DOE-HDBK-1139-2003 Volume 3, Chemical Management Volume 3: Consolidated Chemical User Safety and Health Requirements
Functional areas: Chemical Management, Consolidated Chemical User, Safety and Health, Compressed Gases, Chemical-Related, Chemical Storage
This chapter identifies and consolidates existing user safety and health requirements found in DOE and Federal chemical-related safety and health regulations and National Standards that address hazard analysis of activities involving chemicals (see definition) and chemical products (see definition). State and local codes and requirements are NOT included. This chapter specifically consolidates requirements found in the National Fire Protection Association (NFPA), the American National Standards Institute (ANSI), the Compressed Gas Association (CGA), the Occupational Safety and Health Administration (OSHA), and certain Environmental Protection Agency (EPA) regulations and Department of Energy (DOE) Rules and Orders, including technical standards that are made mandatory by their specific reference within a regulation, rule or DOE Order.
Project Number SAFT-0089
Superseded By:
Version history and related documents
Superseded by
A newer version replaces this document.
Document text
Text extracted from the attached file. Refer to the original document for the authoritative version.
Section 1
TS
NOT MEASUREMENT
SENSITIVE
DOE-HDBK-1139/3-2003
DOE HANDBOOK
CHEMICAL MANAGEMENT
(Volume 3 of 3)
Consolidated Chemical User Safety and Health Requirements
U.S. Department of Energy AREA SAFT
Washington, D.C. 20585
DISTRIBUTION STATEMENT A. Approved for public release; distribution is unlimited.
September 2003
DOE-HDBK-1139/3-2003
This document has been reproduced directly from the best available copy.
It is available to DOE and DOE contractors from ES&H Technical Information
Services, U.S. Department of Energy, (800) 473-4375, fax: (301) 903-9823.
It is available to the public from the U.S. Department of Commerce, Technology
Administration, National Technical Information Service, Springfield, VA 22161;
(703) 605-6000.
i
DOE-HDBK-1139/3-2003
Foreword
Numerous requirements have been promulgated to protect workers, equipment, facilities and the
environment. When work is performed, the specific requirements affecting the work must first be
identified and incorporated into the work-plan. Because such requirements can number in the thousands,
simply identifying all of the applicable chemical safety-related safety and health requirements that govern
any work activity can be a monumental task. Concern over this was addressed in the 1994 DOE
Chemical Vulnerability Study Management Response Plan, which identified the need for a complex-wide
"Roadmap for Requirements". Similarly, discussions within the Energy Facility Contractors Group
(EFCOG)/DOE chemical safety community have indicated that one of the main causes of continuing
chemical safety deficiencies at DOE is the large number of requirements that govern chemical-related
work at the Complex. Many of these requirements approach chemical safety from different perspectives
and contain provisions that overlap and are sometimes contradictory and confusing. An EFCOG/DOE
Chemical Safety Topical Committee (CSTC) Team, the Chemical User Safety and Health Requirements
Roadmap (CUSHR) Team, undertook the task of looking into this issue.
Background
The EFCOG/DOE CSTC CUSHR Team conducted a limited review of how DOE sites address
compressed gases. Results showed that at these sites, only 50-70% of requirements were addressed in site
documentation of chemical-related safety and health requirements. These results confirmed the view that
while all DOE contractors who engage in the same work activities must follow the same requirements,
many either do not know which requirements apply to their work or are confused by them. The Team
concluded that this was likely due to the fact that multiple requirements from many varied sources
frequently overlap, covering the same points in slightly different and sometimes conflicting ways.
To assist the sites in understanding and addressing the myriad requirements with which they must
comply, the CUSHR Team committed to developing a series of activity-based chapters that consolidate
the safety and health requirements that govern DOE chemical-related work activities, removing overlaps
and duplications, where found.
Before beginning its work, the Team conducted a Chemical Storage Requirements Pilot in the summer of
2000 to see if this planned effort would be perceived as "value-added" for the DOE community. The pilot
document provided consolidated chemical-related safety and health requirements for chemical storage, a
universal activity conducted by all that use chemicals throughout the Complex. A listing of consolidated
requirements for safe chemical storage, along with a survey was distributed to chemical users across the
Complex. The survey results demonstrated that the effort to consolidate requirements will be useful to
chemical users throughout the Complex and should continue.
Section 2
In support of this mandate to assist the sites with a requirements roadmap, the CSTC CUSHR Team
developed a series of activity-based chapters which consolidate the safety and health requirements that
govern DOE chemical-related work activities. The ten chapters of this document, Volume 3 of the DOE
Chemical Management Handbook, coordinate with the subjects covered in that Handbook.
Instructions for Use
This volume consolidates existing core safety and health requirements that all sites engaged in chemical-
related activities must follow when applicable and when no exemptions have been granted. It is intended
to consolidate overlapping and/or duplicative chemical-related safety and health requirements. It serves
ii
DOE-HDBK-1139/3-2003
only to consolidate existing DOE and Federal chemical-related safety and health requirements. It
does NOT create any new or additional requirements.
The listing of consolidated requirements contained here includes “pointers” to the sources of those
requirements, showing the user what the requirements are and where each comes from.
In addition to DOE Orders, it includes Occupational Safety and Health Administration (OSHA), National
Fire Protection Association (NFPA), American National Standards Institute (ANSI), and Compressed Gas
Association (CGA) requirements that are cited in either DOE O 440.1A or in OSHA standard
29CFR1910.6 ("Incorporation by Reference"). It also includes technical standards that are made
mandatory by their specific reference within a regulation, rule or DOE Order.
State and local codes including locally adopted building and fire codes are NOT addressed in this
document. U.S. Department of Agriculture (USDA) regulations are NOT addressed since the
impact from these is considered to be negligible at DOE facilities. Similarly, U.S. Environmental
Protection Agency (EPA) pesticide regulations are NOT addressed in this document.
In the web-based version of this document, wherever possible, the referenced requirements are
hyperlinked directly to their source documents. For each consolidation, a source document that is
repeated is hyperlinked only once. Since ANSI, CGA, and NFPA documents are available only to
subscribers to those organizations, the hyperlinks for those referenced requirements will take the reader
only to the web pages of those organizations. Subscribers can then access the specific requirements of
interest. Non-subscribers may be able to find these documents in their site libraries or can purchase them
through the organizations' web pages.
This Requirements Roadmap contains a Glossary of terms and explanatory notes of the various
consolidated chemical-related safety and health requirements.
The numerous requirements included in this document come from a large number of sources that have
different safety purposes. As a result, some of these requirements may not always be applicable to the
work being performed at an individual site or facility. It is the responsibility of each user to determine the
applicability of these requirements to their work and how they are implemented. The reference sources
for the requirements included in this document can be used to determine the applicability of those
requirements to the work being performed. The source requirements are listed to the left of the
corresponding section of the document that consolidates the referenced requirements. If there is any
question as to the applicability of a requirement or if it is thought that any requirement is taken out of
context, then the reader can use the reference sources to research the original requirement.
Section 3
Due to changing regulatory requirements and revisions to consensus standards the user should contact the
subject matter expert (e.g., Fire Protection Engineer, Industrial Safety Engineer, Industrial Hygienist,
Environmental Engineer, etc.) to ensure that the most current document is used, as applicable, depending
on site contractual requirements.
iii
DOE-HDBK-1139/3-2003
Table of Contents
Foreword...................................................................................................................................................ii
Acknowledgements...................................................................................................................................v
Glossary ....................................................................................................................................................vi
Acronyms and Abbreviations ..................................................................................................................xx
Chapter 1 - Hazard Analysis .....................................................................................................................1
Chapter 2 - Acquisition.............................................................................................................................7
Chapter 3 - Chemical Inventory and Tracking..........................................................................................11
Chapter 4 - On-Site Chemical Transportation ..........................................................................................17
Chapter 5 - Chemical Storage ...................................................................................................................23
Chapter 6 - Hazard Control.......................................................................................................................39
Chapter 7 - Pollution Prevention and Waste Minimization ......................................................................67
Chapter 8 - Chemical Emergency Management .......................................................................................75
Chapter 9 - Chemical Disposition.............................................................................................................97
Chapter 10 - Training................................................................................................................................129
Complete List of Sources..........................................................................................................................141
iv
DOE-HDBK-1139/3-2003
ACKNOWLEDGEMENTS
This Department of Energy Handbook was prepared under the sponsorship of the joint Department of Energy
(DOE)/Energy Facility Contractors Group (EFCOG) Chemical Safety Topical Committee (CSTC). It was prepared
over a span of four years by the CSTC’s Chemical User Safety and Health Requirements Roadmap team (the
CUSHR team), consisting of representatives from several sites and DOE headquarters, chaired by Dr. Dave Quigley,
Idaho National Engineering and Environmental Laboratory and co-chaired by Mr. James Morgan, Westinghouse
Savannah River Company and Ms. Gail Kleiner, DOE/EH-52. The preparers would like to gratefully acknowledge
the following specific CUSHR team members who authored the various chapters of this document:
Judi Johannesen, DOE-RL Fred Simmons, WSRC
Murty Kuntamukkula, WSRC Bill Westendorf, Link Technologies, Inc.
John Piatt, PNNL James Woodring, ANL
Dave Quigley, INEEL Jeff Woody, Link Technologies, Inc.
Section 4
No one group of individuals, however, can appropriately take sole credit or responsibility for an undertaking of this
magnitude. The CSTC CUSHR Team would like to gratefully acknowledge the large number of individuals who
have provided comments on the handbook.
Beyond the formal comment process used for documents of this type, the following individuals provided valuable
technical insights and/or specific reviews of this document in its various stages of development:
Theresa Aldridge DOE-RL Ann Schubert WVNS
Ed Branagan DOE-HQ/NE John Serocki DOE-HQ/EM-5
Jerry Coalgate DOE-HQ/EH-413 Reanna Sharp-Geiger LAN
Arnold Edelman DOE-HQ/SC-83 Daniel Stachelski DOE-WV
David Freshwater SAIC Tom Tuccinardi DOE-HQ/SO-411
Brenda Hawks DOE-ORO Bill Von Holle DNFSB
J. C. Laul LANL Rob Vrooman NNSA/NA-53
Bill McArthur DOE-HQ/EH-52 Sharon Walker SNL
James T. Powers NNSA/NA-40 Steven Woodbury DOE-HQ/EH-413
Jane Powers DOE-HQ/EH-413 Stephanie Woolf DOE-ID
v
DOE-HDBK-1139/3-2003
Glossary
Abandon: leave in place.
Approval: authorization from subject matter experts or the appropriate level of management as
defined in local site or facility procedures; or
Approved: acceptable to the authorities having jurisdiction.
CERCLA Hazardous Substance: a substance on the list defined in section 101(14) of CERCLA.
Certain Categories of Property (that Require Special Handling): specific types of hazardous
property, the disposition of which is described in 41CFR109-42.11 and 41CFR101-42.1102, such
as Radioactively or chemically contaminated property, Asbestos, Polychlorinated biphenyls
(PCBs), Controlled substances, Nuclear Regulatory Commission (NRC)-controlled materials,
Drugs and reagents other than controlled substances, Lead-containing paint, U.S. Munitions List
(see definition) that require demilitarization (see definition), etc..
Chemical: any element, compound or mixture of elements and/or compounds. A substance that
a) possesses potentially hazardous properties (including, but not limited to flammability, toxicity,
corrosivity, reactivity); or b) is included on any federal, state, or local agency regulatory list; or c)
is associated with an MSDS and is not an “Article” as defined in 29CFR1910.1200. For the
purposes of this document this definition also applies to chemical product (see definition).
Chemical Product: a mixture of any combination of two or more chemicals that may or may not
be the result, in whole or in part, of a chemical reaction, and that itself has hazardous properties.
Chemical products will have Material Safety Data Sheets (MSDS) associated with them and
include materials such as paints, lubricants, cleaning agents, fuels, etc..
Chemical Storage Area: a location that is segregated by either physical barriers or a distance
approved by a Fire Protection Engineer and is used to store any chemical except those that are
classified as being low hazard (see definition). Example 1: If a flammable liquid storage cabinet
is in a work area, then the inside of the cabinet is the storage area, not the entire work area.
Example 2: Areas used to store chemicals that are of a low hazard are not considered to be
chemical storage areas. Types of chemical storage areas include flammable liquid storage areas,
oxidizer storage areas, and organic peroxide storage areas.
Chemical Tracking: monitoring changes to the inventory data for chemicals over time from
acquisition to disposition in order to keep the inventory up-to-date.
Section 5
Class I Flammable Liquids: Class 1A, Class 1B, and Class 1C flammable liquids.
Class IA Flammable Liquids: liquids having a flash point less than 73°F and boiling points
below 100°F.
Class IB Flammable Liquids: liquids having a flash point less than 73°F and boiling points at or
above 100°F.
vi
DOE-HDBK-1139/3-2003
Class IC Flammable Liquids: liquids having a flash point at or above 73°F and below 100°F.
Class II Combustible Liquids: liquids having a flash point greater than 100°F but less than or
equal to 140°F.
Class IIIA Combustible Liquids: liquids having a flash point greater than 140°F but less than or
equal to 200°F.
Class 1 Oxidizer: an oxidizer that will not result in spontaneous combustion when it comes into
contact with combustible materials, but will slightly increase the burning rate of combustibles that
have already been ignited.
Class 2 Oxidizer: an oxidizer that may cause spontaneous ignition when it comes into contact
with combustible materials or that will cause a moderate increase in the rate at which a
combustible will burn.
Class 3 Oxidizer: an oxidizer that will undergo a vigorous self-sustained decomposition when
exposed to contamination or heat or that will cause a severe increase in the rate at which
combustibles will burn.
Class 4 Oxidizer: an oxidizer that will explosively decompose upon exposure to heat, shock or
contaminants.
Clean-Up Operations: an operation where hazardous substances are removed, contained,
incinerated, neutralized, stabilized, cleared-up, or in any other manner processed or handled with
the ultimate goal of making the site safer for people and the environment.
Commerce Control List Items1: dual use (i.e., commercial/military) items that are subject to
export control by the Bureau of Export Administration, Department of Commerce. These items
have been identified in the U.S. Export Administration Regulations (15CFR774) as export
controlled for reasons of national security, crime control, technology transfer and scarcity of
materials.
Commission: the emergency response commission for the State in which the facility is located or
the Indian Tribe under whose jurisdiction the facility is located. In the absence of an Emergency
Response Commission, the Governor and the chief executive officer, respectively, shall be the
commission. Where there is a cooperative agreement between a State and a Tribe, the
commission shall be the entity identified in the agreement.
Committee or Local Emergency Planning Committee (LEPC): the local emergency planning
committee appointed by the emergency response commission.
1 The Commerce Control List includes deuterium, heavy water, other compounds of deuterium; nuclear-grade
graphite; chemical agents (e.g., tear gas formulation, smoke bombs, and other pyrotechnic articles) having dual
military and commercial use; propellants and constituent chemicals (e.g., fine powders of high-purity aluminum,
beryllium, iron, magnesium, zirconium, boron or boron carbide); guanidine nitrate; liquid oxidizers (e.g., dinitrogen
trioxide, nitrogen dioxide/ dinitrogen tetroxide, dinitrogen pentoxide); certain alloys and polymer composites; high
purity (99.99% or greater) bismuth; hafnium metal and alloys (>60%Hf); helium-3; chlorine trifluoride; precursors
for toxic chemical agents, etc..
vii
DOE-HDBK-1139/3-2003
Section 6
Confined Space: any space not intended for continuous human occupancy and having a limited
means of egress, that is subject to the accumulation of toxic or flammable contaminants or an
oxygen deficient atmosphere. Confined or enclosed spaces include, but are not limited to, storage
tanks, process vessels, bins, boilers, ventilation or exhaust ducts, sewers, underground utility
vaults, tunnels, pipelines, and open top spaces more than 4 feet in depth such as pits, tubs, vaults,
and vessels.
Cryogenic Liquids: gases that are handled in liquid form at relatively low pressures and
extremely low temperatures, usually below –130° F (-90º C).
Dangerous Property: material that exists in a condition that poses a hazard to public health or
safety and thus, requires special care and handling.
Decontamination: the removal of hazardous substances from employees and their equipment to
the extent necessary to preclude the occurrence of foreseeable adverse health effects.
Demilitarization: as defined by the Department of Defense, the act of destroying the military
capabilities inherent in certain types of equipment or material. Such destruction may include deep
sea dumping, mutilation, cutting, crushing, scrapping, melting, burning, or alteration so as to
prevent the further use of the item for its originally intended purpose.
Disposal: the discharge, deposit, injection, dumping, spilling, leaking, or placing of any solid
waste or hazardous waste into or on any land or water so that such solid waste or hazardous waste
or any constituent thereof may enter the environment or be emitted into the air or discharged into
any waters, including ground waters.
Disposition: the process of reutilizing, transferring, donating, selling, abandoning, destroying, or
other disposition of Federal government-owned personal property (i.e., chemicals and chemical
products).
DOE Screening Period: the period of time that reportable excess chemicals (see definition) are
screened throughout the DOE complex for reutilization purposes.
Donee: any of the eligible entities that receive Federal surplus personal property (i.e., chemicals)
through a State Agency for Surplus Property (see definition), for example, a public agency (see
definition), a nonprofit tax-exempt educational or public health institution, or a State or local
government agency.
Departmental Property Management Officer: also designated as the DOE National Utilization
Officer who provides approval for user access to the Federal Disposal System (FEDS) (see
definition).
Dual-use List2: a list of nuclear-related material, equipment, software, and related technology,
that can have valid uses in both commercial and military applications, developed by the Nuclear
2 The Dual-use List includes several metals (e.g., beryllium, and zirconium) and their alloys, and certain high
explosives.
viii
DOE-HDBK-1139/3-2003
Suppliers Group (see definition) and described in the International Atomic Energy Agency
(IAEA) Information Circular (INFCIRC) 254 Part 2.
Energy Asset Disposal System: a module within the Federal Disposal System (FEDS) (see
definition) database, available to DOE and DOE contractor personnel to conduct internal
screening of excess chemicals for use within the agency; it became effective Sept. 1, 1998.
[NOTE: EADS has replaced the Reportable Excess Automated Property System (REAPS)
mentioned in 41CFR109-43.304-1.50].
Section 7
Environmental Management System: The environmental policy, environmental performance,
objectives and targets, implementing program to achieve those objectives, monitoring and
measuring of program effectiveness, environmental problem correction, and continuous
improvement process that helps a company manage, measure, and improve the environmental
aspects of its operations.
Environment: includes water, air, and land and the interrelationship that exists among and
between water, air, and land and all living things.
Especially Designed or Prepared Property: equipment and material designed or prepared
especially for use in the nuclear fuel cycle and described in the Nuclear Suppliers Group (see
definition) Trigger List (see definition) (INFCIRC 254 Part 1). Especially Designed or Prepared
Property is a category under High Risk (Personal) Property (see definition).
Excess Chemicals: Chemicals (see definition) or Chemical Products (see definition) that are still
in good condition and for which the current owner has no further use. This does not include
spent/used material. [NOTE: This term is used in DOE-PMR and FPMR to mean chemicals that
are excess to a holding agency (see definition), such as DOE, that can only be reutilized within
the same agency or by another federal agency]. It includes chemicals identified as high risk
personal property, hazardous property, hazardous materials, extremely hazardous materials,
hazardous items, and certain categories of property that require special handling (see
definitions).
Excess (Personal) Property: any personal property under the control of any Federal agency (the
DOE, for purposes of this document) that is no longer required for that agency's needs, as
determined by the agency head or designee.
Excluded PCB products: materials containing 0 through 49 ppm (see definition) PCB (see
definition).
Export Controlled Property: property, the export of which, is subject to licensing by the U.S.
Department of Commerce, the U.S. Department of State, the U.S. Nuclear Regulatory
Commission, or is authorized by the U.S. Department of Energy. Export Controlled Property is
a category under High Risk (Personal) Property (see definition). Refer to the Commerce
Control List (see definition) for items that are export controlled.
Extremely Hazardous Materials: (a) those materials that are hazardous to the extent that they
generally require special handling such as licensing and training of handlers, protective clothing,
and special containers and storage; (b) those materials that, because of their extreme
flammability, toxicity, corrosivity or other perilous qualities, could constitute an immediate
ix
DOE-HDBK-1139/3-2003
danger or threat to life and property and that usually have specialized uses under controlled
conditions; and (c) those materials that have been determined by the holding agency (see
definition) to endanger public health or safety or the environment, if not rendered innocuous
before release to other agencies or to the general public.
Extremely Hazardous Substance: a substance listed in appendices A and B of 40CFR355.
Federal Disposal System: a real-time, online computer database managed by the GSA (since
1992) for recording, tracking and controlling the nationwide inventory of excess and surplus
personal property inventory (e.g., equipment, commodities, including chemicals) of the Federal
government. For additional information on using FEDS, access http://pub.fss.gsa.gov/property/.
Section 8
Fire Area: an area in a building that is separated from the rest of the building by a one- hour fire
barrier. All penetrations through this fire barrier must be constructed to maintain the one-hour
fire resistance.
First Responder - Awareness Level: individuals who are likely to witness or discover a
hazardous substance release and who have been trained to initiate an emergency response
sequence by notifying the proper authorities of the release. They are temporarily in command of
the incident until the Incident Commander (IC) arrives. They would take no further action
beyond notifying the authorities of the release.
First Responder - Operations Level: individuals who respond to releases or potential releases of
hazardous substances as part of the initial response to the site for the purpose of protecting nearby
persons, property, or the environment from the effects of the release. They are trained to respond
in a defensive fashion without actually trying to stop the release. Their function is to contain the
release from a safe distance, keep it from spreading, and prevent exposures.
Flammable Liquids Storage Rooms: rooms that are designed according to 29CFR1910.106
(d)(4) for the storage of flammable and combustible liquids.
Flammability Rating of “0” or “1”: liquids, solids or semi-solids that have a flash point above
200°F or those materials which will not burn when exposed to a temperature of 1500°F for 5
minutes.
Friable Asbestos Materials: materials that contain more than one percent asbestos by weight and
that can, by hand pressure, be crumbled, pulverized, or reduced to powder, thus allowing for
potential release of asbestos fibers into the air.
Foreseeable Emergency: any potential occurrence such as, but not limited to, equipment failure,
rupture of containers, or failure of control equipment which could result in an uncontrolled
release of a hazardous chemical into the workplace.
Hazard: potential for radiation, a chemical, or other pollutant to cause human illness or injury.
Hazard Analysis: the determination of material, system, process, and plant characteristics that
can produce undesirable consequences, followed by the assessment of hazardous situations
associated with a process or activity. Largely qualitative techniques are used to pinpoint
weaknesses in design or operation of the facility that could lead to accidents.
x
http://pub.fss.gsa.gov/property/
DOE-HDBK-1139/3-2003
Hazardous Chemical: any chemical (see definition) that presents a physical hazard or a health
hazard. A substance that possesses potentially hazardous properties (including, but not limited to
flammability, toxicity, corrosivity, reactivity).
Hazard Control: the management actions or physical measures taken to eliminate, limit, or
mitigate hazards to workers, the public, or the environment, including (1) physical, design,
structural, and engineering features; (2) safety programs and procedures; (3) personal protective
equipment; and (5) administrative limits or operational restrictions.
Hazardous Material: property that is deemed a hazardous material, chemical substance or
mixture, or hazardous waste under the Hazardous Materials Transportation Act (HMTA), the
Resource Conservation and Recovery Act (RCRA), or the Toxic Substances Control Act
(TSCA).3 Generally, a hazardous material has one or more of the following characteristics:
(a) has a flash point below 200°F (93.3°C), closed cup, or is subject to spontaneous heating;
(b) is subject to polymerization with the release of large amounts of energy when handled,
Section 9
stored, or shipped without adequate controls;
(c) in the course of normal operations, may produce fibers, dusts, gases, fumes, vapors, mists, or
smokes which have one or more of the following characteristics:
(1) causes 50 percent fatalities to test animals below 500 mg/kg of test animal weight when a
single oral dose is used (LD50);
(2) is a flammable solid or a strong oxidizing or reducing agent;
(3) causes first degree burns to skin in a short time exposure, or is systemically toxic by skin
contact;
(4) has a permissible exposure limit (PEL) below 1000 ppm for gases and vapors, below 500
mg/mm3 for fumes, below 10 mg/m3 or 2 fibers/cm3 for dust;
(5) causes occupational chemical dermatitis, which is any abnormality of the skin induced or
aggravated by the work environment that includes, but is not limited to, primary irritant
categories, allergic sensitizers, and photo sensitizers;
(d) is radioactive to the extent that it requires special handling;
(e) is a recognized carcinogen according to Occupational Safety and Health Administration
(OSHA) regulations at 29CFR1910; or
(f) possesses special characteristics, which in the opinion of the holding agency (see definition),
could be hazardous to health, safety, or the environment if improperly handled, stored,
transported, disposed of, or otherwise improperly used.
Hazardous Materials Branch Officer: responsible for directing and coordinating all hazardous
materials operations assigned by the incident commander.
Hazardous Materials Regulations: Department of Transportation (DOT) Title 49 Code of
Federal Regulations (CFR) Parts 106-199.
Hazardous Materials Specialists: individuals who respond with and provide support to
hazardous materials technicians. Their duties parallel those of the hazardous materials technician;
however, those duties require a more directed or specific knowledge of the various substances
3 Also see the National Oil and Hazardous Substances Pollution Contingency Plan, 40CFR302.4, for listing of
Hazardous Substances.
xi
DOE-HDBK-1139/3-2003
they may be called upon to contain. The hazardous materials specialist also serves as the site
liaison with Federal, state, local and other government authorities as regards site activities.
Hazardous Materials Technicians: individuals who respond to releases or potential releases for
the purpose of stopping the release. They assume a more aggressive role than a first responder at
the operations level in that they will approach the point of release in order to plug, patch or
otherwise stop the release of a hazardous substance.
Hazardous Operations: includes process operations that are subject to regulatory actions because
of the presence of one or more specific hazardous materials or types of materials that meet or
exceed established thresholds or guidelines. These include operations with chemicals governed
by:
• 29CFR1910.119, “Process Safety Management of Highly Hazardous Chemicals” or
40CFR68.67, “Chemical Accident Prevention Provisions-Process Hazards Analysis;”
• hazard category 1, 2, or 3 nuclear operations as defined in 10CFR830, “Nuclear Safety
Management;”
• operations with Beryllium as defined by 10CFR850;
• facilities with “significant” fire hazards as defined by DOE O 420.1A;
• hazardous waste operations as defined in 29CFR1910.120, “Hazardous Waste Operations and
Emergency Response;” and
• activities subject to NEPA environmental assessment or environmental impact statements as
defined in 10CFR1021.400.
Section 10
Hazardous (Personal) Property: any personal property, including scrap (see definition) or waste
but excluding property involving a radiological hazard, that is ignitable, corrosive, reactive, or
toxic because of its quantity, concentration, or physical, chemical, or infectious characteristics, or
that is deemed a hazardous material, chemical substance or mixture, or hazardous waste under the
Hazardous Material Transportation Act (HMTA) (49 U.S.C. 5101), the Resource Conservation
and Recovery Act (RCRA) (42 U.S.C. 6901-6981), or the Toxic Substances Control Act (TSCA)
(15 U.S.C. 2601-2609). Such property may be in solid, liquid, semi-liquid, or contained gas form
and may cause or significantly contribute to an increase in mortality or illness, or pose present or
potential hazard to human health or the environment when improperly used, treated, stored,
transported, disposed of, or mismanaged. Hazardous (Personal) Property is a category under
High Risk (Personal) Property (see definition).
Hazardous Substance: for the purposes of this document, as defined in 29CFR1910.120: “…A)
any substance defined under section 101(14) of CERCLA; B) any biologic agent and other
disease causing agent which after release into the environment and upon exposure by ingestion,
inhalation, or assimilation by any person, either directly from the environment or indirectly by
ingestion through food chains, will or may reasonably be anticipated to cause death, disease,
behavioral abnormalities, cancer, genetic mutation, physiological malfunctions (including
malfunctions in reproduction) or physical deformations in such persons or their offspring; C) any
substance listed by the U.S. Department of Transportation as hazardous materials under
49CFR172.101 and appendices; and D) hazardous waste either as a waste or combination of
wastes as defined in 40CFR261.3, or those substances defined as hazardous wastes in
49CFR171.8.…”.
xii
DOE-HDBK-1139/3-2003
Hazardous Waste4: those materials or substances, the handling and disposal of which are
governed by 40CFR261, 29CFR1910.120, and 29CFR1926.65.
High Risk (Personal) Property5: property that, because of its potential impact on public health
and safety, the environment, national security interests, or proliferation concerns, must be
controlled, and dispositioned in other than the routine manner. The categories of high risk
property are (1) Especially designed or prepared property, (2) Export controlled property, (3)
Proliferation-sensitive property, (4) Nuclear weapon components or weapon-like components, (5)
Hazardous property, (6) Automatic data processing equipment, (7) Export controlled information,
(8) Radioactive property, (9) Special nuclear material, and (10) Unclassified controlled nuclear
information.
Holding Agency: the Federal agency having accountability for, and generally possession of, the
chemicals involved.
Incident Commander: assumes control of the incident scene.
Inside Liquid Storage: a location inside a building that is segregated by either physical barriers
or a distance approved by a Fire Protection Engineer and is used to store any liquid chemical
except those that are classified as being low hazard (see definition); a room or building used for
the storage of liquids in containers or portable tanks, separated from other types of occupancies.
Inside room: a room totally enclosed within a building and having no exterior walls.
Section 11
Internal Screening Period: See DOE Screening Period (definition).
Labeling: a descriptive name, identification number, instructions, cautions, etc. to be placed
directly on the primary container of hazardous materials.
Laboratory units: for a complete overview of laboratory units and their definition, see NFPA 45,
Fire Protection for Laboratories Using Chemicals.
LC50: the concentration of a vapor or gas that will kill 50% of a test population. Exposure periods
are typically for one hour unless otherwise stated.
4 The definition for hazardous waste, as given in 41CFR101-42.001, includes the following caveats:
(a) In general, hazardous materials (see definition) are hazardous wastes when one or both of the following is
true:
1. they have passed through the disposition cycle without having been successfully reutilized,
transferred, donated, or sold, and the holding agency declares an intent to discard them.
2. they are no longer usable for their intended purpose, a valid alternate purpose, or resource
recovery.
(b) In general, solid (non-hazardous) wastes, as defined at 40CFR261.2, become hazardous wastes when:
1. they exhibit one or more of the characteristics of ignitability, corrosivity, reactivity, or EP
(Extraction Procedure) toxicity; or
2. they are predetermined hazardous wastes upon generation as listed in 40CFR261, Subpart D.
5 Excess chemicals identified as high risk personal property are most likely to belong to category (5), (2) or (3).
xiii
DOE-HDBK-1139/3-2003
Low Hazard Chemicals6: chemicals that have an NFPA flammability rating of “0” or “1”; a
health hazard rating of “0” or “1”; a reactivity rating of “0”; and no special hazard rating such as
“oxidizer”, “water reactive”, or “hazardous polymerization” per NFPA 704, Identification System
for Fire Hazards of Materials.
Marking: a descriptive name, identification number, instructions, cautions, weight, specification,
or UN marks, or combinations thereof, required on outer packaging of hazardous materials.
MSDS7: Material Safety Data Sheet.
Munitions List8: articles, services, and related technical data designated as defense articles and
defense services by the Arms Export Control Act of 1968, as amended. Items are listed in the
International Traffic in Arms Regulation (ITAR) (22CFR121), published by the U.S. Department
of State.
nCi/g: Nanocuries per gram.
NFPA Health Hazard Rating of "3" (for a gas): per NFPA 704, "Identification of the Hazards
of Materials for Emergency Response", any gas whose LC50 (see definition) for acute inhalation
toxicity is greater that 1000 ppm but less than or equal to 3000 ppm.
NFPA Health Hazard Rating of "4" (for a gas): per NFPA 704, "Identification of the Hazards
of Materials for Emergency Response", any gas whose LC50 for acute inhalation toxicity is less
than or equal to 1000 ppm.
No Commercial Value: an item has “no commercial value” when it has neither utility nor
monetary value, as an item or as scrap (see definition).
Non-Appropriated Fund Property: property (i.e., chemicals) procured without the use of Federal
government funds.
Nonfriable Asbestos Materials: materials that contain asbestos which is bonded or otherwise
rendered unavailable for release into the atmosphere through normal usage and that cannot, when
dry, be crumbled, pulverized, or reduced to powder by hand pressure. However, cutting, sanding,
Section 12
6 Low Hazard Chemical: This definition refers to the NFPA 704 hazard identification numbers, which includes
information on how to use them to determine if a chemical is a “low hazard” chemical. A well-developed set of
criteria is needed in order to determine appropriate ratings for those chemicals that have not been rated. Criteria for
these ratings have been well defined in NFPA 704. Those criteria can be used to determine hazard ratings for
chemicals that have yet to be evaluated. (While other rating systems exist, none is as well- accepted nor does any
have criteria that are as well defined for the evaluation of chemicals as does the NFPA 704 system.) It should be
noted, however, that NFPA 704 criteria are developed for acute exposures only. Chronic effects, such as
carcinogenicity, should be factored into any evaluation when determining health ratings. Information concerning
chronic health hazards can be found in numerous resources such as Tomes®, the ACGIH “Guide to Occupational
Exposure Threshold Limit Values”, and the NIOSH “Pocket Guide to Chemical Hazards”.
7 Material Safety Data Sheets (MSDS): Although a manufacturer may provide an MSDS for a chemical, the
issuance of that MSDS does not necessarily indicate that the material is hazardous. Some manufacturers develop
MSDSs for all their chemicals whether the material is hazardous or not.
8 The U.S. Munitions List includes military explosives, propellants, toxicological agents, etc.
xiv
DOE-HDBK-1139/3-2003
crushing, or performing some other disruptive action on items containing nonfriable asbestos can
release asbestos fibers into the air.
Nuclear Suppliers Group: a select group of nuclear supplier countries dedicated to nuclear
nonproliferation that establishes the Trigger List (see definition) and Dual-use List (see
definition) in formulating guidelines for the export of nuclear materials, equipment and
technology and for the transfer of nuclear-related dual-use nuclear equipment, materials, software
and related technology, respectively.
Ozone Depleting Substances: Certain chemical substances that, Public Law 101-549, the Clean
Air Act Amendments of 1990 identifies as those chemicals, the use of which are primarily
responsible for depletion of the earth’s ozone layer. ODS chemicals are also designated in the
1989 Montreal Protocol on Substances that Deplete the Ozone Layer.
ODS, Class I Substance: any substance designated as class I by EPA pursuant to 42 U.S.C.
7671(a), including, but not limited to, chlorofluorocarbons, halons, carbon tetrachloride and
methyl chloroform.
ODS, Class II Substance: any substance designated as class II by EPA pursuant to 42 U.S.C.
7671(a), including, but not limited to, hydrochlorofluorocarbons.
Onsite: any area within the boundaries of a DOE site or facility to which access is controlled.
[NOTE: If hazardous chemicals are transported over a public road that is on-site, DOT
Hazardous Materials Transportation Regulations must be adhered to.]
Operational Emergencies: include the spectrum of significant emergency events or conditions
that involve or affect facilities and activities by causing or having the potential to cause serious
health and safety impacts onsite or offsite to workers or the public, serious detrimental effects on
the environment, direct harm to people or the environment as a result or degradation of security
or safeguards conditions or release (or loss of control) of hazardous materials.
Section 13
Oxidizer: as per 29CFR1910.1200, a chemical other than a blasting agent or explosive as defined
in 29CFR1910.109(a), that initiates or promotes combustion in other materials, thereby causing
fire either of itself or through the release of oxygen or other gases.
Outdoor Storage Locker: a moveable, prefabricated structure, manufactured at a site other than
the final location of the structure and transported completely assembled or in a ready to assemble
package to the final location. It is intended to meet local, state, and federal requirements for the
outside storage of hazardous materials.
PCB Items: materials containing 50 through 499 ppm PCB.
Personal Property: property of any kind, except for real estate and interests therein (such as
easements and rights-of-way), and permanent fixtures which are Federal government-owned,
chartered, rented, or leased from commercial sources by, and in the custody of, DOE or its
designated contractors; source, byproduct, special nuclear materials, and atomic weapons as
defined in section 11 of the Atomic Energy Act of 1954 (42 U.S.C. 2014), as amended; and
petroleum in the Strategic Petroleum Reserve and the Naval Petroleum Reserves. For purposes of
this document, personal property means chemicals/chemical products.
xv
DOE-HDBK-1139/3-2003
Process Hazard Analysis: as defined in 29CFR1910.119, “Process Safety Management
of Highly Hazardous Chemicals”.
Pollution Prevention: any action that reduces or eliminates the generation of waste, the release of
pollutants to the environment, and the use of certain ODSs.
Polychlorinated biphenyls: a class of chlorinated aromatic compounds that is hazardous to
human health and the environment. [NOTE: In 41CFR101-42.1102-2, the same acronym
“PCBs” is used to mean substances containing polychlorinated biphenyls at a concentration of
500 ppm or greater.].
Precious Metals: a term that refers to gold, silver, and the platinum group metals -- platinum,
palladium, rhodium, iridium, ruthenium and osmium.
Proliferation-sensitive Property: nuclear-related or dual-use equipment, material, or technology
as described in the Nuclear Suppliers Group (see definition) Trigger List (see definition) and
Dual-use List (see definition), or equipment, material or technology used in the research, design,
development, testing, or production of nuclear or other weapons. Proliferation-sensitive Property
is a category under High Risk (Personal) Property (see definition).
Property Act: the Federal Property and Administrative Services Act of 1949 (63 Stat. 377), as
amended (codified, as amended, in various sections of Titles 40 and 41 of the United States
Code), the law that centralized Federal property management and disposition functions under the
GSA.
Public Agency: any State, political subdivision thereof, including any unit of local government or
economic development district; any department, agency, or instrumentality thereof, including
instrumentalities created by compact or other agreement between States or political subdivisions;
multi-jurisdictional sub-state districts established by or pursuant to State law; or any Indian tribe,
band, group, pueblo, or community located on a State reservation.
Public Body: any department, agency, special purpose district, or other instrumentality of a State
or local government; any Indian tribe; or any agency of the Federal government.
Regulated Area: an area where entry and exit is restricted and controlled.
Section 14
Release: any spilling, leaking, pumping, pouring, emitting, emptying, discharging, injecting,
escaping, leaching, dumping, or disposing into the environment (including the abandonment or
discarding of barrels, containers, and other closed receptacles) of any chemical, extremely
hazardous substance (see definition), or CERCLA hazardous substance.
Reportable Excess Property: excess property that is reportable to the GSA by the holding agency
(see definition) on Standard Form 120, excluding Hazardous Waste (see definition), Extremely
Hazardous Property (see definition), Scrap (see definition), Controlled substances, Chemicals
determined to be appropriate for abandonment or destruction, Nuclear-related and Proliferation-
sensitive Property (see definition), National security-sensitive property, NRC-controlled
materials, etc. Reportable excess property includes non-hazardous chemicals, drugs and reagents
xvi
DOE-HDBK-1139/3-2003
other than controlled substances; nonfriable asbestos materials, excluded PCB products (i.e.,
those containing less than 49 ppm PCBs), etc..
Reportable Property: excess or surplus property that is reportable to the GSA by the holding
agency (see definition) or receiving organization on an appropriate Standard Form to effect a
disposition transaction or to initiate the next phase of screening.
Resource Conservation and Recovery Act (RCRA): the Solid Waste Disposal Act, as amended
by the Resource Conservation and Recovery Act of 1976, as amended, 42 U.S.C. section 6901 et
seq..
Safety Can: approved container of not more than five (5) gallon capacity having a spring closing
lid and a spout cover and so designed that it will safely relieve internal pressure when subjected
to fire exposure.
Safety Officer (designated as Hazardous Materials Branch Safety Officer in NFPA
regulations): ensures that recognized safe practices are followed and provides other technical
safety advice as needed.
Scrap: property that has no value except for its basic material content.
Screening Period: the period in which excess or surplus personal property is made available for
excess transfer or surplus donation to eligible recipients.
Segregated warehouse: a separated or detached building used specifically for warehousing-type
operations.
Senior Program Official or Designee: controls the acquisition and production of heavy water for
a given program.
Standard Form: used for implementing a disposition action or for reporting purposes.
Shelf-Life: the length of time an age-sensitive material can be stored under prescribed conditions
and can still confidently retain its properties such that it will function as intended when being put
into service.
Shelf-Life Item: any item that deteriorates over time or has unstable characteristics such that a
storage period must be assigned to assure the item is issued within that period to provide
satisfactory performance. Management of such items is governed by 41CFR101-27.2, and by
DOD instructions, for executive agencies and DOD respectively.
Sprinklered Area: an area that has an overhead system designed and installed according to NFPA
13, "Standard for the Installation of Sprinkler Systems" to spray water down from sprinkler heads
during a fire.
State Agency for Surplus Property (SASP): the agency designated under State law to receive
Federal surplus personal property for distribution to eligible donees (see definition) within the
State as provided for in subsection 203(j) of the Property Act (40 U.S.C. 484(j)).
Section 15
xvii
DOE-HDBK-1139/3-2003
Storage: a chemical(s) set aside for future use or safekeeping or an inventory of compressed or
liquefied gases in containers that are not in the process of being used, examined, serviced,
refilled, loaded, or unloaded.
Surplus Chemicals: any excess chemicals that remain with the facility after having undergone
internal screening for reutilization within the DOE complex as well as excess screening for
transfer to another Federal Agency.
Surplus Property (Surplus): excess personal property no longer required by the Federal agencies
as determined by GSA.
Surplus Release Date: the date on which screening of excess chemicals for Federal use is
completed and the chemicals are not needed for any Federal use. On that date, excess chemicals
become surplus and are eligible for donation to non-federal recipients.
Suspect (Property): any material or property that cannot be guaranteed, without further
evaluation, of being free from chemical or radioactive contamination.
Superfund or Superfund Act: common name for CERCLA (Comprehensive Environmental
Response, Compensation, and Liability Act of 1980, as amended).
System: piping, pumps and/or containers that are attached together so that the collection can
perform some specific function.
Threshold planning quantity (TPQ): the minimum amount of a substance present at a site at
which notification is required under 40CFR355. TPQs are listed in appendices A and B of that
regulation.
Toxic gas: any gas that has a National Fire Protection Association (NFPA) health hazard rating
of 3 or 4 (see definition) per NFPA 704, Identification System for Fire Hazards of Materials.
Transuranic Waste: Transuranic waste (TRU waste) contains alpha-emitting radionuclides with
the following characteristics: atomic number greater than 92, half-life greater than 20 years,
concentrations greater than 100 nCi/g (see definition.).
Trigger List9: a compilation of Nuclear materials, equipment, and related technology developed
by the Nuclear Supplier Group (see definition) and maintained by the International Atomic
Energy Agency (IAEA), as Information Circular INFCIRC 254, Part 1. Items on this list "trigger"
the imposition of International Atomic Energy Agency safeguards.
Type I Items: non-extendable shelf-life items that have a definite storage life after which the item
or material is considered to be no longer usable for its primary function and should be discarded.
Examples of Type I items include drugs and medicines with certain characteristics, and
unstable/reactive chemicals (see definition).
9 The Trigger List includes nuclear grade graphite, deuterium and heavy water.
xviii
DOE-HDBK-1139/3-2003
Type II Items: extendable shelf-life items for which successive re-inspection dates can be
established when the items or materials have a continued usability as determined by examination
based upon criteria that have been agreed upon. Examples of Type II items include paints,
coatings and inks.
UL Listed: listed by the Underwriter’s Laboratory to indicate special construction requirements
have been met.
Universal Waste: any of the following hazardous wastes that are managed under the universal
waste requirements of 40CFR273: (1) Batteries as described in 40CFR273.2; (2) Pesticides as
described in 40CFR273.3; (3) Thermostats as described in 40CFR273.4; and (4) Lamps as
described in 40CFR273.5.
Section 16
Unstable/Reactive Chemical: a chemical that in the pure state, or as produced or transported, will
vigorously polymerize, decompose, condense, become self-reactive, or otherwise undergo a
violent chemical change under conditions of shock, pressure or temperature. Such chemicals may
also be identified as Type I items (see definition). Examples include explosives, reactive
monomers, and peroxide formers that produce unstable highly friction-sensitive or shock-
sensitive peroxides, etc..
Upright Position: the position a cylinder is in when the valve is located at a position higher than
any other on the tank.
Water Reactive Material: a substance that will spontaneously react with water to release toxic
gases, flammable gases, or amounts of heat that could become significant (e.g., resulting in
splattering, pressure-volume explosions). It includes those materials that can form explosive
mixtures with water.
xix
DOE-HDBK-1139/3-2003
Acronyms and Abbreviations
ACGIH: American Conference of Governmental Industrial Hygienists.
AL: Acquisition Letter.
ANSI: American National Standards Institute.
ATF: Bureau of Alcohol, Tobacco and Firearms.
CERCLA: the Comprehensive Environmental Response, Compensation and Liability Act of 1980
(also known as “Superfund”), as amended.
CGA: Compressed Gas Association.
CFR: Code of Federal Regulations.
LEPC: Committee or Local Emergency Planning Committee.
CRD: Contractor Requirements Document.
DOD: U.S. Department of Defense.
DOE: U.S. Department of Energy.
DOE-PMR: Department of Energy Property Management Regulations, 41CFR109.
DOT: U.S. Department of Transportation.
DPMO: Departmental Property Management Officer.
EADS: Energy Asset Disposal System.
EMS: Environmental Management System.
EO: Executive Order.
EPA: U.S. Environmental Protection Agency.
EPCRA: Emergency Planning and Community Right-To-Know Act of 1986, Title III of the
Comprehensive Environmental Response, Compensation, and Liability Act
(CERCLA)/Superfund Act of 1980.
FEDS: Federal Disposal System.
FM: Factory Mutual.
FMR: Federal Management Regulation, (Title 41, Subtitle C), 41CFR102.
xx
DOE-HDBK-1139/3-2003
FPMR: Federal Property Management Regulations, (Title 41, Subtitle C), 41CFR101 to 200.
FSC: Federal Supply Classification (as described in the Federal Standard 313).
GSA: General Services Administration.
HAZMAT: hazardous materials.
HMIS: Hazardous Material Information System, sponsored and maintained by the Department of
Defense.
HSWA: The Hazardous and Solid Waste Amendments of 1984 to RCRA.
IC: Incident Commander.
ICS: Incident Command System.
ISMS: Integrated Safety Management System.
LEPC: local emergency planning committee.
MSDS10: Material Safety Data Sheet.
NFPA: National Fire Protection Association.
NIOSH: National Institute for Occupational Safety and Health.
NNSA: National Nuclear Security Administration.
NRC: Nuclear Regulatory Commission.
ODS: Ozone Depleting Substances.
OPMO: Organizational Property Management Officer.
OSHA: Occupational Safety and Health Administration.
P2: Pollution Prevention.
PCBs: polychlorinated biphenyls.
PHA: Process Hazard Analysis.
RCRA: Resource Conservation and Recovery Act.
10 Material Safety Data Sheets (MSDS): Although a manufacturer may provide an MSDS for a chemical, the
issuance of that MSDS does not necessarily indicate that the material is hazardous. Some manufacturers develop
MSDSs for all their chemicals whether the material is hazardous or not.
Section 17
xxi
DOE-HDBK-1139/3-2003
ROI: Return-On-Investment.
SARA: Superfund Amendments and Reauthorization Act of 1986 (see definition).
SASP: State Agency for Surplus Property (see definition).
SF: Standard Form.
TBD: to be determined at a later date.
TRU: Transuranic Waste.
TSCA: Toxic Substances Control Act (15 U.S.C. 2601 – 2692).
USC: United States Code.
xxii
DOE-HDBK-1139/3-2003
INTENTIONALLY BLANK
xxiii
DOE-HDBK-1139/3-2003
Chapter 1 - Hazard Analysis
1.0 Introduction
This chapter identifies and consolidates existing user safety and health requirements found in DOE
and Federal chemical-related safety and health regulations and National Standards that address hazard
analysis of activities involving chemicals (see definition) and chemical products (see definition).
State and local codes and requirements are NOT included. This chapter specifically consolidates
requirements found in the National Fire Protection Association (NFPA), the American National
Standards Institute (ANSI), the Compressed Gas Association (CGA), the Occupational Safety and
Health Administration (OSHA), and certain Environmental Protection Agency (EPA) regulations and
Department of Energy (DOE) Rules and Orders, including technical standards that are made
mandatory by their specific reference within a regulation, rule or DOE Order.
This chapter is intended to list chemical-related safety and health requirements and to consolidate
those that are overlapping and/or duplicative. The list of requirements includes “pointers” to the
sources of those requirements.
This document does NOT create any new or additional requirements.
2.0 Applicability
The information presented here applies to all locations that use chemicals or chemical products.
[NOTE: Throughout this document, the term “chemicals” is used to indicate chemicals and/or
chemical products as described in Section 3, below.] This chapter is intended only to address safety
and health-related hazard and risk analysis requirements applicable to chemical user activities. It
consolidates existing, core safety and health requirements that all sites must follow when engaged in
chemical-related activities.
The requirements included in this chapter come from sources that have different safety purposes. As
a result, some of these requirements may not always be applicable to the work being performed at an
individual site or facility. It is the responsibility of each user to determine the applicability of specific
requirements to their work and how they are implemented. The reference sources for the
requirements included in this chapter can be used to determine the applicability of those requirements
to the work being performed.
3.0 Definitions and Acronyms
See Glossary.
4.0 Requirements for Chemical Hazard Analysis
Sources11 Consolidated Requirements
4.1 General (Applicable to all operations/activities involving
chemicals)
11 Hyperlinks to ANSI, CGA, and NFPA requirements provided here are for general information only, as they
require user subscription to a prescribed service in order to access these organizations’ source requirements.
1
DOE-HDBK-1139/3-2003
Sources11 Consolidated Requirements
ANSI Z49.1, 3.2.2.2;
CGA P-1, 4.1;
DOE 440.1A , 4(i);
NFPA 30, 5.2;
NFPA 45, 7.1;
NFPA 45, 7.2.1.1,
NFPA 430, 2.-1.1;
NFPA 432, 4.7.1;
10CFR835.204(d)(2);
29CFR1910.106(e)(8);
29CFR1910.146(c)(1)-
(d)(2);
29CFR1910.1450(e)(3);
48CFR970.5204-2(c)(2)12
Section 18
4.1.1 Hazards associated with all activities involving chemicals
that could put the employee at risk of injury or illness
shall be evaluated. Those activities include, but are not
limited to a) design of new facilities or modification of
existing facilities and equipment, b) operations and
procedures and c) equipment, products and services that
are selected or purchased.
[NOTE: Numerous other substance-specific hazard
analysis requirements can be found in 29CFR1910,
Subpart Z]
DOE O 440.1A,
Attachment 1 (1)(b)(2)(d)
and Attachment 2
(14)(a)(4);
NFPA 430, 2.1.1;
NFPA 430, 2.10.1;
NFPA 432, 4.7.1;
29CFR1910.132(d)(2)
4.1.1.1 The results of the hazard analysis shall be
documented and approved by the appropriate
safety official or manager.
ANSI Z49.1, 3.2.1.2;
ANSI Z49.1, 3.2.1.3;
ANSI Z49.1, 3.2.1.5;
CGA P-1, 4.1;
NFPA 45, 7. 1;
NFPA 430, 2.7.1;
NFPA 432, 4.2;
29CFR1910.1200(h)(1);
29CFR1910.1450(f)(1) and
(f)(4)(i)(B) and (f)(4)(i)(C);
29CFR1926.21(b)(2)
4.1.2 Before beginning work, employees shall be informed of
the hazards present in their work area.
4.2 Hazardous Operations13 (see definition)
12 This requirement of the DOE Acquisition Regulations (DEAR, ES&H Clause) requires an identification and
evaluation of hazards associated with work, as part of an overall documented safety management system.
2
http://www.ansi.org/
http://www.cganet.com/
http://www.explorer.doe.gov/
http://www.nfpa.org/
http://www.osha-slc.gov/OshStd_data/1910_0106.html
http://www.osha-slc.gov/OshStd_data/1910_0146.html
http://www.osha-slc.gov/OshStd_data/1910_1450.html
http://www.explorer.doe.gov/
http://www.explorer.doe.gov/
http://www.nfpa.org/
http://www.osha-slc.gov/OshStd_data/1910_0132.html
http://www.ansi.org/
http://www.cganet.com/
http://www.osha-slc.gov/OshStd_data/1910_1200.html
http://www.osha-slc.gov/OshStd_data/1910_1450.html
http://www.osha-slc.gov/OshStd_data/1926_0021.html
DOE-HDBK-1139/3-2003
Sources11 Consolidated Requirements
DOE O 151.1A,
Attachment, Chap. IV,
3(a)(1);
DOE O 420.1A, 4.2.1 (5);
10CFR830, Subpart B;
10CFR850.21(a);
10CFR1021.400;
29CFR1910.119(e);
29CFR1910.120(c)(1);
40CFR68.67(a);
40CFR1502.14
4.2.1 Hazardous processes shall be analyzed for possible natural
and man-made events that could lead to or result in a loss of
control of hazardous materials
DOE-STD-1120-98;
DOE-STD-3011-94;
DOE-STD-3016-99;
DOE O 460.1A;
DOE O 460.1B [NOTE: This
order, issued on 4/4/2003,
cancels the DOE O 460.1A];
10CFR830.7;
10CFR830 Subpart B,
204(a) and (b);
29CFR1910.119(e)(2);
40CFR68.67(b);
40CFR1502.24
4.2.1.1 Hazard analysis techniques shall be selected and
used that are appropriate for the hazards and
complexities of work processes being analyzed
DOE-STD-1027-92;
10CFR830 Subpart B,
Part202(b)(3);
29CFR1910.119(d);
29CFR1910.120(c)(3);
40CFR68.65;
40CFR1502.15
4.2.1.2 Process information relevant to the hazard
analysis, such as energy sources and hazardous
materials, shall be identified
DOE O 5480.23, 8(c)(3);
10CFR830.204(b)(3);
29CFR1910.119(e)(3);
4.2.1.3 Consequences of postulated accidents associated
with hazardous processes and their likelihood of
occurrence shall be evaluated
40CFR68.50;
DOE-STD-3009-94;
13 The requirements for hazardous operations are in addition to requirements associated with those activities
specified in Section 4.1.
3
Section 19
http://www.directives.doe.gov/cgi-bin/explhcgi?qryKHAW6a4Sc;doe-32
http://www.explorer.doe.gov/
http://tis.eh.doe.gov/nsps/ourdocs/rules.html
http://tis.eh.doe.gov/be/webdoc4.html-ssi
http://tis.eh.doe.gov/nepa/tools/REGULATE/NEPA_REG/1021/Sub-D.htm
http://www.osha-slc.gov/OshStd_data/1910_0119.html
http://www.osha-slc.gov/OshStd_data/1910_0120.html
http://ceq.eh.doe.gov/nepa/regs/ceq/1502.htm
http://www.directives.doe.gov/cgi-bin/explhcgi?qryUMA88a4Sc;doe-218
http://www.directives.doe.gov/cgi-bin/explhcgi?qryUMA88a4Sc;doe-218
http://www.directives.doe.gov/cgi-bin/explhcgi?qryUMA88a4Sc;doe-218
http://www.directives.doe.gov/cgi-bin/explhcgi?qryUMA88a4Sc;doe-218
http://tis.eh.doe.gov/nsps/ourdocs/rules.html
http://tis.eh.doe.gov/nsps/ourdocs/rules.html
http://www.osha-slc.gov/OshStd_data/1910_0119.html
http://www.access.gpo.gov/nara/cfr/cfrhtml_00/Title_40/40cfr68_00.html
http://ceq.eh.doe.gov/nepa/regs/ceq/1502.htm
http://tis.eh.doe.gov/techstds/standard/appframe.html
http://tis.eh.doe.gov/nsps/ourdocs/rules.html
http://www.osha-slc.gov/OshStd_data/1910_0119.html
http://www.osha-slc.gov/OshStd_data/1910_0120.html
http://www.access.gpo.gov/nara/cfr/cfrhtml_00/Title_40/40cfr68_00.html
http://ceq.eh.doe.gov/nepa/regs/ceq/1502.htm
http://www.directives.doe.gov/cgi-bin/explhcgi?qryRIAr7a4Sc;doe-324
http://tis.eh.doe.gov/nsps/ourdocs/rules.html
http://www.osha-slc.gov/OshStd_data/1910_0119.html
DOE-HDBK-1139/3-2003
Sources11 Consolidated Requirements
29CFR1910.120(c)(7);
40CFR68.25;
40CFR68.28;
40CFR68.67(c);
40CFR1502.16;
40CFR1508.8
10CFR850.21(b);
29CFR1910.119(e)(4);
40CFR68.67(d)
4.2.1.4 Hazard analyses shall be performed by qualified
personnel
10CFR1021.310;
10CFR830 Subpart B,
204(a) and (b);
29CFR1910.119(e)(5);
29CFR1910.120(b)(4);
40CFR68.39;
40CFR68.67(e);
40CFR1508.10
4.2.1.5 Results of hazard analyses shall be documented
and approved by appropriate management
10CFR830 Subpart B,
204(c)(1) and (c)(2);
29CFR1910.119(e)(6);
40CFR68.67(f)
4.2.1.6 Hazard analyses shall be updated and revalidated
periodically
10CFR830.6;
29CFR1910.119(e)(7);
40CFR68.67(g)
4.2.1.7 Hazard analysis results and documentation,
including updates, shall be retained for the life of
the process operation
40CFR68.22;
5.0 Source Documents
ANSI Z49.1 (1994), “Safety in Welding, Cutting, and Allied processes”.
CGA P-1 (2000), “Safe Handling of Compressed Gases in Containers”.
DOE O 151.1, “Comprehensive Emergency Management System”.
DOE O 420.1A, “Facility Safety”.
DOE O 440.1A, “Worker Protection Management for DOE Federal and Contractor Employees”.
DOE O 460.1A, “Packaging and Transportation Safety”.
DOE O 460.1B, “Packaging and Transportation Safety” [NOTE: This order, issued on 4/4/2003,
cancels the DOE O 460.1A].
DOE-STD-1027-92, “Hazard Categorization and Accident Analysis Techniques for Compliance with
DOE O 5480.23, Nuclear Safety Analysis Reports”.
4
http://www.osha-slc.gov/OshStd_data/1910_0120.html
http://ceq.eh.doe.gov/nepa/regs/ceq/1502.htm
http://ceq.eh.doe.gov/nepa/regs/ceq/1508.htm
http://tis.eh.doe.gov/be/webdoc4.html-ssi
http://www.osha-slc.gov/OshStd_data/1910_0119.html
http://www.access.gpo.gov/nara/cfr/cfrhtml_00/Title_40/40cfr68_00.html
http://tis.eh.doe.gov/nepa/tools/REGULATE/NEPA_REG/1021/Sub-C.htm
http://tis.eh.doe.gov/nsps/ourdocs/rules.html
http://www.osha-slc.gov/OshStd_data/1910_0119.html
http://www.osha-slc.gov/OshStd_data/1910_0120.html
http://www.access.gpo.gov/nara/cfr/cfrhtml_00/Title_40/40cfr68_00.html
http://www.access.gpo.gov/nara/cfr/cfrhtml_00/Title_40/40cfr68_00.html
http://ceq.eh.doe.gov/nepa/regs/ceq/1508.htm
http://tis.eh.doe.gov/nsps/ourdocs/rules.html
http://www.osha-slc.gov/OshStd_data/1910_0119.html
http://www.access.gpo.gov/nara/cfr/cfrhtml_00/Title_40/40cfr68_00.html
http://tis.eh.doe.gov/nsps/ourdocs/rules.html
http://www.osha-slc.gov/OshStd_data/1910_0119.html
http://www.access.gpo.gov/nara/cfr/cfrhtml_00/Title_40/40cfr68_00.html
Section 20
DOE-HDBK-1139/3-2003
DOE-STD-1120-98, “Integration of Environment, Safety, and Health into Facility Disposition
Activities”.
DOE-STD-3009-94, “Preparation Guide for U.S. DOE Nonreactor Nuclear Facility Safety Analysis
Reports”.
DOE-STD-3011-94, “Guidance for Preparation of DOE 5480.22 (TSR) and DOE 5480.23 (SAR)
Implementation Plans”.
DOE-STD-3016-99, “Limited Standard; Hazard Analysis Reports for Nuclear Explosive Operations”.
NFPA 30 (2000), “Flammable and Combustible Liquids Code”.
NFPA 45 (2000), “Standard on Fire Protection for Laboratories Using Chemicals”.
NFPA 430 (2000), “Storage of Liquid and Solid Oxidizers”.
NFPA 432 (2002), “Storage of Organic Peroxides Formulation”.
10CFR830, “Nuclear Safety Management,” Subpart B, “Safety Basis Requirements”.
10CFR835, “Occupational Radiation Protection”.
10CFR850, “Chronic Beryllium Disease Prevention Program”.
10CFR1021, “National Environmental Policy Act Implementing Procedures”.
29CFR1910.106, “Flammable and Combustible Liquids”.
29CFR1910.119, “Process Safety Management of Highly Hazardous Chemicals”.
29CFR1910.120, “Hazardous Waste Operations and Emergency Response”.
29CFR1910.132, “Personal Protective Equipment”.
29CFR1910.146, “Permit-required Confined Spaces”.
29CFR1910.1200, “Hazard Communication”.
29CFR1910.1450, “Occupational Exposure to Hazardous Chemicals in Laboratories”.
29CFR1926.21, ”Safety Training and Education”.
40CFR68, “Chemical Accident Prevention Provisions”.
40CFR1500-1508, “Chapter V-Council on Environmental Quality”.
48CFR970, “DOE Management and Operating Contracts”.
5
DOE-HDBK-1139/3-2003
INTENTIONALLY BLANK
6
DOE-HDBK-1139/3-2003
Chapter 2 – Acquisition
1.0 Introduction
This chapter identifies and consolidates existing user safety and health requirements found in DOE
and Federal chemical-related safety and health regulations and National Standards that address the
acquisition of chemicals (see definition) and chemical products (see definition). State and local codes
and requirements are NOT included. This chapter specifically consolidates requirements found in the
National Fire Protection Association (NFPA), the Occupational Safety and Health Administration
(OSHA), the Bureau of Mines, the Bureau of Alcohol, Tobacco and Firearms and certain
Environmental Protection Agency (EPA) regulations and Department of Energy (DOE) Rules and
Orders, including technical standards that are made mandatory by their specific reference within a
regulation, rule or DOE Order.
Direct requirements for acquisition are found in “Federal Acquisition Regulations” (FAR) and
“Department of Energy Acquisition Regulations” (DEAR). In addition, there are many regulations
and standards that include implied requirements for the acquisition of chemicals and chemical
products. Therefore, implied requirements are summarized here but are not included as mandatory
requirements in this chapter.
This chapter is intended only to consolidate overlapping and/or duplicative chemical-related safety
and health requirements. The listing of consolidated chemical-related safety and health requirements
contained here includes “pointers” to the sources of those requirements, showing the user what the
requirements are and where each comes from.
This document does NOT create any new or additional requirements.
2.0 Applicability
Section 21
The information presented here applies to all locations that purchase or use chemicals, chemical
products or services that involve the use of chemicals or chemical products. [NOTE: Throughout this
chapter, the term “chemicals” is used to indicate chemicals and/or chemical products as described in
Section 3, below.] This chapter consolidates existing, core safety and health requirements that all
sites must follow when engaged in chemical-related activities.
The requirements included in this chapter come from sources that have different safety purposes. As
a result, some of these requirements may not always be applicable to the work being performed at an
individual site or facility. It is the responsibility of each user to determine the applicability of specific
requirements to their work and how they are implemented. The reference sources for the
requirements included in this chapter can be used to determine the applicability of those requirements
to the work being performed.
3.0 Definitions and Acronyms
See Glossary.
7
DOE-HDBK-1139/3-2003
4.0 Requirements for the Acquisition of Chemicals
Sources10 Consolidated Requirements
4.1 General (Applicable to all acquisitions involving chemicals)
DOE O 440.1A , 4(i);
48CFR970.5223-1
4.1.1 Hazards associated with all activities involving chemicals
that could put the employee at risk of injury or illness shall
be identified and evaluated before purchase.
10CFR1021;
48CFR970.5223-2
4.1.2 Substitution of materials that are less hazardous and/or have
less of an environmental impact shall be evaluated before
purchase.
DOE O 460.1A , 4(i);
DOE O 460.1B [NOTE: This
order, issued on 4/4/2003,
cancels the DOE O 460.1A]
4.1.3 Packaging and Transportation Safety requirements shall be
addressed as a part of the acquisition process.
NFPA 45 7.1 4.1.4 When a chemical is ordered, it’s hazards shall be
determined and that information shall be provided to those
who will receive, store, use, or dispose of the chemical.
Restrictions imposed by local governmental regulations and
in-house rules shall be followed.
29CFR1910.1200(g)(6)( iii);
29CFR1910.1200(g)(8);
29CFR1910.1450(f)(3)(v)
4.1.5 The manufacturer’s Material Safety Data Sheet shall be
obtained for all new chemical purchases and shall be made
readily available to those who l receive, store, use or
dispose of the chemicals. In laboratories subject to
29CFR1910.1450, other reference materials may be used.
Additional Procurement Requirements
(Non Health and Safety Requirements are provided for Informational purposes)
4.2 Alcohol
27CFR22.41;
48CFR908.7107
4.2.1 Applications to purchase tax free alcohol shall be submitted
to the ATF.
4.3 Helium
The Helium Act (Pub. L.
86-777, as amended (50
U.S.C. 167(d));
30CFR602;
48CFR908.7108;
49 FR 11945 (3/28/84), as
amended;
59 FR 9105 (2/25/94)
4.3.1 DOE and its authorized contractors shall, to the extent that
supplies are readily available, whether in gaseous or liquid
form, purchase all major requirements large quantities of
helium from the Secretary of Interior, Bureau of Mines, or
from the Bureau of Mines distribution contractors eligible
to sell Bureau of Mines helium to Federal agencies.
The purchase document shall contain the following
statement: "Helium furnished under this contract shall be
Bureau of Mines Helium."
8
http://www.explorer.doe.gov/
http://www.explorer.doe.gov/
DOE-HDBK-1139/3-2003
Sources10 Consolidated Requirements
4.4 Fuel and Petroleum
41CFR101-26.602;
Section 22
48CFR908.7109
4.4.1 Acquisitions of fuel and packaged petroleum products by
DOE offices and contractors shall be from Defense
sources.
41CFR101-26.602;
48CFR908.7110 1.1.8
4.4.2 DOE offices and authorized contractors may participate
in the Defense Fuel Supply Center (DFSC) coal-
contracting program for carloads or larger lots.
4.5 Arms and Ammunition
48CFR908.7111;
49 FR 11945, Mar. 28, 1984,
as amended at 49 FR 38950,
Oct. 2, 1984
4.5.1 Acquisition of arms and ammunition readily procurable
in the civilian market shall be made in accordance with
local site acquisition procedures.
4.6 DOE-specific materials acquisitions14
Contracting activities shall require authorized contractors to obtain
the special materials identified in the following subsections in
accordance with the procedures stated therein.
48CFR908.7121 4.6.1 Heavy water. The Senior Program Official or designee
controls the acquisition and production of heavy water for
a given program. Requests for the acquisition or
production of heavy water orders shall be placed directly
with the cognizant Senior Program Official or designee
(see definition).
[54 FR 27646, June 30,
1989, as amended at 59 FR
9105, Feb. 25, 1994];
[62 FR 2312, Jan. 16, 1997]
4.6.2 Precious metals15. DOE offices and authorized
contractors shall coordinate with the Oak Ridge operating
contractor regarding the availability of the above metals
prior to the purchase of these metals on the open market.
[62 FR 2312, Jan. 16, 1997] 4.6.3 Lithium16. The DOE Oak Ridge Operations Office
supplies of Lithium shall be considered the first source of
supply prior to procurement of lithium compounds from
any other source.
13 This section covers the purchase of materials peculiar to the DOE program. While purchases of these materials
are unclassified, the specific quantities, destination or use may be classified. See appropriate sections of the
Classification Guide.
15 The DOE Oak Ridge Operations Office is responsible for maintaining the DOE supply of precious metals. These
metals are platinum, palladium, iridium, osmium, rhodium, ruthenium, gold, and silver.
16 Lithium is available at no cost other than normal packing, handling, and shipping charges from the DOE Oak
Ridge Operations Office.
9
DOE-HDBK-1139/3-2003
Sources10 Consolidated Requirements
21CFR1316 4.7 Controlled Substances
Use of controlled substances in research requires a permit or license.
5.0 Source Documents
DOE O 440.1A, “Worker Protection Management”.
DOE O 460.1A, “Packaging and Transportation Safety”.
DOE O 460.1B, “Packaging and Transportation Safety” [NOTE: This order, issued on 4/4/2003,
cancels the DOE O 460.1A].
The Helium Act (Pub. L. 86-777, as amended (50 U.S.C. 167(d).
NFPA 45 (2000)“Standard on Fire Protection for Laboratories Using Chemicals”.
10CFR1021, “National Environmental Policy Act Implementing Procedures”.
21CFR1316, “Drug Enforcement Administration; Administrative Functions, Practices, and
Procedures”.
27CFR22.41, “Distribution and Use of Tax-Free Alcohol, Qualification”.
29CFR1910.1200, “Occupational Safety and Health Standards – Hazard Communication”.
29CFR1910.1450, “Occupational Safety and Health Standards – Occupational Exposure to
Hazardous Chemicals in Laboratories”.
30CFR602, Bureau of Mines, Department of the Interior - Chapter VI - Subchapter A--Helium and
Coal”.
41CFR101-26.602, ” Federal Property Management Regulations - Procurement Sources and
Program”.
48CFR, “Department of Energy Acquisition Regulations”.
Section 23
[49 FR 11945, Mar. 28, 1984, as amended at 49 FR 38950, Oct. 2, 1984].
[49 FR 11945, Mar. 28, 1984, as amended at 59 FR 9105, Feb. 25, 1994].
[54 FR 27646, June 30, 1989, as amended at 59 FR 9105, Feb. 25, 1994].
[62 FR 2312, Jan. 16, 1997].
10
DOE-HDBK-1139/3-2003
Chapter 3 - Chemical Inventory and Tracking
1.0 Introduction
This chapter identifies and consolidates existing user safety and health requirements found in DOE
and Federal chemical-related safety and health regulations and National Standards that address the
inventory and tracking of chemicals (see definition) and chemical products (see definition). State
and local codes and requirements are NOT included. This chapter specifically consolidates
requirements found in the Occupational Safety and Health Administration (OSHA), and certain
Environmental Protection Agency (EPA) regulations and Department of Energy (DOE) Rules and
Orders, including technical standards that are made mandatory by their specific reference within a
regulation, rule or DOE Order.
Direct requirements for an inventory and tracking system are found in OSHA’s regulation
29CFR1910.1200, and EPA’s 40CFR370.25. In addition, there are many regulations and standards
for which an inventory and tracking system is an implied requirement, since inventory information
facilitates compliance. Therefore, implied requirements are summarized here but are not included as
mandatory requirements in this chapter.
This chapter is intended to list chemical-related safety and health requirements and to consolidate
those that are overlapping and/or duplicative. The list of requirements includes “pointers” to the
sources of those requirements.
This document does NOT create any new or additional requirements.
2.0 Applicability
The information presented here applies to all locations that use or store chemicals or chemical
products. It applies to chemicals prior to their becoming waste (See Disposition, Chapter 9, for
requirements for the disposition of chemicals and chemical products.) [NOTE: Throughout this
document, the term “chemicals” is used to indicate chemicals and/or chemical products as described
in Section 3, below.] This chapter consolidates existing, core safety and health requirements that all
sites must follow when engaged in chemical-related activities.
The requirements included in this chapter come from sources that have different safety purposes. As
a result, some of these requirements may not always be applicable to the work being performed at an
individual site or facility. It is the responsibility of each user to determine the applicability of specific
requirements to their work and how they are implemented. The reference sources for the
requirements included in this chapter can be used to determine the applicability of those requirements
to the work being performed.
3.0 Definitions and Acronyms
See Glossary.
4.0 Requirements for Chemical Inventory and Tracking
[NOTE: The information that follows is a consolidation of existing Federal safety and health
requirements and national standards that relate to the inventorying and tracking of chemicals. It
11
DOE-HDBK-1139/3-2003
Section 24
therefore contains "shall" statements that are taken from, or based on "shall" statements in those
existing requirements. While requirements from national standards that are referenced here are not,
in and of themselves, mandatory, they are made mandatory by DOE and Federal requirements,
including OSHA regulation 29CFR1910.6, which incorporates them by reference. DOE O 440.1A
mandates compliance with OSHA regulations found in Title 29 of the Code of Federal Regulations
(CFR). National standard requirements referenced here are thereby made mandatory for DOE
contractors through contracts that include DOE O 440.1A. Please see the Introduction to this section
of the Chemical Management Handbook for more information.]
Sources10 Consolidated Requirements
4.1 Chemical Inventory Requirements
29CFR1910.1200(e)(1) 4.1.1 Maintain a list of the hazardous chemicals known to be
present using an identity that is referenced on the
appropriate material safety data sheet (the list may be
compiled for the workplace as a whole or for individual
work areas).
[NOTE: Some chemical specific regulations, such as those
for Asbestos and Beryllium, may also contain their own
inventory tracking requirements.]
40CFR370.25(a) to (d)
4.1.2 The owner or operator of a facility shall annually submit an
inventory form (Tier 1 or equivalent State or local form)
containing information on specified hazardous chemicals
present at the facility during the preceding calendar year
above specified threshold levels to the state emergency
response commission, the local emergency planning
committee, or the fire department with jurisdiction over the
facility. For any specific hazardous chemical at the facility,
the owner or operator may submit a Tier II form
(40CFR371.41) in lieu of the Tier I information.
NFPA 45, 7.2.3.3
4.1.3 For laboratories chemical inventories shall be maintained
within facility limits.
While requirements from
national standards that are
referenced here are not, in and
of themselves, mandatory, they
are made mandatory by DOE
and Federal requirements,
including OSHA regulation
29CFR1910.6, which
incorporates them by reference.
DOE O 440.1A mandates
compliance with OSHA
regulations found in Title 29 of
the Code of Federal Regulations
(CFR). National standard
requirements referenced here
are thereby made mandatory for
4.2 Implied Chemical Inventory Requirements.
There are many mandatory standards that do not directly require an
inventory of hazardous chemicals, but for which use of a chemical
inventory and tracking system would be necessary for, or would
facilitate compliance. A list of major standards with implied
requirements for keeping a chemical inventory and/or for tracking
chemicals follows. The applicability of specific DOE Orders will
depend on each site’s individual contract.
12
DOE-HDBK-1139/3-2003
Sources10 Consolidated Requirements
DOE contractors through
contracts that include DOE O
440.1A.
29CFR1910.38 4.2.1 Employee Emergency Plans and Fire Prevention Plans.
Maintain a list of the major workplace fire hazards and their
proper handling and storage procedures; potential ignition
sources and their control procedures; and the type of fire
protection equipment or systems that can control a fire
involving the identified hazards.
29CFR1910.1450 4.2.2 Occupational Exposure to Hazardous Chemicals in
Section 25
Laboratories. Requires employee protection for work in
laboratory environments with particularly hazardous
substances, including carcinogens, reproductive toxins, and
substances with a high acute toxicity. Requires an approved
Chemical Hygiene Plan covering the tasks, hazards, and
controls before beginning the work. Upon assignment,
employees must be provided with information and training
to ensure that they are apprised of the hazards of chemicals
in their work areas. This information and training must be
provided to employees prior to the start of any work in the
area, including the start-up of any new operation or task.
29CFR1910.1020 4.2.3 Access to Employee Exposure and Medical Records.
Authorizes employee access to MSDSs or to a chemical
inventory or any other record that may reveal the identity of
toxic substances or harmful physical agents and where and
when they were used in order to give employees some idea
of their potential chemical exposures.
DOE O 151.1A 4.2.4 Comprehensive Emergency Management System. Uses a
hazard assessment to develop an emergency management
program that protects workers, the public, and the
environment. Additions or deletions of chemical hazards, or
changes in the magnitude of a chemical hazard from an up-
to-date chemical inventory can be used in development and
maintenance of the emergency management hazards
assessment. During an emergency response, a real-time
chemical inventory can provide the basis for consequence
assessments used for protective action determinations.
13
DOE-HDBK-1139/3-2003
Sources10 Consolidated Requirements
DOE O 440.1A 4.2.5 Worker Protection Management for DOE Federal and
Contractor Employees. Mandates an Industrial Hygiene
Program with surveys of all work areas and operations to
identify and evaluate potential health hazards through
appropriate workplace monitoring. A chemical inventory can
help to identify locations where chemical health hazards may
be present. Managers must ensure that applicable explosives
operations comply with DOE M 440.1-1. Requires
compliance with OSHA regulations (29CFR1910 and
29CFR1926).
29CFR1910.119 4.2.6 Process Safety Management of Highly Hazardous Chemicals
(PSM). Establishes requirements to protect workers by
preventing or minimizing the consequences of 1)
catastrophic releases of toxic, reactive, or flammable
chemicals used in quantities at or above specified thresholds
or 2) ignition of explosives in manufacturing processes.
Chemical tracking is needed to determine where threshold
quantities are exceeded. PSM also requires an employer to
keep process safety information on the chemicals used and
specify the maximum intended inventory of any listed
chemical.
DOE O 420.1, Chg 3 4.2.7 Facility Safety. All new construction shall, as a minimum,
conform to the Model Building Codes applicable for the
state or region, supplemented with additional safety
requirements associated with the facility hazards.
Inventories of chemicals must be tracked in order to ensure
that chemical limits specified in applicable regulations are
not exceeded.
Local building and fire
codes.
Section 26
4.2.8 Local Codes. Establish requirements for the prevention,
control and mitigation of dangerous conditions created by
hazardous materials and for providing information needed
by emergency response personnel. Permits are required to
store, dispense, use or handle quantities of hazardous
materials exceeding listed permit amounts. The authority
having jurisdiction may require that a Hazardous Materials
Management Plan and/or Hazardous Materials Inventory
Statement accompany the permit. In addition, inventories of
chemicals must be tracked in order to determine whether or
not listed permit quantities of chemicals have been
exceeded. Each facility is responsible for determining the
applicability of their local building and fire codes.
14
DOE-HDBK-1139/3-2003
Sources10 Consolidated Requirements
The DEAR Clause 4.2.9 Department of Energy Acquisition Regulation (DEAR)
970.5204-2, “Integration of Environment, Safety and Health
into Work Planning and Execution”. The contractor shall
comply with, and assist the Department of Energy in
complying with ES&H requirements of all applicable laws
and regulations, and applicable directives identified in the
clause of this contract on Laws, regulations, and DOE
Directives. The contractor shall cooperate with Federal and
non-Federal agencies having jurisdiction over ES&H matters
under his/her contract. Before work is performed, the
associated hazards are evaluated and an agreed-upon set of
ES&H standards and requirements are established which, if
properly implemented, provide adequate assurance that
employees, the public, and the environment are protected
from adverse consequences. Administrative and engineering
controls to prevent and mitigate hazards are tailored to the
work being performed and its associated hazards. Emphasis
should be on designing the work and/or controls to reduce or
eliminate the hazards and to prevent accidents and
unplanned releases and exposures. [See also Safety
Management System Policy (DOE P 450.4) and
Integrated Safety Management System Guide (DOE G
450.4-1B)].
10CFR830
4.2.10 Nuclear Safety Management. The documented safety
analysis requires a systematic identification of all natural and
man-made hazards associated with the facility. Some DOE
contracts may still contain the earlier, more general safety
analysis Order, Nuclear Safety Analysis Reports (DOE O
480.23), or it’s predecessor, Safety Analysis and Review
System (DOE O 481.1B) for non-nuclear facilities.
40CFR68
4.2.11 Chemical Accident Prevention Provisions. Requires offsite
consequence analysis, development, and implementation of a
Risk Management Plan to protect the public and the
environment by preventing or minimizing the consequences
of catastrophic releases of toxic, reactive, or flammable
chemicals used in quantities at or above specified thresholds.
Inventories of chemicals must be tracked in order to ensure
that specified chemical limits are not exceeded.
40CFR355 4.2.12 Emergency Planning and Notification. Establishes the list of
extremely hazardous substances, threshold planning
quantities and facility notification responsibilities necessary
for development of state and local emergency response
plans.
15
DOE-HDBK-1139/3-2003
Sources10 Consolidated Requirements
40CFR61;
40CFR63
Section 27
4.2.13 National Emission Standards for Hazardous Air Pollutants
(NESHAPs) Standards are provided for specific types of
sources and processes involving hazardous air pollutants
(including radionuclides). Requires registration of emission
sources and quantity of air contaminant emissions. Contains
standards for specific processes involving hazardous
chemicals. A chemical inventory is needed to identify and
track locations and quantities of chemicals that may be
released as hazardous air pollutants.
40CFR82 4.2.14 Protection of Stratospheric Ozone. A system to track the
acquisition and inventory of ozone depleting substances can
be used to accomplish the required annual certification that
each ozone depleting substance is being used only for
laboratory applications and is not being resold or used in
manufacturing.
5.0 Source Documents
DEAR 970.5204-2, “Integration of Environment, Safety and Health into Work Planning and
Execution”.
DOE O 151.1A, “Comprehensive Emergency Management System”.
DOE O 420.1 Chg 3, “Facility Safety”.
DOE O 440.1A, “Worker Protection Management for DOE Federal and Contractor Employees”.
10CFR830, “Nuclear Safety Management”.
29CFR1910.38, “Employee Emergency Plans and Fire Prevention Plans”.
29CFR1910.119, “Process Safety Management of Highly Hazardous Chemicals”.
29CFR1910.1020, “Access to Employee Exposure and Medical Records”.
29CFR1910.1200, "Hazard Communication".
29CFR1910.1450, “Occupational Exposure to Hazardous Chemicals in Laboratories”.
40CFR61, “National Emission Standards for Hazardous Air Pollutants (NESHAPs)”.
40CFR63, “National Emission Standards for Hazardous Air Pollutants for Source Categories”.
40CFR68, “Chemical Accident Prevention Provisions”.
40CFR82, “Protection of Stratospheric Ozone”.
40CFR355, “Emergency Planning and Notification”.
40CFR370, “Hazardous Chemical Reporting: Community Right-To-Know”.
16
DOE-HDBK-1139/3-2003
Chapter 4 - On-Site Chemical Transportation
1.0 Introduction
This chapter identifies and consolidates existing user safety and health requirements found in DOE
and Federal chemical-related safety and health regulations and National Standards that address the
on-site transport of non-radioactive chemicals (see definition) and chemical products (see definition).
State and local codes and requirements are NOT included. This chapter specifically consolidates
requirements found in DOE O 460.1A and DOE O 460.1B, [NOTE: This order, issued on 4/4/2003,
cancels the DOE O 460.1A], Occupational Safety and Health Administration (OSHA) regulations
29CFR1910.101, 29CFR1910.253, and 29CFR1926.350, the American National Standards Institute
(ANSI) standard ANSI Z49.1, and the Compressed Gas Association (CGA) Pamphlets G-1 and P-1,
including technical standards that are made mandatory by their specific reference within a regulation,
rule or DOE Order.
This chapter is intended to list chemical-related safety and health requirements and to consolidate
those that are overlapping and/or duplicative. The list of requirements includes “pointers” to the
sources of those requirements.
This document does NOT create any new or additional requirements.
2.0 Applicability
The information presented here applies to all transport of chemicals or chemical products on-site. It
includes hazardous materials offered for transportation on-site, and the packaging, labeling or
marking of hazardous materials for transportation on-site. [NOTE: Throughout this document, the
term “chemicals” is used to indicate chemicals and/or chemical products as described in Section 3,
below.] This chapter consolidates existing, core safety and health requirements that all sites must
follow when engaged in chemical-related activities.
Section 28
The requirements included in this chapter come from sources that have different safety purposes. As
a result, some of these requirements may not always be applicable to the work being performed at an
individual site or facility. It is the responsibility of each user to determine the applicability of specific
requirements to their work and how they are implemented. The reference sources for the
requirements included in this chapter can be used to determine the applicability of those requirements
to the work being performed.
3.0 Definitions and Acronyms
See Glossary.
4.0 Requirements for On-Site Chemical Transportation
Sources10 Consolidated Requirements
DOE O 460.1A, 4.b;
DOE O 460.1B [NOTE: This
order, issued on 4/4/2003,
cancels the DOE O 460.1A]
4.1 Onsite Hazardous Materials Transfers - shall comply with
either:
17
DOE-HDBK-1139/3-2003
Sources10 Consolidated Requirements
49CFR171-179 4.1.1 the Hazardous Materials Regulations (see definition) that
cover, but are not limited to, such subjects as: shipper’s
responsibilities, shipping papers, packaging, handling,
labeling of material containers, marking packages place
carding and emergency response information, OR
DOE O 460.1A, 4.b;
DOE O 460.1B [NOTE: This
order, issued on 4/4/2003,
cancels the DOE O 460.1A]
4.1.2 the site- or facility-specific Document , from the cognizant
Operations or Field Office, that describes the methodology
and compliance process to meet equivalent safety for any
deviation from the Hazardous Materials Regulations.
DOE O 460.1A, 4.b;
DOE O 460.1B [NOTE: This
order, issued on 4/4/2003,
cancels the DOE O 460.1A]
4.1.2.1 For multiple-tenant DOE sites, safety documents for
several contractor organizations may be combined
into a single document.
DOE O 460.1A, 4.b;
DOE O 460.1B [NOTE: This
order, issued on 4/4/2003,
cancels the DOE O 460.1A]
4.1.2.2 DOE-operated sites (specifically, Morgantown and
Pittsburgh Energy Technology Centers) may approve
their own Transportation Safety Documents.
DOE O 460.1A, 4.b;
DOE O 460.1B [NOTE: This
order, issued on 4/4/2003,
cancels the DOE O 460.1A]
4.1.2.3 Approved Transportation Safety Documents shall be
in effect no later than 1 year from incorporation of
DOE O 460.1A or DOE O 460.1B into the
contractor's contracts.
4.2 Specific materials
29CFR1910.101(b) 4.2.1 Compressed Gas Cylinders
CGA P-1
4.2.1.1 The in-plant handling of all compressed gases in
cylinders, portable tanks, rail cars, or motor vehicle
cargo tanks shall be in accordance with the CGA
(see definition) P-1.
29CFR1910.253(b)(1)(i);
49CFR171-179
4.2.1.2 All portable cylinders used for the shipment of
compressed gases shall be constructed and
maintained in accordance with the regulations of
the U.S. Department of Transportation, 49CFR171-
179.
ANSI Z49.1;
29CFR1910.253(b)(1)(ii)
4.2.1.3 Compressed gas cylinders shall be legibly marked,
for the purpose of identifying the gas content, with
either the chemical or the trade name of the gas.
Such marking shall be by means of stenciling,
stamping, or labeling, and shall not be readily
removable. Whenever practical, the marking shall
be located on the shoulder of the cylinder.
18
DOE-HDBK-1139/3-2003
Sources10 Consolidated Requirements
CGA P-1, 3.4.2;
29CFR1926.350(a)(1)
4.2.1.4 Valve protection caps shall be in place and secured
when not in use or being transported.
ANSI Z49.1,10.8.3.8;
CGA P-1, 3.5;
CGA P-1, 3.5.2;
29CFR1926.350(a)(2);
29CFR1910.253(b)(1)(iv)
Section 29
4.2.1.5 Ropes, chains, or slings shall not be used to suspend
cylinders unless provisions have been made on the
cylinder for appropriate lifting attachments such as
lugs. Where appropriate lifting attachments have
not been provided on the cylinder, suitable cradles,
sling boards, platforms or pallets to hold the
cylinder shall be used for lifting. Lifting
attachments or other attachments shall never be
welded to cylinders. Cylinders shall not be hoisted
or transported by means of magnets or choker
slings.
29CFR1926.350(a)(3)
4.2.1.6 Cylinders shall be moved by tilting and rolling
them on their bottom edges. They shall not be
rolled in the horizontal position or dragged. They
shall not be intentionally dropped, struck, or
permitted to strike each other violently.
CGA P-1, 3.5;
29CFR1926.350(a)(4)
4.2.1.7 A suitable hand truck, forklift, cylinder pallet
system, or similar material-handling device shall∗
be used with the container properly secured to the
device. When powered vehicles transport
cylinders, they shall be secured in a vertical
position.
ANSI Z49.1, 10.8.3.7;
29CFR1926.350(a)(5)
4.2.1.8 Valve protection caps shall not be used for lifting
cylinders from one vertical position to another.
Bars shall not be used under valves or valve
protection caps to pry frozen cylinders loose.
Warm, not boiling, water shall be used to thaw
frozen cylinders loose.
ANSI Z49.1, 10.8.3.10;
29CFR1926.350(a)(6)
4.2.1.9 Unless cylinders are firmly secured on a special
carrier intended for this purpose, regulators shall be
removed from the cylinders and valve protection
caps put in place before cylinders are moved.
ANSI Z49.1, 10.8.3.10;
29CFR1926.350(a)(8)
4.2.1.10 When cylinders are moved at any time, the cylinder
valve shall be closed.
*The CGA Pamphlet uses the word “should.” Since the DOE incorporates the CGA documents by reference the
requirement may be interpreted as mandatory.
19
DOE-HDBK-1139/3-2003
Sources10 Consolidated Requirements
CGA P-1, 4.7.2
4.2.2 Cryogenic liquid containers - In addition to the requirements
listed above for other compressed gases, cryogenic liquids
must be moved by use of a four-wheeled hand truck
designed to move cryogenic liquefied gas containers with a
capacity greater than 20 gal (76L). Hand trucks must be
kept in good operating condition.
CGA G-1 4.2.3 Acetylene - The in-plant transfer of acetylene in cylinders
shall be in accordance with CGA G-1.
CGA G-1, 5.1.1
4.2.3.1 Acetylene shall be called by its proper name,
“Acetylene.” Acetylene shall not be referred to
merely by the word “Gas.”
CGA G-1, 5.2.1
4.2.3.2 When acetylene cylinders are moved, they should*
not be subjected to abnormal mechanical shocks
that might damage the cylinders, the valves, or the
fusible pressure relief devices. Care shall be
exercised to ensure that acetylene cylinders are not
dropped or permitted to strike each other violently.
CGA G-1, 5.2.2
4.2.3.3 Acetylene cylinders should* not be dropped while
being unloaded or loaded from a truck or dock.
[NOTE: Trucks with elevator tailgates provide a
very good means of unloading or loading acetylene
cylinders safely.]
CGA G-1, 5.2.3
4.2.3.4 When transporting acetylene cylinders by crane or
derrick, lifting magnets, slings, ropes or chains, or
any other device in which the cylinders themselves
form a part of the carrier should* never be used for
hoisting acetylene cylinders. When transporting
acetylene cylinders by crane, a platform, cage or
ladle should* be if will protect the cylinders from
damage and will keep them from falling out.
Section 30
CGA G-1, 5.2.4
4.2.3.5 A positive method such as chaining should* be
used in securing acetylene cylinders that are
standing upright. During movement, acetylene
cylinders shall not be transported when lying
horizontally with the valves unprotected in a
position that would allow the valves to collide with
stationary objects.
CGA G-1, 5.2.4 4.2.3.6 Acetylene cylinders should* never be dragged from
place to place.
20
DOE-HDBK-1139/3-2003
Sources10 Consolidated Requirements
CGA G-1, 5.2.5 4.2.3.7 Valves shall always be closed before acetylene
cylinders are moved.
CGA G-1, 5.2.5 4.2.3.8 Unless acetylene cylinders are to be moved while
secured in an upright position to a suitable hand
truck, pressure regulators should* be removed and
valve protection caps, if provided for in the
cylinder design, should* be attached.
*The CGA Pamphlet uses the word “should.” Since the DOE incorporates the CGA documents by reference the
requirement may be interpreted as mandatory.
5.0 Source Documents
ANSI, Z49.1 (1999), “Safety in Welding, Cutting, and Allied Processes”.
CGA G-1 (1996), “Compressed Gas Association General Requirements for Compressed Gases”.
CGA P-1 (2000), “Compressed Gas Association Requirements for Acetylene”.
DOE O 460.1A, “Packaging and Transportation Safety”.
DOE O 460.1B, “Packaging and Transportation Safety” [NOTE: This order, issued on 4/4/2003,
cancels the DOE O 460.1A].
29CFR1910.101, “Compressed Gases”.
29CFR1910.102, “Acetylene”.
29CFR1910.253, “Oxygen-Fuel Gas Welding and Cutting”.
29CFR1926.350, “Gas Welding and Cutting”.
40CFR302.4, “Listing of Hazardous Substances for the National Oil and Hazardous Substances
Pollution Contingency Plan”.
49CFR171-179, “Hazardous Materials Transportation”.
21
DOE-HDBK-1139/3-2003
INTENTIONALLY BLANK
22
DOE-HDBK-1139/3-2003
Chapter 5 - Chemical Storage
1.0 Introduction
This chapter identifies and consolidates existing user safety and health requirements found in DOE
and Federal chemical-related safety and health regulations and National Standards that address the
storage of chemicals (see definition) and chemical products (see definition). It specifically
consolidates requirements found in the American National Standards Institute (ANSI) Z49.1, the
Compressed Gas Association (CGA) G-1, and CGA P-1, National Fire Protection Association
(NFPA) 30, NFPA 45, NFPA 51, NFPA 55, NFPA 430, NFPA 432, the Occupational Safety and
Health Administration (OSHA) regulations found at 29CFR1910.6, 29CFR1910.106,
29CFR1910.134, 29CFR1910.253, 29CFR1926.350, and 29CFR1910.1200. It includes requirements
that are cited in either DOE O 440.1A or 29CFR1910.6 ("Incorporation by Reference") and technical
standards that are made mandatory by their specific reference within a regulation, rule or DOE Order.
State and local codes and requirements are NOT included. USDA regulations are NOT addressed
since the impact from these is considered to be negligible at DOE facilities. Similarly, EPA pesticide
regulations are NOT addressed in this document since most DOE sites do not routinely store
pesticides.
This chapter is intended to list chemical-related safety and health requirements and to consolidate
those that are overlapping and/or duplicative. The list of requirements includes “pointers” to the
sources of those requirements.
This document does NOT create any new or additional requirements.
2.0 Applicability
Section 31
This chapter applies to all locations that store chemicals or chemical products.
[NOTE: Throughout this document, the term “chemicals” is used to indicate chemicals
and/or chemical products as described in Section 3, below.]
This document does NOT apply to:
• chemicals stored in tanks with a greater than 735-pound water capacity;
• drums that have a greater than 55 gallon capacity;
• chemical distribution systems (see definition);
• storage containers attached to a system;
• waste chemical storage;
• the building or design of chemical storage areas [a design engineer who is acquainted with those
requirements should be consulted before a chemical storage facility is built or before an existing
facility is converted to chemical storage.]
Special laboratory requirements presented in this document apply to laboratories that are constructed
and operated in accordance with NFPA 45, "Standard on Fire Protection for Laboratories Using
Chemicals."
This chapter consolidates existing core safety and health requirements that all sites must follow when
engaged in chemical-related activities. The requirements included in this chapter come from sources
that have different safety purposes. As a result, some of these requirements may not always be
23
DOE-HDBK-1139/3-2003
applicable to the work being performed at an individual site or facility. It is the responsibility of each
site or facility to determine the applicability of specific requirements to their work and how they are
implemented. The reference sources for the requirements included in this chapter can be used to
determine the applicability of those requirements to the work being performed.
3.0 Definitions and Acronyms
See Glossary.
4.0 Requirements for Chemical Storage
Sources10 Consolidated Requirements
DOE O 440.1A;
[NOTE: The information that follows is a consolidation of existing Federal
safety and health requirements and National Standards that relate to the
storage of chemicals. It therefore contains "shall" statements that are taken
from, or based on "shall" statements in those existing requirements. While
NFPA and CGA requirements that are referenced here are not, in and of
themselves mandatory, they are made mandatory by OSHA regulation
29CFR1910.6, which incorporates them by reference. DOE O 440.1A
mandates compliance with OSHA regulations found in Title 29 of the Code
of Federal Regulations (CFR). NFPA and CGA requirements referenced
here are thereby made mandatory for DOE contractors through contracts
that include DOE O 440.1A. Please see the Introduction to this section of
the DOE Chemical Management Handbook for more information.]
4.1 General
NFPA 45, 7.2.3.3
4.1.1 Facilities shall be evaluated to determine chemical storage
limits, allowable chemical container storage sizes, and stacking
limits. Quantities of chemicals stored shall remain within those
limits.17
NFPA 430, 2.1.1;
NFPA 430, 2.10.1;
NFPA 432, 4.7.1
4.1.2 The identification or design of chemical storage areas (see
definition),or maintenance work on chemical storage areas shall
be reviewed.18
NFPA 430, 2.6.1
4.1.2.1 New facility design shall take into account the need for
containment to protect the environment from oxidizers,
fire suppression agents, and decomposition products.
NFPA 430, 2.6.2
4.1.2.2 Approval (see definition) of chemical storage areas shall
take into consideration the potential for large quantities
of smoke and toxic fumes, especially as storage affects
29CFR1910.6
Section 32
17 Facility chemical quantity limits stem primarily from the local fire and building codes. NFPA 45 may modify
these for laboratories, by local ordinances or by other codes that are specific to one particular class of chemicals
such as NFPA 30, "Flammable and Combustible Liquids".
18 There are restrictions and requirements for welding and cutting activities at locations where chemicals are used
and stored. Consult your local welding and cutting program to determine what these requirements are.
24
http://www.explorer.doe.gov:1776/cgi-bin/w3vdkhgw?qryUBAi2k9W_;doe-1350
http://www.nfpa.org/
DOE-HDBK-1139/3-2003
Sources10 Consolidated Requirements
manual fire fighting operations, building egress, and
evacuation of adjacent facilities.
NFPA 432, 4.7.2
4.1.2.3 Cutting and welding operations in areas where organic
peroxides are stored shall not be performed until all
organic peroxide formulations have been removed.
ANSI Z 49.1, 10.8.2.1;
CGA G-1, 4.2.14;
CGA P-1, 3.7.3.2;
NFPA 30, 4.7.4;
NFPA 51, 2.2.1;
NFPA 55, 7.1.3.2;
29CFR1910.253(b)(2)
(ii);
29CFR1926.350(a)(11)
4.1.3 Chemical storage areas shall be secured using physical or
administrative controls to prevent unauthorized entry. 19
CGA P-1, 4.2.1.5;
NFPA 55, 7.6.3.2:
NFPA 430, 2.9.2;
NFPA 432, 4.6
4.1.4 “No smoking” signs shall be posted at all entrances to areas
where oxidizers, organic peroxides, or flammable gases are
stored.
NFPA 30, 4.10;
NFPA 430, 2.9.1
4.1.5 Ignition sources such as open flames, smoking, spark producing
equipment, static electricity, and other hot sources shall not be
permitted in areas where chemicals are stored unless reviewed
and approved.20
NFPA 430, 2.2.3;
29CFR1910.1200(f)
4.1.6 All chemicals shall be properly labeled.
CGA P-1, 3.7.2;
NFPA 45, 7.2.3.4;
NFPA 55, 7.1.5.1.1;
4.1.7 Chemicals shall be stored compatibly and in a way to prevent
contact with incompatible materials. This includes preventing
liquids from flowing out of a chemical storage area into another
area where they may be exposed to incompatible materials.
19It is recommended that a graded approach be used in meeting this requirement.
20 Restrictions and requirements for welding and cutting activities at locations where chemicals are used and stored
are based on specific conditions. Consult your local facility welding and cutting program to determine what
requirements are applicable to specific activities and conditions at your site.
21This requirement is intended to keep chemicals safe during routine storage and during an upset condition such as a
fire. Therefore, chemicals that are only incompatible at elevated temperatures are still considered incompatible
during routine storage conditions due to the possibility of fire or other upset condition. This document does not
25
http://www.ansi.org/
http://www.cganet.com/
http://www.nfpa.org/
http://www.osha-slc.gov/OshStd_data/1910_0253.html
http://www.osha-slc.gov/OshStd_data/1926_0350.html
http://www.nfpa.org/
http://www.nfpa.org/
http://www.osha-slc.gov/OshStd_data/1910_1200.html
http://www.cganet.com/
http://www.nfpa.org/
DOE-HDBK-1139/3-2003
Sources10 Consolidated Requirements
NFPA 432, 2.3 4.1.7.1 All construction materials in a chemical storage area
shall be compatible with those chemicals being
stored.
NFPA 430, 2.4.2.1
4.1.7.2 Special care shall be taken to prevent the
contamination of chemicals in storage.
NFPA 430, 2.4.2.2
Section 33
4.1.7.3 When flammable and combustible liquids are stored
in segregated warehouses (see definition) with
oxidizers, they shall be separated from those
oxidizers by a distance of 25 ft. with dikes, drains, or
sloping floors present to prevent the flammable
liquids from encroaching on the separation.
NFPA 45, 7.2.3.5;
NFPA 45, 10.3.2
4.1.8 Chemicals that might become hazardous upon prolonged storage
shall be dated when first opened and evaluated for safety every 6
months thereafter.
NFPA 45, 7.2.3.5 4.1.8.1 Chemicals that are found to be unsafe and cannot be
made safe shall be disposed of safely and in
compliance with applicable requirements.
CGA G-1, 4.2.2;
CGA G-1, 4.2.6;
CGA G-1, 4.2.15;
CGA P-1, 4.2.1.3;
NFPA 30, 4.3;
NFPA 45, 7.2.3.6
NFPA 51, 2.2.2;
NFPA 51, 2.3.2;
NFPA 55, 6.17;
29CFR1910.106(d)(4)
(iv)
4.1.9 Indoor chemical storage areas shall have either natural or
mechanical ventilation designed to provide a minimum of six air
exchanges per hour and shall discharge the air a minimum of 50
ft. from any air intakes for air handling systems, air compressors,
etc.
[EXCEPTION: Under NFPA 30, 4.3 and NFPA 45, 7-2.3.6 this
requirement does not apply to flammable liquid storage
cabinets.]
NFPA 55, 3.-1.3.b;
29CFR1910.106(d)(4)
(iv)
4.1.9.1 A manual shutoff shall be provided outside the toxic
gas (see definition) and flammable/combustible
liquids storage areas adjacent to the entry door and
shall be labeled “Ventilation System Emergency
Shutoff.”
NFPA 55, 6.17.9
4.1.9.2 Exhaust ventilation shall not be recirculated within
any room or building.
intend to direct which compatibility scheme should be used. Each site or facility must determine for itself which
compatibility scheme they will use to implement this requirement.
26
http://www.nfpa.org/
http://www.nfpa.org/
http://www.nfpa.org/
http://www.ifci.org/
http://www.nfpa.org/
http://www.cganet.com/
http://www.nfpa.org/
http://www.osha-slc.gov/OshStd_data/1910_0106.html
http://www.osha-slc.gov/OshStd_data/1910_0106.html
http://www.nfpa.org/
DOE-HDBK-1139/3-2003
Sources10 Consolidated Requirements
NFPA 432, 4.9.1 4.1.10 Good housekeeping shall be maintained in areas where
chemicals are stored.
NFPA 30, 4.4.3.1;
NFPA 30, 4.5.1.2;
NFPA 30, 5.9.1;
29CFR1910.106(d)(5)
(i)
4.1.10.1 Aisles established for the movement or egress of
personnel shall be maintained clear of obstructions,
including stored chemicals.
NFPA 30, 4.7.4;
NFPA 430, 2.13.1;
NFPA 432, 4.-9.1
4.1.10.2 Accumulation of wastes, debris, weeds, and other
combustible materials shall be prohibited.
NFPA 430, 2.13.2;
NFPA 432, 4.9.2
4.1.10.3 Spilled chemicals and broken containers shall be
immediately managed using appropriate procedures.
NFPA 430, 2.13.3
4.1.10.4 Each used and empty container shall be stored in a
manner appropriate for the chemical that existed in
that container until it is disposed of or cleaned;
OR
stored in a detached or sprinklered area (see
definition) until disposed of or cleaned.
NFPA 430, 2.13.4
4.1.10.5 Storage operations shall be arranged to prevent the
accumulation of fugitive dust from the stored
chemical.
NFPA 432, 4.9.3
4.1.10.6 Specific disposal procedures shall be developed for
all areas where organic peroxides are stored.
NFPA 45, 7.2.3.1
4.1.11 Hazardous chemicals stored in the open in laboratory work
areas shall be kept to the minimum necessary for the work
being done.
NFPA 45, 8.1.6.5
4.2 Compressed Gases
[NOTE: In a laboratory a compressed gas cylinder shall be considered
“in use” if it is:
Section 34
a) connected through a regulator to deliver gas to a laboratory
operation; or
b) connected to a manifold being used to deliver gas to a laboratory
operation; or
c) a single cylinder secured alongside the cylinder in (a) above as the
reserve cylinder.]
CGA P-1, 3.7.1;
NFPA 55, 6.13.1
4.2.1 Hazard identification signs shall be placed at all entrances to
areas where compressed gas is stored.
27
http://www.nfpa.org/
http://www.nfpa.org/
http://www.osha-slc.gov/OshStd_data/1910_0106.html
http://www.nfpa.org/
http://www.nfpa.org/
http://www.nfpa.org/
http://www.nfpa.org/
http://www.nfpa.org/
http://www.nfpa.org/
http://www.nfpa.org/
DOE-HDBK-1139/3-2003
Sources10 Consolidated Requirements
NFPA 55, 6.1.13(A);
NFPA 704
4.2.1.1 Hazard ratings shall be assigned in accordance with
NFPA 704.
NFPA 55, 6.13.2.1 4.2.1.2 Signs shall not be obscured or removed.
CGA G-1, 4.2.9;
CGA P-1, 4.2.1.5;
NFPA 55, 6.13.2.2;
NFPA 55, 7.1.1;
NFPA 55, 7.6.3.2;
29CFR1910.253(b)(3)
(i)
4.2.1.3 Signs shall prohibit smoking or an open flame within 20
ft of where toxic, pyrophoric, oxidizing, or flammable
gases are stored.
ANSI Z49.1, 10.8.2.1;
CGA G-1, 4.2.4;
CGA P-1, 3.7.2;
CGA P-1, 3.7.3;
NFPA 51, 2.2.1;
NFPA 55, 7.1.5.4;
NFPA 55, 7.1.5.6;
NFPA 55, 7.1.5.9;
29CFR1926.350(a)(11)
4.2.2 Compressed gas cylinders shall be stored away from stairways,
elevators, exit routes, or gangways, in assigned places where
they will not be exposed to physical damage (for example,
damage from vehicles, damage from falling ice, etc.).
ANSI Z49.1, 10.8.2.1;
CGA G-1, 4.2.8;
CGA P-1, 3.7.4;
NFPA 55, 2.2.1.6;
NFPA 55, 7.1.3.4;
NFPA 55, 7.2.1.2;
29CFR1910.253(b)(2)
(ii)
4.2.3 Compressed gas cylinders shall be stored in an upright position
(see definition) with their valve protection caps in place and
secured to prevent cylinders from falling over or being knocked
over.
[EXCEPTION: All requirements cited here indicate that upright
storage is not required for lecture bottles or cylinders used in
self-contained breathing apparatus.]
NFPA 55, 6.6.2
4.2.4 Overhead cover for outdoor storage areas of compressed gases
shall be of non-combustible construction, open on three sides
and shall not be considered indoor storage.
NFPA 55, 7.1.5.3
4.2.4.1 Storage areas shall be kept clear of dry vegetation and
combustible materials for a minimum distance of 15 ft in
all directions.
CGA P-1, 3.7.3.1;
CGA G-1, 4.2.13;
NFPA 55, 2.1.6.1.b
4.2.4.2 Cylinders stored outdoors shall not be placed in direct
contact with the earth or on surfaces where water can
accumulate.
28
http://www.nfpa.org/
http://www.nfpa.org/
http://www.cganet.com/
http://www.nfpa.org/
http://www.osha-slc.gov/OshStd_data/1910_0253.html
http://www.ansi.org/
http://www.cganet.com/
http://www.nfpa.org/
http://www.osha-slc.gov/OshStd_data/1926_0350.html
http://www.ansi.org/
http://www.cganet.com/
http://www.nfpa.org/
http://www.osha-slc.gov/OshStd_data/1910_0253.html
http://www.nfpa.org/
http://www.nfpa.org/
http://www.cganet.com/
http://www.nfpa.org/
DOE-HDBK-1139/3-2003
Sources10 Consolidated Requirements
ANSI Z49.1, 10.8.1.8;
CGA G-1, 4.2.3;
CGA P-1, 3.7.2;
NFPA 51, 2.2.1;
NFPA 55, 6.6.1;
NFPA 55, 7.1.5.7
4.2.5 Compressed gas cylinders in storage shall not be heated above
125°F 22.
ANSI Z49.1, 10.8.2.2;
ANSI Z49.1, 10.8.2.3;
CGA G-1, 4.2.5;
CGA P-1, 4.2.4;
CGA P-1, 4.4.4;
NFPA 51, 2.2.1;
NFPA 51, 2.4.3;
NFPA 55, 7.1.5.2;
29CFR1926.350(a)(10;
29CFR1926.350(a)(11;
29CFR1910.253(b)(2)
(ii);
29CFR1910.253(b)(4)
(iii)
Section 35
4.2.6 Compressed gases in storage shall be segregated from
incompatible materials or combustibles in storage by either a
distance of 20 ft. or by a noncombustible partition with a fire
resistance rating of ½ hour and extending not less than 18 inches
above and to the sides of the stored material. The
noncombustible barrier shall be five feet high for those cylinders
that are less than three and a half feet tall.
[EXCEPTION: Under ANSI Z49.1 and NFPA 55 welding gases
located on a weld cart are considered to be "in use" and not in
storage. This is also consistent with the NFPA 45 definition of
"in use". Under these cited standards, then, this requirement
does not apply to oxygen and fuel gases on a weld cart.
Similarly, since oxygen and fuel gases on a weld cart are
considered to be "in use" under these standards, they also are
not required to be segregated from each other.]
[NOTE: The intent of these requirements is to discourage the
manufacture of unsafe weld carts and to prevent the practice of
removing welding gases from carts at the end of every work shift
or day, since this additional handling of the gases is considered
to be inherently more hazardous than is their temporary storage
on weld carts. It should be noted , however, that keeping oxygen
and fuel gases on a weld cart for excessively long periods
without any actual use would counter the intent of these
requirements.]
NFPA 55, 2.2.1.5 4.2.6.1 Flammable gas cylinders shall be stored a minimum
distance of 20 ft. from storage of flammable and
combustible liquids and solids.
29CFR1910.253(b)(3)
(i)
4.2.7 The inside storage of more than 2,000 standard cubic ft. (scf) of
flammable gas, or more than 300 pounds of liquefied petroleum
gas requires a separate room, compartment, or special storage
building.
22 This requirement includes the storage of compressed gas cylinders in direct sunlight where the sunlight may cause
the cylinder to overheat.
29
http://www.ansi.org/
http://www.cganet.com/
http://www.nfpa.org/
http://www.ansi.org/
http://www.cganet.com/
http://www.nfpa.org/
http://www.osha-slc.gov/OshStd_data/1926_0350.html
http://www.osha-slc.gov/OshStd_data/1910_0253.html
http://www.nfpa.org/
http://www.osha-slc.gov/OshStd_data/1910_0253.html
DOE-HDBK-1139/3-2003
Sources10 Consolidated Requirements
NFPA 55, Chapter 6
4.2.7.1 Indoor storage in one fire area of multiple groups of
cylinders containing flammable gas shall be performed
according to specifications in NFPA 55, Chapter 6.
NFPA 55, Chapter 6
4.2.8 Indoor storage in one fire area of multiple groups of cylinders
containing flammable gas shall be performed according to
specifications in NFPA 55, Chapter 6.
NFPA 55, 2.2.1.7.b
4.2.8.1 Groups may be separated from each other by masonry
walls with a fire resistance rating of 2 hours instead of
by a minimum distance.
NFPA 55, 2.2.1.8
4.2.8.2 Different flammable gases shall be allowed to be stored
together.
CGA G-1 4.2.6;
NFPA 51, 2.3.1;
NFPA 55, 2.2.2.1.a
4.2.9 Flammable gases with a collective volume between 2,501 and
5,000 scf, when stored indoors, shall be stored in rooms or
enclosures with a minimum 1-hour fire resistance rating.
NFPA 55, 2.2.2.2.1 4.2.9.1 Multiple groups of flammable gas cylinders in one
sprinklered fire area shall be stored a minimum of 100
ft. apart.
NFPA 51, 2.3.2;
NFPA 55, 2.2.3.1
4.2.10 Flammable gases with a collective volume greater than 5,000
scf, when stored indoors, shall be stored in a room or enclosure
with a minimum fire resistance of 2 hours.
Section 36
NFPA 51, 2.3.2;
NFPA 55, 2.2.3.2
4.2.10.1 Rooms used to store compressed gases shall be
sprinklered according to NFPA 13.
NFPA 55, 7.9.2.1;
NFPA 55, 7.9.6.5;
NFPA 55, 7.9.6.6
4.2.11 Indoor compressed gas storage areas that are used to store toxic
or highly toxic gases indoors shall be equipped with a
continuous monitoring system that would provide warning of
toxic gas concentrations that could present a hazard to life.
NFPA 55, 7.9.2.2;
NFPA 55,7.10.2
4.2.12 Outdoor storage areas of toxic gases shall be located 75 ft from
a line of property, public ways, places of assembly.
NFPA 55, 7.9 4.2.13 Other requirements for the storage of toxic and highly toxic
b f d i NFPA 55 7 929CFR1910.134 4.2.14 Where toxic gases are stored, a minimum of two NIOSH
approved self-contained breathing apparatus (SCBAs) shall be
kept available at all times for use in upset conditions. They
shall be cleaned and disinfected after each use, properly
maintained and stored, inspected at least monthly, and checked
for proper function before and after each use.
CGA P-1, 4.5.1.3;
CGA P-1, 4.5.1.4
4.2.14.1 NIOSH approved SCBAs shall also be provided where
protection is deemed necessary for entry into
atmospheres containing asphyxiant or corrosive gases.23
23 Any other respirator used must go through a NIOSH approval process for equivalency. This process must be
described in the facility’s written respiratory protection program.
30
http://www.nfpa.org/
http://www.nfpa.org/
http://www.nfpa.org/
http://www.nfpa.org/
http://www.cganet.com/
http://www.nfpa.org/
http://www.nfpa.org/
http://www.nfpa.org/
http://www.nfpa.org/
http://www.nfpa.org/
http://www.nfpa.org/
http://www.nfpa.org/
http://www.osha-slc.gov/OshStd_data/1910_0134.html
http://www.cganet.com/
DOE-HDBK-1139/3-2003
Sources10 Consolidated Requirements
CGA P-1, 4.5.1.4
4.2.14.2 One of the two SCBAs present shall be in the
possession of a qualified backup person present at the
scene when the SCBAs are being used.
4.3 Flammable and Combustible Liquids
NFPA 30, 4.4.3.3;
NFPA 30, 4.4.3.4;
29CFR1910.106(d)(4)
(v)
4.3.1 Aisles in areas that qualify as indoor liquid storage areas as per
NFPA 30, "Flammable and Combustible Liquids Code", shall
be 4 ft wide. Aisles in other flammable liquid storage areas
shall be 6 ft wide.
29CFR1910.106(d)(5)
(vi)(f)
4.3.1.1 Aisles at least 3 ft wide shall be provided where
necessary to allow for access to doors, windows, or
standpipe connections.
NFPA 30, 4.4.3.5;
NFPA 30, 4.5.14;
NFPA 30, 4.5.2.5
4.3.2 Class I flammable liquids (see definition) shall not be stored in
basement areas. Class II and Class IIIA combustible liquids
(see definition) shall not be stored in basement areas unless
those areas are protected with automatic sprinkler systems.
NFPA 30, 4.5.1.2
4.3.3 Class I flammable liquids shall not be stored such that a fire in
the liquid storage area would prevent egress from the area.
NFPA 30, 4.5.28.(a)
4.3.4 In general purpose warehouses, flammable and combustible
liquids shall not be stored in the same pile or on the same rack as
ordinary combustibles.
NFPA 30, 4.4.3.6;
NFPA 30, 4.4.3.7;
NFPA 30, 4.5.2.8.(b)
4.3.4.1 Ordinary combustibles, other than those used for
packaging flammable liquids, shall be stored a minimum
of 8 ft from flammable or combustible liquids.
NFPA 30, 4.5.2.8.(a)
4.3.4.2 Where flammable liquids are packaged together with
ordinary combustibles, such as in kits, storage shall be
considered on the basis of whichever commodity
predominates.
Section 37
NFPA 30, 4.4.3.7 4.3.5 Storage of empty or idle pallets inside a flammable liquid storage
area shall not exceed 2,500 ft.2 and 6 ft. in height.
NFPA 30, 4.-4.3.8;
29CFR1910.106(d)(5)
(vi)(c)
4.3.6 Containers in piles shall be stacked in such a manner as to
provide stability and to prevent excess stress on container walls.
31
http://www.cganet.com/
http://www.nfpa.org/
http://www.osha-slc.gov/OshStd_data/1910_0106.html
http://www.osha-slc.gov/OshStd_data/1910_0106.html
http://www.nfpa.org/
http://www.nfpa.org/
http://www.nfpa.org/
http://www.nfpa.org/
http://www.nfpa.org/
http://www.nfpa.org/
http://www.nfpa.org/
http://www.osha-slc.gov/OshStd_data/1910_0106.html
DOE-HDBK-1139/3-2003
Sources10 Consolidated Requirements
NFPA 4.4.3.8;
29CFR1910.106(d)(5)
(vi)(d)
4.3.6.1 Portable tanks stored over one tier high shall be nested
securely without dunnage.
NFPA 30, 4.4.3.8
4.3.6.2 Material handling equipment shall be suitable to handle
containers and tanks safely at the upper tier level.
NFPA 30, 4.4.4.2;
29CFR1910.106(d)(4)
(v)
4.3.7 Containers over 30 gallons in size that contain Class I or Class II
liquids shall not be stored over one level high in inside rooms
(see definition).
NFPA 30, 4.4.3.9;
29CFR1910.106(d)(5)
(vi)(e)
4.3.8 No stack of flammable or combustible liquids shall be closer
than 3 ft. to the nearest beam, chord, or other construction, and
shall be 3 ft. below sprinkler deflectors, discharge orifices of
water spray, or other overhead fire protection systems.
NFPA 30, 4.9;
29CFR1910.106(d)(7)
(i)
4.3.9 Suitable fire control devices shall be available at locations where
flammable and combustible liquids are stored.
29CFR1910.106(d)(7)
(i)(a);
29CFR1910.106(d)(7)
(i)(b)
4.3.10 At least one portable fire extinguisher having a rating of not less
than 40-B units shall be located outside but not more than 10 ft.
from any door to a flammable and combustible liquids storage
room or any area where Class I or Class II liquids are stored.
NFPA 30, 4.10.1;
29CFR1910.106(d)(7)
(iv)
4.3.11 Water reactive materials (see definition) shall not be stored in
the same area with flammable or combustible liquids.24
NFPA 30, 4.5.2.3
4.3.12 Class I and Class II liquids in plastic containers shall only be
stored in flammable liquids storage rooms (see definition) or
flammable liquid storage cabinets.
NFPA 30, 4.5.1.3
4.3.13 Liquids used for building maintenance, painting, or other similar
infrequent maintenance purposes shall be permitted to be stored
temporarily in closed containers outside of flammable liquids
storage cabinets or flammable liquids storage areas, if the
amount stored does not exceed a 10-day supply at anticipated
use rates.
24 This requirement is intended to protect water reactive chemicals from exposure to water in water based fire
suppression systems that may be used where flammable liquids are stored. Spraying water on a water reactive
material during an upset condition could increase the severity and danger of the upset condition. While not required,
consideration should be given to applying a similar restriction in oxidizer storage areas. See section 4.4.2.
32
http://www.nfpa.org/
http://www.osha-slc.gov/OshStd_data/1910_0106.html
http://www.nfpa.org/
http://www.nfpa.org/
http://www.osha-slc.gov/OshStd_data/1910_0106.html
http://www.nfpa.org/
http://www.osha-slc.gov/OshStd_data/1910_0106.html
http://www.nfpa.org/
http://www.osha-slc.gov/OshStd_data/1910_0106.html
http://www.osha-slc.gov/OshStd_data/1910_0106.html
http://www.nfpa.org/
http://www.osha-slc.gov/OshStd_data/1910_0106.html
http://www.nfpa.org/
http://www.nfpa.org/
Section 38
DOE-HDBK-1139/3-2003
Sources10 Consolidated Requirements
NFPA 45, 2.2.1(a);
29CFR1910.106(e)(2)
(ii)(b)(1)
4.3.14 The quantity of flammable and combustible liquids that can be
stored outside a flammable liquids storage room or flammable
liquids storage cabinet is as follows25:
a. 25 gallons of Class IA liquids in containers per fire area
(see definition), and
b. 120 gallons of Class IB, IC, II, or IIIA liquids in containers
per fire area.
OR
a. 570 L (150 gallons) of Class I liquids in sprinklered
laboratory units (see definition), and
b. 757 L (200 gallons) of Class I, II, and IIIA liquids in
sprinklered laboratory units.
[NOTE: Second set of “a.” and “b.” refers to Class C
laboratories only. See NFPA 45 for proper quantities for Class
A, B and D laboratories.]
NFPA 45, 2.2.1.4
4.3.15 With the exception of Section 4.3.12 and 4.3.13, all Class I, II,
and IIIA flammable and combustible liquids not in a flammable
liquids storage room shall be stored in flammable liquid storage
cabinets when not in use.
NFPA 30, 4.3.1 4.3.15.1 The total quantity of liquids shall not exceed 120
gallons per cabinet.
NFPA 30, 4.3
4.3.15.2 Flammable liquid storage cabinets shall be FM
approved or UL listed or built in accordance with
NFPA 30.
NFPA 30, 4.3.2 4.3.15.3 Not more than three flammable liquid storage cabinets
are allowed in any one fire area, except as follows:
[EXCEPTION 1: In an industrial occupancy,
additional groups of storage cabinets can be located in
any fire area if a minimum100-foot separation is
maintained.
EXCEPTION 2: In an industrial occupancy that is
protected by an automatic fire sprinkler system, the
number of cabinets can be increased to 6 in a group.
EXCEPTION 3: In a laboratory fire area, the number
of flammable liquid storage cabinets is not limited;
however, the total quantity of flammable and
combustible liquids is limited to the quantities as
defined in 4.3.14.4.]
25 Numerous types of storage areas (e.g., cutoff storage rooms, mercantile storage areas, inside storage rooms, etc.)
can exist. Storage limits for laboratories have been defined in 4.3.14. There are many other types of storage areas
and limits for each of these are not included in this document. A fire protection engineer should be consulted to
determine storage limits for these other storage areas.
33
http://www.nfpa.org/
http://www.nfpa.org/
http://www.nfpa.org/
http://www.nfpa.org/
DOE-HDBK-1139/3-2003
Sources10 Consolidated Requirements
NFPA 45, 2.2.1.3
4.3.15.4 The maximum amount of Class I, II, and IIIA
flammable and combustible liquids that can be stored in
a laboratory fire area is 400 gallons of which the
maximum amount of Class I flammable liquids is 300
gallons.
NFPA 30, 4.6.4
4.3.16 Sites for outdoor storage lockers (see definition) shall be
reviewed to ensure proper placement, separation, etc.
NFPA 30, 4.6.4 4.3.16.1 Multiple outdoor storage lockers at a given site shall be
separated according to requirements in NFPA 30.
NFPA 30, 4.6.4.4.1
4.3.16.2 In outdoor storage lockers, containers in their original
shipping packages shall be permitted to be stored either
on pallets or in piles, while unpacked containers shall
be stored on shelves or on the floor.
NFPA 30, 4.6.4.4.2
4.3.16.3 No other flammable or combustible materials shall be
stored at designated outdoor storage locker sites.
NFPA 30, 4.6.4.4.3;
NFPA 704
4.3.16.4 Outdoor storage lockers shall be placarded according to
NFPA 704.
4.4 Oxidizers
Section 39
[NOTE: Additional requirements can be found in NFPA 430, "Code for
Storage of Solid and Liquid Oxidizers", when quantities exceed 4,000
pounds of Class 1 oxidizer (see definition), 1,000 pounds of Class 2
Oxidizer (see definition), 200 pounds of Class 3 Oxidizer (see
definition), or 10 pounds of Class 4 Oxidizer (see definition). Oxidizer
classes are defined in NFPA 430".]
NFPA 430, 2.2.1
4.4.1 Oxidizer storage areas shall be conspicuously identified with the
words “Class (appropriate classification number) Oxidizers.”
NFPA 430, 2.2.2
4.4.1.1 Areas used to store oxidizers of different classes shall be
marked as containing the most severe hazard.
NFPA 430, 2.11.6 4.4.2 Water based manual fire fighting equipment shall be used in
oxidizer storage areas.26
26Oxidizer storage areas and flammable liquids storage areas require water- based fire suppression systems. While
there are no requirements to keep water reactive materials away from oxidizers, when storing oxidizers,
consideration should be given to the additional hazard posed by the presence of water reactive materials when water
suppression systems are activated.
34
http://www.nfpa.org/
http://www.nfpa.org/
http://www.nfpa.org/
http://www.nfpa.org/
http://www.nfpa.org/
http://www.nfpa.org/
http://www.nfpa.org/
http://www.nfpa.org/
http://www.nfpa.org/
DOE-HDBK-1139/3-2003
Sources10 Consolidated Requirements
NFPA 430, 2.11.6.1
4.4.2.1 The placement and use of dry chemical extinguishers
containing ammonium compounds (Class ABC) shall be
prohibited in oxidizer storage areas where oxidizers that
can release chlorine are stored.
NFPA 430, 2.11.6.2
4.4.2.2 Halon extinguishers shall not be used in oxidizer storage
areas.
NFPA 430, 2.12
4.4.3 Combustible construction materials that could come into contact
with oxidizers shall be coated with a compatible material to
prevent their impregnation with the oxidizers.
NFPA 430, 2.13.5
4.4.4 Absorptive packing materials, wooden pallets, etc., that are
exposed to water containing oxidizers or that contain water
soluble oxidizers, and are exposed to water shall be immediately
relocated to a safe outside area and properly disposed of.
NFPA 430, 2.8.1
4.4.5 Oxidizers shall not be stored where they can be heated to within
25°F of their decomposition temperature or above 120°F,
whichever is lower.27
4.5 Organic Peroxides
NFPA 432, 4.1
4.5.1 Chemical storage areas used for the storage of organic peroxides
shall be conspicuously identified with the words “Organic
Peroxides” and by the class.
NFPA 432, 4.1.1
4.5.1.1 Areas used to store organic peroxides of different classes
per NFPA 432, shall be marked as containing the most
severe hazard.
NFPA 432, 4.1.2
4.5.1.2 Packages containing organic peroxide formulations shall
be individually marked with chemical name and other
pertinent information to allow proper classification.
NFPA 432, 4.1.3
4.5.1.3 Packages of organic peroxides that require temperature
control shall be marked with the recommended storage
range.
NFPA 432, 4.11.2
4.5.2 A clear space of at least 2 ft. shall be maintained between organic
peroxide storage and uninsulated metal walls.
27 Attention should be used to ensure that oxidizers stored in direct sunlight are not heated above allowed
temperatures by radiant heating.
35
http://www.nfpa.org/
http://www.nfpa.org/
http://www.nfpa.org/
http://www.nfpa.org/
http://www.nfpa.org/
http://www.nfpa.org/
http://www.nfpa.org/
http://www.nfpa.org/
http://www.nfpa.org/
http://www.nfpa.org/
Section 40
DOE-HDBK-1139/3-2003
Sources10 Consolidated Requirements
NFPA 432, 4.11.3.1 4.5.3 Incompatible materials and flammable liquids shall not be stored
within 25 ft. of organic peroxide formulations in chemical storage
areas.
[NOTE: Organic peroxide formulations that are also classified
as flammable liquids may be stored with other organic peroxide
formulations.]
NFPA 432, 4.11.3.2
4.5.3.1 If a 25-foot separation cannot be maintained, then a 1-
hour, liquid-tight fire barrier shall be permitted.
NFPA 432, 4.11.4
4.5.4 Only closed containers shall be permitted in an organic peroxide
storage area.
NFPA 432, 4.11.6
4.5.5 Fifty-five-gallon drums of organic peroxide formulations shall
not be stacked.
NFPA 432, 4.4.1
4.5.6 Storage temperatures in chemical storage areas shall be
maintained within the recommended storage temperature range
for the materials being stored.28
NFPA 432, 4.4.2
4.5.6.1 High and low temperature switches, as applicable, shall
be provided in addition to normal temperature controls.
These switches shall actuate an alarm to ensure prompt
response.
NFPA 432, 4.4.3
4.5.6.2 Heating systems shall use low-pressure steam, hot water,
or indirectly heated air; cooling systems shall not use
direct expansion of a flammable gas.
NFPA 432, 4.4.4
4.5.6.3 Heating or cooling pipes and other heat transfer devices
shall not come into contact with organic peroxide
containers to cause their overheating or cooling.
NFPA 432, 4.5.2
4.5.7 Refrigerators used for storing organic peroxide formulations
shall be Class I, Group D, and Division I (i.e., "explosion-
proof", as defined in Article 500 of NFPA 70.
NFPA 432, 4.5.3
4.5.8 Unventilated, unrefrigerated storage cabinets used for the
storage of organic peroxides shall be considered Class I,
Division I as defined in Article 500 of NFPA 70.
NFPA 432, 4.5.4
4.5.9 Ventilated storage cabinets shall be considered Class I, Division
II as defined in Article 500 of NFPA 70. Ventilation must be a
minimum of 1 cubic foot/minute/square foot of floor area.
28 Attention should be used to ensure that organic peroxides stored in direct sunlight are not heated above allowed temperatures
by radiant heating.
36
http://www.nfpa.org/
http://www.nfpa.org/
http://www.nfpa.org/
http://www.nfpa.org/
http://www.nfpa.org/
http://www.nfpa.org/
http://www.nfpa.org/
http://www.nfpa.org/
http://www.nfpa.org/
DOE-HDBK-1139/3-2003
5.0 Source Documents
ANSI Z49.1 (1999), "Safety in Welding, Cutting and Allied Processes".
CGA G-1 (1996), "Acetylene"
CGA P-1 (2000), "Safe Handling of Compressed Gases in Containers".
DOE O 440.1A, "Worker Protection Management For DOE Federal And Contractor Employees".
NFPA 30 (2000), "Flammable and Combustible Liquids Code".
NFPA 45 (2000), "Standard on Fire Protection for Laboratories Using Chemicals".
NFPA 51 (1997), "Standard for the Design and Installation of Oxygen-Fuel Gas Systems".
NFPA 55 (2003), "Standard for the Storage, Use, and Handling of Compressed and Liquefied Gases
in Portable Cylinders".
NFPA 430 (2000), "Code for the Storage of Liquid and Solid Oxidizers".
NFPA 432 (2002), “Code for the Storage of Organic Peroxide Formulations”.
NFPA 704 (2001), "Identification of the Hazards of Materials for Emergency Response".
29CFR1910.6, "Incorporation by Reference".
29CFR1910.106, "Flammable and Combustible Liquids".
29CFR1910.134, "Respiratory Protection".
29CFR1910.253, "Oxygen-Fuel Gas Welding and Cutting".
29CFR1910.1200, "Hazard Communication".
29CFR1926.350, "Gas Welding and Cutting".
Section 41
37
DOE-HDBK-1139/3-2003
INTENTIONALLY BLANK
38
DOE-HDBK-1139/3-2003
Chapter 6 - Hazard Control
1.0 Introduction
This chapter identifies and consolidates existing user safety and health requirements found in DOE
and Federal chemical-related safety and health regulations and National Standards that address the
control of hazards associated with activities involving chemicals (see definition) and chemical
products (see definition). State and local codes and requirements are NOT included. This chapter
specifically consolidates requirements found in the National Fire Protection Association (NFPA), the
American National Standards Institute (ANSI), the Compressed Gas Association (CGA), the
Occupational Safety and Health Administration (OSHA), and certain Environmental Protection
Agency (EPA) regulations and Department of Energy (DOE) Rules and Orders, including technical
standards that are made mandatory by their specific reference within a regulation, rule or DOE Order.
This chapter is intended to list chemical-related safety and health requirements and to consolidate
those that are overlapping and/or duplicative. The list of requirements includes “pointers” to the
sources of those requirements.
This document does NOT create any new or additional requirements.
2.0 Applicability
The information presented here applies to all locations that use chemicals or chemical products.
[NOTE: Throughout this document, the term “chemicals” is used to indicate chemicals and/or
chemical products as described in Section 3, below.] This chapter is intended only to address
chemical hazard control requirements applicable to chemical user activities. It consolidates existing,
core safety and health requirements that all sites must follow when engaged in chemical-related
activities.
The requirements included in this chapter come from sources that have different safety purposes. As
a result, some of these requirements may not always be applicable to the work being performed at an
individual site or facility. It is the responsibility of each user to determine the applicability of specific
requirements to their work and how they are implemented. The reference sources for the
requirements included in this chapter can be used to determine the applicability of those requirements
to the work being performed.
3.0 Definitions and Acronyms
See Glossary.
4.0 Requirements for Hazard Control
Sources10 Consolidated Requirements
4.1 General (Applicable to all operations/activities involving
chemicals)
39
DOE-HDBK-1139/3-2003
Sources 10 Consolidated Requirements
DOE O 440.1A, sec. 4(j)
48CFR970.5204, 2(b)(6)29
4.1.1 A hazard prevention/abatement process shall be
implemented to ensure that all identified hazards are
managed through final abatement or control.
DOE O 440.1A, sec. 4(j)(1)
4.1.1.1 Controls shall be incorporated into facility design
and procedures.
DOE O 440.1A, sec. 4(j)(2)
4.1.1.2 Abatement actions shall be prioritized based on
risks to workers and promptly implemented for
existing hazards identified in the workplace.
Workers shall be protected immediately from
imminent danger conditions.
DOE O 440.1A, sec. 4(j)(4);
29CFR1910.120(g)(1);
29CFR1910.134(a);
29CFR1910.1450(i)
4.1.1.3 Hazard controls shall be selected using the
following hierarchy: (1) Elimination of the hazard
through practices such as chemical substitution or
process modification; (2) Engineering controls; (3)
Work practices and administrative controls; and (4)
Personal protective equipment
Section 42
DOE O 440.1A, sec. (4)(e);
29CFR1910.132(d)
4.1.1.4 Workers shall be informed of and involved in
identifying and controlling workplace hazards,
including decisions on selection of PPE.
DOE O 440.1A, Attachment
1, sec. 5;
DOE O 440.1A, Attachment
2;
29CFR1910.1450(c) and (e)
4.1.2 An industrial hygiene program shall be implemented by
professionally- and technically-qualified industrial
hygienists to reduce the risk of work-related disease or
illness in all chemical operations including laboratories.
The program shall specify appropriate process modification
(including chemical substitution), engineering,
administrative, work practice, and/or personal protective
control methods to limit exposures to hazardous materials
to acceptable levels.
4.2 Hazardous Operations30 (see definition)
DOE O 420.1A, 4.2.1;
DOE-STD-1120-98;
DOE-STD-3011-94;
DOE-STD-3016-99
10CFR830 Subpart B,
204(b)(4);
4.2.1 An appropriate combination of chemical substitution,
engineering and administrative controls (including the
appropriate application of detection methodologies), safe
work practices, and PPE shall be implemented to
prevent/mitigate adverse impacts from hazardous chemicals
on workers, the public, or environment.
29CFR1910.1200(h)(1- 3);
DOE-STD-3009-94;
29 This requirement of the DOE Acquisition Regulations (DEAR, ES&H Clause) requires development and implementation of
controls as part of an overall documented safety management system.
30 The requirements for hazardous operations are in addition to requirements associated with those activities specified in Section
4.1.
40
http://www.explorer.doe.gov/
http://www.explorer.doe.gov/
http://www.explorer.doe.gov/
http://www.explorer.doe.gov/
http://www.osha-slc.gov/OshStd_data/1910_1450.html
http://www.explorer.doe.gov/
http://www.osha-slc.gov/OshStd_data/1910_0132.html
http://www.explorer.doe.gov/
http://www.explorer.doe.gov/
http://www.osha-slc.gov/OshStd_data/1910_1450.html
http://www.explorer.doe.gov/
http://tis.eh.doe.gov/nsps/ourdocs/rules.html
DOE-HDBK-1139/3-2003
Sources10 Consolidated Requirements
10CFR850.25(c);
29CFR1910.119(e)(3)(iii);
29CFR1910.120(c)(1);
29CFR1910.120(d) and
(g)(1);
40CFR68.67(c)(3);
40CFR1502.14;
40CFR1502.16
DOE O 420.1A, 4.2.1(3);
29CFR1910.119(f);
40CFR68.69(b)
4.2.1.1 Written operating procedures shall be developed
that include (1) precautions necessary to prevent
worker exposure to chemical hazards, e.g.,
chemical substitution/process change, engineering
controls, administrative controls and PPE); (2)
control measures to be taken if physical contact or
airborne exposure to chemical hazards can occur;
(3) fire safety procedures that govern the use and
storage of combustible, flammable and other
hazardous materials; (4) measures for controlling
hazardous chemical inventory; and (5) any
required safety systems and their functions.
29CFR1910.119(j);
40CFR68.73
4.2.1.2 Process safety equipment and engineering controls
shall have (1) written procedures on maintaining
their integrity; (2) training of personnel involved
in process maintenance activities; (3) documented
inspection and testing that meets manufacturer’s
recommendations and good engineering practices;
(4) prompt correction of deficiencies that are
outside of acceptable operating limits;
29CFR1910.119(f)(4);
29CFR1910.120(d) and
(g)(1);
40CFR68.69(d)
4.2.1.3 Safe work practices shall be implemented such as
lockout/tagout; permitted confined space entry;
removal of non-essential personnel from
hazardous material areas; and site and building
access control.
Section 43
29CFR1910.119(k)
40CFR68.85
4.2.1.4 Hot work operations (e.g., cutting, welding,
brazing) conducted on or near hazardous
operations shall be in accordance with fire
prevention and protection requirements in
29CFR1910.252(a) and shall have a permit that
authorizes the work to be performed.
41
http://tis.eh.doe.gov/be/webdoc4.html-ssi
http://www.osha-slc.gov/OshStd_data/1910_0119.html
http://www.osha-slc.gov/OshStd_data/1910_0120.html
http://www.osha-slc.gov/OshStd_data/1910_0120.html
http://www.access.gpo.gov/nara/cfr/cfrhtml_00/Title_40/40cfr68_00.html
http://ceq.eh.doe.gov/nepa/regs/ceq/1502.htm
http://ceq.eh.doe.gov/nepa/regs/ceq/1502.htm
http://www.explorer.doe.gov/
http://www.osha-slc.gov/OshStd_data/1910_0119.html
http://www.access.gpo.gov/nara/cfr/cfrhtml_00/Title_40/40cfr68_00.html
http://www.osha-slc.gov/OshStd_data/1910_0119.html
http://www.access.gpo.gov/nara/cfr/cfrhtml_00/Title_40/40cfr68_00.html
http://www.osha-slc.gov/OshStd_data/1910_0119.html
http://www.osha-slc.gov/OshStd_data/1910_0120.html
http://www.access.gpo.gov/nara/cfr/cfrhtml_00/Title_40/40cfr68_00.html
http://www.osha-slc.gov/OshStd_data/1910_0119.html
http://www.access.gpo.gov/nara/cfr/cfrhtml_00/Title_40/40cfr68_00.html
DOE-HDBK-1139/3-2003
Sources10 Consolidated Requirements
4.3 Requirements for Laboratory Use of Chemicals
29CFR1910.1450(e)(3) 4.3.1 A chemical hygiene plan shall be prepared for laboratory
operations that includes safe operating procedures, hazard
control measures, operability requirements for protective
equipment, provisions for employee training and medical
consultations, designation of individuals responsible for
implementing the plan, and provisions for employee
protection against extremely hazardous substances.
29CFR1910.1450(e)(3)(viii) 4.3.1.1 Extremely hazardous substances (see definition)
include “select carcinogens,” reproductive toxins,
and substances with a degree of acute toxicity.
Provisions, where appropriate, shall include:
• Establishment of a designated area
• Use of containment devices
• Procedures for safe removal of contaminated
waste
• Decontamination procedures
NFPA 45, 2.2.1.1-4 4.3.2 Fire Hazard Classification – Laboratory units shall be
classified Class A (High Fire Hazard), Class B (Moderate
fire Hazard), Class C (Low fire Hazard), or Class D
(Minimal Fire Hazard), according to the quantities of
flammable and combustible liquids present in the lab
(outside of the storage area) as specified in Table 2.2.1(a)
and Table 2.2.1(b) in NFPA 45.
NFPA 45, 2.2.1.5
4.3.2.1 For the purposes of determining laboratory fire hazard
classification and the use of tables 2.2.1(a) and (b),,
quantities of liquefied flammable gases shall be
treated as if they were Class I flammable liquids (see
definition); that is, 4L (1.1gal) of liquefied flammable
gas is to be considered equivalent to 4L (1.1 gal) of
Class I flammable liquid.
NFPA 45, 4.1-4.6
4.3.3 All laboratory units shall be provided with fire protection
appropriate to the fire hazard, including: automatic fire
extinguishing systems, standpipe and hose systems,
portable fire extinguishers, fire alarm systems, fire
prevention programs, and emergency plans.
42
DOE-HDBK-1139/3-2003
Sources10 Consolidated Requirements
NFPA 45, 5.1 4.3.4 If a laboratory contains explosion hazards, as defined in
sections 2.3.1 and 2.3.2 of NFPA 45, protection shall be
provided by one or more of the following:
• limiting the amounts of flammable or reactive chemicals
Section 44
or chemicals with unknown characteristics used in or
exposed by experiments;
• special preventive or protective measures for the
reactions, equipment, or materials themselves (e.g.,
high-speed fire detection with deluge sprinklers,
explosion-resistant equipment or enclosures);
• remote control equipment;
• sufficient deflagration venting in outside walls; and,
• conducting experiments in a detached or isolated
building, or outdoors.
NFPA 45, 5.2 -5.5 4.3.4.1 Other explosion hazard protection may be
considered including:
• Explosion-resistant construction;
• Explosion venting;
• Controlled access to laboratory; and,
• Regularly scheduled inspection and maintenance
NFPA 45, 7.2 4.3.5 Handling of laboratory chemicals
NFPA 45, 7.2.1.1 4.3.5.1 Chemicals shall not be brought into a laboratory
work area unless design, construction, and fire
protection of the facilities are commensurate with
the quantities and hazards of the chemicals
involved.
NFPA 45, 7.2.2.1 4.3.5.2 Receiving, transporting, unpacking, and dispensing
of chemicals and other hazardous materials shall be
carried out by trained personnel in such locations
and in such a manner as to minimize hazards from
flammable, reactive, or toxic materials.
NFPA 45, 7.2.2.5 4.3.5.3 Class I liquids shall not be stored or transferred
from one vessel to another in any access corridor,
open plan buildings, or ancillary spaces
unprotected from the exit access corridor.
NFPA 45, 7.2.2.6 4.3.5.4 Transfer of Class I liquids to smaller containers
from bulk stock containers not exceeding 19L (5
gal.) in capacity shall be performed as follows:
• In a laboratory hood;
• In an area provided with ventilation adequate to
prevent accumulations of flammable vapor/air
mixtures from exceeding 25 percent of the lower
flammable limit;
• In a liquid storage area specifically designed and
43
DOE-HDBK-1139/3-2003
Sources10 Consolidated Requirements
protected for dispensing Class I flammable
liquids that meet the requirements of NFPA 30.
NFPA 45, 7.2.2.7 4.3.5.5 Transfer of Class I liquids from containers of 19L
(5 gal.) or more capacity shall be carried out as
follows:
• In a separate building; OR
• In a liquid storage area specifically designed for
dispensing Class I flammable liquids that meet
the requirements of NFPA 30.
NFPA 45, 7.2.2.8 4.3.5.6 Class I liquids shall not be transferred between
conductive containers of greater than 4L (1.1 gal.)
capacity unless the containers are electrically
interconnected by direct bonding or indirect
bonding through a common grounding system.
When dispensing Class I liquids involves
nonconductive containers larger than 4L (1.1gal.),
which can be difficult to bond or ground, special
dispensing procedures commensurate with the
electrical characteristics of the liquid shall be
developed and implemented.
NFPA 45, 7.2.3.2 4.3.5.7 Individual containers of flammable or combustible
liquids shall not exceed the capacities listed in
NFPA 45, Table 7.2.3.2.
NFPA 45, 7.3-5 4.3.5.8 The quantity of flammable solids, solid or liquid
oxidizers, or peroxides allowed shall be limited to
the minimum quantity necessary to perform the
work being done. Handling of materials shall
conform to the manufacturers’ recommendations.
NFPA 45, 8.1.4-6 4.3.6 Laboratory Compressed Gases – In addition to the
requirements in Section 4.3, above, compressed gas
cylinders in laboratories must also meet the
requirements in sections 4.3.6.1-5 below.
Section 45
NFPA 45, 8.1.4.1 4.3.6.1 Lecture bottle-sized cylinders of the following
gases located in laboratory units shall be kept in a
continuously mechanically ventilated hood or other
continuously mechanically ventilated enclosure:
(1) All gases that have an NFPA 45 Health Hazard
Ratings of 3 or 4;
(2) All gases that have a NFPA 45 Health Hazard
Rating of 2 without physiological warning
properties; and
(3) Pyrophoric gases
44
DOE-HDBK-1139/3-2003
Sources10 Consolidated Requirements
NFPA 45, 8.1.4.2 4.3.6.2 Cylinders of gases that are greater than lecture
bottle size and have NFPA 45 Health Hazard
Ratings of 3 or 4, and cylinders of gases that have a
Health Hazard Rating of 2 without physiological
warning properties that are located in laboratory
units shall meet both the following conditions:
(1) Storage in approved continuously mechanically
ventilated gas cabinets; and
(2) Compliance with the requirements of Chapter
3, Toxic Gases, of NFPA 55.
NFPA 45, 8.1.4.3 4.3.6.3 Cylinders of pyrophoric gases that are greater than
lecture bottle size that are located in laboratory
units shall be kept in approved continuously
mechanically ventilated, sprinklered gas cabinets.
NFPA 45, 8.1.5.2.1-2
4.3.6.4 Regulator systems in laboratory operations shall be
equipped with two gauges, either on the regulator
or remote from the regulator, installed as to show
both the cylinder pressure and the outlet pressure.
When the source cylinder is outside of the
laboratory, a station regulator and gauge shall be
installed at the point of use to show the outlet
pressure.
NFPA 45 8.1.6.3-4 4.3.6.5 Only in use cylinders shall be allowed in the
immediate work area. A compressed gas cylinder
shall be considered in use when it is:
(1) connected through a regulator to deliver gas;
or
(2) connected to a manifold being used to deliver
gas; or
(3) a single cylinder secured as a reserve cylinder
alongside the cylinder described in (1).
NFPA 45, 8.1.6.5 4.3.6.6 The maximum internal volume (water volume) of
all cylinders in each of the listed classifications, in
use in the laboratory work area, shall comply with
the following [based on internal cylinder volume at
21°, 101 kPa (70°F, 1 atm)]:
(a) Maximum Quantity of Flammable Gases.
(1) For a laboratory work areas of 500 ft² or
less, the internal cylinder volume in
standard cubic feet equals 6.0.
(2) For a laboratory work area greater than
500 ft² or less, the internal cylinder
volume is 0.012 ft³ per ft² lab work area.
45
DOE-HDBK-1139/3-2003
Sources10 Consolidated Requirements
(b) Maximum Quantity of Oxidizing Gases.
(1) For a laboratory work area of 500 ft² or
less, the internal cylinder volume in
standard cubic feet equals 6.0.
(2) For a laboratory work area greater than
500 ft ² or less, the internal cylinder
volume is 0.012³ ft per ft² lab work area.
(c) Maximum Quantity of Liquefied Flammable
Gases.
(1) For a laboratory work area of 500 ft² or
less, the internal cylinder volume in
standard cubic feet equals 1.2.
(2) For a laboratory work area greater than
500 ft², the internal cylinder volume is
0.0018 ft³ per ft² labor work area.
(d) Maximum Quantity of Health Hazard 3 or 4
gases.
(1) For a laboratory work area of 500 ft² or
less, the internal cylinder volume in
standard cubic feet equals 0.3.
(2) For a laboratory work area greater than
500 ft ², the internal cylinder volume is
0.0006 ft³ per ft² lab work area.
NFPA 45, 9.1.2-9.2.7.2 4.3.7 Laboratory Operations and Apparatus – NFPA 45 contains
Section 46
additional laboratory safety controls covering:
• Operations: heating, distillation, other separation
procedures, drying, mixing and grinding, and
operations involving reactions at temperatures and
pressures above and below ambient conditions.
• Apparatus: refrigeration and cooling equipment,
heating equipment, pressure equipment, and analytical
instruments.
4.4 Combustible Liquids
NFPA 30, 5.2 4.4.1 Operations involving flammable or combustible liquids
shall be located and operated so that they do not
constitute a significant fire or explosion hazard to life or
property.
NFPA 30, 5.9.1;
29CFR1910.106(b)(6);
29CFR1910.106(e)(6)(1)
4.4.2 Precautions shall be taken to prevent the unintentional
ignition of flammable vapors.
46
DOE-HDBK-1139/3-2003
Sources10 Consolidated Requirements
NFPA 30, 5.-9.2
4.4.2.1 Smoking shall be permitted only in designated
and properly identified areas.
NFPA 30, 5.-9.3;
29CFR1910.106(e)(8)
4.4.2.2 Welding, cutting, and similar spark-producing
operations shall not be permitted in areas
containing flammable or combustible liquids
until a written permit authorizing such work
has been issued.
NFPA 30, 5.9.4;
29CFR1910.106(e)(6)(ii)
4.4.2.3 All equipment (such as tanks, machinery, and
piping) where an ignitable mixture could be
present shall be bonded or connected to a
ground. The bond or ground or both shall be
physically applied or shall be inherently
present by the nature of the installation.
Electrically isolated sections of metallic
piping or equipment shall be bonded to the
other portions of the system or shall be
individually grounded.
29CFR1910.106(d)(2)(iii)
4.4.331 Individual containers of flammable or combustible
liquids shall not exceed the capacities listed in
29CFR1910.106, Table H-12.
NFPA 30, 4.5.5.2
4.4.4 In an office occupancy, containers of Class I liquids
that are outside of an inside liquid storage (see
definition) area shall not exceed a capacity of one
gallon (3.8 liters).
[EXCEPTION: safety cans (see definition) are
permitted up to a two-gallon capacity.]
NFPA 30, 4.5.5.3
4.4.5 In an office occupancy, not more than ten gallons (37.8
liters) of Class I and Class II liquids (see definition)
combined shall be kept in a single fire area (see
definition) outside of a storage cabinet or an inside
liquid storage area, unless the liquids are in safety cans
(see definition).
31 Glass or plastic containers up to one gallon in size may be used for Class IA or IB liquids if either (1) the liquid
would be rendered unfit for its intended use by contact with metal, (2) the liquid would corrode a metal container so
as to create a leakage hazard, (3) the process would require more than the allowed quantities of liquid of a single
assay lot to be used at one time, or (4) the process would require the maintenance of an analytical standard liquid of
a quality which is not met by the specified standards of liquids available, and the quantity of the analytical standard
liquid required for any one control process exceeds one-sixteenth the capacity of the container allowed under Table
1.
47
DOE-HDBK-1139/3-2003
Sources10 Consolidated Requirements
NFPA 30, 4.-5.5.4
4.4.6 In an office occupancy, not more than 25 gallons (94.6
liters) of Class I and Class II liquids (see definition)
combined shall be kept in a single fire area in safety
cans outside of a storage cabinet or an inside liquid
storage area.
NFPA 30, 4.5.5.5
Section 47
4.4.7 In an office occupancy, not more than 60 gallons (227
liters) of Class III liquids (see definition) shall be
stored outside of an inside liquid storage area or storage
cabinet.
NFPA 30, 5.13.2.1
4.4.8 Wherever flammable or combustible liquids are used,
either fire extinguishers or pre-connected hoses shall be
provided in accordance with NFPA 30.
29CFR1910.106(a)(18)(iii)
4.4.9 Whenever a combustible liquid is heated for use to
within 30°F (16.7°C) of its flash point, it shall be
handled in accordance with the requirements for the
next lower class of liquids.
NFPA 30, 5.13.4.1
4.4.10 An approved (see definition) means for prompt
notification of fire or emergency to those within the
plant and to the fire department shall be provided.
NFPA 30, 5.13.4.2
4.4.11 Those areas, including buildings, where a potential
exists for a flammable liquid spill shall be monitored
for the presence of those liquids.
NFPA 30, 5.13.6.1
4.4.12 All fire protection equipment, and associated alarms,
interlocks, and controls, shall be properly maintained,
and periodic inspections and tests shall be done in
accordance with both standard practice and the
equipment manufacturer’s recommendations.
NFPA 30, 5.13.6.2;
29CFR1910.106(e)(9)(i)
4.4.13 Maintenance and operating practices shall control
leakage and prevent spillage of flammable liquids.
29CFR1910.106(e)(9)(i)
4.4.14 Spills shall be cleaned up promptly.
NFPA 30, 5.13.6.3;
29CFR1910.106(e)(9)(iii)
4.4.15 Combustible waste material and residues in operating
areas shall be kept to a minimum, shall be stored in
covered metal containers, and shall be disposed of
daily.
48
DOE-HDBK-1139/3-2003
Sources10 Consolidated Requirements
NFPA 30, 5.13.6.4;
29CFR1910.106(e)(9)(iv)
4.4.16 Ground areas around facilities where liquids are used
shall be kept free of weeds, trash, or other unnecessary
combustible materials.
NFPA 30, 5.13.6.5;
29CFR1910.106(e)(9)(ii)
4.4.17 Aisles established for movement of personnel shall be
maintained clear of obstructions.
NFPA 30, 5.5.2;
29CFR1910.106(e)(2)(iv)(d)
4.4.18 Flammable liquids or combustible liquids at
temperatures at or above their flash points shall be
drawn from or transferred into vessels, containers, or
portable tanks using one of the following methods:
• from original shipping containers with a capacity
of five gallons (19 liters) or less;
• from safety cans;
• through a closed piping system;
• from portable tanks or containers by means of a
device that has anti-siphoning protection and that
draws through an opening in the top of the tank or
container;
• by gravity through a listed self-closing valve or
self-closing faucet.
[NOTE: Class I-A liquids (see definition) shall not be
dispensed by gravity from tanks.]
29CFR1910.106(e)(2)(iv)(d)
4.4. 19 Transferring flammable or combustible liquids by
means of air pressure on the container or tank shall be
prohibited.
29CFR1910.106(d)(4)(v)
4.4.20 Dispensing in inside storage rooms shall be by
approved pump or self-closing faucet only.
NFPA 30, 5.5.2.1
4.4.21 If hose is used in the transfer operation, it shall be
equipped with a self-closing valve without a hold-open
latch in addition to the outlet valve. Only listed or
approved hose shall be used.
NFPA 30, 5.5.2.2
4.4.22 Means shall be proved to minimize generation of static
electricity. Such means shall meet the requirements of
NFPA 30.
29CFR1910.106(e)(6)(ii)
4.4.23 Class I liquids (see definition) shall not be dispensed
into containers unless the nozzle and container are
electrically interconnected.
Section 48
49
DOE-HDBK-1139/3-2003
Sources10 Consolidated Requirements
NFPA 30, 5.5.2.3
4.4.24 If pumps are used to transfer liquids, means shall be
provided to stop the transfer in the event of a spill or
fire.
29CFR1910.106(e)(2)(iii)
4.4.25 Areas in which flammable or combustible liquids are
transferred from one tank or container to another
container shall be separated from other operations in
the building by adequate distance or by construction
having adequate fire resistance. Adequate natural or
mechanical ventilation shall be provided.
NFPA 30, 4.4.5.1
4.4.26 Dispensing of flammable liquids or dispensing of
combustible liquids at temperatures at or above their
flash points shall not be permitted in cutoff rooms or
attached buildings that exceed 1000 ft2 (93m2) in floor
area or in liquid warehouses unless the dispensing area
is suitably cut off from the storage areas in accordance
with NFPA 30.
NFPA 30, 4.5.2.9
4.4.27 Dispensing of flammable liquids or of Class II
combustible liquids shall not be permitted in general
purpose warehouses unless the dispensing area is
suitably cut off from other ordinary combustible or
liquid storage areas in accordance with NFPA 30, and
otherwise complies with NFPA 30.
29CFR1910.106(e)(2)(iv)(a)
4.4.28 Flammable liquids shall be kept in covered containers
when not actually in use.
29CFR1910.106(e)(2)(iv)(b)
4.4.29 Where flammable or combustible liquids are used or
handled, except in closed containers, means shall be
provided to dispose promptly and safely of leakage and
spills.
29CFR1910.106(e)(2)(iv)(c)
4.4.30 Class I liquids shall be used only where there are no
open flames or other sources of ignition within the
possible path of vapor travel.
4.5 Compressed Gases
29CFR1910.101
4.5.1 Compressed gas cylinders shall be used in accordance with
the Compressed Gas Association (CGA).
NFPA 55, 4.2;
29CFR1910.253(b)(1)(ii)
4.5.2 Compressed gas cylinders shall be appropriately labeled.
Whenever possible, labels shall be located near the
shoulder of the cylinder.
50
DOE-HDBK-1139/3-2003
Sources10 Consolidated Requirements
CGA P-1, 3.2.5
4.5.2.1 The color of the cylinder shall not be the only
means used to identify the gas it contains.
ANSI Z49.1, 10.8.1.4 and 5;
CGA G-1, 5.1.3;
CGA P-1, 3.2.2;
NFPA 55, .7.1.2.2;
29CFR1910.253(b)(5)(ii)(L)
4.5.2.2 Labels or markings placed on compressed gas
cylinders by the manufacturer or distributor shall
not be defaced or removed.
ANSI Z49.1, 10.8.1.4
4.5.2.3 Cylinders not bearing a legible label or other
identification shall not be used and shall be
returned to the manufacturer or distributor.
NFPA 51, 2.1.3
4.5.2.4 Gas name markings shall not be cut into the metal
of the cylinder by the user.
CGA P-1, 3.3.3
4.5.3 Compressed gas cylinders shall not be subjected to
temperature extremes.
ANSI Z-49.1, 10.8.1.8;
CGA P-1, 3.3.3;
NFPA 55, 7.1.5.5;
29CFR1910.253(b)(2)(i)
4.5.3.1 Compressed gas cylinders shall not be exposed to
temperatures exceeding 125°F
CGA P-1, 3.3.3;
CGA P-1, 4.2.2;
CGA G-1, 5.1.6;
CGA G-1, 5.3.3.12;
NFPA 55, 7.1.5.7;
29CFR1926.350(b)(3)
4.5.3.2 Direct flames or heat shall not be applied to a
compressed gas cylinder.
CGA P-1, 3.3.6;
NFPA 55, 7.1.8
4.5.3.2.1 Cylinders exposed to fire shall not be
shipped or used until the manufacturer
or supplier requalifies them in
accordance with the pressure and
vessel code under which they were
manufactured.
51
DOE-HDBK-1139/3-2003
Sources10 Consolidated Requirements
Section 49
ANSI Z49.1 10.8.4.13;
29CFR1910.253(b)(5)(ii)(L);
29CFR1926.350(b)(1)
4.5.3.2.2 Cylinders shall be kept far enough
away from operations such as welding
to prevent sparks, hot slag, flames, etc.,
from reaching them. If cylinders
cannot be kept a sufficient distance
away, then fire-resistant shields shall
be used to separate the cylinders from
the hot operations.
CGA P-1, 3.3.4
4.5.3.3 Cylinders shall not be subjected to artificially low
temperatures without the permission of the
supplier. Outside storage is not affected by this
requirement.
CGA P-1, 3.3.8;
NFPA 55, 7.1.1.2.1;
NFPA 55, 7.1.9.1;
29CFR1926.350(c)(3)
4.5.4 No structurally damaged or defective cylinders shall be
used. Damaged or defective cylinders shall be removed
from service.
ANSI Z49.1, 10.8.1.2;
ANSI Z49.1, 10.8.1.3;
CGA P-1, 3.6;
CGA G-1, 5.1.7;
29CFR1910.253(b)(5)(ii)(M);
29CFR1926(c)(2)
4.5.5 No person other than the cylinder supplier shall mix or
refill gases in cylinders. Used, non-refillable containers
shall be disposed of according to the manufacturer’s
recommendation.
29CFR1926.350(c)(2) 4.5.5.1 No one shall use a cylinder’s contents for
purposes other than those intended by the
supplier.
ANSI Z49.1, 10.8.3.4;
CGA P-1, 3.2;
CGA G-1, 5.1.6;
29CFR1910.253(b)(5)(ii)(N);
29CFR1910.253(b)(5)(iii)(H)
4.5.6 No one shall tamper with safety devices in cylinders or
valves.
CGA P-1, 3.2;
CGA P-1, 3.3.8;
NFPA 55, 7.1.1.2.1;
29CFR1910.253(b)(5)(ii)(R)
(1) and (2)
4.5.6.1 No attempt shall be made to maintain or repair
cylinder safety devices. Suppliers instructions
as to the disposition of the cylinder shall be
followed if a cylinder with a faulty valve or
safety device is found or if the cylinder is
otherwise found to be defective.
52
DOE-HDBK-1139/3-2003
Sources10 Consolidated Requirements
29CFR1910.253(b)(5)(ii)(R)
(3)
4.5.6.2 Complete removal of the stem from a
diaphragm-type cylinder valve shall be
avoided.
[NOTE: Stems may be removed before
cylinder disposal.]
ANSI Z-49.1, 10.8.4.10;
CGA G-1, 5.3.3.11;
CGA G-1, 4.2.11;
29CFR1910.253(b)(2)(ii);
29CFR1910.253(b)(2)(iii);
29CFR1910.253(b)(5)(ii)(G);
29CFR1910.253(b)(5)(ii)(H);
29CFR1926.350(a)(8)
4.5.7 When compressed gas cylinders are not in use or are
empty, their valves shall be closed.
ANSI Z-49.1, 10.8.3.6;
CGA G-1, 5.1.9;
CGA G-1, 5.5.1;
CGA P-1, 3.4.1;
NFPA 55, 7.1.4.2;
29CFR1910.253(b)(2)(iv);
29CFR1910.253(b)(5)(ii)(A);
29CFR1926.350(a)(1)
4.5.8 Where cylinders are designed to accept valve
protection caps, caps shall be in place and hand tight at
all times except when connected for use.
CGA P-1, 3.4.2;
NFPA 55, 7.1.4.3.1
4.5.9 Where valve outlet caps and/or plugs are provided by
the manufacturer, the user shall keep the device on the
valve outlet at all times except when secured and
connected for use.
CGA G-1, 5.5.1;
CGA P-1, 3.4.3
4.5.9.2 Valve outlet caps and/or plugs shall be in place
and tightened before shipment of the cylinder
back to the supplier.
ANSI Z-49.1, 10.8.3.2;
29CFR1910.253(b)(5)(ii)(C);
29CFR1926.350(a)(5)
4.5.10 Pry bars shall not be used under valves or valve
protection caps to pry cylinders loose when frozen or
otherwise affixed to the ground.
29CFR1926.350(a)(5)
4.5.10.1 Warm, not boiling water shall be used to
thaw cylinders loose.
53
DOE-HDBK-1139/3-2003
Sources10 Consolidated Requirements
ANSI Z49.1, 10.8.3.3;
CGA P-1, 3.3.1;
CGA G-1 5.1.10;
29CFR1910.253(b)(5)(ii)(K);
29CFR1926, 350(c)(1)
4.5.11 Compressed gas cylinders shall not be used as rollers or
supports.
Section 50
29CFR1926. 350(a)(11)
4.5.12 Compressed fuel gas cylinders shall not be kept in
unventilated enclosures such as lockers or cupboards.
ANSI Z-49.1, 10.8.4.14;
CGA P-1, 3.3.2;
CGA G-1, 5.1.8;
NFPA 55, 7.1.5.10;
29CFR1910.253(b)(5)(ii)(J);
29CFR1926.350(b)(2)
4.5.13 Compressed gas cylinders shall not be placed where
they can inadvertently become part of an electrical
circuit.
CGA P-1, 3.3.2
4.5.13.1 When used in conjunction with electric
welding, compressed gas cylinders shall not
be grounded or used for grounding.
ANSI Z49.1, 10.8.4.14;
29CFR1926.350(b)(2);
29CFR1910.253(b)(5)(ii)(J)
4.5.13.2 Electrodes shall not be struck against a
compressed gas cylinder to strike an arc.
ANSI Z49.1, 10.8.2.5;
ANSI Z49.1,10.8.4.12;
CGA P-1, 3.7.4;
NFPA 45, 8.1.5.1;
NFPA 55, 7.1.3.4;
NFPA 55, 7.2.1.2.2;
NFPA 55, 7.3.1.7.1;
NFPA 55, 7.3.1.8;
29CFR1926.350(a)(7) and
(9);
29CFR1926.350(b)(3)
4.5.14 Compressed gas cylinders shall be secured in an
upright position when being used unless specifically
designed for a horizontal application.
[EXCEPTION: Cylinders containing non-flammable
liquefied gases may be used in the inverted position
when the liquid phase is used.]
54
DOE-HDBK-1139/3-2003
Sources10 Consolidated Requirements
ANSI Z49.1, 10.3.3;
ANSI Z49.1, 10.6.5;
CGA G-1, 5.3.3.4;
CGA P-1, 3.8.7;
29CFR1910.253(3)(1);
29CFR1926.350(f)(1)
4.5.15 Oxygen and fuel and other compressed gas cylinders,
equipment, pipelines or apparatus shall not be used
interchangeably with any other gas and each shall be
used only for the service for which it was approved.
ANSI Z49.1, 10.5.2.1;
CGA G-1, 5.3.3.6;
CGA P-1, 3.8.4;
NFPA 55, 7.3.1.4.1
4.5.16 All connections shall be gas tight and no leaks shall be
present in the system.
ANSI Z49.1, 10.5.2.1;
CGA P-1, 4.2.1.5
4.5.16.1 A flame shall not be used for the detection of
leaks in compressed gas systems. Soapy
water is one acceptable method.
CGA P-1, 3.7.5;
CGA P-1, 3.8.2;
NFPA 55, 7.3.1.4.2
4.5.17 Backflow protection shall be used when the backflow
of gas can result in a hazardous condition.
NFPA 55, 7.3.1.2;
NPFA 55, 7.5-7.10
4.5.18 Compressed gas systems shall be designed for their
intended use and shall be designed by persons
competent in such design. .
[NOTE: Additional requirements for corrosive,
flammable, oxidizing, pyrophoric, toxic/highly toxic,
and unstable reactive gases can be found in NFPA 55,
7.5-7.10.]
ANSI Z49.1, 10.8.4.1;
CGA G-1, 5.3.1;
CGA P-1, 3.8.8;
NFPA 45, 8.1.5.2;
NFPA 51, 3-1.4;
NFPA 51, 3-2.5;
NFPA 51, 3-4.5;
29CFR1926.350(d)(3);
29CFR1910.253(b)(5)(iii)(I)
4.5.19 Compressed gases shall never be used from cylinders or
high pressure manifolds without reducing the pressure
through a suitable regulator unless the equipment used
is designed to withstand full cylinder pressure.
55
DOE-HDBK-1139/3-2003
Sources10 Consolidated Requirements
29CFR1910.253(b)(5)(ii)(P) 4.5.19.1 Unless connected to a manifold, oxygen from
a cylinder shall not be used without a
regulator.
ANSI Z49.1, 10.7.1;
ANSI Z49.1, 10.7.2;
CGA G-1, 5.3.3.4;
NFPA 51, 5-6;
NFPA 45, 8.1.5.2;
29CFR1910.253(a)(3);
29CFR1910.253(e)(6)(i)
4.5.20 Approved gas regulators and pressure reducing valves
shall be used only for the gas and pressures for which
they are labeled.
29CFR1926.350(h); 4.5.21 Regulators, including their related gauges, shall be in
proper working order while in use.
ANSI Z49.1, 10.7.3;
29CFR1910.253(e)(6)(iv)
Section 51
4.5.21.1 Union nuts and connections shall be
inspected before cylinder use to detect faulty
seals, which could cause leakage. Faulty
nuts and connectors shall be replaced.
ANSI Z49.1 10.7.6;
CGA G-1, 5.1.5;
29CFR1910.253(e)(6)(ii)
4.5.21.2 A qualified mechanic shall perform repair of
regulators or their parts.
ANSI Z49.1, 10.7.5;
ANSI Z49.1, 10.8.4.11;
CGA G-1, 5.3.3.11;
CGA P-1, 3.8.6;
29CFR1910.253(b)(5)(iii)(D);
29CFR1926.350(d)(4)
4.5.22 Before a regulator is removed from a cylinder, the
cylinder valve shall be closed and the pressure released
from the regulator.
ANSI Z49.1, 10.7.5;
ANSI Z49.1, 10.8.4.4;
CGA G-1, 5.3.3.7;
CGA P-1, 3.8.1.1;
29CFR1910.253(b)(5)(iii)(J);
29CFR1926.350(d)(2)
4.5.23 Cylinder valves shall always be opened slowly to
prevent damage to the regulator.
ANSI Z49.1 10.8.4.4;
CGA P-1, 3.8.1
4.5.23.1 Personnel shall stand to the side and not in
front of the regulator orifice when the cylinder
valve is opened.
56
DOE-HDBK-1139/3-2003
Sources10 Consolidated Requirements
ANSI Z49.1, 10.8.4.7
4.5.24 When a high pressure gas (non-liquefied) cylinder is in
use, the valve shall be fully opened to prevent leakage
around the valve stem.
ANSI Z49.1, 10.8.4.6;
CGA G-1, 5.3.3.10;
CGA P-1, 3.8.1.1;
29CFR1910.253(b)(5)(ii)(E);
29CFR1910.253(b)(5)(iii)(L);
29CFR1926.350(d)(5)
4.5.25 Cylinders not having a fixed hand wheel shall have
keys, handles or non-adjustable wrenches on valve
stems while cylinders are in service.
29CFR1926.350(d)(2)
4.5.25.1 Manifolded or coupled cylinders shall have at
least one such wrench always available.
ANSI Z49.1, 10.8.4.5;
CGA P-1, 3.8.1.1 ;
CGA G-1, 5.3.3.2;
29CFR1910.253(b)(5)(ii)(Q)
(1)
4.5.26 Cylinders having hand wheels shall not be opened
using wrenches, hammers or other tools. If the valve
cannot be opened by hand, then the manufacturer shall
be notified and their directions followed.
ANSI Z-49.1, 10.8.3.10;
CGA G-1, 5.2.5;
29CFR1910.253(b)(5)(ii)(D);
29CFR1926.350(a)(6)
4.5.27 When cylinders are secured in a suitable hand truck,
regulators do not have to be removed and valve
protection caps need not be in place before cylinders
are moved. When cylinders are to be moved with
regulators attached, the cylinder valve must be closed.
ANSI Z-49.1, 10.8.3.5;
CGA P-1, 3.8.1;
29CFR1910.253(b)(5)(ii)(F);
29CFR1926.350(a)(8)
4.5.28 Cylinder valves shall be closed before moving
cylinders.
ANSI Z-49.1, 10.8.3.7;
CGA P-1, 3.5.1;
29CFR1910.253(b)(5)(ii)(C);
29CFR1926.350(a)(5)
4.5.29 Valve protection caps shall not be used for lifting
cylinders.
ANSI Z-49.1, 10.8.3.8;
CGA G-1, 5.2.3;
29CFR1910.253(b)(5)(ii)(A);
29CFR1926.350(a)(2)
4.5.30 When using a crane, derrick, etc. to transport cylinders,
a cradle, boat, pallet, slingboard or other suitable
platform shall be used. Compressed gas cylinders shall
be secured to the lifting device before they are hoisted.
57
DOE-HDBK-1139/3-2003
Sources10 Consolidated Requirements
ANSI Z-49.1, 10.8.3.8;
CGA G-1, 5.2.3;
CGA P-1, 3.5. 2;
29CFR1910.252(b)(5)(ii)(A);
29CFR1926.350(a)(2)
4.5.30.1 Choker slings, ropes, chains or magnets shall
not be used to hoist compressed gas
cylinders.
ANSI Z49.1, 10.8.3.1;
CGA G-1, 5.2.1, 2 and 6;
CGA P-1, 3.5;
29CFR1910.253(b)(5)(ii)(B)
and (O);
29CFR1910.253(b)(5)(iii)(B);
29CFR1926.350(a)(3)
4.5.31 Compressed gas cylinders shall not be purposely
dropped, struck or permitted to strike each other
violently.
ANSI Z-49.1, 10.8.3.9;
CGA G-1, 5.2.5;
29CFR1926.350(a)(4) and (9)
Section 52
4.5.32 When compressed gas cylinders are transported by
motor vehicle, they shall be secured in an upright
position.
29CFR1926.350(a)(3)
4.5.33 When large cylinders are moved by hand, they shall be
tilted and rolled on their bottom edge.
ANSI Z49.1, 10.8.4.3;
CGA G-1, 5.3.3.3;
29CFR1910.253(b)(5)(iii)(C);
29CFR1926.350(d)(1)
4.5.34 Before connecting a regulator to an oxygen or fuel
cylinder valve, the valve shall be inspected, wiped
clean and the valve shall be opened momentarily and
then closed immediately. This process is called
“cracking”.
ANSI Z49.1, 10.8.4.3;
CGA P-1, 3.3.9;
29CFR1910.253(b)(5)(iii)(C);
29CFR1926.350(d)(1)
4.5.34.1 The person cracking the valve shall stand to
one side and not in front of the gas stream.
Compressed gas streams shall not be directed
towards any person.
ANSI Z49.1, 10.8.4.3;
29CFR1910.253(b)(5)(iii)(D);
29CFR1926.350(d)(1)
4.5.34.2 Fuel cylinder valves shall not be cracked near
ignition sources such as flames, welding
work, sparks, etc..
58
DOE-HDBK-1139/3-2003
Sources10 Consolidated Requirements
29CFR1926.350(e)(3)
4.5.34.3 Hose connections shall be kept free of grease
and oil.
ANSI Z 49.1, 10.6.1;
29CFR1910.253(e)(5)(i)
4.5.35 Hoses for oxy-fuel gas service shall comply with the
Rubber Manufacturers Association IP-7 Specification
for Rubber Welding Hose.
ANSI Z49.1, 10.6.2;
29CFR1926.350(f)(1)
4.5.36 Fuel gas hoses shall be red and oxygen hoses shall be
green when they are used for welding and cutting
activities.
ANSI Z49.1, 10.6.3;
29CFR1910.253(e)(5)(ii);
29CFR1926.350(f)(2)
4.5.37 When parallel lengths of oxygen and fuel gas hoses are
taped together such as in a welding operation, not more
than 4 inches out of every 12 shall be covered by tape.
ANSI Z49.1, 10.6.4;
29CFR1910.253(e)(5)(v);
29CFR1926.350(f)(3)
4.5.38 All hoses used for welding, cutting and other hot work
that will be used to carry hazardous gas (for example,
oxygen, fuel gases, oxidizers) shall be inspected at the
beginning of each working shift that they are to be
used and any defective hoses shall be removed from
service.
[NOTE: Defects in hoses that shall render the hose no
longer useable include leaks, burns, and worn places
that render the hose unfit for service.]
ANSI Z49.1, 10.6.5;
29CFR1910.253(e)(5)(iii)
4.5.39 Hose connections shall comply with the CGA
Pamphlet E-1, Regulator Connection Standards.
ANSI Z49.1, 10.6.5
4.5.39.1 Hose connections for welding gas lines shall
not be compatible with breathing air
equipment.
ANSI Z49.1, 10.6.6;
29CFR1910.253(e)(5)(iv)
4.5.39.2 Hose connections shall be able to withstand,
without leakage, twice the normal operating
pressure and not less than 300 psi.
ANSI Z49.1, 10.6.6;
29CFR1910.253(e)(5)(iv)
4.5.39.3 Oil-free air or an oil-free inert gas shall be
used to test hose connections.
29CFR1926.350(f)(6)
4.5.39.4 Storage areas for hoses shall be well
ventilated.
ANSI Z49.1, 10,9.3;
ANSI Z49.1, 10.9.4;
ANSI Z49.1, 10.9.5;
NFPA 51;
29CFR1910.253
4.5.40 Fuel gas and oxygen manifolds capacity limits,
locations and design criteria shall be in accordance
with NFPA 51 and 29CFR1910.253.
59
DOE-HDBK-1139/3-2003
Sources10 Consolidated Requirements
CGA G-1, 5.1.4;
29CFR1910.253(c)(5)(i)
4.5.41 Fuel gas and oxygen manifolds shall be installed under
the supervision of someone familiar with the proper
practices.
ANSI Z49.1, 10.9.2;
29CFR1910.253(c)(5)(ii)
4.5.42 All manifolds and their parts shall be used only for
those gases for which they are approved.
Section 53
ANSI Z49.1, 10.9.1;
NFPA 51, 3-2.1;
NFPA 51, 3-1.1;
29CFR1910.253(c)(1)(i)
4.5.42.1 Manifolds shall be approved either
separately for each of their components or
as an assembled unit.
29CFR1926.350(e)(1)
4.5.43 Manifolds shall bear the name of the substance
contained inside in letters at least 1 inch high either
directly painted upon the manifold or on a sign
permanently affixed to the manifold.
NFPA 51, 3-3.5
4.5.43.1 Low pressure manifolds shall be marked as
such to prevent the attachment of high
pressure cylinders.
29CFR1926.350(e)(2)
4.5.44 Fuel gas and oxygen manifolds shall be located in safe,
well ventilated, accessible locations and not within
enclosed spaces.
29CFR1926.350(e)(3)
4.5.45 Fuel gas and oxygen manifold hose connections shall
be such that hoses cannot be interchanged between fuel
gas and oxygen manifolds and supply header
connections.
29CFR1926.350(e)(3)
4.5.45.1 Adapters shall not be used to permit the
interchange of hoses.
29CFR1926.350(e)(4)
4.5.46 When not in use, fuel gas and oxygen manifold and
header connections shall be capped.
29CFR1926.350(3)(5)
4.5.47 Nothing shall be placed on top of a fuel gas and
oxygen manifold that will damage the manifold or
interfere with the quick closing of the valves.
NFPA 51, 3-4.1
4.5.48 Portable outlet headers shall not be used indoors except
for temporary service as approved by the Occupational
Safety and Fire Protection Department.
60
DOE-HDBK-1139/3-2003
Sources10 Consolidated Requirements
ANSI Z-49.1, 10.3.1;
CGA P-1, 4.4.1;
29CFR1910.253(b)(5)(i);
29CFR1926.350(h)(i)
4.5.49 Oxygen cylinders, cylinder valves, couplings,
regulators, hoses, and other apparatus shall be kept free
from oil, grease, dirt and other flammable or explosive
substances. These materials shall not be handled with
oily hands or gloves.
29CFR1910.253(b)(5)(I);
29CFR1926.350(h)(i)
4.3.49.1 A jet of oxygen gas shall not be directed at
an oily surface, greasy clothes, etc.
ANSI Z49.1, 10.7.4;
29CFR1910.253(e)(6)(iii)
4.5.50 Gauges used for oxygen service shall be marked “Use
No Oil”.
ANSI Z49.1, 10.3.2
4.5.51 Oxygen shall not be used as a substitute for
compressed air. For example, it shall not be used in
pneumatic tools, to blow out pipelines, to dust off
clothing or any similar application.
ANSI Z49.1, 10.7.5 4.5.52 Oxygen regulators shall be drained of oxygen before
they are attached to a cylinder or a manifold or before
the cylinder valve is opened.
CGA P-1, 4.4.2
4.5.53 Oxygen in work areas shall not be allowed to exceed
23 percent by volume.
ANSI Z49.1, 10.8.2.5;
29CFR1910.253(b)(3)(ii);
29CFR1910.253(b)(5)(iii)(A)
4.5.54 Fuel gas cylinders shall be used valve end up.
NFPA 55, 7.6.3.1
4.5.55 Where ignition of a flammable gas by static electricity
is possible, means shall be provided to prevent static
discharge.
ANSI Z49.1, 10.8.4.9;
CGA G-1, 5.3.3.9;
29CFR1910.253(b)(5)(iii)(E);
29CFR1926.350(d)(2)
4.5.56 Nothing shall be placed on fuel cylinders while in use
that could damage safety devices or interfere with the
quick closing of the valve.
ANSI Z49.1, 10.8.4.8;
CGA G-1, 5.3.3.8;
29CFR1910.253(b)(5)(iii)(K);
29CFR1926.350(d)(2)
4.5.57 Quick opening valves on fuel gas cylinders shall be
opened between ¾ and 1 ½ turns unless otherwise
specified by the manufacturer.
ANSI Z49.1, 10.8.4.15
4.5.58 Withdrawal rates from gas cylinders shall not exceed
manufacturer’s recommendations.
61
DOE-HDBK-1139/3-2003
Sources10 Consolidated Requirements
Section 54
ANSI Z49.1, 10.8.5.1;
CGA G-1, 5.6.2;
29CFR1926.350(d)(5)
4.5.59 If a leak is found around the valve stem of a fuel gas
cylinder, then the packing nuts shall be tightened and
the cylinder valve closed.
ANSI Z49.1, 10.8.5.2;
CGA G-1, 5.6.3;
29CFR1910.253(b)(5)(iii)(F);
29CFR1926.350(d)(5)
4.5.59.1 If these actions do not stop the leak (because
the leak is in the valve stem, valve seat,
cylinder fuse plug, etc.) then the cylinder
shall be moved from the work area to a safe
location outdoors and the cylinder shall be
properly marked.
ANSI Z49.1, 10.8.5.2;
CGA G-1, 5.6.3;
29CFR1910.253(b)(5)(iii)(G)
4.5.59.2 Precautionary signs warning of a fire hazard
shall be posted where leaking fuel cylinders
are located.
ANSI Z49.1, 10.8.5.2
4.5.59.3 If a leaking fuel cylinder cannot be moved,
then the area shall be evacuated and the fire
department shall be summoned for
assistance.
ANSI Z49.1, 10.8.5.3
4.5.59.4 Small fires at fuel gas cylinders shall be
extinguished if possible without endangering
personnel by either shutting off the valve or
by the use of water.
ANSI Z49.1, 10.8.5.3
4.5.59.4.1 Personnel shall evacuate the area
and the fire department
summoned for assistance if a
cylinder fire cannot be easily
extinguished.
NFPA 51, 4-4.2;
NFPA 51, 4-5.2;
29CFR1910.253(d)(5)(ii)
4.5.60 When compressed gas lines are being purged of air,
oxygen or combustible gas, then sources of ignition
shall not be allowed near uncapped openings.
NFPA 51, 1-3.1 4.5.61 The use of liquid acetylene is prohibited.
4.5.62 Details for the following compressed gases can be
found in the listed citations:
29CFR1910.102
4.5.62.1 Acetylene
29CFR1910.103
4.5.62.2 Hydrogen
29CFR1910.104
4.5.62.3 Oxygen
62
DOE-HDBK-1139/3-2003
Sources10 Consolidated Requirements
29CFR1910.105
4.5.62.4 Nitrous Oxide
4.6 Specific Chemicals – In addition to the chemical safety controls
identified in sections 4.1 through 4.5 of this chapter, there are
control requirements for many specific chemicals such as those
listed in sections 4.6.1 through 4.6.31 below . Details can be
found in the specific citations.
29CFR1910.1014 4.6.1 2-Acetylaminofluorene
29CFR1910.1045 4.6.2 Acrylonitrile
29CFR1910.1011 4.6.3 4-Aminodiphenyl
29CFR1910.1018 4.6.4 Arsenic, inorganic
29CFR1910.1001 4.6.5 Asbestos
29CFR1910.1028 4.6.6 Benzene
29CFR1910.1010 4.6.7 Benzidine
10CFR850 4.6.8 Beryllium
29CFR1910.1051 4.6.9 1,3-Butadiene
29CFR1910.1027 4.6.10 Cadmium
29CFR1910.1008 4.6.11 bis-Chloromethyl ether
29CFR1910.1044 4.6.12 1,2-dibromo-3-chloropropane
29CFR1910.1007 4.6.13 3,3’-Dichlorobenzidine (and its salts)
29CFR1910.1015 4.6.14 4-Dimethylaminoazobenzene
29CFR1910.1012 4.6.15 Ethyleneimine
29CFR1910.1047 4.6.16 Ethylene oxide
29CFR1910.1048 4.6.17 Formaldehyde
29CFR1910.1025 4.6.18 Lead
NFPA 484 4.6.19 Lithium
NFPA 484 4.6.20 Magnesium solids and powders
29CFR1910.1006 4.6.21 Methyl chloromethyl ether
29CFR1910.1052 4.6.22 Methylene chloride
63
DOE-HDBK-1139/3-2003
Sources10 Consolidated Requirements
29CFR1910.1050 4.6.23 Methylenedianiline
29CFR191 0.1004
4.6.24 alpha-Naphthylamine
29CFR1910.1009
4.6.25 beta-Naphthylamine
29CFR1910.1003
4.6.26 4-Nitrobiphenyl
29CFR1910.1016
4.6.27 N-Nitrosodimethylamine
29CFR1910.1013
4.6.28 beta-Propiolactone
NFPA 484
4.6.29 Titanium
29CFR1910.1017
4.6.30 Vinyl chloride
NFPA 484 4.6.31 Zirconium
5.0 Source Documents
ANSI Z49.1 (1999), "Safety in Welding, Cutting, and Allied processes”.
Section 55
CGA P-1 (2000), "Safe Handling of Compressed Gases in Containers”.
DOE O 420.1A, “Facility Safety”.
DOE O 440.1A, “Worker Protection Management”.
DOE-STD-1120-98, “Integration of Environment, Safety, and Health into Facility Disposition
Activities”.
DOE-STD-3009-94, “Preparation Guide for U.S. DOE Nonreactor Nuclear Facility Safety Analysis
Reports”.
DOE-STD-3011-94, “Guidance for Preparation of DOE O 5480.22 (TSR) and DOE O 5480.23
(SAR) Implementation Plans”.
DOE-STD-3016-99, “Limited Standard; Hazard Analysis Reports for Nuclear Explosive Operations”.
NFPA 30 (2000), “Flammable and Combustible Liquids Code”.
NFPA 45 (2000), “Standard on Fire Protection for Laboratories Using Chemicals”.
NFPA 55 (2003), “Storage, Use, and Handling of Compressed Gases and Cryogenic Fluids in
Portable and Stationary Containers, Cylinders, and Tanks”.
NFPA 471 (2002), “Recommended Practice for Responding to Hazardous Materials”.
NFPA 472 (2002), “Standard on Professional Competence of Responders to Hazardous Materials
Incidents”.
NFPA 484 (2002), “Standard for Combustible Metals, Metal Powders, and Metal Dusts”.
10CFR830, “Nuclear Safety Management,” Subpart B, “Safety Basis Requirements”.
64
DOE-HDBK-1139/3-2003
10CFR850, “Chronic Beryllium Disease Prevention Program”.
10CFR1021, “National Environmental Policy Act Implementing Procedures”.
29CFR1910.101, “Compressed Gases (general requirements)”.
29CFR1910.102, “Acetylene”.
29CFR1910.103, “Hydrogen”.
29CFR1910.104, “Oxygen”.
29CFR1910.105, “Nitrous oxide”.
29CFR1910.119, “Process Safety Management of Highly Hazardous Chemicals”.
29CFR1910.120, “Hazardous Waste Operations and Emergency Response”.
29CFR1910.132, “Personal Protective Equipment”.
29CFR1910.134, “Respiratory Protection”.
29CFR1910.253, “Oxygen-fuel Gas Welding and Cutting”.
29CFR1910.1001, “Asbestos”.
29CFR1910.1003, “13 Carcinogens (4-Nitrobiphenyl, etc.)”.
29CFR1910.1004, “alpha-Naphthylamine”.
29CFR1910.1006, “Methyl chloromethyl ether”.
29CFR1910.1007, “3,3’-Dichlorobenzidine (and its salts)”.
29CFR1910.1008, “bis-Chloromethyl ether”.
29CFR1910.1009, “beta-Naphthylamine”.
29CFR1910.1010, “Benzidine”.
29CFR1910.1011, “4-Aminodiphenyl”.
29CFR1910.1012, “Ethyleneimine”.
29CFR1910.1013, “beta-Propiolactone”.
29CFR1910.1014, “2-Acetylaminofluorene”.
29CFR1910.1015, “4-Dimethylaminoazobenzene”.
29CFR1910.1016, “N-Nitrosodimethylamine”.
29CFR1910.1017, “Vinyl Chloride”.
29CFR1910.1018, “Inorganic Arsenic”.
29CFR1910.1025, “Lead”.
29CFR1910.1027, “Cadmium”.
29CFR1910.1028, “Benzene”.
29CFR1910.1044, “1,2-dibromo-3-chloropropane”.
29CFR1910.1045, “Acrylonitrile”.
29CFR1910.1047, “Ethylene Oxide”.
29CFR1910.1048, “Formaldehyde”.
29CFR1910.1050, “Methylenedianiline”.
29CFR1910.1051, “1,3-Butadiene”.
29CFR1910.1052, “Methylene Chloride”.
29CFR1910.1200, “Hazard Communication”.
29CFR1910.1450, “Occupational Exposure to Hazardous Chemicals in Laboratories”.
29CFR1926.21, “Safety Training and Education”.
40CFR68, “Chemical Accident Prevention Provisions”.
48CFR970, “DOE Management and Operating Contracts“.
65
DOE-HDBK-1139/3-2003
INTENTIONALLY BLANK
66
DOE-HDBK-1139/3-2003
Chapter 7 - Pollution Prevention and Waste Minimization
1.0 Introduction
Section 56
This chapter identifies and consolidates existing user safety and health requirements found in DOE
and Federal chemical-related safety and health regulations and National Standards that address
pollution prevention (P2) (see definition) and waste minimization for chemicals (see definition) and
chemical products (see definition). This chapter specifically consolidates requirements found in 42
USC, 40CFR; the “Greening the Government” Executive Orders 13101, 13148; DOE O 450.1; DOE
Acquisition Letter AL-2002-05; and Secretary of Energy Memorandum November 12, 1999, and
includes technical standards that are made mandatory by their specific reference within a regulation,
rule or DOE Order.
This chapter is intended to list chemical-related safety and health requirements and to consolidate
those that are overlapping and/or duplicative. The list of requirements includes “pointers” to the
sources of those requirements.
Requirements for pollution prevention generally involve the integration of P2 into planning,
execution, and evaluation of site activities. Chemical users’ participation in pollution prevention
arises from their use of chemicals, and from the site’s procurement, distribution, storage and disposal
of chemicals. Safety and health program and environmental pollution prevention program protections
are usually mutually beneficial, and their requirements frequently mutually inclusive.
Consolidated chemical-related safety and health requirements here provide a context for the need for
the chemical user to incorporate pollution prevention into every phase of work, such as planning,
acquisition, operations, waste management/disposal, and continuous improvement. This chapter does
not contain requirements for implementation of Environmental Protection Agency (EPA) reporting
requirements or for environmental regulatory compliance.
This document does NOT create any new or additional requirements.
2.0 Applicability
The information presented here applies to all locations that use chemicals, chemical products or
services that involve the use of chemicals or chemical products. [NOTE: Throughout this document,
the term “chemicals” is used to indicate chemicals and/or chemical products as described in section
3, below.] This chapter is intended only to address chemical health and safety requirements applicable
to chemical user activities. It consolidates existing, core safety and health requirements that all sites
must follow when engaged in chemical-related activities.
The requirements included in this chapter come from sources that have different safety purposes. As
a result, some of these requirements may not always be applicable to the work being performed at an
individual site or facility. It is the responsibility of each user to determine the applicability of specific
requirements to their work and how they are implemented. The reference sources for the
requirements included in this chapter can be used to determine the applicability of those requirements
to the work being performed.
67
DOE-HDBK-1139/3-2003
3.0 Definitions and Acronyms
See Glossary.
4.0 Requirements for Pollution Prevention and Waste Minimization
Sources10 Consolidated Requirements
4.1 Pollution Prevention Policy
DOE O 450.1 sec. 4(a)(1),
CRD sec. 1(a)
4.1.1 Pollution prevention must be integrated into the
planning, execution and evaluation of all site
activities.
EO 13148, sec. 303;
42 USC 13101
Section 57
4.1.2 Federal agencies shall preferentially use pollution
prevention projects and activities to correct and
prevent noncompliance with environmental
regulatory requirements.
4.2 Pollution Prevention Programs
DOE O 450.1 CRD sec. 9;
EO 13148, sec.304
DOE and its contractors shall develop and implement a
pollution prevention program at DOE facilities that
compares the life-cycle costs of treatment and /or disposal
of waste and pollutant streams to the life-cycle costs of
alternatives that eliminate or reduce toxic chemicals or
pollutants at the source.
HSWA sec. 3005(h)(i);
40CFR264.73(b)(9);
40CFR262, 264-265;
40CFR270;
42USC sec. 6922(b) and 6925
(h)
4.2.1 A chemical user who generates hazardous waste
must have a program in place to reduce the volume
or quantity and toxicity of such waste to the degree
determined by the generator to be economically
practicable.32
DOE O 450.1, sec. 4.1.(1)(b),
CRD sec.1(a) and 3
4.2.2 All DOE elements (see definition) must ensure that
sites’ Integrated Safety Management System
(ISMS (see definition) includes an Environmental
Management System (EMS, see definition) that
provides for the systematic planning, integrated
execution and evaluation of programs for pollution
prevention.
32 This is an implied or indirect requirement to have a waste and toxicity reduction program. The actual requirement is for a
certifying signature on hazardous waste manifests; on permits for treatment, storage, or disposal of hazardous waste; and in
Hazardous Waste Generator Biennial Reports as to the existence of a waste and toxicity reduction program. A violation would
be for false certification of the existence of a waste and toxicity reduction program, rather than for not having the program.
68
DOE-HDBK-1139/3-2003
Sources10 Consolidated Requirements
DOE O 450.1, sec. 4.b.(3),
CRD sec. 2(c)
4.2.2.1 DOE contractors must reduce or eliminate
the generation of waste, the release of
pollutants to the environment, and the use
of Class I ozone-depleting substances
(ODS), (see definition) through source
reduction, re-use, segregation, and
recycling and by procuring recycled-
content materials and environmentally
preferable products and services.
[NOTE: DOE O 450.1 requires that this
be done as part of integrating EMSs into
site ISMSs.]
HSWA 3002, sec. (a)(6)(C)-
(D);
40CFR262.41(a)(6)-(7);
40CFR264.75(h)-(i);
40CFR265.75(h)-(i);
42USC sec. 6922 (a)(6)
4.2.3 Chemical users who generate hazardous wastes are
required to submit biennial reports describing:
a) efforts undertaken to reduce the volume and
toxicity of waste generated; and
b) changes in volume and toxicity of waste
actually achieved compared with previous
years, to the extent that such information is
available.
4.3 Waste Minimization Goals
DOE O 450.1, sec. 5.c.(3),
CRD sec.1(c) and 4;
EO 13101, sec 601(1)(a)
4.3.1 Contractors shall include goals in their ISMS that
contribute to the accomplishment of DOE P2
goals.33
Secretary of Energy Memo
to Heads of Departmental
Elements, November 12,
1999
4.3.1.1 Contractors must reduce waste from
routine operations by 2005, using a 1993
baseline, for the following waste types:
• Hazardous by 90 percent;
• Low Level Radioactive by 80 percent;
• Low Level-Mixed Radioactive by 80
percent;
• Transuranic (TRU) by 80 percent.
• Releases of toxic chemicals subject to
Toxic Chemical Release Inventory
reporting by 90 percent.
• Sanitary waste by 75 percent by 2005
and 80 percent by 2010, using a 1993
baseline.
Section 58
• Waste resulting from cleanup,
33 While goals are not required as a part of ISMSs, the EMSs that are required to be integrated into ISMSs include
goals. This requirement refers to the EMS goals that must be included in the ISMSs.
69
DOE-HDBK-1139/3-2003
Sources10 Consolidated Requirements
stabilization, and decommissioning
activities by 10 percent on an annual
basis.
a) Appropriate baselines for new sites
shall be established in performance
agreements in cases where
proposed baseline years do not
apply.
b) Goal requirements shall be
included in annual performance
plans or agreements.
c) By 2005, 45 percent of sanitary
wastes from all operations must be
recycled, and by 2010, 50 percent
of sanitary waste from all
operations must be recycled.
DOE O 450.1, sec. 5.c.(3),
CDR sec. 1(c);
EO 13148 sec. 204 and 502
4.3.1.2 Through innovative pollution prevention,
effective facility management, and sound
acquisition and procurement practices,
contractors shall assist DOE in reducing its
reported releases and off-site transfers of
toxic chemicals subject to annual toxic
release reporting under EPCRA (see
definition) (see section 4.6 of this chapter)
for treatment and disposal by 10 percent
annually, or by 40 percent overall by
December 31, 2006 from year 2000 levels.
DOE O 450.1, sec. 5.c.(3),
CRD sec. 1(c);
EO 13148, sec. 205 and 503;
4.3.1.3 Contractors shall use product substitution
and facility management practices,
including pollution prevention, to reduce
use of selected toxic chemicals,34
hazardous substances, and pollutants by 50
percent annually, or reduce the generation
of hazardous and radioactive waste types at
facilities by 50 percent by December 31,
2006.
[NOTE: DOE has chosen to use the
Secretary’s waste reduction goals cited
above in 4.3.1.1 to meet this requirement.
Sites are still encouraged to reduce
chemical usage.]
34 At the time of this writing, the EPA has not published the list of chemicals affected by this requirement.
70
DOE-HDBK-1139/3-2003
Sources10 Consolidated Requirements
4.4 P2 Opportunities
DOE O 450.1, sec. 5.d.(6),
CRD sec. 9
4.4.1 Contractors shall conduct operational assessments,
such as Pollution Prevention Opportunity
Assessments of site operations to identify
opportunities for source reduction, material
segregation, reuse, recycle, or other P2 projects.
DOE O 450.1, sec. 5.d.(6),
CRD sec. 9
4.4.1.1 Based on the results of these assessments,
contractors shall implement cost-effective P2
projects, using life-cycle assessment concepts
and practices in determining their Return-on-
Investment (ROI).
4.5 Purchasing
DOE O 450.1, CRD sec. 9;
EO 13101, sec. 401
4.5.1 In developing plans, drawings, work statements,
specifications, or other product descriptions,
contractors shall consider, as appropriate, a broad
range of factors including: elimination of virgin
material requirements; use of biobased products; use
of recovered materials; reuse of product; life-cycle
cost; recyclability; use of environmentally preferable
products; waste prevention (including toxicity
reduction or elimination); and ultimate disposal.35
DOE O 450.1, sec. 5.d.(3);
EO 13101, sec. 601(1)(b)
4.5.2 Contractors shall set goals to increase the
procurement of products that are made with
recovered materials to maximize the number of
recycled products purchased, relative to non-recycled
alternatives.
DOE O 450.1, Sec. 4.d.(11),
CRD sec. 8
Section 59
4.5.3 Contractors shall consider P2 in the specification and
acquisition of departmental supplies to cost
effectively maximize procurement of
environmentally preferable products.
DOE O 450.1, sec. 5.d.(5),
CRD sec. 5;
EO 13148, sec. 701(b)
4.5.4 Contractors shall consider the feasibility of
centralized procurement and distribution programs
for purchasing, tracking, distributing, and managing
materials with toxic or hazardous content, and
implement where appropriate.
35 These factors should be considered in acquisition planning for all procurement and in the evaluation and award of
contracts, as appropriate. Program and acquisition managers should take an active role in these activities.
71
DOE-HDBK-1139/3-2003
Sources10 Consolidated Requirements
DOE O 450.1, sec. 5.d.(12),
CRD sec. 8;
DOE Acquisition Letter AL-
2002-05
4.5.5 Contractors shall coordinate all acquisitions with the
Department’s “Green Acquisition Advocates”
established pursuant to Acquisition Letter, AL 2000-
03 (superceded by AL-2002-05).
DOE O 450.1, CRD sec. 4;
EO 13101, Sec. 507;
40CFR247.2(d);
42 USC, sec. 6962 (c)(1)
4.5.6 DOE contractor purchase of certain designated items
shall be only of those composed of the highest
percentage of recovered material practicable,
consistent with maintaining a satisfactory level of
competition, unless the item is not available within a
reasonable length of time, fails to meet performance
standards, or is only available at an unreasonable
price.
DOE O 450.1, sec. 5.d.(11);
EO 13101, sec. 402;
40CFR247.6;
48CFR23.4;
42 USC sec. 6962(i)(2)
4.5.6.1 Chemical users shall support an affirmative
procurement program that must be developed
to ensure that designated items are procured
to the maximum extent possible and
consistent with provisions of the Federal
Acquisition Regulations (FAR). The
program shall contain at a minimum:
a) A preference program for purchasing
the designated items;
b) A program to promote the affirmative
procurement program;
c) Procedures for obtaining required
estimates of the total percentage of
recovered material utilized,
certification of minimum recovered
material content actually used (where
appropriate), and reasonable
verification procedures for estimates
and certification, and;
d) Annual review and monitoring of the
effectiveness of the program.
40CFR247.5;
48CFR23.4;
42 USC, sec. 6962, (i)(3)
4.5.6.1.1 In developing the preference
program described in 4.5.6.1(a),
above, the contractor shall consider
the following options:
a) a policy of awarding contracts
to vendors offering an item of
highest percentage of
recovered materials
practicable;
b) minimum recoverable
materials content
72
DOE-HDBK-1139/3-2003
Sources10 Consolidated Requirements
specifications which are set in
such a way as to assure the
recoverable materials content
required is the maximum
available without jeopardizing
the intended end use of the
item.
4.6 EPCRA (see definition)
40CFR372.22-38;
42 USC 13101;
42 USC 13306, (a) and (b)
4.6.1 Each owner or operator of a facility who is required
to file an annual toxic chemical release form under
40CFR372.22, “Covered Facilities for Toxic
Chemical Release Reporting”36 shall include a source
reduction and recycling report for the preceding
calendar year for the toxic chemicals on the report.
40CFR372.22-38;
42 USC 13101;
42 USC 13306, (a) and (b)
4.6.1.1 For each specified toxic chemical meeting
inventory threshold quantity, the source
reduction and recycling report must list:
a) The quantity released into the environment
Section 60
and the percentage change from the previous
year (including air emissions, discharge to
water/storm water, land, injection);
b) The quantity transferred offsite in waste (e.g.,
to a Publicly Owned Treatment Works or
Treatment, Storage, and Disposal Facility)
and the type of treatment or disposal used;
c) The amount of the chemical recycled (at the
facility or elsewhere), the percentage change
from the previous year, and the recycling
process used;
d) The amount of the chemical treated (at the
facility or elsewhere) during the year and the
percentage change from the previous year;
[NOTE: The specific chemical identity of Trade
Secrets may be withheld if the generic class or
category of the hazardous chemical, extremely
hazardous substance, or toxic chemical is
provided in its place.]
4.7 Ozone-Depleting Substances
DOE O 450.1, sec. 5.d.(10),
CRD 12;
4.7.1 Contractors shall develop and implement a program
and procedures to maximize the use of safe
36 These reporting requirements are threshold driven.
73
DOE-HDBK-1139/3-2003
Sources10 Consolidated Requirements
EO 13148, sec. 206
alternatives to ODS whereby:
a) procurement of Class I ODS for all non-excepted
uses37 is discontinued by December 31, 2010,
and
b) recovered/reclaimed ODS is transferred to DOD.
4.8 Recycling
DOE O 450.1;
EO 13101, Sec. 705(a)(1)
4.8.1 A program to promote cost-effective waste
prevention and recycling of reusable materials shall
be developed.
EO 13101, sec. 705(a)(2)
4.8.1.1 A recycling coordinator shall be designated
for each facility or installation.
EO 13101, sec. 705(a)(2)
4.8.1.1.1 The recycling coordinator shall
implement or maintain the waste
prevention and recycling programs.
5.0 Source Documents
DOE Acquisition Letter AL-2000-03, “Greening the Government Requirements in Contracting” (May
16, 2000) (Superceded by AL-2002-05).
DOE Acquisition Letter AL-2002-05, “Greening the Government Requirements in Contracting” (July
10, 2002).
DOE O 450.1, “Environmental Protection Program”.
Executive Order 13101 of September 14, 1998, “Greening the Government Through Waste
Prevention, Recycling, and Federal Acquisition”.
Executive Order 13148 of April 21, 2000, “Greening the Government Through Leadership in
Environmental Management”.
The Hazardous and Solid Waste Amendments of 1984 (HSWA).
Secretary of Energy Memorandum, November 12, 1999, “Pollution Prevention and Energy Efficiency
Leadership Goals for Fiscal Year 2000 and Beyond”.
40CFR260-282, “The Resource Conservation and Recovery Act of 1976”.
48CFR, “Federal Acquisition Regulations”.
42 USC 6901 – 6992(k), “The Solid Waste Disposal Act of Oct. 21, 1976”.
42 USC 13101 – 13109, “The Pollution Prevention Act of 1990”.
37 Non-excepted uses are developed by EPA under the Montreal Protocol and the Clean Air Act. Clarification of
non-excepted uses relevant to ODS is available from the DOE Office of Environmental Policy and Guidance (EH-
41) website at http://www.eh.doe.gov/oepa/guidance/ozone/.
74
DOE-HDBK-1139/3-2003
Chapter 8 - Chemical Emergency Management
1.0 Introduction
Section 61
This chapter identifies and consolidates existing user safety and health requirements found in DOE
and Federal chemical-related safety and health regulations and National Standards that address
emergency management for facilities with activities involving chemicals (see definition) and
chemical products (see definition). State and local codes and requirements are NOT included.
This chapter consolidates requirements found in the National Fire Protection Association (NFPA),
the Occupational Safety and Health Administration (OSHA), and certain Environmental Protection
Agency (EPA) regulations and Department of Energy (DOE) Rules and Orders, including technical
standards that are made mandatory by their specific reference within a regulation, rule or DOE
Order. It specifically consolidates requirements found in OSHA’s regulations 29CFR1910.38,
29CFR1910.119, 29CFR1910.120, 29CFR1910.1200, and 29CFR1910.1450, EPA’s regulations at
40CFR355 and 40CFR68, NFPA 471, 472, and 1620, and DOE O 151.1A.
This chapter is intended to list chemical-related safety and health requirements and to consolidate
those that are overlapping and/or duplicative. The list of requirements includes “pointers” to the
sources of those requirements.
This document does NOT create any new or additional requirements.
2.0 Applicability
The information presented here applies to all locations that use chemicals or chemical products.
[NOTE: Throughout this document, the term “chemicals” is used to indicate chemicals and/or
chemical products as described in Section 3, below.] This chapter consolidates existing, core safety
and health requirements that all sites must follow when engaged in chemical-related activities.
The requirements included in this chapter come from sources that have different safety purposes.
As a result, some of these requirements may not always be applicable to the work being performed
at an individual site or facility. It is the responsibility of each user to determine the applicability of
specific requirements to their work and how they are implemented. The reference sources for the
requirements included in this chapter can be used to determine the applicability of those
requirements to the work being performed.
3.0 Definitions and Acronyms
See Glossary.
4.0 Requirements for Chemical Emergency Management
Sources10 Consolidated Requirements
DOE O 151.1A, Chapter XI,
sec. 3 and sec. 4;
29CFR1910.38(a);
29CFR1910.119(n);
29CFR1910.120(q)
4.1 Emergency response plan - An emergency response plan shall be
prepared which documents the emergency management program
and the implementation procedures to handle anticipated
emergencies, including operational emergencies, prior to the
commencement of emergency response operations.
75
Link Technologies
Bill - Needs to be consistent with the previous sections. If these are sources they need to be in the Appendix. (This section is missing an Appendix)
DOE-HDBK-1139/3-2003
Sources10 Consolidated Requirements
40CFR68.95(b)
4.1.1 The plan shall include procedures for handling releases
and shall be in writing and available for inspection and
copying by employees, their representatives, and, where
applicable, OSHA personnel.
29CFR1910.38(a)
4.1.2 The plan shall cover those designated actions employers
and employees must take to ensure employee safety from
fire and other emergencies.
DOE O 151.1A Chapter III,
sec. 3.a
Section 62
4.1.3 A hazards survey (i.e., qualitative examination) shall be
used to identify the conditions to be addressed by the
comprehensive emergency management program. Much of
the hazards survey should already have been done in the
course of meeting other DOE and Federal agency
requirements.
DOE O 151.1A, Chapter III,
sec. 3.c(1);
DOE O 151.1A, Chapter III,
sec. 3.c(2);
DOE O 151.1A, Chapter III,
sec. 3.c(3);
DOE O 151.1A, Chapter III,
sec. 3.c(4);
DOE O 151.1A, Chapter III,
sec. 3.c(5);
DOE O 151.1A, Chapter III,
sec. 5.a(1);
DOE O 151.1A, Chapter IV,
sec. 1-4;
NFPA 471, Chapter 4;
NFPA 471, Chapter 638;
NFPA 471, 6.4;
NFPA 471, Chapter 9
NFPA 162039;
29CFR1910.38(a);
4.1.4 Elements of an emergency response plan.40 The
emergency response shall address, as a minimum, the
following areas:
• Pre-emergency planning and coordination with outside
parties such as State, Tribal, and local agencies.
• Personnel roles including Incident Commander, lines of
authority, training/competencies, and internal
communications (See NFPA 471, 6.4 for more detailed
requirements for internal communications.)
• Names or regular job titles of persons or departments
who can be contacted for further information or
explanation of duties under the plan [29CFR1910.38(a)].
• Emergency recognition including criteria for quickly
determining if an event is an Operational Emergency,
response levels (See NFPA 471, Chapter 4 for more
detailed requirements), and prevention.
• Emergency shutdown procedures and responsibilities
[29CFR1910.38(a)].
• Re-entry planning shall include contingency planning to
ensure the safety of re- entry personnel, such as planning
for the rescue of re-entry teams.
38 NFPA 471, Chapter 6 requires site safety considerations including a personnel accountability system, provisions
for rest and rehabilitation for responders, the elimination of all ignition sources, and the application of control zones.
39 Emergency response organizations may use the local emergency response plan or the state emergency response
plan or both, as part of their emergency response plan to avoid duplication. Those items of the emergency response
plan that are being properly addressed in the SARA Title III plans may be included in the emergency response plan,
or otherwise made available to employees.
40 NFPA 1620 provides extensive details on pre-incident planning that involves the evaluation of protection systems,
building construction, contents, and operating procedures that can impact emergency operations. Major topics
include physical elements and site considerations, occupant considerations, protection systems and water supplies,
special hazard considerations, emergency operations, and plan testing and maintenance.
76
DOE-HDBK-1139/3-2003
Sources10 Consolidated Requirements
29CFR1910.120(q)(2);
40CFR68.95(a)(1)(i)
• Continued operation of critical plant function].
• Safe distances and places of refuge.
• Site security and control.
• Evacuation routes and procedures including accounting
for all employees after the emergency evacuation has
been completed.
• Decontamination (See NFPA 471, Chapter 9 for more
detailed requirements).
• Rescue and Emergency medical treatment and first aid.
• Emergency alerting, reporting and response procedures
[29CFR1910.38(a)] including prompt initial notification
of workers, emergency response personnel, and response
organizations, including DOE elements and State,
Tribal, local organizations, and the public with
continued effective communications throughout
emergency as part of an pre-established Emergency
Public Information Program.
Section 63
• PPE and emergency equipment.
29CFR1910.38(a)(5)(ii)(A),(B),
and (C);
40CFR68.95(a)(4)
4.1.5 Plan Review - The employer shall review the plan with each
employee covered by the plan when the plan is developed;
whenever the employee's responsibilities or designated
actions under the plan change; and whenever the plan is
changed.
4.1.6 Posting.
29CFR1910.38(a)(5)(iii)
4.1.6.1 The written plan shall be kept at the workplace and
made available for employee review.
29CFR1910.1200
4.1.6.2 Material Safety data Sheets (MSDS) shall contain
emergency procedures.
DOE O 151.1A, Chapter III,
sec. 4.a;
29CFR1200(h)(3)(iii);
29CFR1450(f)(4)(i)(C);
29CFR1910.120(q)(6);
40CFR68.95(a)(3)
4.2 Training
• Training and other emergency information on site-specific
conditions and hazards shall be made available to offsite
personnel who may be required to participate in response to
an emergency at the DOE or NNSA site/facility.
• To ensure the competencies of all responders, training shall
be based on the duties and function to be performed by
each responder of an emergency response organization. The
skill and knowledge levels required for all new responders
shall be conveyed to them through training before they are
permitted to take part in actual emergency response to an
incident. Employees who participate, or who are expected
to participate, in emergency response, shall be trained as
described below.
77
DOE-HDBK-1139/3-2003
Sources10 Consolidated Requirements
NFPA 472, Chapter 441;
29CFR1910.120(q)(6)(i)
4.2.1 First Responder – Awareness Level (See definition, Section
3 above, for definitions of this and other levels of
emergency personnel). Shall have sufficient training, or
have had sufficient experience to objectively demonstrate
competencies that include, but are not limited to:
• An understanding of what hazardous substances are, and
the risks associated with them in an incident.
• An understanding of the potential outcomes associated
with an emergency created when hazardous substances
are present.
• The ability to recognize the presence of hazardous
substances in an emergency.
• The ability to identify the hazardous substances.
• An understanding of the role of the first responder
awareness individual in the employer's emergency
response plan including site security and control and
the U.S. Department of Transportation's Emergency
Response Guidebook.
• The ability to realize the need for additional resources,
and to make appropriate notifications to the incident
response communication center.
NFPA 472, Chapter 542;
29CFR1910.120(q)(6)(ii)
4.2.2 First Responder -Operations Level. In addition to the
competencies listed for the awareness level, the employer
shall certify that the first responders at the operational level
have received at least eight hours of training or have had
sufficient experience to objectively demonstrate
competencies that include, but are not limited to:
• Knowledge of the basic hazard and risk assessment
techniques.
• Know how to select and use proper personal protective
equipment provided to the first responder operational
level.
• An understanding of basic hazardous materials terms.
• Know how to perform basic control, containment
and/or confinement operations within the capabilities of
the resources and personal protective equipment
available with their unit.
• Know how to implement basic decontamination
procedures.
• An understanding of the relevant standard operating
procedures and termination procedures.
Section 64
41 Details on these and other required competencies are found in NFPA 472, Chapter 4.
42 Details on these and other required competencies are found in NFPA 472, Chapter 5.
78
DOE-HDBK-1139/3-2003
Sources10 Consolidated Requirements
NFPA 472, Chapter 643;
29CFR1910.120(q)(6)(iii)
4.2.3 Hazardous Materials Technician - The employer shall
certify that the hazardous materials technicians have
received at least 24 hours of training equal to the first
responder operations level and in addition have
competencies including, but not limited to:
• Knowing how to implement the employer's emergency
response plan.
• Knowing the classification, identification and
verification of known and unknown materials by using
field survey instruments and equipment.
• Being able to function within an assigned role in the
Incident Command System.
• Knowing how to select and use proper specialized
chemical personal protective equipment provided to the
hazardous materials technician.
• Understanding hazard and risk assessment techniques.
• Being able to perform advance control, containment,
and/or confinement operations within the capabilities of
the resources and personal protective equipment
available with the unit. Understanding and being able to
implement decontamination procedures.
• Understand termination procedures.
• Understanding basic chemical and toxicological
terminology and behavior.
29CFR1910.120(q)(6) 4.2.4 Hazardous materials specialists shall have received at least
24 hours of training equal to the technician level and in
addition have competency in the following areas and the
employer shall so certify:
• Know how to implement the local emergency response
plan.
• Understand classification, identification and
verification of known and unknown materials by using
advanced survey instruments and equipment.
• Know the state emergency response plan.
• Be able to select and use proper specialized chemical
personal protective equipment provided to the
hazardous materials specialist.
• Understand in-depth hazard and risk techniques.
• Be able to perform specialized control, containment,
and/or confinement operations within the capabilities of
the resources and personal protective equipment
available.
• Be able to determine and implement decontamination
procedures.
43 Details on these and other required competencies are found in NFPA 472, Chapter 6.
79
DOE-HDBK-1139/3-2003
Sources10 Consolidated Requirements
• Have the ability to develop a site safety and control
plan.
• Understand chemical, radiological and toxicological
terminology and behavior.
NFPA 472, Chapter 9 4.2.5 Hazardous materials branch officer must demonstrate
competencies including, but not limited to:
• Ability to analyze the magnitude of the problem and
estimate the potential outcomes.
• Know how to plan a response taking into account the
abilities of the available personnel and equipment.
• Ability to implement a response that will improve the
outcomes consistent with standard operating procedures
and the local emergency response plan.
• Know how to evaluate the on-going progress of the
plan implementation and to adjust the plan accordingly.
• Know how and when to terminate the incident
including, critiques, debriefings, and reports.
NFPA 472, Chapter 10 4.2.6 Safety officer (also known as Hazardous Materials Branch
Safety Officer in NFPA) must demonstrate competencies
including, but not limited to the ability to:
• Determine the magnitude of the safety problems
Section 65
involved in the incident.
• Identify the safety considerations for the response plan.
• Monitor the safety of personnel involved in the
response.
• Evaluate the progress of the plan implementation as to
deviations from safety considerations.
• Upon incident termination, provide reports, debriefings,
and critique of safety.
NFPA 472, Chapter 744;
29CFR1910.120(q)(6)
4.2.7 Incident commander - The employer shall certify that the
incident commanders have received at least 24 hours of
training equal to the first responder operations level and, in
addition, have competencies including, but not limited to:
• Know and be able to implement the employer's incident
command system.
• Know how to implement the employer's emergency
response plan.
• Know and understand the hazards and risks associated
with employees working in chemical protective
clothing.
• Know how to implement the local emergency response
plan.
44 Details on these and other required competencies are found in NFPA 472, Chapter 7.
80
DOE-HDBK-1139/3-2003
Sources10 Consolidated Requirements
• Know of the state emergency response plan and of the
Federal Regional Response Team.
• Know and understand the importance of
decontamination procedures.
NFPA 472, Chapters 11,12,
and 1345;
29CFR1910.120(q)(4)
4.2.7 Skilled support personnel shall be given an initial briefing
at the site before their participation in any emergency
response. The initial briefing shall include instruction in
the wearing of appropriate personal protective equipment,
what chemical hazards are involved, and what duties are to
be performed. All other appropriate safety and health
precautions provided to the employer's own employees
shall be used to assure the safety and health of these
personnel.
29CFR38(a)(5)(i)
4.2.9 Employee Protection Training and Drills
DOE O 151.1A, Chapter III,
sec. 4a
4.2.9.1 Employee information, training, and drills shall
include measures employees can take to protect
themselves from exposure to chemicals in
emergencies, including specific emergency
procedures the employer has implemented to
protect employees. This training is required when
they are employed, when their expected actions
change, or when the emergency plan changes.
DOE O 151.1A, Chapter IV,
sec. 4a
4.2.9.2 Drills shall provide supervised, "hands-on" training
for members of emergency response organizations.
29CFR1910.38(a)(5)(1) 4.2.9.3 Before implementing the emergency action plan,
the employer shall designate and train a sufficient
number of persons to assist in the safe and orderly
emergency evacuation of employees.
29CFR1910.120(q)(7)
4.2.10 Trainers shall have either:
• Satisfactorily completed a training course for
teaching the subjects they are expected to teach, such
as the courses offered by the U.S. National Fire
Academy, OR,
• the training and/or academic credentials and
instructional experience necessary to demonstrate
competent instructional skills and a good command
of the subject matter of the courses they are to teach.
45 NFPA 472 identifies three such skilled support personnel and specifies, in detail, their required competencies: 1)
tank car specialist (Chapter 11), 2) cargo tank specialist (Chapter 12), and 3) intermodal tank specialist (Chapter 13).
In general, they must be able to analyze the incident, plan the response, and implement the plan.
81
DOE-HDBK-1139/3-2003
Sources10 Consolidated Requirements
29CFR1910.120(q)(8) 4.2.11 Refresher training
DOE O 151.1A, Chapter IV,
sec. 4a;
Section 66
29CFR1910.120(q)(8)
4.2.11.1 Those employees who are trained in
accordance with paragraph 4.2 of this chapter
shall receive annual refresher training of
sufficient content and duration to maintain their
competencies, or shall demonstrate competency
in those areas at least yearly.
29CFR1910.120(q)(8)
4.2.11.2 A statement shall be made of the training (and
retraining) or competency, and if a statement of
competency is made, the employer shall keep a
record of the methodology used to demonstrate
competency.
DOE O 151.1A, Chapter III,
sec. 4.b
4.2.12 Exercises
• At a minimum, each site/facility shall conduct
building evacuation exercises consistent with Federal
regulations [e.g., 41CFR101-20.105-1(c)(1)], local
ordinances, or National Fire Protection Association
Standards. Exercises shall be conducted as often as
needed to ensure that employees are able to safely
evacuate their work area.
• For each site or facility, as applicable, the
organization responsible for communications with
DOE Headquarters, operations/field offices, and
offsite agencies shall test communications systems at
least annually or as often as needed to ensure that
communications systems are operational.
DOE O 151.1A, Attachment 1,
#1
4.3 Implementation – A comprehensive emergency management plan,
commensurate With the hazards present, shall be implemented at
the site/facility/activity level.
DOE O 151.1A, Attachment 1,
#9;
NFPA 471, Chapter 646;
NFPA 471, Chapter 847
4.3.1. Ensure immediate mitigative and corrective emergency
response actions and appropriate protective actions to
minimize the consequences of the emergency, protect
worker and public health and safety, provide security, and
ensure the continuance of such actions until the emergency
is declared terminated.
46 Also see NFPA 471, Chapter 6, for site safety requirements during an emergency.
47 NFPA 471, Chapter 8, has details on numerous physical and chemical means of mitigating the incident.
82
DOE-HDBK-1139/3-2003
Sources10 Consolidated Requirements
DOE O 151.1A,Chapter III,
sec. 3.c(1);
29CFR1910.120(q)(3)(i)
4.3.2 The senior emergency response official responding to an
emergency shall become the Incident Commander (IC). All
emergency responders and their communications shall be
coordinated and controlled through the IC assisted by the
senior official present or by each employer.
4.3.3 The IC shall identify, to the extent possible, all hazardous
substances or conditions present and shall address as
appropriate site analysis, use of engineering controls,
maximum exposure limits, hazardous substance handling
procedures, and use of any new technologies. The IC shall
also implement appropriate emergency operations and
assure that the personal protective equipment worn is
appropriate for the hazards encountered.
4.3.4 Employees engaged in emergency response and exposed to
hazardous substances, which present an inhalation hazard
or potential inhalation hazard, shall wear positive pressure
self-contained breathing apparatus while engaged in
emergency response, until such time that the IC determines
through the use of air monitoring that a decreased level of
respiratory protection will not result in hazardous exposures
to employees.
DOE O 151.1A, Chapter III,
sec. 5.a (1)
4.3.5 All individuals involved in re-entry shall receive a
hazards/safety briefing prior to emergency response
activities consistent with Federal, State, and local laws and
regulations.
Section 67
4.3.6 The IC shall limit the number of emergency response
personnel at the emergency site, in those areas of potential
or actual exposure to incident or site hazards, to those who
are actively performing emergency operations. However,
operations in hazardous areas shall be performed using the
buddy system in groups of two or more.
4.3.7 Back-up personnel shall be standing by with equipment
ready to provide assistance or rescue. Qualified basic life
support personnel, as a minimum, shall also be standing by
with medical equipment and transportation capability.
29CFR1910.120(q)(3)(vii)
29CFR1910.120(q)(3)(ii) and
(iii)
29CFR1910.120(q)(3)(iv)
29CFR1910.120(q)(3)(v)
29CFR1910.120(q)(3)(vi)
4.3.8 The IC shall designate a safety officer, who is
knowledgeable in the operations being implemented at the
emergency response site, with specific responsibility to
identify and evaluate hazards and to provide direction with
respect to the safety of operations for the emergency at
hand.
83
http://www.nfpa.org/
http://www.nfpa.org/
http://www.nfpa.org/
http://www.nfpa.org/
http://www.nfpa.org/
http://www.nfpa.org/
http://www.nfpa.org/
http://www.nfpa.org/
http://www.nfpa.org/
http://www.nfpa.org/
http://www.nfpa.org/
http://www.nfpa.org/
DOE-HDBK-1139/3-2003
Sources10 Consolidated Requirements
29CRF1910.120(q)(3)(viii) 4.3.9 When activities are judged by the safety officer to be an
IDLH (immediate danger in life or health) and/or to involve
an imminent danger condition, the safety officer shall have
the authority to alter, suspend, or terminate those activities.
The safety official shall immediately inform the IC of any
actions needed to be taken to correct these hazards at the
emergency scene.
29CFR1910.120(q)(3)(x)
4.3.10 When deemed necessary by the safety officer for meeting
the tasks at hand, approved self-contained compressed air
breathing apparatus may be used with approved cylinders
from other approved self-contained compressed air
breathing apparatus provided that such cylinders are of the
same capacity and pressure rating. All compressed air
cylinders used with self-contained breathing apparatus shall
meet U.S. Department of Transportation (USDOT) and
National Institute for Occupational Safety and Health
(NIOSH) criteria.
40CFR355.40(b)(1);
40CFR355.40(b)(4)(ii)
4.3.11 In addition, if extremely hazardous chemicals are released,
the owner or operator of a facility subject to this section
shall immediately notify the community emergency
coordinator for the LEPC of any area likely to be affected
by the release and the State emergency response
commission of any State likely to be affected by the
release. If there is no LEPC, notification shall be provided
under this section to relevant local emergency response
personnel (LERP).
[EXCEPTION: An owner or operator of a facility from
which there is a transportation-related release may meet
the requirements of this section by providing the
information indicated below in paragraph 4.3.11.1 to the
911 operators, or in the absence of a 911 emergency
telephone number, to the telephone operator. A
transportation-related release means a release during
transportation or storage incident to transportation if the
stored substance is moving under active shipping papers
and has not reached the ultimate consignee.]
40CFR355.40(b)(2)
4.3.11.1 The notice required under this section shall
include the following to the extent known at the
time of notification and so long as no delay in
notification of emergency response results:
a) The chemical name or identity of any
Section 68
substance involved in the release.
b) An indication of whether the substance is an
extremely hazardous substance.
DOE O 151.1A, Chapter III,
sec. 3.c(5);
84
http://www.nfpa.org/
http://www.nfpa.org/
http://www.nfpa.org/
http://www.nfpa.org/
http://www.nfpa.org/
http://www.nfpa.org/
http://www.nfpa.org/
http://www.nfpa.org/
http://www.nfpa.org/
http://www.nfpa.org/
http://www.nfpa.org/
http://www.nfpa.org/
http://www.nfpa.org/
http://www.nfpa.org/
http://www.nfpa.org/
http://www.nfpa.org/
http://www.nfpa.org/
http://www.nfpa.org/
http://www.nfpa.org/
http://www.nfpa.org/
http://www.nfpa.org/
http://www.nfpa.org/
http://www.nfpa.org/
DOE-HDBK-1139/3-2003
Sources10 Consolidated Requirements
c) An estimate of the quantity of any such
substance that was released into the
environment.
e) The medium or media into which the release
occurred.
f) Any known or anticipated acute or chronic
health risks associated with the emergency
and, where appropriate, advice regarding
medical attention necessary for exposed
individuals.
g) Proper precautions to take as a result of the
release, including evacuation (unless such
information is readily available to the
community emergency coordination pursuant
to the emergency plan).
h) The names and telephone number of the
person or persons to be contacted for further
information.
a) Actions taken to respond to and contain the
release,
b) Any known or anticipated acute or chronic
health risks associated with the release, and,
c) Where appropriate, advice regarding medical
attention necessary for exposed individuals.
DOE O 151.1A, Chapter IV,
sec. 4.b-4.i • During the response phase of an emergency, shall
cooperatively ensure that an adequate public
information program is established and maintained,
commensurate with site hazards, to ensure that
information can be provided to the public and the
media during an emergency. The emergency public
information program shall be adequately staffed with
personnel trained to serve as spokesperson and news
writer, and to provide support in media services,
public inquiry, media inquiry, Joint Information
Center management and administrative activities, and
media monitoring. Persons with technical expertise
d) The time and duration of the release.
4.3.11.2 As soon as practicable after a release which
requires notification under 4.3.11 herein, such
owner or operator shall provide a written follow-
up emergency notice (or notices, as more
information becomes available) setting forth and
updating the information required under
paragraph 4.3.11.1 of this section, and including
additional information with respect to:
40CFR355.40(b)(3)
4.3.12 Public Information
85
http://www.nfpa.org/
http://www.nfpa.org/
http://www.nfpa.org/
http://www.nfpa.org/
http://www.nfpa.org/
http://www.nfpa.org/
http://www.nfpa.org/
http://www.nfpa.org/
http://www.nfpa.org/
http://www.nfpa.org/
http://www.nfpa.org/
DOE-HDBK-1139/3-2003
Sources10 Consolidated Requirements
about the emergency and with spokesperson training
shall also be assigned to the emergency public
information staff.
• In situations involving classified information, the
Department will provide sufficient unclassified
information to explain the emergency response and
protective actions required for the health and safety
of workers and the public.
• An information officer shall be assigned to the
emergency public information response team
involved in a significant offsite response deployment
Section 69
• A Headquarters official or team shall provide support
to the affected Program Offices/ Emergency
Management Team and/or requesting operations/field
office, as appropriate.
• The Director of Public Affairs and the Headquarters
Emergency Manager shall be informed of all DOE or
NNSA emergency public information actions
• An emergency public information communications
system shall be established among Headquarters,
operations/field office, and on-scene locations.
DOE O 151.1A, Chapter IV;
29CFR1910.119;
40CFR68.130;
40CFR355
4.4 Additional Requirements for Significant Quantities of
Hazardous Chemicals - The Operational Emergency
Hazardous Material Program adds to the base program.
Depending on the findings of the hazards survey DOE or NNSA
sites/facilities may be required to establish and maintain a
quantitative hazards assessment, which will be used to define
the provisions of the Operational Emergency Hazardous
Material Program to ensure the program is commensurate with
the hazards identified. Such hazards assessments are required if
the hazard survey identifies hazardous materials in quantities
exceeding the lower of the Threshold Quantities listed in
29CFR1910.119, or 40CFR68.130, or 40CFR355.
DOE O 151.1A, Chapter IV,
sec. 3b(2) and 5a
4.4.1 Emergency Classification – Provisions shall be established
to categorize and classify emergency events. Events shall
be classified based on potential severity of the
consequences as detailed in Chapter IV of DOE O 151.1A.
• Initial news releases or public statements shall be
approved by the DOE or NNSA official responsible
for emergency public information review and
dissemination. Following initial news releases and
public statements, updates shall be coordinated with
the Director of Public Affairs.
86
http://www.nfpa.org/
http://www.nfpa.org/
http://www.nfpa.org/
http://www.nfpa.org/
http://www.nfpa.org/
http://www.nfpa.org/
http://www.nfpa.org/
DOE-HDBK-1139/3-2003
Sources10 Consolidated Requirements
DOE O 232.1A;
40CFR355.30
4.4.2 Emergency Planning Notification
DOE O 151.1A, Chapter III,
sec. 3c(2);
40CFR355.30(a)
4.4.2.1 The owner or operator of a facility subject to this
section shall notify the Commission that it is a
facility subject to the emergency planning
Requirements of this part. Such notification shall be
within sixty days after a facility first becomes
subject to the requirements of this section,
whichever is later.
40CFR68.12(b)(3);
40CFR355.30(c)
4.4.2.2 The owner or operator of a facility subject to this
section shall designate a facility representative who
will participate on the local emergency planning
committee (LEPC) as a facility emergency response
coordinator.
40CFR355.30(d)(1)
4.4.2.3 The owner or operator of a facility subject to this
section shall inform the LEPC of any changes
occurring at the facility which may be relevant to
emergency planning.
40CFR355.30(d)(2)
4.4.2.4 Upon request of the local emergency planning
committee, the owner or operator of a facility
subject to this section shall promptly provide to
the LEPC any information necessary for
development or implementation of the local
emergency plan.
87
http://www.nfpa.org/
http://www.nfpa.org/
http://www.nfpa.org/
http://www.nfpa.org/
http://www.nfpa.org/
http://www.nfpa.org/
http://www.nfpa.org/
http://www.nfpa.org/
http://www.nfpa.org/
http://www.nfpa.org/
http://www.nfpa.org/
http://www.nfpa.org/
http://www.nfpa.org/
http://www.nfpa.org/
http://www.nfpa.org/
http://www.nfpa.org/
http://www.nfpa.org/
http://www.nfpa.org/
http://www.nfpa.org/
http://www.nfpa.org/
Section 70
DOE-HDBK-1139/3-2003
Sources10 Consolidated Requirements
40CFR355.30(e) 4.4.3 Calculation of threshold planning quantities (TPQs) for
solids and mixtures
40CFR355.30(e)(1) 4.4.3.1 If a container or storage vessel holds a mixture or
solution of an extremely hazardous substance, then
the concentration of extremely hazardous substance,
in weight percent (greater than 1 percent), shall be
multiplied by the mass (in pounds) in the vessel to
determine the actual quantity of extremely hazardous
substance therein.
40CFR355.30(e)(2) 4.4.3.2 Extremely hazardous substances that are solids are
subject to either of two threshold planning quantities
as shown in appendices A and B of 40CFR355 (i.e.,
500 or 10,000 pounds). The lower quantity applies
only if the solid exists in powdered form and has a
particle size less than 100 microns ; or is handled in
solution or in molten form ; or meets the criteria
for an NFPA rating of 2, 3 or 4 for reactivity. If the
solid does not meet any of these criteria, it is subject
to the upper (10,000 pound) threshold planning
quantity as shown in appendices A and B of
40CFR355.
48
50
DOE O 151.1A, Chapter IV,
sec. 3b(5)
4.4.4 Provisions shall be established to adequately assess the
potential or actual on and offsite consequences of an
emergency. Consequence assessments shall (a) be timely
throughout the emergency; (b) be integrated with the event
classification and protective action process; (c) incorporate
monitoring of specific indicators and field measurements; and
(d) be coordinated with Federal, State, local, and Tribal
organizations.
sec. 4b
4.4.5 A formal exercise program shall be established to validate all
elements of the emergency management program over a multi-
year period. Each exercise shall have specific objectives and
shall be fully documented. Exercises shall be evaluated using
an established critique process. Corrective actions shall be
identified and incorporated into the program.
DOE O 151.1A, Chapter VIII,
sec. 2a
49
DOE O 151.1A, Chapter IV,
4.4.6 Provisions shall be established for prompt initial
notification of workers and emergency response personnel
and organizations, including appropriate DOE and NNSA
elements and other Federal, State, Tribal, and local
48 The 100 micron level may be determined by multiplying the weight percent of solid with a particle size less than
100 microns in a particular container by the quantity of solid in the container.
49 The amount of solid in solution may be determined by multiplying the weight percent of solid in the solution in a
particular container by the quantity of solution in the container.
50 The amount of solid in molten form must be multiplied by 0.3 to determine whether the lower threshold planning
quantity is met.
88
http://www.nfpa.org/
http://www.nfpa.org/
http://www.nfpa.org/
http://www.nfpa.org/
http://www.nfpa.org/
http://www.nfpa.org/
http://www.nfpa.org/
DOE-HDBK-1139/3-2003
Sources10 Consolidated Requirements
organizations. Provisions shall also be established for
continuing effective communication among the response
organizations throughout an emergency.
4.4.6.1 Adherence to notification and reporting requirements
shall be demonstrated in all emergency management
exercises.
DOE O 151.1A, Chapter VIII,
sec. 3
4.4.6.2 Initial emergency notifications shall be made to
workers, emergency response personnel, and
organizations, including DOE and NNSA elements
and other local, State, Tribal, and Federal
organizations.
Section 71
DOE O 151.1A, Chapter VIII,
sec. 4.a
4.4.6.3 Notify State and local officials and the DOE or NNSA
Field and Headquarters Emergency Operations
Centers within 15 minutes and all other organizations
within 30 minutes of the declaration of an Alert, Site
Area Emergency, or General Emergency.
DOE O 151.1A, Chapter VIII,
sec. 4.a(1)(a)
4.4.6.4 Notify the DOE or NNSA Field and Headquarters
Emergency Operations Centers within 30 minutes of
the declaration of an other than hazardous material
Operational Emergency.
DOE O 151.1A, Chapter VIII,
sec. 4.a(1)(b)
4.4.6.5 Notify local, State, and Tribal organizations within 30
minutes or as established in mutual agreements for
declaration of an other than hazardous material
Operational Emergency.
DOE O 151.1A, Chapter VIII,
sec. 4.a(1)(c)
4.4.6.6 Headquarters Watch Office staff in the Headquarters
Emergency Operations Center and Headquarters
Emergency Management Team personnel shall be
responsible for the following:
DOE O 151.1A, Chapter VIII,
sec. 4.a(2);
DOE O 151.1A, Chapter VIII,
sec. 4.a(2)(a);
DOE O 151.1A, Chapter VIII,
sec. 4.a(2)(b)
• Record incoming verbal notifications, receive
emergency event information by other data
transmission means or mechanisms, and
disseminate such information to Cognizant
Secretarial Officer representatives and appropriate
Headquarters organizations of other Federal
agencies.
• Facilitate communications among Headquarters
organizations, DOE and NNSA field
organizations, and contractor personnel.
DOE O 151.1A, Chapter VIII,
4.b
4.4.6.7 Emergency status reports shall be forwarded to the
next-higher Emergency Management Team on a
continuing basis until the emergency is terminated.
89
DOE-HDBK-1139/3-2003
Sources10 Consolidated Requirements
4.4.6.8 Effective communications methods shall be
established between event scene responders,
emergency managers, and response facilities.
DOE O 151.1A, Chapter VIII,
sec. 4.c
4.5 Emergency Equipment and Facilities - Provision of facilities and
equipment adequate to support emergency response, including:
• the capability to notify employees of an emergency to
facilitate the safe evacuation of employees from the work
place, immediate work area, or both; and
DOE O 151.1A, Chapter III,
sec. 3.c(8);
DOE O 151.1A, Chapter IV,
sec. 9.c;
29CFR1910.120(q)(10); • operable personal protective equipment and clothing (PPE)
to be used by organized and designated HAZMAT team
members, or to be used by hazardous materials specialists.
PPE shall meet the needs determined by the hazards
assessment and the requirements noted in sections 4.5.1
through 4.5.5, below.
40CFR68.95(a)(2)
29CFR1910.120(g)(3)(i) and
(ii)
4.5.1 PPE shall be selected and used which will protect employees
from the hazards and potential hazards they are likely to
encounter as identified during the emergency characterization
and analysis.
4.5.2 Positive pressure self-contained breathing apparatus, or
positive pressure air-line respirators equipped with an escape
air supply shall be used when chemical exposure levels
present will create a substantial possibility of immediate
death, immediate serious illness or injury, or impair the
ability to escape.
29CFR1910.120(g)(3)(iii)
29CFR1910.120(g)(3)(iv)
4.5.3 Totally-encapsulating chemical protective suits (protection
equivalent to Level A protection as recommended in
Appendix B of 29CFR1910.120) shall be used in conditions
where skin absorption of a hazardous substance may result in
a substantial possibility of immediate death, immediate
serious illness or injury, or impair the ability to escape.
Section 72
29CFR1910.120(g)(4)(iii) 4.5.3.1 Totally encapsulating suits shall be capable of
maintaining positive air pressure, and preventing
inward test gas leakage of more than 0.5 percent 51.
51 See Appendix A of 29CFR1910.120 for a test method which may be used to evaluate this requirement.
90
DOE-HDBK-1139/3-2003
Sources10 Consolidated Requirements
4.5.4 The level of protection provided by PPE selection shall be
increased when additional information or emergency
conditions show that increased protection is necessary to
reduce employee exposures below permissible exposure
limits and published exposure levels for hazardous substances
and health hazards. (See Appendix B of 29CFR1910.120 for
guidance on selecting PPE ensembles.)
29CFR1910.120(g)(3)(v);
29CFR1910.120, Appendix B
[EXCEPTION: The level of employee protection provided
may be decreased when additional information or site
conditions show that decreased protection will not result in
hazardous exposures to employees.]
NFPA 471, Chapter 7 ; 52
29CFR1910.120(g)(3)(vi);
29CFR1910.120(g)(5);
29CFR1910, Subpart I
4.5.5 At a minimum, all personal protective equipment shall be
selected and used to meet the following elements:
• PPE selection based upon site hazards,
• PPE use and limitations of the equipment,
• Work mission duration,
• PPE maintenance and storage,
• PPE decontamination and disposal,
• PPE training and proper fitting,
• PPE inspection procedures prior to, during, and after use,
• Evaluation of the effectiveness of the PPE program, and
• Limitations during temperature extremes, heat stress, and
other appropriate medical considerations.
sec. 3.c(6);
40CFR68.95(a)(1)(ii)
4.6 Medical Support
• Medical treatment and planning for mass casualty situations
shall be provided in accordance with DOE O 440.1A.
• Internal medical consultation and surveillance shall be as noted
in sections 4.6.1 through 4.6.8, below.
29CFR1910.120(q)(9)(I)
4.6.1 Members of an organized and designated HAZMAT team and
hazardous materials specialists shall receive a baseline
physical examination which shall be performed as described
below in sections 4.6.2 through 4.6.8.
• PPE donning and doffing procedures,
DOE O 151.1A, Chapter III,
52 NFPA 471 Chapter 7, has additional details on personal protective equipment requirements including four levels
protection: A – when highest level of respiratory, skin, and eye protection is required; B – when the highest
respiratory protection is required, but lesser skin protection is needed; C – when the concentration of airborne
contaminants is known and air purifying respirators are required; D – when only nuisance contamination exists.
Note: There are numerous other NFPA requirements for PPE, many of which are cited in NFPA 471, Chapter 7.
91
http://www.explorer.doe.gov/
http://www.explorer.doe.gov/
http://www.explorer.doe.gov/
http://www.explorer.doe.gov/
http://www.explorer.doe.gov/
DOE-HDBK-1139/3-2003
Sources 10 Consolidated Requirements
NFPA 471, Chapter 1053;
29CFR1910.1450(g)(1)(iii)
• as soon as possible following the emergency incident or
development of signs or symptoms;
• at additional times, if the examining physician
determines that follow-up examinations or consultations
are medically necessary.
29CFR1910.120(f)(4)
Section 73
4.6.3 Medical examinations required by section 4.6 shall include a
medical and work history (or updated history if one is in the
employee's file) with special emphasis on symptoms related
to the handling of hazardous substances and health hazards,
and to fitness for duty including the ability to wear any
required PPE under conditions (i.e., temperature extremes)
that may be expected at the work site. The content of medical
examinations or consultations made available to employees
shall be determined by the attending physician. The
guidelines in the Occupational Safety and Health Guidance
Manual for Hazardous Waste Site Activities should be
consulted.
29CFR1910.1200(i)(2)
4.6.4 Where a treating physician or nurse determines that a medical
emergency exists and the specific chemical identity is
necessary for emergency or first-aid treatment, the chemical
manufacturer, importer, or employer shall immediately
disclose the specific chemical identity of a trade secret
chemical to that treating physician or nurse, regardless of the
existence of a written statement of need or a confidentiality
agreement. The chemical manufacturer, importer, or
employer may require a written statement of need and
confidentiality agreement as soon as circumstances permit.
29CFR1910.120(f)(5)
4.6.5 All medical examinations and procedures shall be performed
by or under the supervision of a licensed physician,
preferably one knowledgeable in occupational medicine, and
shall be provided without cost to the employee, without loss
of pay, and at a reasonable time and place.
4.6.2 Any emergency response employees who exhibit signs or
symptoms which may have resulted from exposure to
hazardous substances during the course of an emergency
incident either immediately or subsequently and all
employees who are injured, become ill or develop signs or
symptoms due to possible overexposure involving hazardous
substances or health hazards from an emergency response,
shall be provided with medical consultation as follows:
53 NFPA 471, Chapter 10, addresses not only post-entry medical examination requirements, but also requires pre-
entry, during entry, follow-up, and treatment procedures.
92
DOE-HDBK-1139/3-2003
Sources10 Consolidated Requirements
29CFR1910.120(f)(6);
29CFR1910.134
4.6.6 The employer shall provide one copy of 29CFR1910.120 and
its appendices to the attending physician and in addition the
following for each employee:
• a description of the employee's duties as they relate to
the employee's exposures;
• the employee's exposure levels or anticipated exposure
levels;
• a description of any personal protective equipment used
or to be used;
• information from previous medical examinations of the
employee which is not readily available to the
examining physician; and,
• information required by 29CFR1910.134 (Respiratory
Protection).
29CFR1910.120(f)(7)
4.6.7 The employer shall obtain and furnish the employee with a
copy of a written opinion from the examining physician. The
written opinion obtained by the employer shall not reveal
specific findings or diagnoses unrelated to occupational
exposure, but shall contain the following:
• the physician's opinion as to whether the employee has
any detected medical conditions which would place the
employee at increased risk of material impairment of the
employee's health from work in hazardous waste
operations or emergency response, or from respirator
use;
• the physician's recommended limitations upon the
employees assigned work;
Section 74
• the results of the medical examination and tests if
requested by the employee; and,
• a statement that the employee has been informed by the
physician of the results of the medical examination and
any medical conditions which require further
examination or treatment.
29CFR1910.120(f)(8);
29CFR1910.1020
4.6.8 An accurate record of the medical surveillance required by
this section shall be retained. This record shall be retained for
the period specified and meet the criteria of 29CFR1910.20.
The record required of this section shall include at least the
following information:
• the name and social security number of the employee;
• physicians' written opinions, recommended limitations
and results of examinations and tests;
• any employee medical complaints related to exposure to
hazardous substances; and,
• a copy of the information provided to the examining
physician by the employer, with the exception of the
standard and its appendices.
93
DOE-HDBK-1139/3-2003
Sources10 Consolidated Requirements
DOE O 151.1A, Chapter IV,
sec. 5b
4.7 Post-Incident Requirements – Predetermined criteria for
termination of emergencies shall be established.
29CFR1910.120(b)–(o);
29CFR1910.120(q)(3)(ix);
29CFR1910.120(q)(11)
4.7.1 After emergency operations have terminated, the IC shall
implement appropriate decontamination procedures. If it is
determined that it is necessary to remove hazardous
substances, health hazards and materials contaminated with
them (such as contaminated soil or other elements of the
natural environment) from the site of the incident, the
employer conducting the clean-up shall comply with one of
the following:
• meet all the requirements of paragraphs (b) through (o)
of 29CFR1910.120 ; OR
• where the clean-up is done on plant property using plant
or workplace employees, such shall have completed the
training requirements of section 4.2 herein and other
appropriate safety and health training made necessary by
the tasks that they are expected to perform such as the
use of personal protective equipment and
decontamination procedures. All equipment to be used
in the performance of the clean-up work shall be in
serviceable condition and shall have been inspected
prior to use by a qualified person.
DOE O 151.1A, Chapter III,
sec. 5.b
4.7.2 Recovery shall include notifications associated with
termination of an emergency and establishment of criteria for
resumption of normal operations.
DOE O 151.1A, Chapter IV,
sec. 3.b(4)
4.7.3 Following termination of emergency response, and in
conjunction with the Final Occurrence Report (see DOE O
232.1A), each activated Emergency Management Team shall
submit a final report on the emergency response to the
Emergency Manager for submission to the Director of
Emergency Operations.
DOE O 151.1A, Attachment 1,
#11
4.7.4 Provide for investigation of emergency root cause(s) and
corrective action(s) to prevent recurrence in accordance with
Departmental requirements (e.g., see DOE O 225.1A and
DOE O 5480.19).
DOE O 151.1A, Attachment 1,
#14
4.7.5 Respond to all external evaluation, appraisal, and assessment
findings within 90 days of receipt of findings.
5.0 Source Documents
DOE O 151.1A, “Comprehensive Emergency Management System”.
DOE O 225.1A, “Accident Investigations”.
DOE O 5480.19, “Conduct of Operations Requirements for DOE Facilities”.
94
DOE-HDBK-1139/3-2003
Section 75
NFPA 471 (2002), “Recommended Practice for Responding to Hazardous Materials”.
NFPA 472 (2002), “Standard on Professional Competence of Responders to Hazardous Materials
Incidents”.
NFPA 1620 (1998), “Recommended Practice for Pre-Incident Planning”.
29CFR1910.20, “Preservation of Records (medical and exposure)”.
29CFR1910.38, “Employee Emergency Plans and Fire Prevention Plans”.
29CFR1910.119, “Process Safety Management (PSM)”.
29CFR1910.120, “Hazardous Waste Operations and Emergency Response (HAZWOPER)”.
29CFR1910.134, “Respiratory Protection”.
29CFR1910.1200, “Hazard Communication”.
29CFR1910.1450, “Occupational Exposure to Hazardous Chemicals in Laboratories”.
40CFR68, “Chemical Accident Prevention Provisions”.
40CFR355, “Emergency Planning and Community Right-to-Know Act (EPCRA)”.
95
DOE-HDBK-1139/3-2003
INTENTIONALLY BLANK
96
DOE-HDBK-1139/3-2003
97
Chapter 9 - Chemical Disposition
1.0 Introduction
This chapter identifies and consolidates existing user safety and health requirements found in DOE
and Federal chemical-related safety and health regulations and National Standards that address the
disposition (see definition) of excess chemicals54 (see definition) and chemical products (see
definition), including reutilization until final disposal55 (see definition) as waste. Direct requirements
for disposition are found in the Department of Energy Property Management Regulations (DOE-
PMR), Federal Property Management Regulations (FPMR), and Federal Management Regulations
(FMR). In addition, there are many regulations and standards that include implied requirements for
the disposition of excess chemicals. Implied requirements are not included as mandatory
requirements in this chapter. This chapter specifically consolidates requirements found in the
Department of Energy Personal Property Letter (DOE-PPL) 970-3, 41 Code of Federal Regulations
(CFR) 109 (Subchapter H), 41CFR101 (Subchapter H), 41CFR102 Parts 36 and 37, and National Fire
Protection Association (NFPA) code 45, including technical standards that are made mandatory by
their specific reference within a regulation, rule or DOE Order. State and local codes and
requirements are NOT included.
This chapter is intended to list chemical-related safety and health requirements and to consolidate
those that are overlapping and/or duplicative. The list of requirements includes “pointers” to the
sources of those requirements.
This document does NOT create any new or additional requirements.
2.0 Applicability
The information presented here applies to all locations that use chemicals or chemical products. It
consolidates existing, core safety and health requirements that all sites must follow when engaged in
chemical-related activities. This chapter specifically applies to DOE contractors and field
54 DOE offices and designated contractors are responsible [41CFR109-43.101, 41CFR102-36.35, 41CFR102-
36.45(e)] for identifying chemicals that are no longer needed at DOE facilities as “excess chemicals” and for
making them available to other potential users on site, returning them to the vendor (when practical and
economical), or for exploring other avenues of reutilization off-site. The following disposition options may be
available to an excess chemical in the prescribed order: screening for utilization at other DOE sites; transfers to
other federal agencies; donations, via state government agencies, to approved non-profit organizations; or sales
to the public (e.g., competitive bid sales or auctions).
Section 76
The Department of Energy Property Management Regulations (41CFR109), Federal Property Management
Regulations (41CFR101) and Federal Management Regulations (41CFR102) govern potential off-site
reutilization pathways for excess chemicals. Any surplus chemicals (see definition), remaining after the above
disposition routes have been exhausted, should be disposed of under applicable environmental regulations. For
certain chemicals (e.g., ethylene glycol, anti-freeze solutions, precious metals) recycling and recovery exist as
appropriate options. Pesticides and certain products containing chemicals, including those meeting the OSHA
(see definition) Hazard Communication Standard efinition of an “article” (29CFR1910.1200(c)) (such as
batteries and fluorescent lamps), are potential candidates for regulation as “Universal Waste” (see definition)
(40CFR273).
55 Unused surplus chemicals at the end of the disposition cycle are “commercial chemical products” and do not
become solid waste (40CFR260) unless they are discarded, abandoned or disposed of.
d
DOE-HDBK-1139/3-2003
98
organizations that are involved in the utilization and disposition of chemicals and chemical products.
It does not cover requirements related to chemical storage (refer to Chapter 5 of this document),
transportation (refer to Chapter 4 of this document), or waste operations, including the identification,
storage, handling, transportation, and disposal of waste.
[NOTE: Throughout this document, the term “chemicals” is used to indicate chemicals and/or
chemical products. For purposes of this document, the terms, “personal property” and “property”,
as used in the property management regulations, mean chemicals and/or chemical products, unless
otherwise specified.]
This chapter addresses the disposition of chemicals belonging to any of the following categories
under DOE-PMR, FPMR or FMR, namely, high risk (personal) property (see definition), hazardous
property (see definition), hazardous materials (see definition), extremely hazardous materials (see
definition), dangerous property (see definition), and certain categories of property that require
special handling (see definition). Nuclear materials and radiological materials are excluded from the
scope of this chapter.
Among the ten categories of high risk personal property, only excess chemicals identified as
hazardous property, export controlled property (see definition), and proliferation-sensitive property
(see definition) are within the scope of this chapter.
The DOE-PMR (41CFR109) implements and supplements the FPMR (41CFR101) issued by the
General Services Administration (GSA) and will supercede the FPMR in the event of a deviation
affecting the DOE’s personal property management program. The FPMR and DOE-PMR apply to all
direct operations and to designated contractors. The DOE-PMR does not apply to facilities and
activities conducted under Executive Order 12344, “Naval Nuclear Propulsion Program” (February 1,
1982) and Public Law 98-525, “Department of Energy National Security and Military Applications of
Nuclear Energy Authorization Act of 1985”.
The FMR (41CFR102) is the successor regulation to the FPMR and it applies to executive agencies
such as DOE, unless otherwise extended to Federal agencies in specific parts of the CFR.
Section 77
The requirements included in this chapter come from sources that have different safety purposes. As
a result, some of these requirements may not always be applicable to the work being performed at an
individual site or facility. It is the responsibility of each user to determine the applicability of specific
requirements to their work and how they are implemented. The reference sources for the
requirements included in this chapter can be used to determine the applicability of those requirements
to the work being performed.
3.0 Definitions and Acronyms
See Glossary.
4.0 Requirements for Chemical Disposition
Sources10 Consolidated Requirements
4.1 Disposition of Excess (or Surplus) Chemicals
[NOTE: Prescribed disposition options, in a descending order of
implementation, may include reutilization within the DOE complex,
DOE-HDBK-1139/3-2003
99
Sources10 Consolidated Requirements
transfer to another federal agency, donation to a non-profit
organization via a state agency, or sale to a public entity. Available
disposition options are limited by the hazard, risk or value
characteristics of the chemical. See Appendix A of this chapter for
typical screening process steps.]
41CFR102-36.30;
41CFR102-36.35(a);
41CFR102-36.45(e);
41CFR109-43.101
4.1.1 Identification and Disposition of Excess Chemicals - DOE
offices and designated contractors shall promptly identify
chemicals under their control that are excess to their needs and
make them available for use elsewhere. They must ensure that
final disposition complies with applicable environmental,
health, safety, and national security regulations.
DOE-PPL 970-3;
41CFR109-1.53
4.1.2 Disposition of Four Categories of High Risk (Personal
Property) Chemicals - Excess chemicals that fall under any of
the four specific categories of high risk personal property,
namely, Especially designed or prepared property, Export
controlled property, Proliferation-sensitive property, and
Nuclear weapon components or weapon-like components, shall
be subject to the identification, accounting, control, and
disposition policy guidance available from DOE-PPL 970-3 and
41CFR109-1.53.
41CFR109-1.5303(b)(2)
4.1.2.1 The DOE or designated contractor shall process high
risk (personal property) chemicals into a
reutilization/disposition program only after completing
the reviews prescribed by the local high risk property
management system.
41CFR109-1.5303(b)(3);
41CFR101 (Subchapter H);
41CFR109 (Subchapter H);
DOE Guidelines on Export
Control and
Nonproliferation
4.1.2.2 The disposition and handling of high risk property
chemicals shall be subject to applicable provisions of
Subchapter H of the FPMR (41CFR101), Subchapter
H of DOE-PMR (41CFR109), and DOE’s “Guidelines
on Export Control and Nonproliferation.”
41CFR109-1.5303(b)(4) 4.1.2.3 All applicable documentation, including records related to the
chemical’s categorization as high risk, shall be included
with all property transfers, internal or external to DOE.
41CFR109-1.5303(b)(5)
4.1.2.4 Unless an alternative disposition path is available,
surplus Trigger List (see definition) chemicals (e.g.,
those identified under Especially designed/ prepared
property, Proliferation-sensitive property, or Export
controlled property, as defined in Section 3.0, above)
shall either be sold for scrap (see definition) after
being rendered useless for their originally intended
function or destroyed, with the destruction verified and
documented.
Section 78
DOE-HDBK-1139/3-2003
100
Sources10 Consolidated Requirements
41CFR109-1.5303(b)(6) 4.1.2.5 The Export Restriction Notice specified in 41CFR109-
1.5303(b)(6), or an approved equivalent notice, shall
be included in all transfers, donations, sales or other
disposition actions.
41CFR109-43.305-50;
Standard Form 120
4.1.2.6 Excess nuclear-related and proliferation-sensitive
chemicals shall not undergo formal internal screening
within DOE or be reported to the GSA on Standard
Form (SF) 120 (Report of Excess Personal Property).
See Sections 4.1.2.2 and 4.1.2.4, above for control and
disposition options (such as destruction, conversion to
scrap that can be sold to the public, or other DOE
authorized option).
29CFR1910.1200;
41CFR101-42.202(a)
through (c)
4.1.3 Identification and Documentation of Hazardous Materials -
Actual or potential hazards associated with an excess hazardous
material shall be documented with a Material Safety Data Sheet
(MSDS) supplied by the manufacturer, distributor or importer.
If an MSDS is not available, a Hazardous Materials
Identification System (HMIS) record from the automated
Department of Defense database is acceptable. If an MSDS or
HMIS record is not available, a hazard identification document
prepared by the owning DOE organization that meets the
MSDS content requirements for hazardous chemicals set forth
in the OSHA Hazard Communication Standard
(29CFR1910.1200) shall be used.
41CFR101-42.202(d);
41CFR101-42.202(a);
41CFR101-42.1101
4.1.3.1 For hazardous items acquired prior to the
implementation of the Federal acquisition standards
(i.e., Federal Standards 313 and 123), the owning or
holding agency (see definition) shall identify and
document the potential hazards associated with these
items.
[NOTE: Hazardous materials are found in most
Federal Supply Classification (FSC) classes. Refer to
Table B-1 (List of FSC classes composed
predominantly of hazardous items) and Table B-2
(Selective list of FSC classes and groups that contain a
significant number of hazardous items) in Appendix B
of this chapter.]
41CFR101-42.202(e) 4.1.3.2 When an item is identified as hazardous, the owning
DOE organization shall document the accountable
inventory record accordingly.
DOE-HDBK-1139/3-2003
101
Sources10 Consolidated Requirements
29CFR1910.1200;
41CFR101-42.202(e)
4.1.3.3 If the hazardous item (or material) has not been
properly labeled by the manufacturer, the owning
DOE organization shall label, mark, or tag the item in
accordance with the OSHA Hazard Communication
Standard requirements regarding the actual or potential
hazard associated with the handling, storage, or use of
the item (or material).
41CFR101-42.202(e)
4.1.3.4 Hazard and special care or handling information shall
be maintained in the item record for use in preparation
of reports of excess property, and reassignment or
transfer documentation.
41CFR101-27.204
4.1.4 Disposition of Unstable/Reactive Chemicals - Unstable/reactive
chemicals (see definition) that are identified as non-extendable
shelf-life items (also known as Type I items (see definition))
shall be safely discarded at the expiration of their designated
shelf life.
NFPA 45, Sec. 7.2.3.5;
NFPA 45, Sec. 10.3.2
4.1.5 If shelf life is unknown, unstable/ reactive chemicals that might
become hazardous during prolonged storage shall be evaluated
or tested, at six-month intervals as a minimum, to assure
continued safe use. Material found to be unsafe or incapable of
being rendered safe shall be discarded.
Section 79
41CFR101-27.204;
41CFR101-42.001
4.1.6 Unless shelf life is extended on the basis of technical evaluation
(e.g. for Type II extendable shelf-life items (see definition)),
hazardous materials with an expired shelf life shall be
reclassified as “hazardous waste” (see definition), if required
by federal, state and/or local environmental laws or regulations.
41CFR101-42.2;
41CFR101-42.11;
41CFR102-36;
41CFR109-42.11;
41CFR109-43
4.2 Utilization of Excess Chemicals
Hazardous Materials – General:
The utilization and transfer of hazardous materials and certain
categories of property within the Federal government shall be
governed by the special policies and methods prescribed by the GSA
in 41CFR101-42.2, 41CFR101-42.11 and 41CFR102-36 in addition to
any superceding DOE requirements found in 41CFR109-43 and
41CFR109-42.11.
4.2.1 Offsite Utilization Within DOE Complex - Internal DOE
Screening.
41CFR102-36.45(e)(1);
41CFR109-43.304-1.50(a)
4.2.1.1 Prior to reporting excess chemicals to the GSA,
reportable property (see definition) shall be screened
for reutilization (or reassignment) within DOE using
the Energy Assets Disposal System (EADS) (see
definition) for a 15-day period.
[NOTE: Refer to Appendix A of this chapter for a
description of typical disposition steps for an excess
chemical.]
DOE-HDBK-1139/3-2003
102
Sources10 Consolidated Requirements
41CFR109-43.304-1.50(e) 4.2.1.2 In general, simultaneous internal DOE screening and
Federal agency excess screening shall not be
conducted.
41CFR109-43.304-1.51;
SF 122
4.2.1.3 Transfer of excess chemicals within DOE generally
shall be effected by the completion of a Standard Form
(SF) 122 (Transfer Order Excess Personal Property) by
the receiving contractor and approval by the cognizant
DOE property administrator for the receiving site.
41CFR101-42.203;
SF 122
4.2.1.4 Information on the actual or potential hazard shall be
included in the SF 122, and the receiving contractor
shall identify the nature of the hazard in the
accountable inventory record.
41CFR101-42.206 4.2.1.5 The holding DOE organization shall properly store
excess hazardous materials and provide necessary
safeguards including warning signs, labels, and the use
of personal protective equipment by utilization
screeners when inspecting the excess.
4.2.2 Utilization Reports of Excess Chemicals - General
41CFR102-36.230(a);
41CFR102-36.230(b);
41CFR109-43.304-2;
SF 120
4.2.2.1 To initiate federal excess screening, reportable property
(i.e., excess chemicals) will be electronically submitted
by EADS directly to GSA’s Federal Disposal System
(FEDS) (see definition) following internal DOE
screening, OR
Paper submissions of Standard Form (SF) 120 (Report of
Excess Personal Property) shall be made to the GSA
office for the region where the excess chemicals are
located.
41CFR101-42.204 (c) 4.2.2.2 Hazardous waste (see definition) shall be disposed of by
the DOE organization under the EPA, State, and local
regulations and it shall not be reported to GSA on the SF
120.
41CFR101-42;
41CFR101-42.204(a);
41CFR102-36.45(e)(2);
41CFR102-36.425;
SF 120
4.2.2.3 Hazardous Property/Hazardous Materials/Hazardous
Items - Excess chemicals that are identified as hazardous
property (including hazardous materials, but excluding
hazardous waste and extremely hazardous property) shall
be reported promptly on SF 120 to the GSA for further
reuse by eligible recipients, together with a full
description of the actual or potential hazard associated
with the handling, storage, or use of the chemicals.
Section 80
DOE-HDBK-1139/3-2003
103
Sources10 Consolidated Requirements
29CFR1910.1200;
41CFR101-42.204(b);
SF 120
4.2.2.4 If available, a copy of the MSDS or HMIS record that
describes the hazardous nature of the item shall be
included with the SF 120; if not, an MSDS-equivalent
document shall be provided by the owning DOE
organization.
29CFR1910.1200;
41CFR101-42.204(b);
49CFR.178-180
4.2.2.5. The description of the hazard should include a
certification by an authorized DOE official that the item
has been properly labeled (refer to Section 4.1.3.3, above)
and that the container and/or packaging meets or exceeds
DOT specifications for a hazardous material container.
4.2.3 Exceptions to Utilization Reporting of Excess Chemicals
41CFR101-42;
41CFR101-42.1102-3;
41CFR101-42.1102-4;
41CFR102-36.165;
41CFR102-36.220(b);
41CFR102-36.220(c)
4.2.3.1 DOE or DOE contractors shall not report the following
types of chemicals as excess to the GSA on Standard
Form 120 to initiate the excess screening process by
federal agencies:
• Chemicals determined appropriate for abandonment/
destruction (See Section 4.2.4, below);
• Non-appropriated fund property (see definition).
Such property may be transferred to a Federal agency
with reimbursement or offered for public sale. It shall
not be donated;
• Scrap;
• Hazardous waste (See Section 4.2.2.2, above);
• Controlled substances (refer to 41CFR101-42.1102-3
in Section 4.8.2, below);
• Nuclear Regulatory Commission-controlled materials
(refer to 41CFR101-42.1102-4 in Section 4.8.2,
below);
• Property dangerous to public health and safety (e.g.,
asbestos, PCBs (see definition), lead-containing
paint) (refer to Sections 4.8.3, 4.8.4 and 4.8.2,
below);
• Classified items or property determined to be
sensitive for reasons of national security (e.g.,
Especially prepared or designed property,
Proliferation-sensitive property, Nuclear components
or materials, Nuclear technology related components
and materials).
41CFR101-42.205 (a);
41CFR101-42.205(b);
SF 120
4.2.3.2 Excess chemicals determined by the holding DOE
organization to be extremely hazardous property shall not
be reported on SF 120, unless so directed by the GSA.
When such an item becomes excess, the holding DOE
organization shall notify the appropriate GSA regional
office to obtain guidance on a case-by-case basis, on the
utilization, donation, sales, or other disposition
requirements.
DOE-HDBK-1139/3-2003
104
Sources10 Consolidated Requirements
4.2.4 Abandonment or Destruction of Excess or Surplus Chemicals
41CFR102-36.35(d);
41CFR102-36.305;
41CFR109-45.901
4.2.4.1 The holding DOE organization or designated contractor
may abandon or destroy (excess or surplus) property or
donate it to public bodies (without reporting to the GSA)
only after the OPMO (see definition) makes a written
determination that the property has “no commercial
value” or its continued maintenance cost would exceed its
estimated sale proceeds.
41CFR101-45;
41CFR102-36.315(b);
41CFR102-36.325
4.2.4.2 In general, DOE or DOE contractor must implement sales
procedures (in accordance with 41CFR101-45) in lieu of
abandonment/ destruction when an eligible recipient
shows interest in purchasing these excess chemicals.
41CFR102-36.325;
41CFR102-36.330
4.2.4.3 Exceptions to Public Notice - The required public notice
of intent (41CFR102-36.325) to abandon/destroy excess
chemicals, including an offer to sell them to the public,
prior to their actual disposition is not needed in the
following cases:
Section 81
• The value of the property, including any expected
sale proceeds, is significantly less than the cost of its
care and handling pending abandonment/destruction,
or
• Abandonment or destruction is required because of
health, safety, or security reasons; or
• When the original acquisition cost of the item
(estimated if unknown) is less than $500.
41CFR102-36.310;
41CFR109-45.902-2
4.2.4.4 Abandonment or Destruction without Public Notice - The
head of the DOE field organization shall coordinate with
the OPMO, a review of the findings prepared by a
designated official, to justify the abandonment or
destruction of property without a public notification of
the pending action.
41CFR101-42;
41CFR102-36.315(a);
41CFR109-42.11;
41CFR109-43.307;
41CFR109-44.7;
41CFR109-44.702-3;
41CFR109-45.9
4.2.4.5 The owning DOE organization shall not abandon or
destroy excess (or surplus) chemicals in a manner that
endangers public health or safety. Specific information
can be found in 41CFR109-42.11, 41CFR109-43.307,
41CFR109-44.7, 41CFR109-45, and 41CFR101-42 for
hazardous materials.
41CFR102-36.35(d);
41CFR102-36.320
4.2.4.6 Donation to a Public Body (see definition) - Excess
chemicals determined to be appropriate for abandonment/
destruction may be donated only to a public body without
going through the GSA.
DOE-HDBK-1139/3-2003
105
Sources10 Consolidated Requirements
41CFR109-44.701
4.2.4.7 The Director, Office of Administrative Services and
heads of field organizations shall designate officials to
make required findings and reviews to justify donation of
excess or surplus chemicals to public bodies.
41CFR101-42;
41CFR109-42.11;
41CFR109-44.702-3
4.2.4.8 The Director, Office of Administrative Services and
heads of field organizations shall ensure that the donation
of excess or surplus hazardous materials to public bodies
complies with applicable requirements in 41CFR109-
42.11 and 41CFR101-42.
4.3 Off-Site Transfer to Other Federal Agencies -- Federal Excess
Screening
29CFR1910.1200;
41CFR101-42.207(a);
SF 122
4.3.1 Transfer of Hazardous Materials and Certain Categories of
Property - Excess hazardous materials may be transferred
between DOE and other Federal agencies except that the
Standard Form (SF) 122 (Transfer Order Excess Personal
Property), prepared by the transferee (i.e., receiving agency)
shall contain a full description of the actual or potential hazard
associated with the handling, storage, or use of each item. The
description shall consist of an MSDS or HMIS data record, if
available, or a written MSDS-equivalent narrative meeting the
OSHA Hazard Communication Standard requirements.
41CFR101-42.207(a)
4.3.2 A certification by an authorized DOE official that the
hazardous item has been properly labeled and its packaging
meets OSHA and DOT requirements (see Section 4.2.2.5,
above), shall be included in the description of the hazard.
41CFR101-42.207(b);
SF 122
4.3.3 The transferee agency (i.e., receiving agency) shall document
the inventory or control record of the transferred hazardous
item to indicate the hazard associated with the handling,
storage, or use of the item. If available, an MSDS or HMIS (or
equivalent) data record must be filed with the SF 122.
41CFR101-42.208 4.3.4 Custody of Extremely hazardous materials - Custody of
excess extremely hazardous materials shall be the
responsibility of the owning or holding DOE site. Custody of
other hazardous materials may be fully or partially transferred
to another Federal agency with that agency's consent.
Section 82
41CFR102-36.35(c) 4.4 Donation or Sale of Surplus Chemicals to the Public
[NOTE: Surplus chemicals not selected for donation are offered for
sale to the public by competitive offerings such as sealed bid sales,
spot bid sales or auctions. DOE or DOE contractor may conduct the
sale if the GSA is made aware of DOE’s intent at the time the excess is
reported or the GSA will conduct the sale, by default.]
DOE-HDBK-1139/3-2003
106
Sources10 Consolidated Requirements
4.4.1 General Requirements
41CFR102-36.35(b)
4.4.1.1 To comply with the Property Act (see definition),
surplus chemicals (i.e., excess chemicals that have not
been transferred to Federal agencies) shall be
distributed to eligible recipients by an agency
established by each State for this purpose, the State
Agency for Surplus Property (SASP).
41CFR101-45.102 4.4.1.2 A need for surplus chemicals expressed by any Federal
agency shall take precedence to any disposition action
by sale, provided that need is relayed in time for the
DOE organization to respond.
41CFR101-45;
41CFR101-45.105-1
4.4.1.3 Although policies and methods prescribed in
41CFR101-45 for the disposition of surplus chemicals
by public sale or abandonment/destruction do not apply
to materials acquired for the national stockpile or the
supplemental stockpile or to materials acquired under
section 303 of the Defense Production Act of 1950, as
amended (50 U.S.C. App. 2093), these provisions
should be followed to the extent feasible in the
disposition of such materials.
41CFR102-37.40
4.4.1.4 All surplus chemicals are available for donation to
eligible recipients, except for the following property
categories:
• Non-appropriated fund property
• Property that requires reimbursement upon transfer
• Controlled substances.
• Items that may be specified from time to time by
the GSA Office of Government-wide Policy
41CFR109-43.307-2.50 4.4.2 Monitoring of Hazardous Chemicals for Radioactive/Chemical
Contamination - To prevent inadvertent release of hazardous
personal property from the DOE sites by transfer or sale to the
public, all hazardous or suspected hazardous property chemicals
shall be checked for radioactive or chemical contamination56 by
environmental, safety, and health officials.
41CFR109-43.307-2.50 4.4.2.1 Contamination-free chemicals will carry a certification
tag authorizing release for transfer or sale.
56 Examples include radioactively-contaminated chemical containers or chemicals stored or used in
radioactively-contaminated areas.
DOE-HDBK-1139/3-2003
107
Sources10 Consolidated Requirements
41CFR109-43.307-2.50 4.4.2.2 Contaminated chemicals will be referred back to the
DOE program office for appropriate action.
41CFR109-43.307-2.51
4.4.3 Holding Hazardous Property Chemicals - Excess or surplus
hazardous property chemicals shall be stored compatibly and not
with non-hazardous property chemicals while awaiting
disposition action.
4.4.4 High Risk Property - Export Controlled Property
41CFR109-43.307-50(a) 4.4.4.1 DOE or the DOE contractor must obtain the necessary
export license when chemicals subject to export controls
are to be exported directly.
41CFR109-43.307-50(b) 4.4.4.2 When chemicals subject to export controls are transferred
under work-for-others agreements, co-operative
agreements, or technical programs, the recipients will be
informed in writing about export control restrictions that
must be followed in the event of a change in custody of
the materials.
Section 83
4.4.5 High Risk Property - Nuclear-related or Proliferation-sensitive
Personal Property
41CFR109-43.307-52(a) 4.4.5.1 All nuclear-related and proliferation-sensitive personal
property (see definition) shall be physically tagged with a
certification from an authorized DOE program official at
the time of excess determination.
41CFR109-43.307-52(b)
4.4.5.2 Excess nuclear-related and proliferation-sensitive
personal property shall be stripped of all of its distinctive
characteristics, as determined by the cognizant program
office, prior to disposition. To the extent practicable,
such action shall be accomplished without compromising
any civilian utility or commercial value of the chemical.
41CFR109-43.315(d)
4.5 Donation of Surplus Hazardous Materials to Public Agencies (see
definition) via State Agencies for Surplus Property (SASPs) (see
definition) - DOE contracting officers shall maintain a record of the
number of certified non-Federal agency screeners operating under their
authority and shall immediately notify the appropriate GSA regional
office of any changes in screening arrangements.
41CFR101-42;
41CFR101-42.3;
41CFR102-37;
41CFR109-42.11;
41CFR109-44.702-3
4.5.1 Donation of Hazardous Materials and Certain Categories of
Property (General) - The Director, Office of Administrative
Services and heads of DOE field organizations shall provide the
safeguards, notifications, and certifications required for the
donation of hazardous materials consistent with the requirements
in 41CFR109-42.11 and 41CFR101-42.
DOE-HDBK-1139/3-2003
108
Sources10 Consolidated Requirements
[NOTE: Donation of hazardous materials and certain categories
of property (see definition) is governed by the special policies
and methods prescribed in 41CFR101-42.3 in addition to the
requirements of 41CFR102-37.]
41CFR101-42.301(a)
4.5.1.1 Surplus chemicals identified as hazardous material and
not required for transfer as excess chemicals to Federal
agencies shall normally be made available for donation.
41CFR101-42.301(a)
4.5.1.2 State Agencies for Surplus Property (SASPs) shall not
acquire hazardous materials without first confirming
eligible donees (see definition) for these products.
41CFR101-42.301(a) 4.5.1.3 Surplus chemicals identified as hazardous may be
donated provided the donee is warned about the
hazardous nature of the product via MSDS, HMIS data,
or equivalent safety documentation and is provided with
special handling information.
41CFR101-42.301(b)
4.5.1.4 The donee shall sign a required certification as prescribed
in 41CFR101-42.301(b) to the effect that he/she is aware of
the hazards associated with the chemical product and that
he/she is legally responsible for the use, storage, handling,
transport and disposal of the hazardous material(s).
41CFR101-42.202;
41CFR101-42.203;
41CFR101-42.302(a)
4.5.2 Responsibilities for Donation of Hazardous Materials - The
holding agency (i.e., DOE) shall be responsible for the
identification and reporting of hazardous materials as stated in
41CFR101-42.202 and 41CFR101-42.203 (see Section 4.1.3,
above).
29CFR1910.1200;
41CFR101-42.302(b);
Standard Form 123
4.5.2.1 The State Agency for Surplus Property (SASP) or the
donee, when applicable, shall prepare Standard Form
(SF) 123 (Transfer Order Surplus Personal Property). A
full description of the actual or potential hazard
associated with handling, storage, or use of the item must
be provided with an MSDS, HMIS data, or an equivalent
document that complies with the requirements of the
OSHA Hazard Communication Standard.
Section 84
41CFR101-42.301(b);
41CFR101-42.302(b);
SF 123
4.5.2.2 The SASP and/or donee shall sign the certification
stipulated in 41CFR101-42.301(b) and forward it with the
SF 123 to the GSA regional office. The certification is an
acknowledgment by the donee of the legal transfer of
custody of the hazardous material from the DOE
organization and the acceptance of liabilities it may entail
DOE-HDBK-1139/3-2003
109
Sources10 Consolidated Requirements
to the donee.
41CFR101-42.301(b);
41CFR101-42.303;
4.5.2.3 Donation of surplus hazardous material distributed by the
SASP to the donee shall be effected by the use of State
agency distribution document. The donee shall also sign
the required certification (see Section 4.5.2.2, above).
41CFR101-42.302(c) 4.5.2.4 DOE and DOE contractors shall obtain approval from the
GSA regional office to transfer hazardous materials for
donation.
41CFR101-42.304;
41CFR101-42.1102
4.5.3 Special Requirements for Donation of Certain Hazardous
Materials
[NOTE: Special donation requirements for specific
hazardous materials are provided in 41CFR101-42.1102.
Many hazardous materials require special storage and
handling. (See Sections 4.8.2, 4.8.3, and 4.8.4, below.)]
41CFR102-37.220(d);
41CFR101-42.1102-2
4.5.3.1 A SASP must obtain written justification from the
prospective donee, and submit it to GSA along with the
transfer request, prior to allocation of items containing 50
ppm or greater of polychlorinated biphenyl (PCB).
41CFR101-42.304;
41CFR102-37.245
4.5.3.2 The Federal holding agency or the SASP shall properly
store hazardous materials, ensure the use of necessary
safeguards, and instruct donation screeners on personal
protection when inspecting the surplus.
41CFR101-42.304;
49CFR171
4.5.3.3 The SASP and/or the donee shall comply with DOT
regulations (49CFR171 et seq.) when transporting
hazardous materials.
4.6 Sale Of Hazardous Materials To Public Bodies - General
41CFR101-45.103-2;
41CFR101-45;
41CFR101-46;
41CFR101-42;
41CFR109-42
4.6.1 Holding Agency Sales - All provisions of 41CFR101-45 and
41CFR101-46 shall be followed in conducting sales of Federal
government-owned surplus chemicals, if not superceded by DOE-
PMR and 41CFR101-42.
41CFR109-45.105-3;
41CFR101-45
4.6.1.1 Contractor chemical inventory held by DOE designated
contractors is exempted from the GSA conducted sales
provisions of 41CFR101-45.
41CFR109-45.300-50 4.6.1.2 Sales of surplus contractor chemical inventory by
designated contractors will be conducted with the
approval of heads of field organizations and with
oversight by OPMOs and program officials to ensure that
DOE-HDBK-1139/3-2003
110
Sources10 Consolidated Requirements
chemicals requiring special handling or program office
certification are sold in compliance with regulatory
requirements.
41CFR109-45.301-51 4.6.1.3 The Export/import clause specified in 41CFR109-45.301-
51, warning the purchaser not to export the chemicals
overseas and to inform the next potential owner about
export/import restrictions shall be included in all sales
invitations for bid.
41CFR101-42.400;
41CFR101-42.401;
41CFR101-42.402;
41CFR101-42.403;
4.6.2 Sales of Hazardous Chemicals through GSA Regional Offices.
[NOTE: Sales of hazardous materials are done through GSA
regional offices in accordance with 41CFR101-42.400,
41CFR101-42.401, 402 (reporting), and 403 (Sale methods and
Procedures).]
41CFR101-42.45;
41CFR101-42.400;
41CFR101-45;
41CFR109-45
Section 85
4.6.1.1 The sale, abandonment, or destruction of hazardous
materials and certain categories of property shall be
conducted in accordance with the special policies and
procedures prescribed in 41CFR101-42.400 and the
additional requirements of 41CFR109-45 and 41CFR101-
45.
41CFR101-42.401(a) 4.6.2.2 Sale of hazardous materials for DOE and DOE
contractors shall be conducted through the regional
offices of GSA.
41CFR101-42.401(a);
41CFR109-45.304;
41CFR101-42.403
4.6.2.3 DOE designated contractors and field organizations shall
follow sales methods and procedures in accordance with
41CFR109-45.304. These holding agency (DOE) sales
of hazardous materials shall meet or exceed the
requirements in 41CFR101-42.403.
41CFR101-42.401(b);
41CFR101-45.103-2
4.6.2.4 Holding agencies shall prepare hazardous materials for
sale as provided for in 41CFR101-45.103-2. Pending
disposition, each holding agency shall care for and handle
its hazardous materials, including posting appropriate
warning signs and rendering extremely hazardous
property innocuous, or providing adequate safeguards.
41CFR101-42.402;
41CFR101-45.303
4.6.2 Reporting hazardous materials for sale - DOE and DOE
contractors that elect to have GSA sell their hazardous
materials shall report them to the GSA regional office for
the region in which the surplus chemicals are located in the
following manner:
41CFR101-42.402(a) 4.6.3.1 Reportable property - Hazardous materials reported for
utilization screening, if not transferred or donated, will be
programmed for sale by the GSA regional office.
DOE-HDBK-1139/3-2003
111
Sources10 Consolidated Requirements
41CFR101-45.303(b);
41CFR101-42.402(b);
SF 126
4.6.3.2 Nonreportable property - Hazardous materials not
required to be reported for utilization screening, and for
which any required donation screening has been
completed, shall be reported to the appropriate GSA
regional office on Standard Form (SF) 126 (Report of
Personal Property for Sale).
29CFR1910.1200;
41CFR101-42.202(e);
41CFR101-42.204;
41CFR101-42.402(c);
49CFR178-180;
SF 126
4.6.3.3 Description and certification - The SF 126 shall contain a
certification from an authorized DOE official that the
hazardous item has been properly labeled and packaged
as required in 41CFR101-42.202(e) (see Section 4.1.3.3,
above) and 41CFR101-42.204 (see Section 4.2.2.5,
above).
29CFR1910.1200;
41CFR101-42.402(c);
SF 126
4.6.3.4 The SF 126 shall also include a full description of the
actual or potential hazard associated with handling,
storage, or use of the item. This description shall be
furnished by providing: an MSDS, or a copy of the HMIS
record, or an MSDS-equivalent narrative that complies
with the requirements of the OSHA Hazard
Communication Standard.
41CFR101-42.403;
41CFR101-45.304
4.6.4 Sale Methods and Procedures for Hazardous materials.
Hazardous materials shall be sold in accordance with the
provisions of 41CFR101-45.304 and the following special
methods and procedures:
41CFR101-42.403(a)
4.6.4.1 Sales that offer hazardous materials shall be conducted
separately from other sales. Sale catalogs or listings shall
be sent to only those parties with an active interest in
purchasing such materials.
41CFR101-42.403(b) 4.6.4.2 Sale catalogs, listings, and invitations for bids, shall
• limit the hazardous materials in each lot to a single
Federal supply group;
• indicate if an MSDS is available for the product
being sold; and
• indicate if a hazardous item is being sold only for its
Section 86
material content.
41CFR101-42.403(c) 4.6.4.3 For a bid to be considered for award, the bidder must sign
the certification specified in 41CFR101-42.403(c) to the
effect that he/she will comply with all applicable
regulations related to the care, handling, storage,
shipment, resale, export, or other use of the hazardous
material being purchased and that he/she will assume all
legal liabilities after the purchase.
DOE-HDBK-1139/3-2003
112
Sources10 Consolidated Requirements
29CFR1910.1200;
41CFR101-42.403(d)
4.6.4.4 MSDSs, HMIS records, where applicable, or a written
description in compliance with the requirements of the
OSHA Hazard Communication Standard shall be sent to
purchasers of hazardous materials with their notice of
award.
4.6.5 Sale of High Risk Personal Property
41CFR109-43.307-2.50;
41CFR109-45.304;
41CFR109-45.309;
41CFR109-45.309-2.50
4.6.5.1 Suspect (definition) hazardous property shall be made
available for sale only after the review and certification
requirements for contamination-free status (see Section
4.4.2, above) have been met.
41CFR109-43.307-50;
41CFR109-45.309-51
4.6.5.2 Export controlled property shall be made available for
sale only after the export license requirements (see
Section 4.4.4, above) have been met.
41CFR109-43.307-52;
41CFR109-45.309-53
4.6.5.3 Nuclear-related or proliferation-sensitive property shall
be made available for sale only after the stripping and
certification requirements (see Section 4.4.5, above)
have been met.
41CFR101-42.403(e) 4.6.6 Sale of Extremely Hazardous Property - DOE or DOE contractor
shall not sell extremely hazardous property unless authorized by
the appropriate GSA regional office. Any authorized sale
requires the DOE/DOE contractor to provide adequate safeguards
for the material or render it innocuous (without a loss of its utility
or commercial value) (see Section 4.6.2.3, above).
41CFR101-42.404;
41CFR101.42.1102
4.6.7 Sale of Certain Hazardous Materials - DOE or DOE contractors
shall follow the special sales requirements provided in
41CFR101.42.1102 for certain hazardous materials (e.g.,
asbestos, polychlorinated biphenyls, controlled substances, etc.)
(see Sections 4.8.1 through 4.8.4, below). The holding agency
(DOE) shall properly store hazardous items and provide
information to ensure that prospective bidders are aware of the
hazards, as well as the precautions they should take to protect
themselves.
41CFR101-42.1102;
41CFR102-36.305 through
102-36.330
4.7 Abandonment or Destruction57 of Surplus Hazardous Materials
and Certain Categories of Property - DOE and DOE contractors shall
follow the requirements for the abandonment or destruction of surplus
hazardous chemicals as prescribed in 41CFR102-36.305 through 102-
36.330 and additional requirements found in 41CFR101-42.1102.
57 Surplus chemicals remaining after normal donation screening are generally subject to the sale process in
accordance with the provisions of 41CFR101-45. However, if the criteria in 41CFR102-36.305 are met, these
chemicals may be destroyed. [41CFR102-37.80]
DOE-HDBK-1139/3-2003
113
Sources10 Consolidated Requirements
41CFR102-37.565;
41CFR102-37.570;
41CFR109-44.701
4.7.1 A written finding must be made by an authorized DOE official
(see Sections 4.2.4.1 and 4.2.4.7 above) that a surplus chemical
has “no commercial value” or its continued maintenance would
cost more than its estimated sale proceeds, before it can be
abandoned or destroyed, or donated to public bodies.
Section 87
41CFR101-42.406;
41CFR101-42.1102;
41CFR102-36.305 through
102-36.330;
41CFR102-37.570;
41CFR109-44.702-3
4.7.2 In addition to the requirements in 41CFR102-36.305 through
102-36.330 and 41CFR101-42.1102, surplus hazardous materials,
including empty hazardous material containers, shall be
abandoned or destroyed in accordance with appropriate Federal,
State, and local waste disposal, and air and water pollution
control standards.
41CFR102-37.35(c);
41CFR102-37.125(a)(2) ;
41CFR102-37.125(b);
41CFR102-37.570
4.7.3 Donation58 to Public Bodies - The holding DOE organization or
designated contractor shall not donate chemicals that require
destruction for health, safety, or security reasons (see Section
4.2.4.8, above).
41CFR101-42.1101(a)
4.8 Disposition of Special Types of Hazardous Materials and Certain
Categories of Property
Hazardous material identification is required for all material that, by
virtue of its potentially dangerous nature, requires controls to assure
adequate safety to life, property, and the environment.
41CFR101-42.1101;
41CFR101-42.1101(b);
Federal Standard 313
4.8.1 Federal Supply Classification (FSC) Groups and Classes that
Contain Hazardous Materials.
[NOTE: To facilitate identification of hazardous materials or
items using Federal Supply Classification (FSC) groups or
classes, two listings, based on Federal standard 313, are
provided in Appendix B of this chapter. Table B-1 contains a
complete list of FSC classes composed predominantly of
hazardous items and Table B-2 contains a selective listing of FSC
classes and groups that contain a significant number of
hazardous items.]
58 The holding DOE organization may donate surplus chemicals, which would otherwise be abandoned or destroyed,
directly to public bodies, without going through the GSA, in accordance with Subpart H of DOE-PMR (41CFR109)
and ubpart H of FPMR (41CFR101). As there is no special form to process donations, the holding agency may use
any document that has an audit trail to record the transaction. [41CFR102-37.35(c); 41CFR102-37.575]
S
DOE-HDBK-1139/3-2003
114
Sources10 Consolidated Requirements
41CFR101-42.1102;
41CFR101-42.1102-3;
41CFR101-42.1102-4;
41CFR101-42.1102-5;
41CFR101-42.1102-7;
41CFR101-42.1102-8;
41CFR101-42.1102-9
4.8.2 Special Requirements for Disposition of Certain Hazardous
Materials and Certain Categories of Property
[NOTE: Special requirements for the utilization, donation, sale,
and disposition of chemical products, including those belonging
to certain Federal Supply Classes or Groups, that contain
hazardous chemicals such as asbestos, polychlorinated biphenyls
(PCBs), explosives, etc. are covered in various sections of
41CFR101.42.1102, as listed below:
• Controlled substances (refer to 41CFR101-42.1102-3)
• Nuclear Regulatory Commission (NRC)-controlled materials
(refer to 41CFR101-42.1102-4)
• Drugs, biologicals, and reagents other than controlled
substances (refer to 41CFR101-42.1102-5)
• Lead-containing paint and items bearing lead-containing
paint (refer to 41CFR101-42.1102-7)
• U.S. Munitions list items which require demilitarization (refer
to 41CFR101-42.1102-8)
• Acid contaminated and Explosive contaminated property
(refer to 41CFR101-42.1102-9)]
41CFR101-42.1102-1
4.8.3 Asbestos - Special Requirements
[NOTE: The following disposition requirements apply to
chemical products containing friable asbestos (see Section
4.8.3.1, below) and nonfriable asbestos (see Section 4.8.3.2,
below)]
Section 88
4.8.3.1 Friable Asbestos Materials (see definition)
41CFR101-42.1102-1 (b)(1);
SF 120
4.8.3.1.1 Utilization – Excess chemicals known to
contain friable asbestos shall not be reported to
the GSA on SF 120 or transferred among
Federal agencies.
41CFR101-42.1102-1(c)(1);
41CFR101-42.1102-1(d)(1)
4.8.3.1.2 Donation and sales59 - Surplus chemicals
containing friable asbestos shall not be
donated or sold.
41CFR101-42.1102-1(e)(1);
40CFR61.156
4.8.3.1.3 Abandonment and destruction - Excess or
surplus personal property, which contains
friable asbestos, shall be buried in an EPA-
approved site, in accordance with the
requirements of 40CFR61.156.
1
59 Exception: DOE and DOE contractors may, on a case-by-case basis, request approval from the GSA Central
Office to transfer, donate, or sell (excess/surplus) chemicals containing friable asbestos. [41CFR101-42.1102-
1(a)(4)]
DOE-HDBK-1139/3-2003
115
Sources10 Consolidated Requirements
4.8.3.2 Nonfriable Asbestos Materials (see definition)
41CFR101-42.1102-
1(b)(2)(i);
41CFR102-36;
SF 120;
SF 122
4.8.3.2.1 Utilization –Excess chemicals containing
nonfriable asbestos shall be reported to the
GSA and processed routinely, except that a
required cancer hazard warning, as specified
in 40CFR101-42.1102-1(b)(2)(i), shall be
included in the Standard Forms 120 and 122.
1
41CFR101-42.1102-
1(b)(2)(ii)
4.8.3.2.2 All excess chemical products known to
contain nonfriable asbestos shall be labeled
with a cancer hazard warning as prescribed in
41CFR101-42.1102-1(b)(2)(ii).
41CFR101-42.1102-
1(c)(2)(i);
41CFR102-37;
SF 123
4.8.3.2.3 Donation – Surplus chemicals containing
nonfriable asbestos may be donated in the
normal manner, except that the Standard
Form (SF) 123 shall include the cancer
hazard warning stipulated in Section
4.8.3.2.1, above.
41CFR101-42.1102-
1(c)(2)(ii);
41CFR101-42.1102-
1(d)(2)(ii)
4.8.3.2.4 All surplus chemicals to be donated or sold,
that contain nonfriable asbestos, shall be
labeled as stated in Section 4.8.3.2.2, above.
41CFR101-42.1102-
1(d)(2)(i);
41CFR101-45
4.8.3.2.5 Sale – Surplus chemicals containing
nonfriable asbestos may be sold, except that
all sale-related documentation including
product literature, advertisements, and post-
sale agreements shall include a cancer hazard
warning as specified in Section 4.8.3.2.1,
above.
41CFR101-42.1102-1(e)(2);
41CFR102-36.305 through
102-36.330
4.8.3.2.6 Abandonment and destruction – Surplus
chemicals containing nonfriable asbestos
which are not transferred, donated, or sold
shall be abandoned or destroyed as provided
for in 41CFR102-36.305 through 102-
36.330. However, if DOE is concerned about
the nonfriable asbestos within the chemical
product having the potential to become
friable during the process of abandonment or
destruction, the product shall be disposed of
by burial (See Section 4.8.3.1.3 above).
41CFR101-42.1102-2(a)(2) 4.8.4 Polychlorinated biphenyls – Special Requirements
41CFR101-42.1102-2(a)(3);
41CFR101-45;
41CFR102-36;
4.8.4.1 Excluded PCB products (see definition) are not subject
to Federal restrictions and may be transferred, donated,
sold, or otherwise processed under 41CFR Parts 102-36,
DOE-HDBK-1139/3-2003
116
Sources10 Consolidated Requirements
41CFR102-37
102-37, and 101-45, provided such processing conforms
to all applicable State60 and local laws.
41CFR101-42.1102-2(a)(4) 4.8.4.2 All PCBs (see definition) and PCB items (see definition)
Section 89
to be transferred, donated, or sold shall be labeled or
marked clearly with a toxic hazard warning as specified
in 41CFR101-42.1102-2(a)(4).
41CFR101-42.1102-2(a)(5) 4.8.4.3 Unmarked or unlabeled items containing PCBs or PCB
items with an unknown level of concentration of PCBs
shall not be transferred, donated, or sold.
41CFR101-42.1102-2(b)(1) 4.8.4.4 Utilization - PCBs and PCB items shall be reported for
utilization screening as a hazardous property (see
Sections 4.2.2.3 and 4.2.2.4, above).
40CFR761;
41CFR101-42.1102-2(b)(2);
SF 122
4.8.4.5 To obtain GSA’s approval for transfers of excess PCBs or
PCB items, (a) the items shall be intact, non-leaking, and
totally enclosed, and (b) the SF 122 shall cite the specific
provision in 40CFR761 that allows continued use of the
item, and contains a certification that the product has
been inspected by the transferee and that it complies with
all applicable provisions of 40CFR761.
40CFR761;
41CFR101-42.1102-2(b)(3)
4.8.4.6 When a PCB or PCB item is transferred as excess, the
receiving agency shall note in its property accountability
records the nature and concentration of the PCB and shall
list the provisions of 40CFR761 authorizing its use.
40CFR761;
41CFR101-42.1102-2(c)(1);
41CFR102-37;
SF 123
4.8.4.7 Donation - In order for PCB or PCB-contaminated items
to be approved by the GSA for donation under
41CFR102-37, the following must be met:
• the required toxic hazard certification (see Section
4.8.4.2, above) must appear on the SF 123 (Transfer
Order Surplus Personal Property);
• the specific donee must have been selected; and
• a justification from the recipient (i.e., the SASP or
the donee) must be attached stating the proposed use
and citing the specific provision in 40CFR761 that
permits continued use of the item.
41CFR101-42.1102-2(c)(2)
4.8.4.8 All PCBs and PCB items must be in usable condition to
be eligible for donation.
41CFR101-42.1102-2(c)(3) 4.8.4.9 Items to be donated must be intact, totally
enclosed, and non-leaking.
60 Some States regulate PCB concentrations more strictly than does the Federal government.
DOE-HDBK-1139/3-2003
117
Sources10 Consolidated Requirements
40CFR761;
41CFR101-42.1102-2(d)(1);
41CFR101-42.1102-2(d)(2)
4.8.4.10 Sales - The GSA or the holding DOE organization
normally shall not sell surplus PCBs or PCB items.
These items are regarded as extremely hazardous and
shall be disposed of by DOE and DOE contractors
under the EPA regulations.
[NOTE: Holding DOE organizations may request the
authority to sell or that the GSA sell a specific PCB or
PCB item, by citing the specific provision in 40CFR761
that authorizes such sale, along with a justification for
sale of the item instead of disposal under EPA
regulations.]
41CFR42.1102-2(a)(4);
41CFR101-42.1102-2(d)(3)
4.8.4.11 If PCBs or PCB items are to be sold, the invitation for
bid (IFB), any Standard Form that lists such items, and
any sales literature related to these items shall contain
the warning as prescribed in 41CFR42.1102-2(a)(4).
40CFR761;
41CFR101-42.1102-2(e)(1)
4.8.4.12 Abandonment and destruction - PCBs and PCB items
not disposed of via utilization, donation, or sale shall be
destroyed or otherwise disposed of in accordance with
the EPA regulation (40CFR761) and applicable State
laws.
41CFR109-42.11;
41CFR109-42.1100.50
4.9 Utilization and Disposition of Hazardous Materials that are
Radioactively or Chemically Contaminated
Section 90
[NOTE: 41CFR109-42.11 sets forth policies and procedures for the
utilization and disposition outside of DOE of excess and surplus
chemicals, which have been radioactively or chemically contaminated.]
1
41CFR109-42.1100.51
4.9.1 DOE or DOE contractor shall dispose of contaminated chemicals
in accordance with applicable Federal regulations governing
radiation/chemical exposure and environmental contamination.
Appropriate state and local regulations shall be followed in cases
where Federal regulations do not exist or apply.
1
41CFR109-42.1102.51(a)
4.9.2 Suspect Personal Property - Excess chemicals (including scrap)
having a history of use in an area where radioactive or chemical
contamination may occur shall be considered suspect and shall
be monitored.
41CFR109-42.1102.51(b)
4.9.3 If economically feasible, every effort shall be made to reduce the
level of contamination of excess or surplus chemicals to the
lowest practicable level. Contaminated chemicals that exceed
applicable contamination standards shall not be utilized or
disposed outside of DOE.
DOE-HDBK-1139/3-2003
118
Sources10 Consolidated Requirements
41CFR109-42.1102.51(c)
4.9.4 If contamination is suspected and the property is of such size,
construction, or location as to make testing for contamination
impossible, the property shall not be utilized or disposed outside
of DOE.
41CFR109-42.1102.52;
41CFR109-45.5005-1(a);
49CFR171-179
4.9.5 Low Level Contaminated Personal Property - If monitoring of
suspect chemicals indicates that contamination does not exceed
applicable standards, they may be utilized and disposed of in the
same manner as uncontaminated chemicals, provided the
guidance in 41CFR109-45.5005-1(a) has been considered.
However, recipients shall be advised of the hazards where levels
of radioactive contamination require specific controls for
shipment as provided in DOT regulations (49CFR171-179) for
shipment of radioactive personal property.
41CFR109-42.1102.52
4.9.6 When any contaminated chemical is screened within DOE,
reported to GSA, or otherwise disposed of, the kind and degree
of contamination must be clearly indicated on all relevant
documents.
41CFR101-42;
41CFR109-43.307-51;
41CFR109-42;
41CFR109-43.307-50;
41CFR109-43.307-52;
41CFR109-45.50;
41CFR109-45.5005-1
4.9.7 High Risk Personal Property - Excess and surplus chemicals
identified as Nuclear-related, proliferation-sensitive, low level
contaminated property and Classified personal property shall not
be transferred, sold, exchanged, leased, donated, abandoned, or
destroyed without approval of the cognizant DOE program
office. Disposition of such chemicals is subject to the restrictions
contained in applicable sections of the DOE-PMR and FPMR.
4.10 Storage and Handling of Excess or Surplus Chemicals
[NOTE: Chemicals categorized as hazardous materials, extremely
hazardous materials, dangerous property, and hazardous property
require special handling and storage considerations. Requirements
identified in Chapter 5 (“Chemical Storage”) of this document
continue to apply for the storage and handling of excess (or surplus)
chemicals while avenues for their disposition are being sought until
the time the chemicals are identified as waste for final disposal.]
5.0 Source Documents
Department of Energy (July 1999), “Guidelines on Export Control and Nonproliferation”
Department of Energy Personal Property Letter, Issue Number 970-3, Revision 1 (Feb. 3, 1998).
Section 91
Executive Order 12344 (February 3, 1982), “Naval Nuclear Propulsion Program”, 47 Federal Register
4979.
DOE-HDBK-1139/3-2003
119
22CFR Subchapter M (Parts 120-130), Department of State, "International Traffic in Arms
Regulations" (ITAR), and in particular, 22CFR121, “The United States Munitions List”.
29CFR1910.1200, “Hazard Communication”.
40CFR61.156, “Cross-reference to Other Asbestos Regulations” (National Emission Standards for
Hazardous Air Pollutants).
40CFR261, “Identification and Listing of Hazardous Waste”.
40CFR761, “Polychlorinated Biphenyls (PCBs) Manufacturing, Processing, Distribution in
Commerce, and Use Prohibitions”.
41CFR101, “Federal Property Management Regulations” (Parts 101-1 to 101-99); in particular,
Subpart H (Parts 42 to 99).
41CFR102, “Federal Management Regulation (FMR)” (Parts 102-1 to 102-220); in particular,
41CFR102-36, “Disposition of Excess Personal Property” [NOTE: This Part is cross-referenced by
41CFR101-43, “Utilization of Personal Property”, which is no longer in print], and 41CFR102-37,
“Donation of Surplus Personal Property” [NOTE: This Part is cross-referenced by 41CFR101-44,
“Donation of Personal Property”, which is no longer in print].
Federal Standard 123 (or FED-STD-123), “Marking for Shipment (Civil Agencies)”.
Federal Standard 313 (or FED-STD-313), “Material Safety Data, Transportation Data and Disposal
Data for Hazardous Materials Furnished to Government Activities”.
International Atomic Energy Agency (IAEA), Information Circular (INFCIRC) 254, Part 1 (“Trigger
List”) and Part 2 (“Dual-use List”).
NFPA 45 (2000), “Standard on Fire Protection for Laboratories Using Chemicals”.
Public Law 98-525 (10/19/84), “Department of Defense Authorization Act, 1985”; also called
“Department of Energy National Security and Military Applications of Nuclear Energy Authorization
Act of 1985”.
10CFR110, Nuclear Regulatory Commission, "Export and Import of Nuclear Equipment and
Material”.
10CFR810, Department of Energy, "Assistance to Foreign Atomic Energy Activities"
15CFR Subpart C (Parts 730 to 774), Department of Commerce, “Export Administration
Regulations” (EAR); in particular, 15CFR734, “Scope of the Export Administration Regulations”,
15CFR744, "Control Policy: End-User and End-Use Based", and 15CFR774, “The Commerce
Control List”.
29CFR1910, “Occupational Safety and Health Standards”.
29CFR1910.120, “Hazardous Waste Operations and Emergency Response”.
29CFR1910.1001, “Asbestos”.
29CFR1926.65, “Hazardous Waste Operations and Emergency Response”.
40CFR273, “Standards for Universal Waste Management”.
40CFR763, “Asbestos”.
41CFR101-27.2, “Management of Shelf-Life Materials.”
41CFR109, “Department of Energy Property Management Regulations”; in particular, Subpart H
(Parts 42 to 50).
49CFR.171-180 (Subchapter C), “Hazardous Materials Regulations”.
DOE-HDBK-1139/3-2003
120
INTENTIONALLY BLANK
DOE-HDBK-1139/3-2003
121
DISPOSITION OF EXCESS OR SURPLUS CHEMICALS USING FEDS/ EADS:
Appendix A - Typical Screening Process Steps
DOE-PMR, FPMR AND FMR REQUIREMENTS
Section 92
The potential avenues of disposition open to an excess chemical depend on its hazard/risk/value
characteristics. Excess precious metals shall be returned to DOE’s Precious Metals Pool located in Oak
Ridge, Tennessee. As shown in Table A-1, the first step in the typical disposition cycle is to screen excess
chemicals for reutilization within the DOE complex through the Energy Asset Disposal System (EADS)
for a 15-day period. At the conclusion of internal DOE screening, four categories of High risk property
identified as Export controlled property, Proliferation-sensitive property, Especially designed or prepared
property, and Nuclear weapon components or weapon-like components61 shall be dispositioned in
accordance with the DOE Personal Property Letter 970-3 and 41CFR109-1.53, with prior review and
approval by the OPMO. An Export Restriction Notice signed by the recipient organization shall
accompany any resulting property transfers, sales, or other offerings.
Among the remaining six High risk property categories is Hazardous property (as defined in DOE-PPL
970-3 and 41CFR109-1.100-51(a)), which includes hazardous materials as defined in the FPMR
(41CFR101). These chemicals may be screened through the Federal Excess Disposal System (FEDS) for
a period of 21 days, once the internal DOE screening has concluded in accordance with 41CFR109-42,
41CFR101-42, and 41CFR102-36. Excess chemicals may be transferred to another federal agency using
the federal excess screening process in FEDS. The remaining surplus chemicals will become eligible for
donation to non-profit donees through surplus screening by the State Agencies for Surplus Property
(SASPs). The next step in the disposition process is a sale conducted by the GSA regional office (or by
the DOE contractor with approval from GSA) to the public through a competitive bid or auction sale
process. The ultimate fate of any remaining surplus chemicals rests with the owning DOE organization,
which may elect to put the chemicals back into the disposition cycle or declare them as solid waste
(unless they are recyclable under the universal waste provisions) and dispose of them under appropriate
EPA, State, and local laws and regulations.
In cases involving excess or surplus chemicals with no market value, when holding a sale is not an
economically viable option, abandonment or destruction (see Table A-2) may be permitted, with approval
by the authorized DOE property management official. Where feasible, sale to the public as scrap or
donation to public bodies (i.e., any public agency, Indian tribe, or agency of the Federal government) is
the preferred option in lieu of abandoning or destroying the property. Donation is not an option for
chemical products that require destruction for health, safety, or security reasons. A public notice of intent
to destroy shall not be issued in such cases.
Any U.S. Munitions List item (MLI) or Commerce Control List item (CCLI) that requires
demilitarization is identifiable by an assigned demilitarization code that indicates the type of and scope of
demilitarization and/or export controls that must be undertaken before the item could be transferred to a
non-DOD entity. For a listing of these codes and additional guidance, refer to “DOD Demilitarization
and Trade Security Control Manual”, DOD 4160.21-M-1. Only demilitarized property may be offered for
public sale or donated to public bodies.
61 Nuclear materials and radiological materials fall outside the scope of this chapter.
Section 93
DOE-HDBK-1139/3-2003
122
STANDARD FORMS USED IN CHEMICAL DISPOSITION:
Standard Form 120 or SF 120, “Report of Excess Personal Property” – submitted by the holding agency
(i.e., DOE) to the GSA at the end of internal DOE screening to report excess chemicals that are available
for federal screening. If DOE plans to conduct a sale after donation screening, it should so inform GSA at
this time. [NOTE: Do not report extremely hazardous property on SF 120 unless so directed by a GSA
Regional office or GSA Central office. Do not screen within DOE or report to the GSA any Nuclear-
related and Proliferation-sensitive property.]
Standard Form 122 or SF 122, “Transfer Order Excess Personal Property” – used for the transfer of
excess chemicals among Federal agencies, including the DOE. Prepared by the transferee (i.e., receiving
agency) and approved by the GSA regional office (responsible for the region where the property is
located).
Standard Form 123 or SF 123, “Transfer Order Surplus Personal Property” – used for the donation of
surplus chemicals to a non-Federal recipient (e.g., a State agency for Surplus Property (SASP) or Donee).
Prepared by the SASP or donee when applicable and submitted to the GSA regional office (responsible
for the region where the property is located) for approval.
Standard Form 126 or SF 126, “Report of Personal Property for Sale and Certification” – used for
reporting hazardous materials that are not required to be reported on SF 120 for utilization screening, and
for which any required donation screening has been completed. Prepared by the owning DOE
organization and submitted to the GSA regional office for sale.
DOE-HDBK-1139/3-2003
123
REGULATION
TABLE A-1. TYPICAL DISPOSITION OF EXCESS CHEMICALS
DISPOSITION
OPTION
DESCRIPTION
OF ACTIVITY
ELIGIBLE
RECIPIENT
EADS or
FEDS
SCREENING
PROCESS
TIME FRAME
REQUIRED
FORMS
62
1. Unneeded (or
Excess)
Chemical
Reutilization or
Redistribution
Internal
Screening for
transfers within
DOE
Any site in
DOE
Complex
EADS 15 day DOE
Reutilization
Screening
SF 122 and
Approval by
DOE for
Transfer;
SF 120
(Reporting of
Excess) for
remaining
chemicals
41CFR109-43.304-
1.50;
41CFR109-43.304-
1.50(d);
41CFR109-43.304-
1.51;
41CFR101-42;
41CFR102-36
EXCESS RELEASE DATE
2. Excess
Chemical
Transfer
Excess Screening
or Federal
Screening
Any Federal
agency
FEDS 21 day Federal
Excess Screening
SF 122 41CFR109-43;
41CFR101-42.207;
41CFR101-42.1102;
FMPR;
41CFR102-36
SURPLUS RELEASE DATE
3. Surplus
Chemical
Donation
Donation to
Public agencies
through State
government
(SASP) screeners
State agency
or agency-
approved
organization
FEDS Surplus Donation
Screening
SF 123 41CFR109-44;
41CFR109-43.307;
41CFR101-42.3;
41CFR101-42.1102;
FMPR;
41CFR102-37
4. Surplus
Chemical Sale
Sale to Public by
competitive bid
sales or auction
FMPR;
Public or
private
company
FEDS Sale Process SF 126 41CFR109-45.3;
41CFR101-45;
41CFR101-42.4;
41CFR101-42.1102;
41CFR102-37
62 CFR citations listed in the Regulation column are for illustration purposes only, and are not intended to be all-
inclusive.
DOE-HDBK-1139/3-2003
124
TABLE A-2. DISPOSITION OF EXCESS OR SURPLUS CHEMICALS SUBJECT TO
ABANDONMENT OR DESTRUCTION
PROCESS
PRIOR TO
DISPOSITION
DISPOSITION
OPTION
DESCRIPTION
OF ACTIVITY
ELIGIBLE
RECIPIENT
EADS or
FEDS
REQUIRED
FORMS/
APPROVAL
REGULATION63
Sale to the
Public or
Donation to
Public bodies
Section 94
Option in lieu of
abandonment or
destruction
Sold to public
as scrap or
Donated to
public bodies
Public notice/
advertisements
of intent to
destroy or sell
41CFR109-44.7;
41CFR109-45;
41CFR102-36;
41CFR102-37;
41CFR101-42;
41CFR101-45
Not
applicable
SF 126 to report
sale
transactions;
No Standard
Forms to record
a donation -- an
auditable
document
suffices
Abandonment or
Destruction
Applicable to
property with “no
commercial
value” or
estimated
maintenance and
storage costs
exceeding
potential sale
proceeds, or High
risk property with
health, safety or
security concerns
Not
applicable
Written
justification and
approval by
DOE, pending
disposition
action;
Not
applicable
Public notice/
advertisements
of intent to
destroy or sell
prior to actual
disposition;
Notice may be
waived with
DOE review and
approval; Some
property may be
converted to
scrap or
rendered
innocuous or
unfit for use
Eye witness
certification of
destruction
41CFR109-45.9;
41CFR109-1.53;
41CFR101-42.406;
41CFR101-
42.1102;
41CFR101-
45.309-3;
41CFR102-36.35;
41CFR102-36.305
through 102-
36.330;
41CFR102-36.430;
41CFR102-37.80;
41CFR102-37.570
63 CFR citations listed in the Regulation column are for illustration purposes only, and are not intended to be all-
inclusive.
DOE-HDBK-1139/3-2003
125
Appendix B
FEDERAL SUPPLY CLASSES AND GROUPS RELATED TO CHEMICALS
Table B-1. List of Federal Supply Classes Composed Predominantly of Hazardous Items
FSC
Code
Federal Supply Class (FSC)
6810 Chemicals
6820 Dyes
6830 Gases: Compressed and liquefied
6840 Pest control agents and disinfectants
6850 Miscellaneous chemical specialties
7930 Cleaning and polishing compounds and preparations
8010 Paints, dopes, varnishes, and related products
8030 Preservative and sealing compounds
8040 Adhesives
9110 Fuels, solid
9130 Liquid propellants and fuels, petroleum base
9135 Liquid propellant fuels and oxidizers, chemical base
9140 Fuel oils
9150 Oils and greases: Cutting, lubricating, and hydraulic
9160 Miscellaneous waxes, oils, and fats
DOE-HDBK-1139/3-2003
126
Table B-2. Selective List of Federal Supply Classes and Groups that Contain a Significant
Number of Hazardous Items
[NOTE: The following is shown for illustrative purposes; for a complete listing, see 41CFR101-
42.1101(c)]
Examples of Hazardous Materials
Requiring Identification
Federal
Supply
Class/Group
Title
1375 Demolition materials Explosive device.
Group 34
Metalworking machinery. Equipment containing hazardous hydraulic
fluids including PCBs.
3433
Compressed gases. Gas welding, heat cutting, and
Metalizing equipment.
3439
Miscellaneous welding,
soldering and brazing supplies
and accessories.
Hazardous items such as cleaners, acids, flux
and supplies that contain or produce
hazardous fumes.
3610 Printing, duplicating, and
bookbinding equipment.
Flammable or toxic lithographic solutions.
4240
Items which involve oxygen, or compressed
Safety and rescue equipment
gases, or contain emitting charges.
5660
Wallboard, building paper, and
thermal insulation materials.
Asbestos cloth which has loose fibers or
particles that may become airborne and
materials containing formaldehyde.
5910
Capacitors
(PCBs) or sulfuric acid.
Items that contain polychlorinated biphenyls
5950
Coils and transformers.
Items containing polychlorinated biphenyls
(PCBs).
5970
Electrical insulators and
insulating materials.
Items containing flammable solvents.
6135
Section 95
Batteries, primary.
Lead-acid, lithium and mercury batteries and
alkaline (with electrolyte).
6140
Batteries, secondary. Items that are wet or moist containing
corrosive or other hazardous compounds.
6505
Drugs, biologicals and official
reagents.
Hazardous items as defined in 40CFR101-
42.001.
6508
Medicated cosmetics and
Toiletries.
Hazardous items as defined in 40CFR101-
42.001.
6640
Laboratory equipment and
supplies.
Items containing flammable compounds,
mercury, or asbestos.
6685
Pressure, temperature, and
humidity and measuring and
Controlling instruments.
Items containing mercury or compressed
gases.
6750 Photographic supplies.
Items containing hazardous chemicals,
solvents, thinners, and cements.
DOE-HDBK-1139/3-2003
127
7510
Office supplies Hazardous items, such as thinners, cleaning
fluids, flammable inks, and varnishes.
8510
Perfumes, toilet preparations,
and powders.
Shipping containers, pressurized containers
with flammable or nonflammable
propellants.
8720 Fertilizers. Items containing weed and pest control or
other harmful ingredients or because of their
composition, are hazardous.
9390
Miscellaneous fabricated
nonmetallic materials.
Items containing flammable solvents or
asbestos.
DOE-HDBK-1139/3-2003
128
INTENTIONALLY BLANK
DOE-HDBK-1139/3-2003
129
Chapter 10 - Training
1.0 Introduction
This chapter identifies and consolidates existing user safety and health requirements found in DOE
and Federal chemical-related safety and health regulations and National Standards that address
training requirements associated with the handling and use of chemicals (see definition) and chemical
products (see definition). This chapter specifically consolidates requirements found in Occupational
Safety and Health Administration (OSHA) Regulations 29CFR1910 and 29CFR1926, 10CFR850,
and National Fire Protection Association (NFPA) Codes 55, 430, and 432, including technical
standards that are made mandatory by their specific reference within a regulation, rule or DOE Order.
State and local codes and requirements are NOT included.
This chapter is intended to list chemical-related safety and health requirements and to consolidate
those that are overlapping and/or duplicative. The list of requirements includes “pointers” to the
sources of those requirements.
2.0
This document does NOT create any new or additional requirements.
Applicability
This chapter consolidates existing, core safety and health requirements that all sites must follow when
engaged in chemical-related activities. It is intended only to address safety and health-related training
requirements applicable to chemical user activities. This chapter applies to DOE Contractors and
Field Organizations who handle or use chemicals and chemical products. This chapter does NOT
apply to:
• waste operations (the Resource Conservation and Recovery Act (RCRA) requires training
prior to the generation of waste; see 40CFR264.16);
• transportation (training requirements for transporting chemicals are covered in Chapter 4 of
this document, “Transportation”.)
• emergency management (training requirements for Emergency Management are covered in
Chapter 8 of this document, “Emergency Management”.)
[NOTE: Waste operations are NOT included in this consolidation of Chemical User Safety and
Health Requirements. Hence, RCRA is not included is this document. However, RCRA requires
training and must be adhered to as appropriate for site/facility operations.]
Section 96
The information presented here applies to all locations that use chemicals or chemical
products. [NOTE: Throughout this document, the term “chemicals” is used to indicate
chemicals and/or chemical products as described in Section 3, below.] This chapter
consolidates existing, core safety and health requirements that all sites must follow when
engaged in chemical-related activities.
The requirements included in this chapter come from sources that have different safety purposes. As
a result, some of these requirements may not always be applicable to the work being performed at an
individual site or facility. It is the responsibility of each user to determine the applicability of specific
requirements to their work and how they are implemented. The reference sources for the
DOE-HDBK-1139/3-2003
130
requirements included in this chapter can be used to determine the applicability of those requirements
to the work being performed.
3.0 Definitions and Acronyms
See Glossary.
4.0 Requirements for Training
Sources Requirements10 Consolidated 64,65
29CFR1910.1200(h)(1);
29CFR1910.1450(f)
4.1 General Employee Information and Training - Employers shall
provide employees with effective information and training on hazardous
chemicals in their work area at the time of their initial assignment, and
whenever a new physical or health hazard the employees have not
previously been trained about is introduced into their work area.
Information and training may be designed to cover categories of hazards
(e.g., flammability, carcinogenicity) or specific chemicals.
29CFR1910.1450(f)(2)
4.1.1 The frequency of refresher information and training shall be
determined by the employer.
29CFR1910.1200(h)(1)
4.1.2 Chemical-specific information must always be available through
labels and material safety data sheets.
29CFR1910.1200 (h)(2)
4.1.3 Information - Employees shall be informed of:
29CFR1910.1200(h)(2)(i);
29CFR1910.1450(f)(3)(i)
4.1.3.1 The contents of 29CFR1910.1200 and 1450 and their
appendices, and,
29CFR1910.1200(h)(2)(ii)
4.1.3.2 Any operations in their work area where hazardous
chemicals are present; and,
29CFR1910.1200(h)(2)(iii)
4.1.3.3 The location and availability of the written hazard
communication program, including the required list(s)
of hazardous chemicals, and material safety data sheets
required by this section.
64 Some chemical safety requirements contain generalized training statements such as: “employees shall be properly
trained in this area.” These general requirements are NOT included here. Only specific training requirements with
some details are cited.
65 29CFR1910.120(q), HAZWOPER, as required for all emergency response operations are NOT repeated here, and
can be found in Chapter 8 (“Consolidated Requirements for Chemical Emergency Management”) of this volume of
the Chemical Management Handbook.
DOE-HDBK-1139/3-2003
131
Sources10 Consolidated Requirements64,65
4.1.4 Training – Employee training shall include at least:
29CFR1910.1200 (h)(3)(i);
29CFR1910.1450(f)(4)(i)(A)
4.1.4.1 Methods and observations that may be used to detect the
presence or release of a hazardous chemical in the work
area (such as monitoring conducted by the employer,
continuous monitoring devices, visual appearance or
odor of hazardous chemicals when being released, etc.);
29CFR1910.1200 (h)(3)(ii);
29CFR1910.1450(f)(4)(i)(B)
4.1.4.2 The physical and health hazards of the chemicals in the
work area;
29CFR1910.1200(h)(3)(iii);
Section 97
29CFR1910.1450(f)(4)(i)(C)
4.1.4.3 The measures employees can take to protect themselves
from these hazards, including specific procedures the
employer has implemented to protect employees from
exposure to hazardous chemicals, such as appropriate
work practices, emergency procedures, and personal
protective equipment to be used; and,
29CFR1910.1200(h)(3)(iv)
4.1.4.4 The details of the hazard communication program
developed by the employer, including an explanation of
the labeling system and the material safety data sheet,
and how employees can obtain and use the appropriate
hazard information.
29CFR1910.1450(f)
4.2 Chemical Laboratories – In addition to the requirements of Section 4.1
above, employees in chemical laboratories shall also be trained as
follows:
29CFR1910.1450(f) 4.2.1 Information:
29CFR1910.1450(f)(3)(ii)
4.2.1.1 The location and availability of the employer's
Chemical Hygiene Plan;
29CFR1910.1450(f)(3)(iii)
4.2.1.2 The permissible exposure limits for OSHA-regulated
substances or recommended exposure limits for other
hazardous chemicals where there is no applicable
OSHA standard;
29CFR1910.1450(f)(3)(iv)
4.2.1.3 Signs and symptoms associated with exposures to
hazardous chemicals used in the laboratory; and
29CFR1910.1450(f)(3)(v)
4.2.1.4 The location and availability of known reference
material on the hazards, safe handling, storage and
disposal of hazardous chemicals found in the laboratory
including, but not limited to, Material Safety Data
Sheets received from the chemical supplier.
29CFR1910.1450(f)(4)(ii)
4.2.2 Training – The employee shall be trained on the applicable
details of the employer's written Chemical Hygiene Plan.
DOE-HDBK-1139/3-2003
132
Sources10 Consolidated Requirements64,65
29CFR1910.134(k)
4.3 Respirators. The employer shall provide effective training to
employees who are required to use respirators. The training must be
comprehensive, understandable, and recur annually and more often
if necessary.
29CFR1910.134, App. D
4.3.1 This paragraph also requires the employer to provide the basic
information on respirators found in Appendix D of
29CFR1910.134 to all employees who wear respirators,
including those who do so voluntarily (this includes dust
masks).
29CFR1910.134(k)(1)
4.3.2 The employer shall ensure that each employee can demonstrate
knowledge of at least the following:
29CFR1910.134(k)(1)(i)
4.3.2.1 Why the respirator is necessary and how improper fit,
usage, or maintenance can compromise the protective
effect of the respirator;
29CFR1910.134(k)(1)(ii)
4.3.2.2 What the limitations and capabilities of the respirator
are;
29CFR1910.134(k)(1)(iii)
4.3.2.3 How to use the respirator effectively in emergency
situations, including situations in which the respirator
malfunctions;
29CFR1910.134(k)(1)(iv)
4.3.2.4 How to inspect, put on and remove, use, and check the
seals of the respirator;
29CFR1910.134(c)(1)(v);
29CFR1910.134(c)(1)(viii);
29CFR1910.134(k)(1)(i);
29CFR1910.134(k)(1)(v)
4.3.2.5 What the procedures are for cleaning, maintenance and
storage of the respirator;
29CFR1910.134(k)(1)(vi)
4.3.2.6 How to recognize medical signs and symptoms that may
limit or prevent the effective use of respirators; and
29CFR1910.134(k)(1)(vii)
4.3.2.7 The general requirements for Respiratory Protection
found in 29CFR1910.134.
29CFR1910.134(k)(2)
4.3.3 The training shall be conducted in a manner that is
understandable to the employee.
29CFR1910.134(k)(3)
Section 98
4.3.4 The employer shall provide the training prior to requiring the
employee to use a respirator in the workplace.
DOE-HDBK-1139/3-2003
133
Sources10 Consolidated Requirements64,65
29CFR1910.134(k)(4)
4.3.5 An employer who is able to demonstrate that a new employee
has received training within the last 12 months that addresses
the elements specified in paragraphs 4.3.2.1through 4.3.2.7,
above, is not required to repeat such training provided that the
employee can demonstrate knowledge of those elements.
Previous training not provided by the current employer must be
repeated under the auspices of the current employer no later than
12 months from the date of that previous training.
29CFR1910.134(k)(5)
4.3.6 Retraining shall be administered annually, and when the
following situations occur:
29CFR1910.134(k)(5)(i)
4.3.6.1 Changes in the workplace or the type of respirator
render previous training obsolete.
29CFR1910.134(k)(5)(ii)
4.3.6.2 Inadequacies in the employee's knowledge or use of the
respirator indicate that the employee has not retained the
requisite understanding or skill.
29CFR1910.134(k)(5)(iii)
4.3.6.3 Any other situation arises in which retraining appears
necessary to ensure safe respirator use.
29CFR1910.134(k)(6);
29CFR1910.134, App. D
4.3.7 The basic advisory information on respirators, as presented in
Appendix D, shall be provided by the employer in any written or
oral format, to employees who wear respirators, when such use
is not required by 29CFR1910.134 or the employer.
29CFR1910.119
4.4 Highly Hazardous Chemicals (see definition)
29CFR1910.119(g)
4.4.1 Initial Training
29CFR1910.119(g)
4.4.1.1 Each employee presently involved in operating a
process, and each employee, before being involved in
operating a newly assigned process, shall be trained in
an overview of the process and in the operating
procedures. The training shall include emphasis on the
specific safety and health hazards, emergency
operations including shutdown, and safe work practices
applicable to the employee's job tasks.
29CFR1910.119(g)(1)(ii)
4.4.1.2 In lieu of initial training for those employees already
involved in operating a process on May 26, 1992, an
employer may certify in writing that the employee has
the required knowledge, skills, and abilities to safely
carry out the duties and responsibilities as specified in
the operating procedures.
DOE-HDBK-1139/3-2003
134
Sources10 Consolidated Requirements64,65
29CFR1910.119(g)(2)
4.4.2 Refresher training shall be provided at least every three years,
and more often if necessary, to each employee involved in
operating a process to assure that the employee understands and
adheres to the current operating procedures of the process. The
employer, in consultation with the employees involved in
operating the process, shall determine the appropriate frequency
of refresher training.
29CFR1910.119(g)(3)
4.4.3 Training documentation - The employer shall ascertain that each
employee involved in operating a process has received and
understood the training required by this paragraph. The
employer shall prepare a record which contains the identity of
the employee, the date of training, and the means used to verify
that the employee understood the training.
29CFR1910.119(h)(3)
4.4.4 Contract employers shall:
29CFR1910.119(h)(3)(i)
4.4.4.1 assure that each contract employee is trained in the work
practices necessary to safely perform his/her job, and
29CFR1910.119(h)(3)(ii)
Section 99
4.4.4.2 assure that each contract employee is instructed in the
known potential fire, explosion, or toxic release hazards
related to his/her job and the process, and the applicable
provisions of the emergency action plan, and
29CFR1910.119(h)(3)(iii)
4.4.4.3 document that each contract employee has received and
understood the training required by this paragraph. The
contract employer shall prepare a record, which contains
the identity of the contract employee, the date of
training, and the means used to verify that the employee
understood the training.
29CFR1910.119(j)(3)
4.4.5 Training for process maintenance activities - The employer shall
train each employee involved in maintaining the on-going
integrity of process equipment in an overview of that process
and its hazards and in the procedures applicable to the
employee's job tasks to assure that the employee can perform the
job tasks in a safe manner.
29CFR1926.21
4.5 Construction
29CFR1926.21(b)(2)
4.5.1 The employer66 shall instruct each employee in the recognition
and avoidance of unsafe conditions and the regulations
applicable to his work environment to control or eliminate any
hazards or other exposure to illness or injury.
66 Employers should avail themselves of the safety and health training programs provided by the Secretary of Labor.
DOE-HDBK-1139/3-2003
135
Sources10 Consolidated Requirements64,65
29CFR1926.21(b)(3)
4.5.2 Employees required to handle or use poisons, caustics, and other
harmful substances shall be instructed regarding their safe
handling and use, and be made aware of the potential hazards,
personal hygiene, and personal protective measures required to
safely handle or use harmful substances.
29CFR1926.21(b)(5)
4.5.3 Employees required to handle or use flammable liquids, gases,
or toxic materials shall be instructed in the safe handling and use
of these materials and made aware of the specific requirements
contained in Subparts D, F, and other applicable subparts of
29CFR1926.
29CFR1926.21(b)(6)(i)
4.5.4 All employees required to enter into confined or enclosed spaces
shall be instructed as to the nature of the hazards involved, the
necessary precautions to be taken, and in the use of protective
and emergency equipment required. The employer shall comply
with any specific regulations that apply to work in dangerous or
potentially dangerous areas.
4.6 Training requirements for specific materials
NFPA 55, 1-3
4.6.1 Compressed and Liquefied Gases in Portable Cylinders –
Persons responsible for or working in the areas where
compressed gases are produced, stored, handled, or used shall be
trained in the chemical and physical properties of the materials
and the appropriate emergency response.
NFPA 430, 2-7.1 and 2-7.2
4.6.2 Storage of Liquid and Solid Oxidizers – Persons involved in
operations where oxidizers are stored shall receive instruction in
handling the materials in a safe manner, including the
manufacturer’s and processor’s recommendations. Particular
attention shall be given to proper disposal of spilled material to
prevent contamination.
NFPA 432, 2-2
4.6.3 Storage of Organic Peroxides – Personnel involved in operations
in organic peroxide storage areas shall be instructed in proper
and safe handling of such materials, proper use of personal
protective equipment, proper and safe disposal of spilled
material, and proper emergency procedures. Manufacturer’s
instructions shall be consulted for each specific formulation.
Section 100
29CFR1910.253 4.6.4 Oxygen-fueled Gas Welding and Cutting
29CFR1910.253(a)(4)
4.6.4.1 Workmen in charge of the oxygen or fuel-gas supply
equipment, including generators, and oxygen or fuel-gas
distribution piping systems shall be instructed and
judged competent by their employers for this important
work before being left in charge. Rules and instructions
covering the operation and maintenance of oxygen or
fuel-gas supply equipment including generators, and
oxygen or fuel-gas distribution piping systems shall be
readily available.
DOE-HDBK-1139/3-2003
136
Sources10 Consolidated Requirements64,65
29CFR1910.253(e)(6)(ii)
4.6.4.2 Regulators shall be repaired only by skilled mechanics
with appropriate training.
29CFR1910.1003;
29CFR1926.1003-1016
4.6.5 OSHA Regulated Carcinogens – Non-laboratory use of the
following 13 carcinogens requires additional training as
prescribed in sections 4.6.5.1 and 4.6.5.2 below.
Nitrobiphenyl (CAS No.) 92933;
alpha-Naphthylamine, CAS No. 134327;
methyl chloromethyl ether, CAS No. 107302;
3,3'-Dichlorobenzidine (and its salts) CAS No. 91941;
bis-Chloromethyl ether, CAS No. 542881;
beta-Naphthylamine, CAS No. 91598;
Benzidine, CAS No. 92875;
4-Aminodiphenyl, CAS No. 92671;
Ethyleneimine, CAS No. 151564;
beta-Propiolactone, CAS No. 57578;
2-Acetylaminofluorene, CAS No. 53963;
4-Dimethylaminoazo-benezene, CAS No. 60117;
N-Nitrosodimethylamine, CAS No. 62759.
29CFR1910.1003(e)(5)(i)
4.6.5.1 Each employee prior to being authorized to enter a
regulated area (see definition), shall receive a training
and indoctrination program including, but not
necessarily limited to:
29CFR1910.1003(e)(5)(i)(A)
4.6.5.1.1 the nature of the carcinogenic hazards of a
carcinogen addressed by this section,
including local and systemic toxicity;
29CFR1910.1003(e)(5)(i)(B)
4.6.5.1.2 the specific nature of the operation involving
carcinogen addressed by this section that
could result in exposure;
29CFR1910.1003(e)(5)(i)(C)
4.6.5.1.3 the purpose for and application of the medical
surveillance program, including, as
appropriate, methods of self-examination;
29CFR1910.1003(e)(5)(i)(D) 4.6.5.1.4 the purpose for and application of
decontamination practices and purposes;
29CFR1910.1003(e)(5)(i)(E)
4.6.5.1.5 the purpose for and significance of emergency
practices and procedures;
29CFR1910.1003(e)(5)(i)(F)
4.6.5.1.6 the employee's specific role in emergency
procedures;
DOE-HDBK-1139/3-2003
137
Sources10 Consolidated Requirements64,65
29CFR1910.1003(e)(5)(i)(G)
4.6.5.1.7 specific information to aid the employee in
recognition and evaluation of conditions and
situations which may result in the release of a
carcinogen addressed by this section;
29CFR1910.1003(e)(5)(i)(H)
4.6.5.1.8 the purpose for and application of specific
first aid procedures and practices;
29CFR1910.1003(e)(5)(i)(I)
4.6.5.1.9 a review of this section at the employee's first
training and indoctrination program and
annually thereafter.
29CFR1910.1003(e)(5)(ii)
4.6.5.2 Specific emergency procedures shall be prescribed, and
posted, and employees shall be familiarized with their
terms, and rehearsed in their application.
4.6.6 Other Specific Chemicals – In addition to the chemical safety
training requirements for the materials above, there are also
training requirements for other specific chemicals as shown in
the following. Details can be found in the specific citations.
29CFR1910.1045
4.6.6.1 Acrylonitrile
29CFR1910.1018
Section 101
4.6.6.2 Arsenic, inorganic (also see 29CFR1926.1118,
construction)
29CFR1910.1001 4.6.6.3 Asbestos (also see 29CFR1926.1101, construction)
29CFR1910.1028 4.6.6.4 Benzene (also see 29CFR1926.1128, construction)
10CFR850 4.6.6.5 Beryllium
29CFR1910.1051 4.6.6.6 1,3-Butadiene
29CFR1910.1027 4.6.6.7 Cadmium (also see 29CFR1926.1127, construction)
29CFR1910.1044
4.6.6.8 1,2-dibromo-3-chloropropane (also see
29CFR1926.1144, construction)
29CFR1910.1047
4.6.6.9 Ethylene oxide (also see 29CFR1926.1147,
construction)
29CFR1910.1048 4.6.6.10 Formaldehyde (also see 29CFR1926.1148, construction)
29CFR1910.1025 4.6.6.11 Lead (also see 29CFR1926.62, construction)
29CFR1910.1052
4.6.6.12 Methylene chloride (also see 29CFR1926.1152,
construction)
29CFR1910.1050 4.6.6.13 Methylenedianiline (also see 29CFR1926.60,
construction)
29CFR1910.1017
4.6.6.14 Vinyl chloride (also see 29CFR1926.1117,
construction)
DOE-HDBK-1139/3-2003
138
Sources10 Consolidated Requirements64,65
See the specific standards
listed for each chemical
above for the source of the
requirements listed in the
sections that follow.
4.6.6.15 General Training Requirements icals listed
above:
67 for 14 chem
4.6.6.15.1 Training shall be provided at the time of
initial assignment, or upon institution of the
training program, and at least annually
thereafter.
• The emergency procedures developed,
as required by the chemical-specific
regulations cited;
4.6.6.15.2 The employer shall assure that each
employee is informed of the following:
• The information contained in the
appendices in each of the specific chemical
requirements cited; 68
• The quantity, location, manner of use,
release, or storage, and the specific nature
of operations which could result in
exposure, as well as any necessary
protective steps;
• The purpose, proper use, cleaning,
maintenance, storage and limitations of
respirators and personal protective
clothing; The purpose for, and a
description of the medical surveillance
program required by the chemical-specific
regulations cited;
• Engineering and work practice controls,
their function, and the employee's
relationship to these controls; and
• A review of the chemical-specific
regulations cited.
4.6.6.15.3 The employer shall make a copy of the
specific chemical standard and its appendices
readily available to all affected employees.
67This section contains a summary of the training requirement that are common to most of the chemicals listed. The
exact requirements for each chemical may vary, and the chemical-specific regulation cited should be reviewed for
specific training details.
68 These appendices contain additional information regarding the chemicals’ physical and chemical properties, safety
and health data, medical surveillance, emergency actions, etc.
DOE-HDBK-1139/3-2003
139
5.0 Source Documents
NFPA 55 (1998), “Storage, Use, and Handling Of Compressed and Liquefied Gases in Portable
Cylinders”.
29CFR1910.1001, “Asbestos”.
29CFR1910.1018, “Inorganic Arsenic”.
29CFR1910.1025, “Lead”.
29CFR1910.1027, “Cadmium”.
29CFR1910.1044, “1,2-dibromo-3-chloropropane”.
29CFR1910.1048, “Formaldehyde”.
29CFR1910.1052, “Methylene Chloride”.
29CFR1926.21, “Safety Training and Education”.
NFPA 432 (1997), “Storage of Organic Peroxide Formulations”.
10CFR850, “Chronic Beryllium Disease Prevention Program”.
29CFR1910.119, “Process Safety Management of Highly Hazardous Chemicals”.
29CFR1910.134, “Respiratory Protection”.
29CFR1910.253, “Oxygen-fuel Gas Welding and Cutting”.
Section 102
29CFR1910.1003, “4-Nitrobiphenyl”.
29CFR1910.1017, “Vinyl Chloride”.
29CFR1910.1028, “Benzene”.
29CFR1910.1045, “Acrylonitrile”.
29CFR1910.1047, “Ethylene Oxide”.
29CFR1910.1050, “Methylenedianiline”.
29CFR1910.1051, “1,3-Butadiene”.
29CFR1910.1200, “Hazard Communication”.
29CFR1910.1450, “Occupational Exposure to Hazardous Chemicals in Laboratories”.
DOE-HDBK-1139/3-2003
140
INTENTIONALLY BLANK
DOE-HDBK-1139/3-2003
141
ANSI Z49.1 (2000), “Safety in Welding, Cutting, and Allied processes”.
CGA P-1 (1999), "Safe Handling of Compressed Gases in Containers".
Department of Energy Acquisition Regulation (DEAR) 970.5204-2, “Integration of Environment,
Safety and Health into Work Planning and Execution”.
DOE Acquisition Letter AL-2000-03, “Greening the Government Requirements in Contracting”
(May 16, 2000) (Superceded by AL-2002-05).
DOE Acquisition Letter AL-2002-05, “Greening the Government Requirements in Contracting”
(July 10, 2002).
DOE O 450.1, “Environmental Protection Program”.
Executive Order 12344 (February 3, 1982), “Naval Nuclear Propulsion Program”, 47 Federal
Register 4979.
Executive Order 13148 of April 21, 2000, “Greening the Government Through Leadership in
Environmental Management”.
Complete List of Sources69
CGA G-1 (1996), "Acetylene".
Department of Energy (July 1999), “Guidelines on Export Control and Nonproliferation”.
Department of Energy Personal Property Letter, Issue Number 970-3, Revision 1 (February 3,
1998).
DOE O 151.1, “Comprehensive Emergency Management System”.
DOE O 225.1A, “Accident Investigations”.
DOE O 420.1A, “Facility Safety”.
DOE O 440.1A, “Worker Protection Management for DOE Federal and Contractor Employees”.
DOE O 460.1A, “Packaging and Transportation Safety”.
DOE O 460.1B, “Packaging and Transportation Safety” [NOTE: This order, issued on 4/4/2003,
cancels the DOE O 460.1A].
DOE O 5480.19, “Conduct of Operations Requirements for DOE Facilities”.
DOE-STD-1027-92, “Hazard Categorization and Accident Analysis Techniques for Compliance
with DOE O 5480.23, Nuclear Safety Analysis Reports”.
DOE-STD-1120-98, “Integration of Environment, Safety, and Health into Facility Disposition
Activities”.
DOE-STD-3009-94, “Preparation Guide for U.S. DOE Nonreactor Nuclear Facility Safety Analysis
Reports”.
DOE-STD-3011-94, “Guidance for Preparation of DOE 5480.22 (TSR) and DOE 5480.23 (SAR)
Implementation Plans”.
DOE-STD-3016-99, “Limited Standard; Hazard Analysis Reports for Nuclear Explosive
Operations”.
Executive Order 13101 of September 14, 1998, “Greening the Government Through Waste
Prevention, Recycling, and Federal Acquisition”.
69 Hyperlinks to ANSI, CGA, and NFPA requirements provided here are for general information only, as they require user
subscription to a prescribed service in order to access these organizations’ source requirements.
DOE-HDBK-1139/3-2003
142
NFPA 30 (2000), “Flammable and Combustible Liquids Code”.
NFPA 430 (2000), “Storage of Liquid and Solid Oxidizers”.
NFPA 704 ( 2001), "Identification of the Hazards of Materials for Emergency Response".
Public Law 98-525 (10/19/84), “Department of Defense Authorization Act, 1985”; also called
“Department of Energy National Security and Military Applications of Nuclear Energy
Authorization Act of 1985”.
10CFR110, Nuclear Regulatory Commission, "Export and Import of Nuclear Equipment and
Material”.
10CFR835, “Occupational Radiation Protection”.
Section 103
15CFR Subpart C (Parts 730 to 774), Department of Commerce, “Export Administration
Regulations” (EAR); in particular, 15CFR734, “Scope of the Export Administration Regulations”,
15CFR744, "Control Policy: End-User and End-Use Based", and 15CFR774, “The Commerce
Control List”.
29CFR1910, “Occupational Safety and Health Standards”.
Federal Standard 123 (or FED-STD-123), “Marking for Shipment (Civil Agencies)”.
Federal Standard 313 (or FED-STD-313), “Material Safety Data, Transportation Data and Disposal
Data for Hazardous Materials Furnished to Government Activities”.
The Hazardous and Solid Waste Amendments of 1984 (HSWA).
The Helium Act (Pub. L. 86-777, as amended (50 U.S.C. 167(d).
International Atomic Energy Agency (IAEA), Information Circular (INFCIRC) 254, Part 1
(“Trigger List”) and Part 2 (“Dual-use List”).
NFPA 45 (2000), “Standard on Fire Protection for Laboratories Using Chemicals”.
NFPA 51 (2002), "Standard for the Design and Installation of Oxygen-Fuel Gas Systems".
NFPA 55 (2003), "Standard for the Storage, Use, and Handling of Compressed and Liquefied
Gases in Portable Cylinders".
NFPA 430 (1995), "Code for the Storage of Liquid and Solid Oxidizers".
NFPA 432 (2002), “Code for the Storage of Organic Peroxide Formulations”.
NFPA 471 (2002), “Recommended Practice for Responding to Hazardous Materials”.
NFPA 472 (2002), “Standard on Professional Competence of Responders to Hazardous Materials
Incidents”.
NFPA 484 (2002), “Standard for Combustible Metals, Metal Powders, and Metal Dusts”.
NFPA 1620 (1998), “Recommended Practice for Pre-Incident Planning”.
Secretary of Energy Memorandum, November 12, 1999, “Pollution Prevention and Energy
Efficiency Leadership Goals for Fiscal Year 2000 and Beyond”.
10CFR810, Department of Energy, "Assistance to Foreign Atomic Energy Activities".
10CFR830, “Nuclear Safety Management”.
10CFR850, “Chronic Beryllium Disease Prevention Program”.
10CFR1021, “National Environmental Policy Act Implementing Procedures”.
21CFR1316, “Drug Enforcement Administration; Administrative Functions, Practices, and
Procedures”.
22CFR Subchapter M (Parts 120-130), Department of State, "International Traffic in Arms
Regulations" (ITAR), and in particular, 22CFR121, “The United States Munitions List”.
27CFR22.41, “Distribution and Use of Tax-Free Alcohol, Qualification”.
DOE-HDBK-1139/3-2003
143
29CFR1910.20, “Preservation of Records (medical and exposure)”.
29CFR1910.102, “Acetylene”.
29CFR1910.103, “Hydrogen”.
29CFR1910.106, “Flammable and Combustible Liquids”.
29CFR1910.132, “Personal Protective Equipment”.
29CFR1910.1004, “alpha-Naphthylamine”.
29CFR1910.1012, “Ethyleneimine”.
29CFR1910.1015, “4-Dimethylaminoazobenzene”.
29CFR1926.65, “Hazardous Waste Operations and Emergency Response”.
29CFR1910.6, "Incorporation by Reference".
29CFR1910.38, “Employee Emergency Plans and Fire Prevention Plans”.
29CFR1910.101, “Compressed Gases (general requirements)”.
29CFR1910.104, “Oxygen”.
29CFR1910.105, “Nitrous oxide”.
29CFR1910.119, “Process Safety Management of Highly Hazardous Chemicals”.
29CFR1910.120, “Hazardous Waste Operations and Emergency Response”.
29CFR1910.134, "Respiratory Protection".
29CFR1910.146, “Permit-required Confined Spaces”.
29CFR1910.253, "Oxygen-Fuel Gas Welding and Cutting".
29CFR1910.1001, “Asbestos”.
29CFR1910.1003, “13 Carcinogens (4-Nitrobiphenyl, etc.)”.
Section 104
29CFR1910.1006, “Methyl chloromethyl ether”.
29CFR1910.1007, “3,3’-Dichlorobenzidine (and its salts)”.
29CFR1910.1008, “bis-Chloromethyl ether”.
29CFR1910.1009, “beta-Naphthylamine”.
29CFR1910.1010, “Benzidine”.
29CFR1910.1011, “4-Aminodiphenyl”.
29CFR1910.1013, “beta-Propiolactone”.
29CFR1910.1014, “2-Acetylaminofluorene”.
29CFR1910.1016, “N-Nitrosodimethylamine”.
29CFR1910.1017, “Vinyl Chloride”.
29CFR1910.1018, “Inorganic Arsenic”.
29CFR1910.1020, “Access to Employee Exposure and Medical Records”.
29CFR1910.1025, “Lead”.
29CFR1910.1027, “Cadmium”.
29CFR1910.1028, “Benzene”.
29CFR1910.1044, “1,2-dibromo-3-chloropropane”.
29CFR1910.1045, “Acrylonitrile”.
29CFR1910.1047, “Ethylene Oxide”.
29CFR1910.1048, “Formaldehyde”.
29CFR1910.1050, “Methylenedianiline”.
29CFR1910.1051, “1,3-Butadiene”.
29CFR1910.1052, “Methylene Chloride”.
29CFR1910.1200, "Hazard Communication".
29CFR1910.1450, “Occupational Exposure to Hazardous Chemicals in Laboratories”.
29CFR1926.21, ”Safety Training and Education”.
29CFR1926.350, "Gas Welding and Cutting".
30CFR602, Bureau of Mines, Department of the Interior - Chapter VI - Subchapter A--Helium and
Coal”.
40CFR61, “National Emission Standards for Hazardous Air Pollutants” (NESHAPs).
DOE-HDBK-1139/3-2003
144
40CFR82, “Protection of Stratospheric Ozone”.
40CFR302.4, “Listing of Hazardous Substances for the National Oil and Hazardous Substances
Pollution Contingency Plan”.
40CFR761, “Polychlorinated Biphenyls (PCBs) Manufacturing, Processing, Distribution in
Commerce, and Use Prohibitions”.
40CFR61.156, (National Emission Standards for Hazardous Air Pollutants) “Cross-reference to
Other Asbestos Regulations”.
40CFR63, “National Emission Standards for Hazardous Air Pollutants for Source Categories”.
40CFR68, “Chemical Accident Prevention Provisions”.
40CFR260-282, “The Resource Conservation and Recovery Act of 1976”.
40CFR261, “Identification and Listing of Hazardous Waste”.
40CFR273, “Standards for Universal Waste Management”.
40CFR355, “Emergency Planning and Notification”.
40CFR370, “Hazardous Chemical Reporting: Community Right-To-Know”.
40CFR763, “Asbestos”.
48CFR970, “DOE Management and Operating Contracts“.
40CFR68, “Chemical Accident Prevention Provisions”.
40CFR1500-1508, “Chapter V-Council on Environmental Quality”.
41CFR101, “Federal Property Management Regulations” (Parts 101-1 to 101-99); in particular,
Subpart H (Parts 42 to 99).
41CFR101-26.602, “Federal Property Management Regulations - Procurement Sources and
Program”.
41CFR101-27.2, “Management of Shelf-Life Materials”.
41CFR102, “Federal Management Regulation” (Parts 102-1 to 102-220); in particular, 41CFR102-
36, “Disposition of Excess Personal Property” [NOTE: This Part is cross-referenced by 41CFR101-
43, “Utilization of Personal Property”, which is no longer in print], and 41CFR102-37, “Donation
of Surplus Personal Property” [NOTE: This Part is cross-referenced by 41CFR101-44,“Donation
of Personal Property”, which is no longer in print].
41CFR109, “Department of Energy Property Management Regulations”; in particular, Subpart H
(Parts 42 to 50).
48CFR, “Federal Acquisition Regulations”.
48CFR, “Department of Energy Acquisition Regulations System”: (Chapters 1 and 9).
48CFR970, “DOE Management and Operating Contracts”.
49CFR171-180, (Subchapter C), “Hazardous Materials Regulations”.
49CFR171-179, “Hazardous Materials Transportation”.
Section 105
[49 FR 11945, Mar. 28, 1984, as amended at 49 FR 38950, Oct. 2, 1984].
[49 FR 11945, Mar. 28, 1984, as amended at 59 FR 9105, Feb. 25, 1994].
[54 FR 27646, June 30, 1989, as amended at 59 FR 9105, Feb. 25, 1994].
[62 FR 2312, Jan. 16, 1997].
42 USC 6901 – 6992(k), “The Solid Waste Disposal Act of Oct. 21, 1976”.
42 USC 13101 – 13109, “The Pollution Prevention Act of 1990”.
DOE-HDBK-1139/3-2003
145
CONCLUDING MATERIAL
Review Activity: Preparing Activity:
DOE DOE-EH-52
DP, EH, EM, NE, SC, OS, NA
SAFT-0089
Project Number:
Operations Offices
ID, OAK, ORO, RL, SRO
National Laboratories
PNNL, INEEL, LANL, RF, SRS, SNL,
Area Offices
External Agency
DNFSB
Consolidated Requirements
General (Applicable to all operations/activities involving chemicals)
Hazards associated with all activities involving chemicals that could put the employee at risk of injury or illness shall be evaluated. Those activities include, but are not limited to a) design of new facilities or modification of existing facilities a
[NOTE: Numerous other substance-specific hazard analysis requirements can be found in 29CFR1910, Subpart Z]
Consolidated Requirements
4.1General (Applicable to all acquisitions involving chemicals)
Hazards associated with all activities involving chemicals that could put the employee at risk of injury or illness shall be identified and evaluated before purchase.
Substitution of materials that are less hazardous and/or have less of an environmental impact shall be evaluated before purchase.
Packaging and Transportation Safety requirements shall be addressed as a part of the acquisition process.
When a chemical is ordered, it’s hazards shall be
The manufacturer’s Material Safety Data Sheet sha
Additional Procurement Requirements
(Non Health and Safety Requirements are provided for Informational purposes)
4.2 Alcohol
Applications to purchase tax free alcohol shall be submitted to the ATF.
4.3 Helium
DOE and its authorized contractors shall, to the extent that supplies are readily available, whether in gaseous or liquid form, purchase all major requirements large quantities of helium from the Secretary of Interior, Bureau of Mines, or from the Bureau
The purchase document shall contain the following statement: "Helium furnished under this contract shall be Bureau of Mines Helium."
4.4 Fuel and Petroleum
Acquisitions of fuel and packaged petroleum products by DOE offices and contractors shall be from Defense sources.
DOE offices and authorized contractors may participate in the Defense Fuel Supply Center (DFSC) coal-contracting program for carloads or larger lots.
4.5 Arms and Ammunition
Acquisition of arms and ammunition readily procurable in the civilian market shall be made in accordance with local site acquisition procedures.
4.6 DOE-specific materials acquisitions
Contracting activities shall require authorized contractors to obtain the special materials identified in the following subsections in accordance with the procedures stated therein.
Heavy water. The Senior Program Official or designee controls the acquisition and production of heavy water for a given program. Requests for the acquisition or production of heavy water orders shall be placed directly with the cognizant Senior Program O
4.6.2 Precious metals�. DOE offices and authorized contractors shall coordinate with the Oak Ridge operating contractor regarding the availability of the above metals prior to the purchase of these metals on the open market.
4.6.3 Lithium�. The DOE Oak Ridge Operations Office supplies of Lithium shall be considered the first source of supply prior to procurement of lithium compounds from any other source.
4.7 Controlled Substances
Use of controlled substances in research requires a permit or license.
Consolidated Requirements
Chapter 4 - On-Site Chemical Transportation
Section 106
Consolidated Requirements
Consolidated Requirements
4.1.2 The identification or design of chemical storage areas (see definition),or maintenance work on chemical storage areas shall be reviewed.
4.1.2.1 New facility design shall take into account the need for containment to protect the environment from oxidizers, fire suppression agents, and decomposition products.
Approval (see definition) of chemical storage areas shall take into consideration the potential for large quantities of smoke and toxic fumes, especially as storage affects manual fire fighting operations, building egress, and evacuation of adjacent fa
Cutting and welding operations in areas where organic peroxides are stored shall not be performed until all organic peroxide formulations have been removed.
4.1.3 Chemical storage areas shall be secured using physical or administrative controls to prevent unauthorized entry.
4.1.4 “No smoking” signs shall be posted at all
4.1.5 Ignition sources such as open flames, smoking, spark producing equipment, static electricity, and other hot sources shall not be permitted in areas where chemicals are stored unless reviewed and approved.
4.1.6 All chemicals shall be properly labeled.
Chemicals shall be stored compatibly and in a way to prevent contact with incompatible materials. This includes preventing liquids from flowing out of a chemical storage area into another area where they may be exposed to incompatible materials.
[EXCEPTION: NFPA 430, 2-4.2 exempts packaging materials, pallets, and other dunnage from this requirement. However, hydrogen peroxide (Classes II to IV) cannot be stored on wooden pallets.]
4.1.7.1 All construction materials in a chemical storage area shall be compatible with those chemicals being stored.
4.1.7.2 Special care shall be taken to prevent the contamination of chemicals in storage.
4.1.7.3 When flammable and combustible liquids are stored in segregated warehouses (see definition) with oxidizers, they shall be separated from those oxidizers by a distance of 25 ft. with dikes, drains, or sloping floors present to prevent the flamm
4.1.8 Chemicals that might become hazardous upon prolonged storage shall be dated when first opened and evaluated for safety every 6 months thereafter.
4.1.8.1 Chemicals that are found to be unsafe and cannot be made safe shall be disposed of safely and in compliance with applicable requirements.
Indoor chemical storage areas shall have either natural or mechanical ventilation designed to provide a minimum of six air exchanges per hour and shall discharge the air a minimum of 50 ft. from any air intakes for air handling systems, air compressors,
[EXCEPTION: Under NFPA 30, 4.3 and NFPA 45, 7-2.3.6 this requirement does not apply to flammable liquid storage cabinets.]
4.1.9.1 A manual shutoff shall be provided outsid
4.1.9.2 Exhaust ventilation shall not be recirculated within any room or building.
4.1.10 Good housekeeping shall be maintained in areas where chemicals are stored.
Aisles established for the movement or egress of personnel shall be maintained clear of obstructions, including stored chemicals.
Accumulation of wastes, debris, weeds, and other combustible materials shall be prohibited.
Spilled chemicals and broken containers shall be immediately managed using appropriate procedures.
Each used and empty container shall be stored in a manner appropriate for the chemical that existed in that container until it is disposed of or cleaned;
Section 107
OR
stored in a detached or sprinklered area (see definition) until disposed of or cleaned.
Storage operations shall be arranged to prevent the accumulation of fugitive dust from the stored chemical.
Specific disposal procedures shall be developed for all areas where organic peroxides are stored.
4.1.11 Hazardous chemicals stored in the open in laboratory work areas shall be kept to the minimum necessary for the work being done.
4.2 Compressed Gases
a single cylinder secured alongside the cylinder in (a) above as the reserve cylinder.]
4.2.1 Hazard identification signs shall be placed at all entrances to areas where compressed gas is stored.
4.2.1.1 Hazard ratings shall be assigned in accordance with NFPA 704.
4.2.1.2 Signs shall not be obscured or removed.
4.2.1.3 Signs shall prohibit smoking or an open flame within 20 ft of where toxic, pyrophoric, oxidizing, or flammable gases are stored.
4.2.2 Compressed gas cylinders shall be stored away from stairways, elevators, exit routes, or gangways, in assigned places where they will not be exposed to physical damage (for example, damage from vehicles, damage from falling ice, etc.).
Compressed gas cylinders shall be stored in an upright position (see definition) with their valve protection caps in place and secured to prevent cylinders from falling over or being knocked over.
[EXCEPTION: All requirements cited here indicate that upright storage is not required for lecture bottles or cylinders used in self-contained breathing apparatus.]
4.2.4 Overhead cover for outdoor storage areas of compressed gases shall be of non-combustible construction, open on three sides and shall not be considered indoor storage.
4.2.4.1 Storage areas shall be kept clear of dry vegetation and combustible materials for a minimum distance of 15 ft in all directions.
Cylinders stored outdoors shall not be placed in direct contact with the earth or on surfaces where water can accumulate.
4.2.5 Compressed gas cylinders in storage shall not be heated above 125(F �.
Section 108
Compressed gases in storage shall be segregated f
[EXCEPTION: Under ANSI Z49.1 and NFPA 55 welding gases located on a weld cart are considered to be "in use" and not in storage. This is also consistent with the NFPA 45 definition of "in use". Under these cited standards, then, this requirement does no
[NOTE: The intent of these requirements is to discourage the manufacture of unsafe weld carts and to prevent the practice of removing welding gases from carts at the end of every work shift or day, since this additional handling of the gases is consider
4.2.6.1 Flammable gas cylinders shall be stored a minimum distance of 20 ft. from storage of flammable and combustible liquids and solids.
The inside storage of more than 2,000 standard cubic ft. (scf) of flammable gas, or more than 300 pounds of liquefied petroleum gas requires a separate room, compartment, or special storage building.
4.2.7.1 Indoor storage in one fire area of multiple groups of cylinders containing flammable gas shall be performed according to specifications in NFPA 55, Chapter 6.
Indoor storage in one fire area of multiple groups of cylinders containing flammable gas shall be performed according to specifications in NFPA 55, Chapter 6.
4.2.8.1 Groups may be separated from each other by masonry walls with a fire resistance rating of 2 hours instead of by a minimum distance.
4.2.8.2 Different flammable gases shall be allowed to be stored together.
4.2.9 Flammable gases with a collective volume between 2,501 and 5,000 scf, when stored indoors, shall be stored in rooms or enclosures with a minimum 1-hour fire resistance rating.
Multiple groups of flammable gas cylinders in one sprinklered fire area shall be stored a minimum of 100 ft. apart.
4.2.10 Flammable gases with a collective volume greater than 5,000 scf, when stored indoors, shall be stored in a room or enclosure with a minimum fire resistance of 2 hours.
4.2.10.1 Rooms used to store compressed gases shall be sprinklered according to NFPA 13.
4.2.11 Indoor compressed gas storage areas that are used to store toxic or highly toxic gases indoors shall be equipped with a continuous monitoring system that would provide warning of toxic gas concentrations that could present a hazard to life.
4.2.12 Outdoor storage areas of toxic gases shall be located 75 ft from a line of property, public ways, places of assembly.
4.2.13 Other requirements for the storage of toxic and highly toxic gases can be found in NFPA 55, 7.9.
4.2.14 Where toxic gases are stored, a minimum of two NIOSH approved self-contained breathing apparatus (SCBAs) shall be kept available at all times for use in upset conditions. They shall be cleaned and disinfected after each use, properly maintaine
4.2.14.1 NIOSH approved SCBAs shall also be provided where protection is deemed necessary for entry into atmospheres containing asphyxiant or corrosive gases.
4.2.14.2 One of the two SCBAs present shall be in the possession of a qualified backup person present at the scene when the SCBAs are being used.
4.3 Flammable and Combustible Liquids
4.3.1 Aisles in areas that qualify as indoor liquid storage areas as per NFPA 30, "Flammable and Combustible Liquids Code", shall be 4 ft wide. Aisles in other flammable liquid storage areas shall be 6 ft wide.
4.3.1.1 Aisles at least 3 ft wide shall be provided where necessary to allow for access to doors, windows, or standpipe connections.
Section 109
4.3.2 Class I flammable liquids (see definition) shall not be stored in basement areas. Class II and Class IIIA combustible liquids (see definition) shall not be stored in basement areas unless those areas are protected with automatic sprinkler sy
4.3.3 Class I flammable liquids shall not be stored such that a fire in the liquid storage area would prevent egress from the area.
4.3.4 In general purpose warehouses, flammable and combustible liquids shall not be stored in the same pile or on the same rack as ordinary combustibles.
4.3.4.1 Ordinary combustibles, other than those used for packaging flammable liquids, shall be stored a minimum of 8 ft from flammable or combustible liquids.
4.3.4.2 Where flammable liquids are packaged together with ordinary combustibles, such as in kits, storage shall be considered on the basis of whichever commodity predominates.
4.3.5 Storage of empty or idle pallets inside a flammable liquid storage area shall not exceed 2,500 ft.2 and 6 ft. in height.
4.3.6 Containers in piles shall be stacked in such a manner as to provide stability and to prevent excess stress on container walls.
4.3.6.1 Portable tanks stored over one tier high shall be nested securely without dunnage.
4.3.6.2 Material handling equipment shall be suitable to handle containers and tanks safely at the upper tier level.
4.3.7 Containers over 30 gallons in size that contain Class I or Class II liquids shall not be stored over one level high in inside rooms (see definition).
4.3.8 No stack of flammable or combustible liquids shall be closer than 3 ft. to the nearest beam, chord, or other construction, and shall be 3 ft. below sprinkler deflectors, discharge orifices of water spray, or other overhead fire protection systems
4.3.9 Suitable fire control devices shall be available at locations where flammable and combustible liquids are stored.
4.3.10 At least one portable fire extinguisher having a rating of not less than 40-B units shall be located outside but not more than 10 ft. from any door to a flammable and combustible liquids storage room or any area where Class I or Class II liquids a
4.3.11 Water reactive materials (see definition) shall not be stored in the same area with flammable or combustible liquids.
4.3.12 Class I and Class II liquids in plastic containers shall only be stored in flammable liquids storage rooms (see definition) or flammable liquid storage cabinets.
4.3.13 Liquids used for building maintenance, painting, or other similar infrequent maintenance purposes shall be permitted to be stored temporarily in closed containers outside of flammable liquids storage cabinets or flammable liquids storage areas, if
4.3.14 The quantity of flammable and combustible liquids that can be stored outside a flammable liquids storage room or flammable liquids storage cabinet is as follows�:
757 L (200 gallons) of Class I, II, and IIIA liquids in sprinklered laboratory units.
[NOTE: Second set of “a.” and “b.” refers to Cl
4.3.15 With the exception of Section 4.3.12 and 4.3.13, all Class I, II, and IIIA flammable and combustible liquids not in a flammable liquids storage room shall be stored in flammable liquid storage cabinets when not in use.
4.3.15.1 The total quantity of liquids shall not exceed 120 gallons per cabinet.
4.3.15.2 Flammable liquid storage cabinets shall be FM approved or UL listed or built in accordance with NFPA 30.
4.3.15.3 Not more than three flammable liquid storage cabinets are allowed in any one fire area, except as follows:
Section 110
4.3.15.4 The maximum amount of Class I, II, and IIIA flammable and combustible liquids that can be stored in a laboratory fire area is 400 gallons of which the maximum amount of Class I flammable liquids is 300 gallons.
4.3.16 Sites for outdoor storage lockers (see definition) shall be reviewed to ensure proper placement, separation, etc.
4.3.16.1 Multiple outdoor storage lockers at a given site shall be separated according to requirements in NFPA 30.
4.3.16.2 In outdoor storage lockers, containers in their original shipping packages shall be permitted to be stored either on pallets or in piles, while unpacked containers shall be stored on shelves or on the floor.
4.3.16.3 No other flammable or combustible materials shall be stored at designated outdoor storage locker sites.
4.3.16.4 Outdoor storage lockers shall be placarded according to NFPA 704.
4.4 Oxidizers
[NOTE: Additional requirements can be found in NFPA 430, "Code for Storage of Solid and Liquid Oxidizers", when quantities exceed 4,000 pounds of Class 1 oxidizer (see definition), 1,000 pounds of Class 2 Oxidizer (see definition), 200 pounds of Cla
4.4.1 Oxidizer storage areas shall be conspicuou
4.4.1.1 Areas used to store oxidizers of different classes shall be marked as containing the most severe hazard.
4.4.2 Water based manual fire fighting equipment shall be used in oxidizer storage areas.
4.4.2.1 The placement and use of dry chemical extinguishers containing ammonium compounds (Class ABC) shall be prohibited in oxidizer storage areas where oxidizers that can release chlorine are stored.
4.4.2.2 Halon extinguishers shall not be used in oxidizer storage areas.
4.4.3 Combustible construction materials that could come into contact with oxidizers shall be coated with a compatible material to prevent their impregnation with the oxidizers.
4.4.4 Absorptive packing materials, wooden pallets, etc., that are exposed to water containing oxidizers or that contain water soluble oxidizers, and are exposed to water shall be immediately relocated to a safe outside area and properly disposed of.
4.4.5 Oxidizers shall not be stored where they can be heated to within 25(F of their decomposition temperature or above 120(F, whichever is lower.
4.5 Organic Peroxides
4.5.1 Chemical storage areas used for the storag
4.5.1.1 Areas used to store organic peroxides of different classes per NFPA 432, shall be marked as containing the most severe hazard.
4.5.1.2 Packages containing organic peroxide formulations shall be individually marked with chemical name and other pertinent information to allow proper classification.
4.5.1.3 Packages of organic peroxides that require temperature control shall be marked with the recommended storage range.
4.5.2 A clear space of at least 2 ft. shall be maintained between organic peroxide storage and uninsulated metal walls.
4.5.3.1 If a 25-foot separation cannot be maintained, then a 1-hour, liquid-tight fire barrier shall be permitted.
4.5.4 Only closed containers shall be permitted in an organic peroxide storage area.
4.5.5 Fifty-five-gallon drums of organic peroxide formulations shall not be stacked.
4.5.6 Storage temperatures in chemical storage areas shall be maintained within the recommended storage temperature range for the materials being stored.
4.5.6.1 High and low temperature switches, as applicable, shall be provided in addition to normal temperature controls. These switches shall actuate an alarm to ensure prompt response.
4.5.6.2 Heating systems shall use low-pressure steam, hot water, or indirectly heated air; cooling systems shall not use direct expansion of a flammable gas.
4.5.6.3 Heating or cooling pipes and other heat transfer devices shall not come into contact with organic peroxide containers to cause their overheating or cooling.
Refrigerators used for storing organic peroxide formulations shall be Class I, Group D, and Division I (i.e., "explosion-proof", as defined in Article 500 of NFPA 70.
Unventilated, unrefrigerated storage cabinets used for the storage of organic peroxides shall be considered Class I, Division I as defined in Article 500 of NFPA 70.
Ventilated storage cabinets shall be considered Class I, Division II as defined in Article 500 of NFPA 70. Ventilation must be a minimum of 1 cubic foot/minute/square foot of floor area.
Section 111
Consolidated Requirements
General (Applicable to all operations/activities involving chemicals)
A hazard prevention/abatement process shall be implemented to ensure that all identified hazards are managed through final abatement or control.
4.3Requirements for Laboratory Use of Chemicals
A chemical hygiene plan shall be prepared for laboratory operations that includes safe operating procedures, hazard control measures, operability requirements for protective equipment, provisions for employee training and medical consultations, designati
4.3.1.1 Extremely hazardous substances \(see de
Fire Hazard Classification – Laboratory units sha
For the purposes of determining laboratory fire hazard classification and the use of tables 2.2.1(a) and (b),, quantities of liquefied flammable gases shall be treated as if they were Class I flammable liquids (see definition); that is, 4L (1.1gal
4.3.3All laboratory units shall be provided with fire protection appropriate to the fire hazard, including: automatic fire extinguishing systems, standpipe and hose systems, portable fire extinguishers, fire alarm systems, fire prevention programs, and e
4.3.4 If a laboratory contains explosion hazards, as defined in sections 2.3.1 and 2.3.2 of NFPA 45, protection shall be provided by one or more of the following:
limiting the amounts of flammable or reactive chemicals or chemicals with unknown characteristics used in or exposed by experiments;
special preventive or protective measures for the reactions, equipment, or materials themselves (e.g., high-speed fire detection with deluge sprinklers, explosion-resistant equipment or enclosures);
remote control equipment;
sufficient deflagration venting in outside walls; and,
conducting experiments in a detached or isolated building, or outdoors.
4.3.4.1 Other explosion hazard protection may be considered including:
Explosion-resistant construction;
Explosion venting;
Controlled access to laboratory; and,
Regularly scheduled inspection and maintenance
Handling of laboratory chemicals
Chemicals shall not be brought into a laboratory work area unless design, construction, and fire protection of the facilities are commensurate with the quantities and hazards of the chemicals involved.
4.3.5.2 Receiving, transporting, unpacking, and dispensing of chemicals and other hazardous materials shall be carried out by trained personnel in such locations and in such a manner as to minimize hazards from flammable, reactive, or toxic materials.
4.3.5.3 Class I liquids shall not be stored or transferred from one vessel to another in any access corridor, open plan buildings, or ancillary spaces unprotected from the exit access corridor.
4.3.5.4 Transfer of Class I liquids to smaller containers from bulk stock containers not exceeding 19L (5 gal.) in capacity shall be performed as follows:
In a laboratory hood;
In an area provided with ventilation adequate to prevent accumulations of flammable vapor/air mixtures from exceeding 25 percent of the lower flammable limit;
In a liquid storage area specifically designed and protected for dispensing Class I flammable liquids that meet the requirements of NFPA 30.
4.3.5.5 Transfer of Class I liquids from containers of 19L (5 gal.) or more capacity shall be carried out as follows:
In a separate building; OR
In a liquid storage area specifically designed for dispensing Class I flammable liquids that meet the requirements of NFPA 30.
Class I liquids shall not be transferred between conductive containers of greater than 4L (1.1 gal.) capacity unless the containers are electrically interconnected by direct bonding or indirect bonding through a common grounding system. When dispensin
Individual containers of flammable or combustible liquids shall not exceed the capacities listed in NFPA 45, Table 7.2.3.2.
The quantity of flammable solids, solid or liquid
Laboratory Compressed Gases – In addition to the
Pyrophoric gases
Regulator systems in laboratory operations shall be equipped with two gauges, either on the regulator or remote from the regulator, installed as to show both the cylinder pressure and the outlet pressure. When the source cylinder is outside of the labo
4.3.6.5 Only in use cylinders shall be allowed in the immediate work area. A compressed gas cylinder shall be considered in use when it is:
(1) connected through a regulator to deliver gas; or
(2) connected to a manifold being used to deliver gas; or
(3) a single cylinder secured as a reserve cylinder alongside the cylinder described in (1).
4.4Combustible Liquids
Operations involving flammable or combustible liquids shall be located and operated so that they do not constitute a significant fire or explosion hazard to life or property.
Precautions shall be taken to prevent the unintentional ignition of flammable vapors.
Section 112
Smoking shall be permitted only in designated and properly identified areas.
4.4.2.2Welding, cutting, and similar spark-producing operations shall not be permitted in areas containing flammable or combustible liquids until a written permit authorizing such work has been issued.
4.4.2.3All equipment (such as tanks, machinery, and piping) where an ignitable mixture could be present shall be bonded or connected to a ground. The bond or ground or both shall be physically applied or shall be inherently present by the nature of th
4.4.3� Individual containers of flammable or combustible liquids shall not exceed the capacities listed in 29CFR1910.106, Table H-12.
4.4.4In an office occupancy, containers of Class I liquids that are outside of an inside liquid storage (see definition) area shall not exceed a capacity of one gallon (3.8 liters).
4.4.5In an office occupancy, not more than ten gallons (37.8 liters) of Class I and Class II liquids (see definition) combined shall be kept in a single fire area (see definition) outside of a storage cabinet or an inside liquid storage area, unles
4.4.6In an office occupancy, not more than 25 gallons (94.6 liters) of Class I and Class II liquids (see definition) combined shall be kept in a single fire area in safety cans outside of a storage cabinet or an inside liquid storage area.
4.4.7In an office occupancy, not more than 60 gallons (227 liters) of Class III liquids (see definition) shall be stored outside of an inside liquid storage area or storage cabinet.
4.4.8Wherever flammable or combustible liquids are used, either fire extinguishers or pre-connected hoses shall be provided in accordance with NFPA 30.
4.4.9Whenever a combustible liquid is heated for
4.4.10An approved (see definition) means for prompt notification of fire or emergency to those within the plant and to the fire department shall be provided.
4.4.11Those areas, including buildings, where a potential exists for a flammable liquid spill shall be monitored for the presence of those liquids.
4.4.12All fire protection equipment, and associat
4.4.13Maintenance and operating practices shall control leakage and prevent spillage of flammable liquids.
4.4.14Spills shall be cleaned up promptly.
4.4.15Combustible waste material and residues in operating areas shall be kept to a minimum, shall be stored in covered metal containers, and shall be disposed of daily.
4.4.16Ground areas around facilities where liquids are used shall be kept free of weeds, trash, or other unnecessary combustible materials.
4.4.17Aisles established for movement of personnel shall be maintained clear of obstructions.
4.4.18Flammable liquids or combustible liquids at temperatures at or above their flash points shall be drawn from or transferred into vessels, containers, or portable tanks using one of the following methods:
4.4. 19Transferring flammable or combustible liquids by means of air pressure on the container or tank shall be prohibited.
4.4.20Dispensing in inside storage rooms shall be by approved pump or self-closing faucet only.
4.4.21If hose is used in the transfer operation, it shall be equipped with a self-closing valve without a hold-open latch in addition to the outlet valve. Only listed or approved hose shall be used.
4.4.22Means shall be proved to minimize generation of static electricity. Such means shall meet the requirements of NFPA 30.
4.4.23Class I liquids (see definition) shall not be dispensed into containers unless the nozzle and container are electrically interconnected.
4.4.24If pumps are used to transfer liquids, means shall be provided to stop the transfer in the event of a spill or fire.
4.4.25Areas in which flammable or combustible liquids are transferred from one tank or container to another container shall be separated from other operations in the building by adequate distance or by construction having adequate fire resistance. Adequa
Section 113
4.4.26Dispensing of flammable liquids or dispensing of combustible liquids at temperatures at or above their flash points shall not be permitted in cutoff rooms or attached buildings that exceed 1000 ft2 (93m2) in floor area or in liquid warehouses unl
4.4.27Dispensing of flammable liquids or of Class II combustible liquids shall not be permitted in general purpose warehouses unless the dispensing area is suitably cut off from other ordinary combustible or liquid storage areas in accordance with NFPA 3
4.4.28Flammable liquids shall be kept in covered containers when not actually in use.
4.4.29Where flammable or combustible liquids are used or handled, except in closed containers, means shall be provided to dispose promptly and safely of leakage and spills.
4.4.30Class I liquids shall be used only where there are no open flames or other sources of ignition within the possible path of vapor travel.
4.5.1 Compressed gas cylinders shall be used in accordance with the Compressed Gas Association (CGA).
4.5.2Compressed gas cylinders shall be appropriately labeled. Whenever possible, labels shall be located near the shoulder of the cylinder.
4.5.2.1The color of the cylinder shall not be the only means used to identify the gas it contains.
4.5.2.2Labels or markings placed on compressed gas cylinders by the manufacturer or distributor shall not be defaced or removed.
4.5.2.3Cylinders not bearing a legible label or other identification shall not be used and shall be returned to the manufacturer or distributor.
4.5.2.4Gas name markings shall not be cut into the metal of the cylinder by the user.
4.5.3Compressed gas cylinders shall not be subjected to temperature extremes.
4.5.3.1Compressed gas cylinders shall not be exposed to temperatures exceeding 125(F
4.5.3.2Direct flames or heat shall not be applied to a compressed gas cylinder.
4.5.3.2.1Cylinders exposed to fire shall not be shipped or used until the manufacturer or supplier requalifies them in accordance with the pressure and vessel code under which they were manufactured.
4.5.3.3Cylinders shall not be subjected to artificially low temperatures without the permission of the supplier. Outside storage is not affected by this requirement.
4.5.4No structurally damaged or defective cylinders shall be used. Damaged or defective cylinders shall be removed from service.
4.5.6No one shall tamper with safety devices in cylinders or valves.
4.5.6.1No attempt shall be made to maintain or repair cylinder safety devices. Suppliers instructions as to the disposition of the cylinder shall be followed if a cylinder with a faulty valve or safety device is found or if the cylinder is otherwise fou
Complete removal of the stem from a diaphragm-type cylinder valve shall be avoided.
[NOTE: Stems may be removed before cylinder disposal.]
When compressed gas cylinders are not in use or are empty, their valves shall be closed.
Where cylinders are designed to accept valve protection caps, caps shall be in place and hand tight at all times except when connected for use.
Where valve outlet caps and/or plugs are provided by the manufacturer, the user shall keep the device on the valve outlet at all times except when secured and connected for use.
Valve outlet caps and/or plugs shall be in place and tightened before shipment of the cylinder back to the supplier.
Pry bars shall not be used under valves or valve protection caps to pry cylinders loose when frozen or otherwise affixed to the ground.
Warm, not boiling water shall be used to
thaw cylinders loose.
Section 114
Compressed gas cylinders shall not be used as rollers or supports.
4.5.12 Compressed fuel gas cylinders shall not be kept in unventilated enclosures such as lockers or cupboards.
4.5.13Compressed gas cylinders shall not be placed where they can inadvertently become part of an electrical circuit.
When used in conjunction with electric welding, compressed gas cylinders shall not be grounded or used for grounding.
Electrodes shall not be struck against a compressed gas cylinder to strike an arc.
Compressed gas cylinders shall be secured in an upright position when being used unless specifically designed for a horizontal application.
[EXCEPTION: Cylinders containing non-flammable liquefied gases may be used in the inverted position when the liquid phase is used.]
Oxygen and fuel and other compressed gas cylinders, equipment, pipelines or apparatus shall not be used interchangeably with any other gas and each shall be used only for the service for which it was approved.
All connections shall be gas tight and no leaks shall be present in the system.
A flame shall not be used for the detection of leaks in compressed gas systems. Soapy water is one acceptable method.
Backflow protection shall be used when the backflow of gas can result in a hazardous condition.
Compressed gas systems shall be designed for their intended use and shall be designed by persons competent in such design. .
[NOTE: Additional requirements for corrosive, flammable, oxidizing, pyrophoric, toxic/highly toxic, and unstable reactive gases can be found in NFPA 55, 7.5-7.10.]
4.5.19 Compressed gases shall never be used from cylinders or high pressure manifolds without reducing the pressure through a suitable regulator unless the equipment used is designed to withstand full cylinder pressure.
4.5.19.1 Unless connected to a manifold, oxygen from a cylinder shall not be used without a regulator.
4.5.20 Approved gas regulators and pressure reducing valves shall be used only for the gas and pressures for which they are labeled.
Regulators, including their related gauges, shall be in proper working order while in use.
Union nuts and connections shall be inspected before cylinder use to detect faulty seals, which could cause leakage. Faulty nuts and connectors shall be replaced.
A qualified mechanic shall perform repair of regulators or their parts.
Before a regulator is removed from a cylinder, the cylinder valve shall be closed and the pressure released from the regulator.
Cylinder valves shall always be opened slowly to prevent damage to the regulator.
Personnel shall stand to the side and not in front of the regulator orifice when the cylinder valve is opened.
When a high pressure gas (non-liquefied) cylinder is in use, the valve shall be fully opened to prevent leakage around the valve stem.
Cylinders not having a fixed hand wheel shall have keys, handles or non-adjustable wrenches on valve stems while cylinders are in service.
Manifolded or coupled cylinders shall have at least one such wrench always available.
Section 115
Cylinders having hand wheels shall not be opened using wrenches, hammers or other tools. If the valve cannot be opened by hand, then the manufacturer shall be notified and their directions followed.
When cylinders are secured in a suitable hand truck, regulators do not have to be removed and valve protection caps need not be in place before cylinders are moved. When cylinders are to be moved with regulators attached, the cylinder valve must be close
Cylinder valves shall be closed before moving cylinders.
Valve protection caps shall not be used for lifting cylinders.
When using a crane, derrick, etc. to transport cylinders, a cradle, boat, pallet, slingboard or other suitable platform shall be used. Compressed gas cylinders shall be secured to the lifting device before they are hoisted.
Choker slings, ropes, chains or magnets shall not be used to hoist compressed gas cylinders.
Compressed gas cylinders shall not be purposely dropped, struck or permitted to strike each other violently.
When compressed gas cylinders are transported by motor vehicle, they shall be secured in an upright position.
When large cylinders are moved by hand, they shall be tilted and rolled on their bottom edge.
Before connecting a regulator to an oxygen or fue
The person cracking the valve shall stand to one side and not in front of the gas stream. Compressed gas streams shall not be directed towards any person.
Fuel cylinder valves shall not be cracked near ignition sources such as flames, welding work, sparks, etc..
Hose connections shall be kept free of grease and oil.
Hoses for oxy-fuel gas service shall comply with the Rubber Manufacturers Association IP-7 Specification for Rubber Welding Hose.
Fuel gas hoses shall be red and oxygen hoses shall be green when they are used for welding and cutting activities.
When parallel lengths of oxygen and fuel gas hoses are taped together such as in a welding operation, not more than 4 inches out of every 12 shall be covered by tape.
All hoses used for welding, cutting and other hot work that will be used to carry hazardous gas (for example, oxygen, fuel gases, oxidizers) shall be inspected at the beginning of each working shift that they are to be used and any defective hoses shal
[NOTE: Defects in hoses that shall render the hose no longer useable include leaks, burns, and worn places that render the hose unfit for service.]
Hose connections shall comply with the CGA Pamphlet E-1, Regulator Connection Standards.
Hose connections for welding gas lines shall not be compatible with breathing air equipment.
Hose connections shall be able to withstand, without leakage, twice the normal operating pressure and not less than 300 psi.
Oil-free air or an oil-free inert gas shall be used to test hose connections.
Storage areas for hoses shall be well ventilated.
Fuel gas and oxygen manifolds capacity limits, locations and design criteria shall be in accordance with NFPA 51 and 29CFR1910.253.
Fuel gas and oxygen manifolds shall be installed under the supervision of someone familiar with the proper practices.
All manifolds and their parts shall be used only for those gases for which they are approved.
Manifolds shall be approved either separately for each of their components or as an assembled unit.
Manifolds shall bear the name of the substance contained inside in letters at least 1 inch high either directly painted upon the manifold or on a sign permanently affixed to the manifold.
Low pressure manifolds shall be marked as such to prevent the attachment of high pressure cylinders.
Section 116
Fuel gas and oxygen manifolds shall be located in safe, well ventilated, accessible locations and not within enclosed spaces.
Fuel gas and oxygen manifold hose connections shall be such that hoses cannot be interchanged between fuel gas and oxygen manifolds and supply header connections.
Adapters shall not be used to permit the interchange of hoses.
When not in use, fuel gas and oxygen manifold and header connections shall be capped.
Nothing shall be placed on top of a fuel gas and oxygen manifold that will damage the manifold or interfere with the quick closing of the valves.
Portable outlet headers shall not be used indoors except for temporary service as approved by the Occupational Safety and Fire Protection Department.
Oxygen cylinders, cylinder valves, couplings, regulators, hoses, and other apparatus shall be kept free from oil, grease, dirt and other flammable or explosive substances. These materials shall not be handled with oily hands or gloves.
4.3.49.1A jet of oxygen gas shall not be directed at an oily surface, greasy clothes, etc.
Gauges used for oxygen service shall be marked “U
Oxygen shall not be used as a substitute for compressed air. For example, it shall not be used in pneumatic tools, to blow out pipelines, to dust off clothing or any similar application.
Oxygen regulators shall be drained of oxygen before they are attached to a cylinder or a manifold or before the cylinder valve is opened.
Oxygen in work areas shall not be allowed to exceed 23 percent by volume.
Fuel gas cylinders shall be used valve end up.
Where ignition of a flammable gas by static electricity is possible, means shall be provided to prevent static discharge.
Nothing shall be placed on fuel cylinders while in use that could damage safety devices or interfere with the quick closing of the valve.
Quick opening valves on fuel gas cylinders shall
Withdrawal rates from gas cylinders shall not exc
If a leak is found around the valve stem of a fuel gas cylinder, then the packing nuts shall be tightened and the cylinder valve closed.
If these actions do not stop the leak (because the leak is in the valve stem, valve seat, cylinder fuse plug, etc.) then the cylinder shall be moved from the work area to a safe location outdoors and the cylinder shall be properly marked.
Precautionary signs warning of a fire hazard shall be posted where leaking fuel cylinders are located.
If a leaking fuel cylinder cannot be moved, then the area shall be evacuated and the fire department shall be summoned for assistance.
Small fires at fuel gas cylinders shall be extinguished if possible without endangering personnel by either shutting off the valve or by the use of water.
Personnel shall evacuate the area and the fire department summoned for assistance if a cylinder fire cannot be easily extinguished.
When compressed gas lines are being purged of air, oxygen or combustible gas, then sources of ignition shall not be allowed near uncapped openings.
The use of liquid acetylene is prohibited.
4.5.62 Details for the following compressed gases can be found in the listed citations:
4.5.62.1 Acetylene
4.5.62.2 Hydrogen
4.5.62.3 Oxygen
4.5.62.4 Nitrous Oxide
Consolidated Requirements
Consolidated Requirements
Applicability
Consolidated Requirements
4.1.1 Identification and Disposition of Excess Chemicals - DOE offices and designated contractors shall promptly identify chemicals under their control that are excess to their needs and make them available for use elsewhere. They must ensure that fi
Section 117
4.2 Utilization of Excess Chemicals
4.6.5 Sale of High Risk Personal Property
4.8.3 Asbestos - Special Requirements
[NOTE: The following disposition requirements apply to chemical products containing friable asbestos (see Section 4.8.3.1, below) and nonfriable asbestos (see Section 4.8.3.2, below)]
4.8.3.1 Friable Asbestos Materials (see definition)
4.8.3.2.2 All excess chemical products known to contain nonfriable asbestos shall be labeled with a cancer hazard warning as prescribed in 41CFR101-42.1102-1(b)(2)(ii).
4.8.3.2.5 Sale – Surplus chemicals containing
4.8.3.2.6 Abandonment and destruction – Surp
4.8.4.3 Unmarked or unlabeled items containing PCBs or PCB items with an unknown level of concentration of PCBs shall not be transferred, donated, or sold.
4.8.4.6 When a PCB or PCB item is transferred as excess, the receiving agency shall note in its property accountability records the nature and concentration of the PCB and shall list the provisions of 40CFR761 authorizing its use.
4.8.4.9 Items to be donated must be intact, totally enclosed, and non-leaking.
4.8.4.10 Sales - The GSA or the holding DOE organization normally shall not sell surplus PCBs or PCB items. These items are regarded as extremely hazardous and shall be disposed of by DOE and DOE contractors under the EPA regulations.
4.9 Utilization and Disposition of Hazardous Materials that are Radioactively or Chemically Contaminated
4.9.2 Suspect Personal Property - Excess chemicals (including scrap) having a history of use in an area where radioactive or chemical contamination may occur shall be considered suspect and shall be monitored.
4.9.3 If economically feasible, every effort shall be made to reduce the level of contamination of excess or surplus chemicals to the lowest practicable level. Contaminated chemicals that exceed applicable contamination standards shall not be utilized
4.9.4 If contamination is suspected and the property is of such size, construction, or location as to make testing for contamination impossible, the property shall not be utilized or disposed outside of DOE.
Sources10
Consolidated Requirements�,
Untitled