Instrumented Function
(SIF) Implemented as or Within Safety Instrumented Systems
• ISA TR84.00.04, Guideline for the Implementation of ANSI/ISA-84.00.01-2004 (IEC
61511 Mod)
Section 29
• ISA TR84.00.06, Safety Fieldbus Design Considerations for Process Industry Sector
Applications
• IEC 61508, Functional Safety of Electrical/Electronic/Programmable Electronic Safety-
Related Systems
• IEC 61511, Functional Safety – Safety Instrumented Systems for the Process Industry
Sector
H.3 Nuclear Regulatory Commission (NRC) Guidance
These NRC guidance documents should be referred to in support of effective implementation of
this standard.
• NUREG-0700, Rev. 2, Human-System Interface Design Review Guidelines
• NUREG-0711, Human Factors Engineering Program Review Model
• NUREG-0800, BTP 7-14, Guidance on Software Reviews for Digital Computer-Based
Instrumentation and Control Systems
• NUREG-0800, BTP 7-18, Guidance on the Use of Programmable Logic Controllers in
Digital Computer-Based Instrumentation and Control Systems
• NUREG-0800, BTP 7-19, Guidance for Evaluation of Diversity and DID in Digital
Computer-Based Instrumentation and Control Systems
• NUREG-0800, BTP 7-21, Guidance on Digital Computer Real-time Performance
• NUREG-6090, The PLC and its Application in Nuclear Reactor Protection Systems
• NUREG-6303, Method for Performing Diversity and Defense-in-Depth Analyses of
Reactor Protection Systems
• NUREG/CR-6421, A Proposed Acceptance Process for Commercial Off-the–Shelf
(COTS) Software in Reactor Applications
• NUREG/CR-6842, Advanced Reactor Licensing: Experience with Digital I&C Technology
in Evolutionary Plants
• NRC RG 1.152, Rev. 2, Criteria for Use of Computers in Safety Systems of Nuclear
Power Plants
H.4 Other Sources
These documents should be referred to in support of effective implementation of this standard.
Some of these are specifically identified for use within this standard.
DOE-STD-1195-2011
H-4
• EPRI-1008122, Human Factors Guidance for Control Room and Digital Human-System
Interface Design and Modification: Guidelines for Planning, Specification, Design,
Licensing, Implementation, Training, Operation, and Maintenance
• EPRI TR-102260, Supplemental Guidance for the Application of EPRI Report NP-5652
on the Utilization of Commercial Grade Items
• EPRI TR-106439, Guideline on Evaluation and Acceptance of Commercial Grade Digital
Equipment for Nuclear Safety Applications
• INPO 05-003, Performance Objectives and Criteria – Fundamentals of Training
• MIL-STD-1472, Department of Defense Design Criteria Standard – Human Engineering
DOE-STD-1195-2011
I-1
APPENDIX I. ABBREVIATIONS, ACRONYMS, AND DEFINITIONS
I.1 Abbreviations and Acronyms
AC Administrative Controls
ANSI American National Standards Institute
BPCS Basic Process Control System
CCF Common Cause Failure
CGD Commercial Grade Dedication
CSDR Conceptual Safety Design Report
DCS Digital Control System
DID Defense-In-Depth
DOE Department of Energy
DSA Documented Safety Analysis
FCV Flow Control Valve
FMEA Failure Modes and Effects Analysis
FPL Fixed Program Language
FV Steam Isolation Valve
FVL Full Variability Language
HFE Human Factors Engineering
HFT Hardware Fault Tolerance
IPL Independent Protection Layer
IEC International Electrotechnical Commission
ISA International Society of Automation
LCO Limiting Condition of Operation
LVL Limited Variability Language
MTTF Mean Time To Failure
NFPA National Fire Protection Association
DOE-STD-1195-2011
I-2
NRC Nuclear Regulatory Commission
PDSA Preliminary Documented Safety Analysis
PFDavg Average Probability of Failure on Demand
PLC Programmable Logic Controller
Section 30
PSDR Preliminary Safety Design Report
QA Quality Assurance
RTD Resistance Temperature Detector
RRF Risk Reduction Factor
SAC Specific Administrative Control
SC Safety Class
SCM Software Configuration Management
SIF Safety Instrumented Function
SIL Safety Integrity Level
SIS Safety Instrumented System
SQA Software Quality Assurance
SS Safety Significant
SSC Structures, Systems, and Components
SV Solenoid Valve
TE Temperature Element
TSR Technical Safety Requirement
I.2 Definitions
The following definitions are included with this standard for convenience and clarification.
Where applicable, DOE Order definitions shall take precedence over those shown in this
document.
Application Software. Software which is specific to the user application. In general, it
contains logic sequences, permissives, limits and expressions that control the appropriate input,
output, calculations, decisions necessary to meet the safety instrumented functional
requirements. [Ref. ANSI/ISA-84.00.01-2004 Part 1 (IEC 61511-1 Mod); Clause 3.2.81.2.1]
DOE-STD-1195-2011
I-3
Basic Process Control System (BPCS). The system which responds to input signals from the
process, its associated equipment, other programmable systems and/or an operator and
generates output signals causing the process and its associated equipment to operate in the
desired manner but which does not perform any safety instrumented functions with a claimed
SIL ≥ 1. [Ref. ANSI/ISA-84.00.01-2004 Part 1 (IEC 61511-1 Mod); Clause 3.2.3]
Common-Cause Failure (CCF). A failure, which is the result of one or more events, causing
failures of two or more separate channels in a multiple channel system, leading to system
failure. [Ref. ANSI/ISA-84.00.01-2004 Part 1 (IEC 61511-1 Mod); Clause 3.2.6.1]
Common-Mode Failure (CMF). The failure of two or more channels in the same way, causing
the same erroneous result. [Ref. ANSI/ISA-84.00.01-2004 Part 1 (IEC 61511-1 Mod), Clause
3.2.6.2]
Dedication. An acceptance process performed in accordance with this standard to provide
reasonable assurance that a commercial grade item or service will successfully perform its
intended safety function and, in this respect, is deemed equivalent to an item or services
provided under the requirements of this Standard. [NQA-1, 2004]
Dedicating entity. The organization that performs the dedication process. [NQA-1-2004]
Demand Mode Safety Instrumented Function. When a specified action (for example, closing
of a valve) is taken in response to process conditions or other demands. In the event of a
dangerous failure of the safety instrumented function a potential hazard only occurs in the event
of a failure in the process or the BPCS. [Ref. ANSI/ISA-84.00.01-2004 Part 1 (IEC 61511-1
Mod), Clause 3.2.43.1]
Defense-in-Depth (DID). The design and operational philosophy that calls for multiple layers of
protection to prevent and/or mitigate accidents. It may include the use of controls, multiple
physical barriers, redundant safety functions, and emergency response measures.
Dangerous Failure. Failure which has the potential to put the safety instrumented system in a
hazardous or fail-to-function state [Ref. ANSI/ISA-84.00.01-2004 Part 1 (IEC 61511-1 Mod),
Clause 3.2.11]
Detected. In relation to hardware failure and software faults, detected by the diagnostic tests or
through normal operation. [Ref. ANSI/ISA-84.00.01-2004 Part 1 (IEC 61511-1 Mod), Clause
3.2.13]
Section 31
Diagnostic Coverage. Ratio of the detected failure to the total failure rate of the component or
subsystems as detected by diagnostic tests. Diagnostic coverage does not include any faults
detected by proof tests. [Ref. ANSI/ISA-84.00.01-2004 Part 1 (IEC 61511-1 Mod), Clause
3.2.15]
Diversity. The existence of different means performing a required function. [Ref. ANSI/ISA-
84.00.01-2004 Part 1 (IEC 61511-1 Mod), Clause 3.2.16]
Embedded Software. Software that is part of the system supplied by the manufacturer and is
not accessible for modification by the end-user. Embedded software is also referred to as
firmware or system software. [Ref. ANSI/ISA-84.00.01-2004 Part 1 (IEC 61511-1 Mod), Clause
3.2.81.2.2]
DOE-STD-1195-2011
I-4
Electrical/Electronic/Programmable Electronic (E/E/PE). Based on electrical (E) and/or
electronic (E) and/or programmable electronic (PE) technology [Ref. ANSI/ISA-84.00.01-2004
Part 1 (IEC 61511-1 Mod), clause 3.2.17]
Failure. Termination of the ability of a functional unit to perform a required function. [Ref.
ANSI/ISA-84.00.01-2004 Part 1 (IEC 61511-1 Mod), Clause 3.2.20]
Fault. An abnormal condition that may cause a reduction in, or loss of, the capability of a
functional unit to perform a required function. [Ref. ANSI/ISA-84.00.01-2004 Part 1 (IEC 61511-
1 Mod) Clause 3.2.21]
Fixed Program Language (FPL). In this type of language, the user is limited to an adjustment
of a few parameters (for example, range of the pressure transmitter, alarm levels, network
addresses). [Ref. ANSI/ISA-84.00.01-2004 Part 1 (IEC 61511-1 Mod), Clause 3.2.81.1.1]
Full Variability Language (FVL). This type of language is designed to be comprehensible to
computer programmers and provides the capability to implement a wide variety of functions and
applications. [Ref. ANSI/ISA-84.00.01-2004 Part 1 (IEC 61511-1 Mod), Clause 3.2.81.1.3]
Independent Protection Layer (IPL). A structure, system, component, or administrative
control that prevents or mitigates a safety significant hazardous event to an acceptable
condition.
Layer of Protection Analysis (LOPA). LOPA is a simplified form of risk assessment. LOPA
typically uses order of magnitude categories for initiating event frequency, consequence
severity, and the likelihood of failure of independent protection layers (IPLs) to approximate the
risk of scenario. LOPA is limited to evaluating a single cause-consequence pair as a scenario.
[Ref. Chapter 2 of Layer of Protection Analysis Simplified Process Risk Assessment by Center
for Chemical Process Safety, ISBN 0-8169-0811-7.]
Limited Variability Language (LVL). This type of language that is designed to be
comprehensible to process sector users, and provides the capability to combine predefined,
application-specific, library functions to implement the safety requirements specifications. A
LVL provides a close functional correspondence with the functions required to achieve the
application. A typical example of system LVL: standard PLC. [Ref. ANSI/ISA-84.00.01-2004
Part 1 (IEC 61511-1 Mod), Clause 3.2.81.1.2]
Major Modification. A modification to a nuclear facility that substantially changes the existing
safety basis for the facility. [10 CFR 830.3]
Programmable Electronic System (PES). System for control, protection or monitoring based
on one or more programmable electronic devices, including all elements of the system such as
power supplies, sensors and other input devices, data highways and other communication
paths, actuators and other output devices. [Ref. ANSI/ISA-84.00.01-2004 Part 1 (IEC 61511-1
Mod), Clause 3.2.56]
Section 32
Probability of Failure on Demand – Average (PFDavg). The PFDavg for an IPL is the
average probability that, when demanded, it will not perform the required task. Failure to
perform could be caused by:
DOE-STD-1195-2011
I-5
• a component of an IPL being in a failed or unsafe state when the initiating event occurs;
or
• a component failing during the performance of its task; or
• human intervention failing to be effective, etc.
[Ref. Chapter 6 of Layer of Protection Analysis Simplified Process Risk Assessment by Center
for Chemical Process Safety, ISBN 0-8169-0811-7.]
Risk Reduction Factor (RRF). RRF is the inverse of Probability of Failure on Demand
(1/PFD).
Safe Failure. Failure does not have the potential to put the safety instrumented system in a
hazardous or fail-to-function state. [Ref. ANSI/ISA-84.00.01-2004 Part 1 (IEC 61511-1 Mod),
Clause 3.2.65]
Safe Failure Fraction. Faction of the overall random hardware failure rate of a device that
results in either a safe failure or a detected dangerous failure. [Ref. ANSI/ISA-84.00.01-2004
Part 1 (IEC 61511-1 Mod), Clause 3.2.65.1]
Safety Instrumented Function (SIF). Safety function with a specified safety integrity level
which is necessary to achieve functional safety and which can be either a safety instrumented
protection function or a safety instrumented control function. [Ref. ANSI/ISA-84.00.01-2004
Part 1 (IEC 61511-1 Mod), Clause 3.2.71]
Safety Integrity Level (SIL). Discrete level (one out of four) for specifying the safety integrity
requirements of the safety instrumented functions to be allocated to safety instrumented
systems. Safety integrity level 4 is assigned the highest level of safety integrity; while safety
integrity level 1 is the lowest. [Ref. ANSI/ISA-84.00.01-2004 Part 1 (IEC 61511-1 Mod), Clause
3.2.74]
Safety Instrumented System (SIS). Instrumented system used to implement one or more
safety instrumented functions. An SIS is composed of any combination of sensor(s), logic
solver(s), and final element(s). [Ref. ANSI/ISA-84.00.01-2004 Part 1 (IEC 61511-1 Mod), Clause
3.2.72]
Note 1: An SIS may be either automatic or require operator action to bring the
process to a safe state, or mitigate a hazard in response to an alarm or
indication. An automatic SIS is composed of sensor(s), logic solver(s), and
final element(s). An SIS with required operator action is composed of any
combination of sensor(s), logic solver(s), alarm presentation/operator
action(s), and final element(s).
Note 2: An instrumented system, classified as safety significant, that does not take
action to bring the process to a safe state or mitigate a hazard to an
acceptable level is not by definition an SIS and is, therefore, not covered by
this standard.
Safety Life Cycle. Necessary activities involved in the implementation of safety instrumented
function(s) occurring during a period of time that starts at the concept phase of a project and
DOE-STD-1195-2011
I-6
finishes when all of the safety instrumented functions are no longer available for use. [Ref.
ANSI/ISA-84.00.01-2004 Part 1 (IEC 61511-1 Mod), Clause 3.2.76]
Safety Software. [For definition of Safety Software see DOE O 414.1C]
System. Set of elements, which interact according to a design; an element of a system can be
another system, called a subsystem, which may be a controlling system or a controlled system
and may include hardware, software, and human interaction. A person can be of a system. A
system includes the sensors, the logic solvers, final elements, communication, and ancillary
equipment belonging to SIS (for example, cables, tubing, and power supply). [Ref. ANSI/ISA-
84.00.01-2004 Part 1 (IEC 61511-1 Mod), Clause 3.2.84]
DOE-STD-1195-2011
CONCLUDING MATERIAL
Review Activities:
DOE Ops Office Preparing Activity:
NA AL DOE-HS-21
HS SR
EM ID Project Number:
SC NV SAFT-0128
NE OR
GC RL
Energy CTA CH
NNSA CTA
Area/Site Office National Laboratories
Pantex SRNL
Carlsbad LANL
Princeton LLNL
ORP PNNL
Los Alamos INL
Y-12 PPPL
Savannah River ANL
Ames Ames
Argonne BNL
BHSO Berkeley
BSO Fermi
FSO SLAC
NBL TJNAL
PNSO
PPPO
SSO
TJSO